Dimplex WI 9CS, WI 14CS, WI 22CS, WI 27CS Operating Manual

Page 1
1
MOUNTING and
OPERATING MANUAL
Water-to-Water Heat Pump
for Indoor Installation
WI 9CS WI 14CS WI 22CS WI 27CS
Order No.: 452230.67.03 FD 8404
Page 2
2
CONTENTS
1 READ IMMEDIATELY 3
1.1 Important Information
1.2 Legal Provisions and Directives
1.3 Energy-Efficient Use of the Heat Pump
2 PURPOSE OF THE HEAT
PUMP 4
2.1 Application
2.2 Principle of Operation
3 BASELINE UNIT 4
4 TRANSPORT 5
5 INSTALLATION 5
5.1 General Information
5.2 Sound Emissions
6 MOUNTING 6
6.1 General
6.2 Heating-Side Connection
6.3 Heat Source-Side Connection
6.4 Electrical Connection
7 COMMISSIONING 7
7.1 General
7.2 Preparation
7.3 Procedure
8 CARE/CLEANING 7/8
8.1 Care
8.2 Cleaning of Heating Side
8.3 Cleaning of Heat Source Side
8.4 Water Quality Requirements
9 MALFUNCTIONS/TROUBLE-
SHOOTING 8
10 DECOMMISSIONING 8
10.1 Shutdown in Summer
10.2 End-of-Life Decommissioning
11 APPENDIX 9
Page 3
3
1.2 Legal Provisions and Directives
This heat pump is in compliance with all relevant DIN/VDE regulations and EU directives. These are described in more detail in the EC Declaration of Conformity.
The electrical connection of the heat pump must be performed according to and conforming with all relevant VDE, EN and IEC standards. Beyond that, all connection requirements of the local electrical utility company have to be observed.
The heat pump is to be plumbed into the heat source and heating systems in accordance with all relevant regulations.
1.3 Energy-Efficient Use of the Heat Pump
By operating this heat pump, you contribute to the protection of the environment. An important prerequisite for energy-efficient operation is the careful sizing of the heating system and the heat
source. In particular, it is important to keep water flow temperatures as low as possible. All energy consumers connected should therefore be suitable for low flow temperatures. A 1 K higher heating water temperature corresponds to an increase in power consumption of approx. 2.5 %. Underfloor heating systems with flow temperatures between 30 °C and 40 °C are optimally suited for energy-efficient operation.
READ IMMEDIATELY
1
CAUTION!
CAUTION!
CAUTION!
CAUTION!
CAUTION!
CAUTION!
CAUTION!
CAUTION!
READ IMMEDIATELY
1.1 Important Information
The well water must meet the required
water quality standards.
The heat pump is not attached to the
wooden pallet.
The heat pump must not be tilted
more than max. 45° (in either direction).
Do not lift unit by the holes in the panel
assemblies!
Flush the heating system prior to
connecting the heat pump.
When connecting the load lines be
sure to observe the clockwise phase sequence.
Commissioning of the heat pump must be performed in accordance with the operating instructions of the heat pump controller.
Any work on the heat pump may be performed by an authorised and competent customer service only.
Before opening the unit, all electrical circuits must be disconnected from the power supply.
CAUTION!
Page 4
4
BASELINE UNIT
The baseline unit consists of a heat pump, ready for connection, for indoor installation, complete with
housing, control panel and integrated controller. The refrigeration cycle contains the refrigerant R407C. The refrigerant is CFC-free, non-ozone depleting and non-combustible.
All components required for the operation of the heat pump are integrated in the control panel. The power feed for the load and control current must be field-installed by the customer.
The supply lead of the well pump (to be provided by the customer) must be connected to the control panel. When so doing, check whether the capacity of the factory-installed motor protecting device is adequate for the field-installed pump.
12
4
1) Evaporator 3) Condenser
2) Control panel 4) Compressor
PURPOSE OF THE HEAT PUMP
2.1 Application
The water-to-water heat pump is designed for use in existing or newly built heating systems. Water, which can be supplied from wells, or the like, is used as the heat carrier.
To prevent any corrosion damage to the eva­porator, the well water must be evaluated in accordance with DIN 50930 as to the corrosion risk of metallic materials.
More details are contained in the Project Planning and Installation Manual for heat pumps for heating purposes.
The well water must meet the estab­lished water quality standards.
2.2 Principle of Operation
A well pump conveys the water into the evaporator of the heat pump where it gives off heat to the refrigerant in the refrigeration cycle.
The refrigerant is then "sucked in" by the electrically driven compressor, is compressed and "pumped" to a higher temperature level. The electrical power needed to run the compressor is not lost, but most of the generated heat is transferred to the refrigerant as well.
Subsequently, the refrigerant is passed through the condenser where it transfers its heat energy to the heating water.
Based on the thermostat setting, the heating water is thus heated to up to 55 °C.
32
PURPOSE OF HEAT PUMP BASELINE UNIT
CAUTION!
3
Page 5
5
5
TRANSPORT
MOUNTING
CAUTION!
CAUTION!
4
CAUTION!
Do not lift unit using the holes provided in the panel assemblies!
INSTALLATION
5.1 General Information
As a rule, the unit must be installed indoors on a level, smooth and horizontal surface. The entire base frame should thereby make close contact with the surface in order to ensure adequate sound insulation. Failing this, additional sound insulation measures may become necessary.
The heat pump should be located to allow safe and easy maintenance/service access. This is ensured if a clearance of approx. 1 m in front of and to each side of the heat pump is maintained.
5.2 Sound Emissions
The heat pump offers silent operation due to efficient sound insulation. To prevent noise transmission to the foundation, a suitable, sound dampening rubber mat should be placed underneath the base frame of the heat pump.
The transmission of noise to the heating system is prevented by pressure hoses already integrated into the heat pump.
TRANSPORT
A lift truck is suited for transporting the unit on a level surface. If the heat pump needs to be transported on an uneven surface or carried up or down stairs, carrying straps may be used for this type of transport. These straps may be passed directly underneath the wooden pallet.
The heat pump is not secured to the
wooden pallet.
The heat pump must not be tilted
more than max. 45° (in either direction).
For lifting the unit without pallet, the holes provided in the sides of the frame should be used. The side panel assemblies must be removed for this purpose. Any ordinary pipe can be used as a carrying aid.
1m
1m
1m
Page 6
6
6
MOUNTING
CAUTION!
MOUNTING
6.1 General
The following connections need to be established on the heat pump:
- supply/return flow of well system
- supply/return flow of heating system
- power supply
6.2 Heating-Side Connection
The heating system must be flushed prior to connecting the heat pump.
Before completing the heat pump connections on the heating water side, the heating installation must be flushed in order to remove any impurities that may be present, as well as residues of sealing material, and the like. Any accumulation of deposits in the condenser may result in a total failure of the heat pump.
Once the installation on the heating side has been completed, the heating system must be filled, de­aerated and pressure-tested.
Heating water minimum flow rate
The heating water minimum flow rate through the heat pump must be assured in all operating states of the heating system. This can be accomplished, for example, by installing a differential pressure-free manifold or an overflow valve. The procedure for setting an overflow valve is described in the Chapter Commissioning.
Frost protection for installations prone to frost
Provided the controllers and circulating pumps are ready for operation, the frost protection feature of the controller is active. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained. In heat pump installations where a power failure cannot be readily detected (holiday house), the heating circuit must contain a suitable antifreeze product.
6.3 Heat Source-Side Connection
The following procedure must be observed when making the connection:
Connect the well lines to the flow and return pipes of the heat pump.
The well water must meet the required
water quality standard.
6.4 Electrical Connection
The following electrical connections must be established on the heat pump.
- Connection of the control wire to the control panel of the heat pump via terminal X1: L/N/PE.
- Connection of the load wire to the control panel of the heat pump via terminal X5: L1/L2/L3/PE.
- Connection of the well pump load wire to the control panel of the heat pump via terminal X5: L11/L21/L31/PE.
- Connection of the well pump (to be provided by the customer) to the control panel of the heat pump via terminal X1: PE and pump contactor K2: 2/4/6.
When connecting the load wire of the well pump it must be ensured that the power supply for these terminals cannot be disconnected by the tariff contactor in order to ensure the cutout delay of the well pump.
All electrical components required for the operation of the heat pump are located on the control panel.
For detailed instructions concerning the connection and functioning of the heat pump controller refer to the operating manual supplied with the controller..
An all-pole disconnecting-device with a contact­gap of at least 3 mm (e.g. utility company disable contactor or power contactor) as well as a 3-pole
circuit breaker with simultaneous tripping of all external conductors. The required cross-sectional
area of the conductor is to be selected according to the power consumption of the heat pump, the technical connection requirements of the relevant electrical utility company as well as all applicable
provisions. Details on the power consumption of the heat pump are contained on the product information sheet and the rating plate. The terminals
are designed for a conductor cross-section of max. 10 mm˝.
When connecting the load line, make sure that the phase sequence is correct (if the phase sequence is not correct the heat pump will not perform properly and generate abnormal noise).
CAUTION!
CAUTION!
Page 7
7
COMMISSIONING
CARE/CLEANING
7
8
CAUTION!
COMMISSIONING
7.1 General
To ensure proper commissioning it should be carried out by an after-sales service authorized by the manufacturer. Only then can an extended warranty period of 3 years in total be granted (cf. Warranty service).
7.2 Preparation
Prior to commissioning, the following items need to be checked:
- All connections of the heat pump must have been made as described in Chapter 6.
- The heat source system and the heating circuit must have been filled and tested.
- In the well and heating circuits all valves that could impair the proper heating water flow must be open.
- The settings of the heat pump controller must be adapted to the heating installation in accordance with the instructions contained in the controller's operating manual.
7.3 Procedure
The start-up of the heat pump is effected via the heat pump controller.
Commissioning of the heat pump must be performed in accordance with the mounting and operating manual of the heat pump controller.
Where an overflow valve is fitted to assure the minimum heating water flow rate, the valve must be set in accordance with the requirements of the heating installation. An incorrect setting may result in various error symptoms and an increased electric power consumption. To correctly set the overflow valve, the following procedure is re-commended:
a) Open all heating circuits and close the overflow
valve. Determine the resulting temperature difference between supply and return flow.
b) Close all of the heating circuits that may also be
closed during operation (depending on the type of heat pump usage) so that the most unfa­vourable operating state - with respect to the water flow rate - is achieved.
Any malfunctions occurring during operation are displayed on the heat pump controller and can be corrected as described in the operating manual of the heat pump controller.
CARE/CLEANING
8.1 Care
The heat pump is maintenance-free. To prevent malfunctions due to sediments in the heat ex­changers, care must be taken that no impurities can enter the heat source system and heating installa­tion. In the event that operating malfunctions due to contamination occur nevertheless, the system should be cleaned as described below.
8.2 Cleaning of Heating Side
The ingress of oxygen into the heating water circuit may result in the formation of oxidation products (rust). It is therefore important - in particular with respect to the piping of underfloor heating systems - that the installation is executed in a diffusion-proof manner.
Also residues of lubricating and sealing agents may contaminate the heating water.
In the case of severe contamination leading to a reduction of the performance of the condenser in the heat pump, the system must be cleaned by a heating technician.
According to current knowledge, we recommend cleaning with a 5% phosphoric acid solution or, in the case that cleaning needs to be performed more frequently, with a 5% formic acid solution.
In either case, the cleaning fluid should be at room temperature. It is recommended that the heat exchanger be cleaned in the direction opposite to the normal flow direction.
To prevent acidic cleaning agents from entering the circuit of the heating installation we recommend that the flushing device be fitted directly to the supply and return lines of the condenser. To prevent any damage caused by cleaning agent residues that may be present in the system it is important that the system be thoroughly flushed using appropriate neutralising agents.
The acids must be used with great care, all relevant regulations of the employers' liability insurance associations must be adhered to.
If in doubt, contact the manufacturer of the chemicals!
Page 8
8
CARE/CLEANING MALFUNCTIONS/TROUBLESHOOTING DECOMMISSIONING
9
CAUTION!
Any work on the heat pump may only be performed by an authorized and qualified after­sales service.
Prior to opening the unit, all of its electric circuits must be disconnected from the power source.
CAUTION!
Caution - Heating Technicians ! Depending on the filling water quality and quantity, in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form, impairing the proper functioning of the heating installation. A reason for this is the water hardness and oxygen dissolved in the filling water as well as additional oxygen from the air, which may penetrate via valves, fittings and plastic pipes (oxygen diffusion). As a preventive measure it is recommended that a physical water conditio-ner such as ELYSATOR be used.
8.3 Cleaning of Heat Source Side
A strainer is fitted in the heat source inlet of the heat pump in order to protect the evaporator against contamination. Initially, the filter screen of the strainer should be cleaned at relatively short intervals. Once there is less contamination, the intervals can be extended accordingly.
8.4 Water Quality Requirements
To prevent any so-called "ochredisation" (depo­sition of iron and manganese) of the heat pump system from occurring, the ground water must be free of all substances that could result in mineral deposits, and the limit values for IRON (< 0.2 mg/ l) and MANGANESE (< 0,1 mg/l) must be complied with.
The use of surface water or saline water bodies is not permitted. Consult your local waterworks for some general information about any possible ground water usage. Water analyses are prepared by laboratories specialising in water technology.
No water analysis with respect to any corrosion of the evaporator is required if the average annual ground water temperature is not in excess of 13 °C. In this case, only the limit values for iron and manganese must be met ("ochredisation" risk).
MALFUNCTIONS/ TROUBLESHOOTING
This heat pump is a quality product and designed for trouble-free operation. In the event that a malfunction occurs nevertheless, you will be able to correct the problem easily yourself in the majority of cases. Simply consult the Malfunctions and Troubleshooting table in the operating manual of the controller.
Additional malfunctions can be interrogated at the heat pump controller.
If the problem cannot be corrected by the user, please contact the after-sales service in charge
(see Warranty Certificate).
CAUTION!
DECOMMISSIONING
10.1 Placing Out of Service in Summer
Placing the heat pump out of service in summer can be effected by switching the heat pump controller to the "Summer" operating mode.
10.2 End-of-Life Decommissioning/ Disposal
Before removing the heat pump, disconnect the machine from the power supply and close all valves. Environment-relevant requirements re­garding the recovery, recycling and disposal of service fuels and components in accordance with all relevant standards must be adhered to. In this context, particular attention must be paid to the proper disposal of refrigerants and refrigeration oils.
10
Page 9
9
APPENDIXAPPENDIX
APPENDIXAPPENDIX
APPENDIX
11.1 Dimensioned Drawing .. 9CS to .. 27CS 10
11.2 Equipment Data 11
11.3 Performance Curves / Pressure Losses
11.3.1 Performance Curves .. 9CS 12
11.3.2 Pressure Losses .. 9CS 13
11.3.3 Performance Curves .. 14CS 14
11.3.4 Pressure Losses .. 14CS 15
11.3.5 Performance Curves .. 22CS 16
11.3.6 Pressure Losses .. 22CS 17
11.3.7 Performance Curves .. 27CS 18
11.3.8 Pressure Losses .. 27CS 19
11.4 Wiring Diagrams
11.4.1 Control .. 9CS to .. 22CS 20
11.4.2 Load .. 9CS to .. 22CS 21
11.4.3 Terminal Diagram .. 9CS to .. 22CS 22
11.4.4 Legend .. 9CS to .. 22CS 23
11.4.5 Control .. 27CS 24
11.4.6 Load .. 27CS 25
11.4.7 Terminal Diagram .. 27CS 26
11.4.8 Legend .. 27CS 27
11.5 Hydraulic Block Diagram 28
11.6 EC Declaration of Conformity 29
11.7 Warranty Certificate 30
APPENDIX
11
Page 10
10
APPENDIX: 11.1 DIMENSIONED DRAWING
Dimensioned Drawing
Heating-side connections:
.. 9/14CS 1" internal/external thread
.. 22/27CS 1
1
/
4
“ internal/1" external thread
Heat source-side connections:
.. 9/14CS 1
1
/
4
“ internal/external thread
.. 22/27CS 1
1
/
2
" internal/external thread
Heating water return
Heat pump inlet
Heating water supply
Heat pump outlet
Heat source return
Heat pump inlet
Heat source supply
Heat pump outlet
Page 11
11
APPENDIX: 11.2 EQUIPMENT DATA
Equipment Data
EQUIPMENT DATA for water-to-water heat pumps for heating
1
TYPE AND COMMERCIAL DESCRIPTION ..9CS ..14CS ..22CS ..27CS
2
MODEL
2.1 Enclosure type acc. to EN 60 529 IP 20 IP 20 IP 20 IP20
2.2 Installation site indoor indoor indoor indoor
3
PERFORMANCE DATA
3.1 Operating temperature limits:
Heating water supply °C max. 55 max. 55 max. 55 max. 55
Cold water (heat source)
°C +7 to +25 +7 to +25 +7 to +25 +7 to +25
3.2
K 9,5 8,8 9,6 9,4
3.3 Heating capacity / coeff.of perform. at W7 / W55
1)
kW / --- 6,9 / 2,5 12,2 / 2,5 19,0 / 3,2 24,6 / 3,2
at W10 / W50
1)
kW / --- 7,7 / 3,2 13,4 / 3,6 20,8 / 3,8 26,4 / 3,8
at W10 / W35
1)
kW / --- 8,3 / 5,1 13,6 / 5,2 21,5 / 5,5 26,4 / 5,1
3.4 Sound power level dB(A) 53 55 58 59
3.5 Heating water flow rate at internal pressure difference m³/h / Pa 0,75 / 7000 1,3 / 7000 2,0 / 8000 2,4 / 12500
3.6 Cold water flow rate at internal pressure difference m³/h / Pa 2,0 / 6200 3,3 / 19000 5,0 / 20000 7,0 / 16000
(heat source)
3.7 Refrigerant; total charge weight type / kg R407C / 1,7 R407C / 1,6 R407C / 3,2 R407C / 4,5
4
DIMENSIONS, CONNECTIONS AND WEIGHT
4.1 Equipment dimensions without connections
4)
H x W x L mm 1380 x 600 x 500 1380 x 600 x 500 1380 x 600 x 500 1380 x 600 x 500
4.2 Equipment connections for heating system inch G 1" int/ext G 1" int/ext G1¼'' int/G1''ext G 1¼'' i / G 1'' a
4.3 Equipment connections for heat source inch G 1¼" int/ext G 1¼" int/ext G 1½" int/ext G 1½" int/ext
4.4 Weight of transport unit(s) incl. packaging kg 147 151 173 221
5
ELECTRICAL CONNECTION
5.1 Nominal voltage; fusing V / A 400 / 16 400 / 16 400 / 20 400 / 20
5.2 Nominal power consumption
1)
W10 W35 kW 1,62 2,64 3,93 5,15
5.3 Starting current with soft starter A 30 (without SS) 26 27 29
5.4
Nominal current W10 W35 / cos ϕ
A / --- 2,9 / 0,8 4,8 / 0,8 7,0 / 0,8 9,4 / 0,8
6
COMPLIES WITH EUROPEAN SAFETY REGULATIONS
3) 3) 3) 3)
7
OTHER DESIGN CHARACTERISTICS
7.1
2)
yes yes yes yes
7.2 Performance settings 1111
7.3 Controller internal / external internal internal internal internal
1)
2) The heating system circulating pump and the controller of the heat pump must be ready for operation at all times.
3) See EC Declaration of Conformity
4) Please keep in mind that more space is required for pipe connection, operation and maintenance.
Subject to technical modifications
Edition: 24.03.2004
These data characterize the size and performance capability of the system. For economic and energetic reasons, the balance point and control need to be taken into consideration as well. Abbreviations have the following meaning, e.g. W10 / W55: heat source temperature 10 °C and heating water supply temperature 55 °C.
Heating water temperature spread at W10 / W35
Water inside equipment protected against freezing 2)
Page 12
12
0
2
4
6
8
10
12
14
Heizleistung in [kW]
Wasseraustrittstemperatur in [°C]
0
1
2
3
4
5
6
7
8
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
35
50
0
1
2
3
4
5
5 7 9 11 13 15 17 19 21 23 25 27
Kaltwassereintrittstemperatur in [°C]
35
50
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
Bedingungen:
Heizwasserdurchsatz 0,75 m³/h
Kaltwasserdurchsatz 2,0 m³/h
35
50
11.3.1 Performance Curves .. 9CS
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
Conditions:
Heating water flow rate 0.75 m3/h Cold water flow rate 2.0 m3/h
Heating capacity in [kW]
Water outlet temperature in [°C]
Coefficient of performance in the heating mode (incl. proportional pump energy)
Power consumption (incl. proportional pump energy)
Cold water inlet temperature in [°C]
Page 13
13
0
2000
4000
6000
8000
10000
12000
14000
16000
18000
20000
0 0,5 1 1,5 2 2,5 3 3,5 4
Kaltwasserdurchfluß in [m³/h]
Druckverluste Verdampfer
bei 10°C
Druckverlust 6,2 kPa bei
Kaltwasser-Nenndurchfluß 2,0 m³/h
Druckverlust in [Pa]
0
5000
10000
15000
20000
25000
30000
0 0,25 0,5 0,75 1 1,25 1,5
Heizwasserdurchfluß in [m³/h]
Druckverlust in [Pa]
Druckverluste Verflüssiger
bei 35°C
Druckverlust 7 kPa bei
Heizwasser-Nenndurchfluß 0,75 m³/h
11.3.2 Pressure Losses .. 9CS
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
Pressure loss in [Pa]
Pressure losses
evaporator at 10°C
Pressure loss 6.2 kPa at
cold water nominal flow rate 2.0 m3/h
Cold water flow rate in [m3/h]
Pressure loss in [Pa]
Pressure losses
condenser at 35°C
Pressure loss 7 kPa at
heating water nominal flow rate 0.75 m3/h
Heating water flow rate in [m3/h]
Page 14
14
0
2
4
6
8
10
12
14
16
18
20
22
24
Heizleistung in [kW]
Wasseraustrittstemperatur in [°C]
0
1
2
3
4
5
6
7
8
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
35
50
0
1
2
3
4
5
5 7 9 111315171921232527
Kaltwassereintrittstemperatur in [°C]
35
50
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
Bedingungen: Heizwasserdurchsatz 1,3 m³/h Kaltwasserdurchsatz 3,3 m³/h
35
50
11.3.3 Performance Curves .. 14CS
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
Heating capacity in [kW]
Conditions:
Heating water flow rate 1.3 m3/h Cold water flow rate 3.3 m3/h
Water outlet temperature in [°C]
Coefficient of performance in the heating mode (incl. proportional pump energy)
Power consumption (incl. proportional pump energy)
Cold water inlet temperature in [°C]
Page 15
15
0
5000
10000
15000
20000
25000
30000
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5
Kaltwasserdurchfluß in [m³/h]
Druckverluste
Verdampfer bei 10°C
Druckverlust 19 kPa bei
Kaltwasser-Nenndurchfluß 3,3 m³/h
Druckverlust in [Pa]
0
5000
10000
15000
20000
25000
30000
0 0,25 0,5 0,75 1 1,25 1,5 1,75 2 2,25 2,5
Heizwasserdurchfluß in [m³/h]
Druckverlust in [Pa]
Druckverluste
Verflüssiger bei 35°C
Druckverlust 7 kPa bei
Heizwasser-Nenndurchfluß 1,3 m³/h
11.3.4 Pressure Losses .. 14CS
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
Pressure loss in [Pa]
Pressure losses
evaporator at 10°C
Pressure loss 19 kPa at
cold water nominal flow rate 3.3 m3/h
Cold water flow rate in [m3/h]
Pressure loss in [Pa]
Pressure losses
condenser at 35°C
Pressure loss 7 kPa at
heating water nominal flow rate 1.3 m3/h
Heating water flow rate in [m3/h]
Page 16
16
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
Heizleistung in [kW]
Wasseraustrittstemperatur in [°C]
0
1
2
3
4
5
6
7
8
9
10
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
35
50
0
1
2
3
4
5
6
7
5 7 9 111315171921232527
Kaltwassereintrittstemperatur in [°C]
35
50
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
Bedingungen: Heizwasserdurchsatz 2,0 m³/h Kaltwasserdurchsatz 5,0 m³/h
35 50
11.3.5 Performance Curves .. 22CS
APPENDIXG: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
Heating capacity in [kW]
Water outlet temperature in [°C]
Conditions:
Heating water flow rate 2.0 m3/h Cold water flow rate 5.0 m3/h
Coefficient of performance in the heating mode (incl. proportional pump energy)
Power consumption (incl. proportional pump energy)
Cold water inlet temperature in [°C]
Page 17
17
0
5000
10000
15000
20000
25000
30000
35000
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6
Kaltwasserdurchfluß in [m³/h]
Druckverluste
Verdampfer bei 10°C
Druckverlust 20 kPa bei
Kaltwasser-Nenndurchfluß 5,0 m³/h
Druckverlust in [Pa]
0
5000
10000
15000
20000
25000
30000
35000
0 0,5 1 1,5 2 2,5 3 3,5 4
Heizwasserdurchfluß in [m³/h]
Druckverlust in [Pa]
Druckverluste
Verflüssiger bei 35°C
Druckverlust 8 kPa bei
Heizwasser-Nenndurchfluß 2,0 m³/h
11.3.6 Pressure Losses .. 22CS
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
Pressure losses
evaporator at 10°C
Pressure loss 20 kPa at
cold water nominal flow rate 5.0 m3/h
Pressure loss in [Pa]
Cold water flow rate in [m3/h]
Pressure loss in [Pa]
Pressure losses
condenser at 35°C
Pressure loss 8 kPa at
heating water nominal flow rate 2.0 m3/h
Heating water flow rate in [m3/h]
Page 18
18
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
Heizleistung in [kW]
Wasseraustrittstemperatur in [°C]
0
1
2
3
4
5
6
7
8
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
3
50
0
2
4
6
8
5 7 9 111315171921232527
Kaltwassereintrittstemperatur in [°C]
35
5
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
Bedingungen: Heizwasserdurchsatz 2,4 m³/h Kaltwasserdurchsatz 7,0 m³/h
35
50
11.3.7 Performance Curves .. 27CS
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
Heating capacity in [kW]
Water outlet temperature in [°C]
Conditions:
Heating water flow rate 2.4 m3/h Cold water flow rate 7.0 m3/h
Coefficient of performance in the heating mode (incl. proportional pump energy)
Power consumption (incl. proportional pump energy)
Cold water inlet temperature in [°C]
Page 19
19
0
5000
10000
15000
20000
25000
30000
35000
40000
45000
50000
012345678910
Kaltwasserdurchfluß in [m³/h]
Druckverluste
Verdampfer bei 10°C
Druckverlust 16 kPa bei
Kaltwasser-Nenndurchfluß 7,0 m³/h
Druckverlust in [Pa]
0
5000
10000
15000
20000
25000
30000
35000
40000
0 0,5 1 1,5 2 2,5 3 3,5 4
Heizwasserdurchfluß in [m³/h]
Druckverlust in [Pa]
Druckverluste
Verflüssiger bei 35°C
Druckverlust 12,5 kPa bei
Heizwasser-Nenndurchfluß 2,4 m³/h
APPENDIX: 11.3 PERFORMANCE CURVES/PRESSURE LOSSES
11.3.8 Pressure Losses .. 27CS
Pressure loss in [Pa]
Pressure losses
evaporator at 10°C
Pressure loss 16 kPa at
cold water nominal flow rate 7.0 m3/h
Cold water flow rate in [m3/h]
Pressure loss in [Pa]
Pressure losses
condenser at 35°C
Pressure loss 12.5 kPa at
heating water nominal flow rate 2.4 m3/h
Heating water flow rate in [m3/h]
Page 20
20
11.4.1 Control .. 9CS to .. 22CS
APPENDIX: 11.4 WIRING DIAGRAMS
ID8
230 VAC - 50Hz
230 VAC
24 VAC
T1
12 pol.
12 pol.
PE
Netz
X1
3
N
F3
4,0A Tr
L
4,0A Tr
F2
95
F15
96
Verdi.
J12
V2
NO2
X2-G
J5-IDC1
R2
0 VAC
24VAC
J1
G
G
0
R7
X3
B
2
J2
B
1
J3
+VD
C
GND
BC4
B
3
B
4
B
5
J10J9
N1
V1
NO1
J11
C
1
F2 (L)
K1-A1
J14-C7
BC5
J4
VG0
V
G
Y
1
Y
4
Y
3
Y
2
Stö.- M1
X2
24VAC
Stö.- M11
A2
ID7
A1
J1-G
EVS
SPR
J5
ID6
ID3
ID2
ID1
ID4
ID5
NO6
NO3
J13
NO5
NO4
C
4
K5-A1
C
1
C
4
F3 (L)
F4
A1K1A2
K5
A1
F15-A2
0 VAC
J5-IDC1
X4
EGS
J6
B
7
Stö.-Durchfluss
R6
F >
F10
B
6
0 VAC
J1-G0
IDC
1
J12-C1
J13-C4
B
8
J7
ID1
0
ID1
1
ID1
2
GND
ID9
IDC
9
C
7
J14 J15
NO7
NO8
NC8
C
7
C
8
J16
NO9
C
9
NO1
0
NO1
1
C
9
P >
NDHD
F5
P <
F4
J8
ID13H
IDC13
ID14H
ID1
3
ID1
4
M1
M11
J12/NO1
J12/NO3
NO1
2
J17 J18
NC1
3
NO1
3
C12
NC1
2
C13
J12-C1
F5
Mains
Page 21
21
11.4.2 Load .. 9CS to .. 22CS
APPENDIX: 11.4 WIRING DIAGRAMS
Verdrahtung bei Auslieferung
(nicht in W I 9CS)
N7
K1
/1.6
RTS
3
M
U WV
(Einspeisung Brunnenpumpe direkt)
(Einspeisung Verdichter über EVU-Sperrschütz)
3
3/PE 400VAC - 50Hz
Netz
3/PE 400VAC - 50Hz
Netz
L1
L2PEL3
3
2 64
531
L11
L21
L31
PE
3
X5
M
3
M1
2
PE
X1/
SP2A/6 / 1,4A
SP8A/5 / 2,3A
SP3A/6 / 1,4A
SP5A/4 / 1,4A
Hersteller: Grundfos
Pumpen-T yp / Nennstrom
1,4-2,0A (WI 9CS bis -22CS)
2,2-3,5A (WI 27CS)
M11
F15
64
96
In Anlagen ohne EVU-Sperre
kann die direkte Einspeisung
Verdrahtung ändern:
für die Brunnenpumpe
entfallen.
1 3 5
K5
95 /1.4
/1.3
K22
Mains power supply
Mains power supply
(direct supply of well pump)
(compressor supply via utility
company disable contactor)
Wiring upon delivery
Wiring modification:
In systems without utility
company disable facility,
the direct supply for the well
pump may be dispensed with.
(not in WI 9CS)
Manufacturer
Pump type / Nominal current
Page 22
22
11.4.3 Terminal Diagram .. 9CS to .. 22CS
APPENDIX: 11.4 WIRING DIAGRAMS
230 VAC - 50H z
PE
F3 (L)
X1
ID8
F3
J11
F2 (L)
J12
K5-A1
J13
X3
R1
G
G
0
J1
N1
J9 J10
R7
R2
R3
B
5
B
1
J2
B
2
+VD
C
BC4
GND
B
3
B
4
J3
Kontakt offen = WP gesperrt
Die Funktion des 2ten WE
ist wählbar
EVU-Sperrschütz
T<
BC5
VG0
V
G
Y
1
Y
4
Y
3
Y
2
J4
SPR
EVS
T<
ID7
ID6
ID3
ID2
ID1
ID4
ID5
J5
C
1
NO3
NO2
NO1
C
1
K1-A1
V2 V1
Verd i.
3L/PE 400VAC - 50Hz
P
E
Netz
L
2
X5
L
1
L
3
4
xxxxx
N10
M11
2
NO5
NO4
NO6
C
4
-PE
-N
X1
-N
X1
C
4
-PE
-N
X1
HK
Heizsta
b
oder
M13E10
Netz
3
12 pol.
12 pol.
X1
N
M18
J14 J15 J16 J17 J18
0 VAC
J1-G0
24VAC
Kontakt offen = WP gesperrt
2ter Sperr eingang
X2
0 VAC
R5
J1-G0
IDC
1
B
6
J1-G
X4
IDC
9
B
7
J6
B
8
ID1
0
ID1
1
ID1
2
GND
ID9
J7
ID13H
IDC13
ID14H
ID1
3
ID1
4
J8
-PE
E9
-N
43
-N
C
7
NO7
NO8
NC8
C
7
C
8
-PE-PE
-N
X1
MZMA
F2
NO9
NO1
0
NO1
1
C
9
C
9
X1X1
-N
Mischer-
Hauptkreis
4,0A Tr
4,0A Tr
L
X1
3
M16
324
NO1
3
NO1
2
NC1
2
C12
MZ
-PE X1
MA
-N
NC1
3
C13
3
M15
M22
K20
M21
K21
B3 B4
K22 K23
K12
K11
T
1
L
1
max.
200W
A2(-)
A1(+)
J13-C
4
L
1
T
1
M19
A1(+)
A2(-)
J14-C
7
H5
max.
200W
N11
X1 - N
Mains power supply
Mains power supply
Mixer primary
circuit
Utility company shut-off contactor
Contact open = HP disabled
The function of the suppl. heating
system can be selected
2
nd
shut-off input
Contact open = HP disabled
Page 23
23
11.4.4 Legend .. 9CS TO .. 22CS
APPENDIX: 11.4 WIRING DIAGRAMS
A1 Wire jumper, must be removed upon installation of a utility company disable contactor A2 Wire jumper, must be removed if 2nd disable input is used
B3* Thermostat, hot water B4* Thermostat, swimming pool water
E9* Electr. immersion heater, hot water E10* Suppl. heat source (boiler or electr. heating element
F2 Load fuse for N1 relay outputs across J12 at J13 4.0 A slow-acting F3 Load fuse for N1 relay outputs across J15 to J18 4.0 A slow-acting F4 Pressostat high pressure F5 Pressostat low pressure (from ..22CS, F5 is a limiter with manual reset) F10 Flow control switch F15 Overload relay for M11 / the overload relay is designed for the pump included in the brine kit
H5* Fault indicator lamp
J1...J18 Terminal connector at N1
K1 Contactor, compressor K5 Contactor, primary pump K11* Electron. relay remote fault indicator (on relay module) K12* Electron. relay, swimming pool water circulating pump (on relay module) K20* Contactor for E10 K21* Contactor for E9 K22* Utility company disable contactor K23* SPR auxiliary relay
M1 Compressor M11* Primary pump M13* Heating circulating pump M15* Heating circulating pump M16* Auxiliary circulating pump M18* Hot water circulating pump M19* Swimming pool water circulating pump M21* Mixer, primary circuit M22* Mixer heating circuit 2
N1 Heat pump controller N7 Soft start control (not in WI 9CS units) N10* Remote control station N11* Relay module
R1 External sensor R2 Return sensor R3 Hot water sensor (as an alternative to the hot water thermostat) R5 Sensor for heating circuit 2 R6 Freeze protection sensor R7 Coding resistor 10k
T1 Safety isolating transformer 230/24VAC-28VA
X1 Terminal strip mains control L/N/PE-230VAC-50Hz/fuses/N and PE terminal block X2 Terminal strip 24VAC terminal block X3 Terminal strip GND terminal block for sensors R1/-2 and -3 at J2 X4 Terminal strip GND terminal block for sensors R5 and -6 at J6 X5 Terminal strip power supply 3L/PE-400VAC-50Hz
Abbreviations:
EVS Utility company disable input SPR Supplementary disable input
MA* Mixer OPEN - primary heating circuit MZ Mixer CLOSED - primary heating circuit
* Components to be supplied by the customer, or available as accessories
Page 24
24
11.4.5 Control .. 27CS
ANHANG: 11.4 WIRING DIAGRAMS
Stö.- M1
F14-T1
1
11
14
2
ID8
M1
M2
230 VAC - 50Hz
24 VAC
230 VAC
T1
12 pol.
12 pol.
PE
X1
Netz
3
N
F3
4,0A Tr
2
B1
Y4
L 1
1
4,0A Tr
P >
F2
4
14
Q1
11
J12
BC5
X2-G
J5-IDC1
R2
X3
B
1
0 VAC
24VAC
J1
G
G
0
R7
B
5
B
2
J2
J3
J13-NO6
+VD
C
GND
BC4
B
3
B
4
J10
N1
J9
Ver di.
V2
NO2
V1
C
1
F2 (L)
K1.2
-A1
NO1
J11
J1-G
J14-C7
J4
VG0
V
G
Y
1
Y
4
Y
3
Y
2
Stö.- M11
X2
24VAC
A2
A1
J5
ID7
ID6
ID3
ID2
ID1
ID4
ID5
SPR
EVS
J13
NO3
C
1
K5-A1
C
4
NO4
X1-1
F3 (L)
NO6
NO5
C
4
T1
T2
Q2
F14
F12
K1.2
A1
A2
K1.1
K1
A1
A2
A1
A2
18
16
15
K1.2
K5
A1
A2
0 VAC
J5-IDC1
X4
J6
B
7
EGS
Stö.-Durchflu s s
R6
F >
F10
B
6
J1-G0
0 VAC
IDC
1
J13-C4
J14-C7
IDC
9
B
8
J7
ID1
0
ID1
1
ID1
2
GND
ID9
C
7
J14
NO7
NO8
NC8
C
7
C
8
J15
C
9
NO9
NO1
0
NO1
1
C
9
J16
J12/NO1
HD
P >
F5
P <
ND
F4
J8
ID13H
IDC13
ID14H
ID1
3
ID1
4
M1
M11
J12/NO3
NO1
2
NC1
3
NO1
3
C12
NC1
2
J17
C13
J18
F4
F5
J12-C1
J12-C1
Mains power supply
Page 25
25
11.4.6 Load .. 27CS
APPENDIX: 11.4 WIRING DIAGRAMS
Verdrahtung ändern:
In Anlagen ohne EVU-Sperre,
kann die direkte Einspeisung
für die Brunnenpumpe entfallen.
Hersteller: Grundfos
Pumpen-Typ / Nennstrom
SP8A / 2,3A
X1
(Einspeisung Verdichter über EVU-Sperrschütz)
3/PE 400VAC - 50Hz
(Einspeisung Brunnenpumpe direkt)
Netz
3/PE 400VAC - 50Hz
3
Netz
Verdrahtung bei Auslieferung
PE
L31
L21X5L11
3
L2
3
PE
L3
X5
L1
N7
1
11
M1
3
M
M11
135
PE
K5
246
/1.8
246
14
I >I > I >
12 / 1.4
-/1.5
2
F14
/1.5
M2
M
3
M1
U V W
2,2-3,5A
Q1
131355
11
6
5
6
R
F12
2
1
TS
K1.1
46
/1.8
24
35 13
I >
24
I > I >
/1.8
K1
14 12 / 1.5
1313
2,2-3,5A
Q2
55
K22
(direct supply of well pump)
Mains power supply
(compressor supply via utility company
disable contactor)
Mains power supply
Manufacturer
Pump type / Nominal current
Wiring modification:
In systems without utility
company disable facility,
the direct supply for the well
pump may be dispensed with.
Wiring upon delivery
Page 26
26
11.4.7 Terminal Diagram .. 27CS
APPENDIX: 11.4 WIRING DIAGRAMS
230 VAC - 50Hz
12 pol.
-PE
J10J9
J11 J12 J13
BC5
X3
R2
B
1
R1
G
G
0
J1
N1
R7
R3
B
5
J2
B
2
BC4
B
3
GND
B
4
J3
+VD
C
Kontakt offen = WP gesperrt
Die Funktion des 2ten WE
ist wählbar
EVU-Sperrschütz
T<
V
G
Y
1
Y
4
Y
3
Y
2
VG0
J4
SPR
T<
EVS
ID7
ID6
ID3
ID2
ID1
ID4
ID5
J5
ID8
N10
xxxxx
NO2
K1.2
-A1
C
1
NO1
F2 (L)
Verdi.
V1
V2
3L/PE 400VA C - 50Hz
2 x Netz
4
L
2
X5
L
1
L
3
4
P
E
P
E
L11
L21
L31
2
C
4
X1
-PE
NO5
NO4
NO6
C
4
NO3
C
1
K5-A1
-N-N
X1
F3 (L)
X1
Heizsta
b
oder
HK
E10
M11
N
12 pol.
X1
X1-
-N
-PE
1
Netz
M18
M13
J14 J15 J16 J17 J18
0 VAC
J1-G0
Kontakt offen = WP gesperrt
2ter Sperreingang
J6
0 VAC
X2
24VAC
R5
B
6
J1-G0
IDC
1
J1-G
B
7
X4
IDC
9
B
8
ID1
0
ID1
1
ID1
2
GND
ID9
J7
ID13H
IDC13
ID14H
ID1
3
ID1
4
J8
E9
3
C
9
-PE
C
7
NO7
NO8
NC8
C
7
C
8
-N-N
X1
MZMA
F3 F2
-PE
NO9
NO1
0
NO1
1
C
9
X1X1
-N -N
3
4,0A Tr
4,0A Tr
PE L
X1
3
4
M16
3
2
-PE
NO1
3
NO1
2
C12
NC1
2
MZN
X1
MAN
-N
C13
NC1
3
3
M15
4
M22
K20
M21
K12
K11
T
1
L
1
max.
200W
A2(-)
A1(+)
J13-C
4
L
1
T
1
M19
A1(+)
A2(-)
J14-C
7
H5
max.
200W
N11
X1 - N
B3 B4
K22
K23
K21
2x Mains power supply
Mains power supply
2
nd
shut-off input
Contact open = HP disabled
Utility company shut-off contactor
Contact open = HP disabled
The function of the suppl. heating
system can be selected
Page 27
27
11.4.8 Legend .. 27CS
APPENDIX: 11.4 WIRING DIAGRAMS
A1 Wire jumper, must be removed upon installation of a utility company disable contactor A2 Wire jumper, must be removed if 2nd disable input is used
B1 Pressostat power adaptation for hot water preparation B3* Thermostat, hot water B4* Thermostat, swimming pool water
E9* Electr. immersion heater, hot water E10* Suppl. heating system
F2 Load fuse for N1 relay outputs across
J12 and J13 4,0 A slow-acting
F3 Load fuse for N1 relay outputs across J15 to J18 4.0 A slow-acting F4 Pressostat high pressure F5 Pressostat low pressure limiter with manual reset F10 Flow control switch F12 Thermal protector N7 F14 Electronic motor protection compressor 1
H5* Remote fault indicator lamp
J1...J18 Terminal connector at N1
K1 Contactor, compressor K1.1 Contactor, breakaway starting current limiter of M1 K1.2 Time relay, delay K1 K5 Contactor for M1 K11* Electron. relay for H5 K12* Electron. relay for M19 K20* Contactor for E10 K21* Contactor for E9 K22* Utility company disable contactor K23* SPR auxiliary relay
M1 Compressor M11* Primary pump M13* Heating circulating pump M15* Circulating pump, heating circuit 2 M16* Auxiliary circulating pump M18* Hot water circulating pump M19* Swimming pool water circulating pump M21* Mixer primary circuit M22* Mixer heating circuit 2
N1 Heat pump controller N7 Soft start board N10* Remote control station N11* Relay module
Q1 Power circuit-breaker, well pump Q2 Power circuit-breaker, compressor
R1 External sensor R2 Return sensor R3* Hot water sensor (as an alternative to the hot water thermostat) R5 Sensor for heating circuit 2 R6 Freeze protection sensor R7 Coding resistor 10k
T1 Safety isolating transformer 230/24VAC-28VA
X1 Terminal strip mains control L/N/PE-230VAC-50Hz/fuses/N and PE terminal block X2 Terminal strip 24VAC terminal block X3 Terminal strip GND terminal block for sensors R1/-2 and -3 at J2 X4 Terminal strip GND terminal block for sensors R5 and -6 at J6 X5 Terminal strip power supply 3L/PE-400VAC-50Hz
Y4 Solenoid valve power adaptation for hot water preparation
Abbreviations: EVS Utility company disable input SPR Supplementary disable input MA* Mixer OPEN - primary heating circuit MZ Mixer CLOSED - primary heating circuit * Components to be supplied by the customer, or available as accessories
Page 28
28
APPENDIX: 11.5 HYDRAULIC BLOCK DIAGRAM
Hydraulic Block Diagram
Heat pump
Buffer tank
Heat pump controller
Electric distribution
Hot water tank
Ground water
direction of flow
Suction well
Injection well
Shut-off valve
Shut-off valve with drain
Overflow valve
Safety valve
Circulating pump
Expansion vessel
Thermostat/manual valve
Check valve
Shut-off valve with check valve
Heat consumer
Strainer
Temperature sensor
Flexible connecting hose
Well circulating pump
Heating circulating pump
Hot water circulating pump
External wall sensor
Return sensor
Hot water sensor
Cold water
Hot water
Page 29
29
APPENDIX: 11.6 EC DECLARATION OF CONFORMITY
EC Declaration of conformity
Declaration of Conformity
The undersigned
KKW Kulmbacher Klimageräte-Werk GmbH, Division Dimplex Am Goldenen Feld 18 D-95326 Kulmbach
hereby confirm that the design and construction of the product(s) listed below, in the version(s) placed on the market by us, conform to the relevant basic requirements of the applicable EC directives.
This declaration becomes invalidated if any modifications are made to the product(s) without our prior authorization.
Designation of the product(s): EC Directives:
Brine-to-water heat pumps
EC Low Voltage Directive
for indoor installation withR407C (73/23/EEC)
EC EMC Directive (89/336/EEC)
Water-to-water heat pumps
Pressure Equipment Directive
for indoor installation withR407C (97/23/EEC)
Type(s): Harmonized EN Standards:
Order No.: National Standard/Directives:
Kulmbach, 07.05.2002
General Manager Technical Director
SI 5CS SI 7CS SI 9CS SI 11CS SI 14CS SI 17CS SI 21CS
WI 9CS WI 14CS WI 22CS WI 27CS
337 280 337 290 337 300 337 310 337 320 337 330 337 340
Requirements of category II
338 720 337 350 337 360 337 370
Page 30
Notes
Page 31
Notes
Page 32
32
KKW Kulmbacher Klimageräte-Werk GmbH Subject to technical modifications Division Dimplex Fax (0 92 21) 709-589 Am Goldenen Feld 18 www.dimplex.de D-95326 Kulmbach
Loading...