Dimplex SI 5MSR, SI 11MSR, SI 7MSR, SI 9MSR Mounting And Operating Manual

1
MOUNTING and
OPERATING MANUAL
Brine-to-Water Heat Pump
for Indoor Installation
SI 9MSR SI 11MSR
CE
Order No.: 452232.67.04 FD 8404
2
CONTENTS
1 READ IMMEDIATELY 3
1.1 Important Information
1.2 Legal Provisions and Directives
1.3 Energy-Efficient Use of the Heat Pump
2 PURPOSE OF THE HEAT
PUMP 4
2.1 Application
2.2 Principle of Operation
3 BASELINE UNIT 4
4 ACCESSORIES 5
4.1 Brine Manifold
5 TRANSPORT 5
6 INSTALLATION 6
6.1 General Information
6.2 Sound Emissions
7 MOUNTING 6/7
7.1 General
7.2 Connection on Heating Side
7.3 Connection on Heat Source Side
7.4 Electrical Connection
8 COMMISSIONING 7
8.1 General
8.2 Preparation
8.3 Procedure for Commissioning
9 CARE/CLEANING 8
9.1 Care
9.2 Cleaning of Heating Side
9.3 Cleaning of Heat Source Side
10 MALFUNCTIONS/TROUBLE-
SHOOTING 9
11 DECOMMISSIONING 9
11.1 Shutdown in Summer
11.2 End-of-Life Decommissioning
12 Appendix 10
3
READ IMMEDIATELY
1.1 Important Information
The heat pump is not attached to the
wooden pallet.
The heat pump must not be tilted
more than max. 45° (in either direction).
Do not lift unit by the holes in the
panel assemblies!
Flush the heating system prior to
connecting the heat pump.
The supplied strainer is to be fitted in the heat source inlet of the heat pump in order to protect the evaporator against contamina­tion.
The brine must contain at least 25 % of a frost and corrosion protection agent on a monoethyleneglycol or propyleneglycol basis.
Commissioning of the heat pump must be performed in accordance with the mounting and operating manual of the heat pump controller.
Any work on the heat pump may only be performed by authorised and qualified customer service technicians.
1
READ IMMEDIATELY
CAUTION!
CAUTION!
CAUTION!
CAUTION!
CAUTION!
CAUTION!
CAUTION!
All power circuits must be dis­connected from the power source prior to opening the cabinet.
1.2 Legal Provisions and Directives
This heat pump conforms to all relevant DIN/VDE regulations and EU directives. For details refer to the EC Declaration of Conformity in the appendix.
The electrical connection of the heat pump must be performed according to and conforming with all re­levant VDE, EN and IEC standards. Beyond that, the connection requirements of the local utility compa­nies have to be observed.
The heat pump is to be connected to the heat source and heating systems in accordance with all applicable provisions.
1.3 Energy-Efficient Use of the Heat Pump
By operating this heat pump you contribute to the protection of our environment. A prerequisite for an efficient operation is the proper design and sizing of the heating system and the heat source system. In particular, it is important to keep water flow temperatures as low as possible. All energy consumers connected should therefore be suitable for low flow temperatures. A 1 K higher heating water temperature corresponds to an increase in power consumption of approx. 2.5 %. Underfloor heating systems with flow temperatures between 30 °C and 40 °C are optimally suited for energy-efficient operation.
CAUTION!
CAUTION!
4
BASELINE UNIT
The baseline unit consists of a heat pump, ready for connection, for indoor installation complete with sheet metal cabinet, control panel and integrated controller. The refrigeration cycle contains the refrigerant R407C. Refrigerant R407C is CFC-free, non-ozone depleting and non-combustible.
All components required for the operation of the heat pump are located on the control panel. The power feed for the load and control current must be field­installed by the customer.
The supply lead of the brine pump (to be provided by the customer) must be connected to the control panel. When so doing, a motor protecting device is to be installed, if required.
The collector loops including brine manifold must be provided by the customer.
1 2
34
1) Condenser 3) Compressor
2) Control panel 4) Evaporator
32
PURPOSE OF HEAT PUMP BASELINE UNIT
PURPOSE OF THE HEAT PUMP
2.1 Application
The brine-to-water heat pump is designed for use in existing or newly built heating systems. Brine is used as the heat carrier in the heat source system. Ground coils, ground collectors or similar systems can be used as the heat source.
2.2 Principle of Operation
Heating
The heat generated by the sun, wind and rain is stored in the ground. This heat stored in the ground is collected by the brine circulating in the ground collector, ground coil or similar device, at low temperature. A circulating pump then conveys the "heated" brine to the evaporator of the heat pump. There, the heat is given off to the refrigerant in the refrigeration cycle. When so doing, the brine cools so that it can again take up heat energy in the brine circuit.
The refrigerant, however, is drawn in by the electrically driven compressor, is compressed and "pumped" to a higher temperature level. The electrical power needed to run the compressor is not lost in this process, but most of the generated heat is trans­ferred to the refrigerant as well.
Subsequently, the refrigerant is passed through the condenser where it transfers its heat energy to the heating water. Based on the thermostat setting, the heating water is thus heated to up to 55 °C.
Cooling
In the Cooling mode, the operating process of the evaporator and condenser is reversed.
The heating water transfers the heat to the refrigerant via the condenser that is now working as the evaporator. In the compressor the temperature of the refrigerant is raised. The heat is rejected to the brine, and ultimately to the ground, via the condenser (which acts as the evaporator in the heating mode).
5
54
ACCESSORIES
4.1 Brine Manifold
The brine manifold ties the individual collector loops of the heat source system into a single main line which is connected to the heat pump. Integrated ball valves allow individual brine circuits to be shut off for venting purposes.
ACCESSORIES
TRANSPORT
TRANSPORT
A lift truck is suited for transporting the unit on a level surface. If the heat pump needs to be transported on an uneven surface or carried up or down stairs, carrying straps may be used for this type of transport. These straps may be passed directly underneath the wooden pallet.
The heat pump is not secured to the wooden pallet.
The heat pump must not be tilted more than max. 45° (in either direction).
For lifting the unit without pallet, the holes provided in the sides of the frame should be used. The side panel assemblies must be removed for this purpose. A commercially available pipe can be used as a carrying aid.
Do not use the holes in the panel assemblies for lifting the unit!
CAUTION!
CAUTION!
CAUTION!
6
MOUNTING
7.1 General
The following connections need to be established on the heat pump:
- supply/return flow of the brine system
- supply/return flow of the heating system
- power supply
7.2 Connection on Heating Side
The heating system must be flushed prior to connecting the heat pump.
Before completing the heat pump connections on the heating water side, the heating installation must be flushed in order to remove any impurities that may be present, as well as residues of sealing material, and the like. Any accumulation of deposits in the condenser may result in a total failure of the heat pump.
Once the installation on the heating side has been completed, the heating system must be filled, de­aerated and pressure-tested.
Heating water minimum flow rate
The heating water minimum flow rate through the heat pump must be assured in all operating states of the heating system. This can be accomplished, for example, by installing a differential pressure-free manifold or an overflow valve. The procedure for setting an overflow valve is described in the Chapter Commissioning.
Frost protection for installations prone to frost
Provided the controllers and circulating pumps are ready for operation, the frost protection feature of the controller is active. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained. In heat pump installations where a power failure cannot be readily detected (holiday house), the heating circuit must contain a suitable antifreeze product.
INSTALLATION
6.1 General Information
As a rule, the unit must be installed indoors on a level, smooth and horizontal surface. The entire base frame should thereby make close contact with the surface in order to ensure adequate sound insulation. Failing this, additional sound insulation measures may become necessary.
The heat pump should be located to allow safe and easy maintenance/service access. This is ensured if a clearance of approx. 1 m in front of and to each side of the heat pump is maintained.
6.2 Sound Emissions
The heat pump offers silent operation due to efficient sound insulation. To prevent noise transmission to the foundation, a suitable, sound dampening rubber mat should be placed underneath the base frame of the heat pump.
To prevent any sound transmission to the heating system it is recommended that the heat pump is connected to the heating system by means of hose sections.
7
INSTALLATION MOUNTING
6
CAUTION!
7
7.4 Electrical Connection
The following electrical connections must be established on the heat pump:
- Connection of the control wire to the control panel of the heat pump via terminals X1: L/N/PE.
- Connection of the load wire to the control panel of the heat pump via terminals X6: L/N/PE.
- Connection of the brine pump (to be provided by the customer) to the control panel of the heat pump via terminal X1: PE and pump contactor K5: 2/4.
All electrical components required for the operation of the heat pump are located on the control panel.
For detailed instructions concerning the connection and functioning of the heat pump controller refer to the operating manual supplied with the controller.
A disconnecting device with a contact gap of at least 3 mm (e.g. utility company shut-off contactor or power contactor) as well as a 1-pole circuit breaker have to be provided. The required cross-sectional area of the conductor is to be selected according to the
7.3 Connection on Heat Source Side
The following procedure must be observed when making the connection:
Connect the brine line to the flow and return pipe of the heat pump.
The supplied strainer must be fitted in the heat source inlet of the heat pump in order to protect the evaporator against the ingress
of impurities.
In addition, a powerful vent must be installed at the highest point of the heat source system. The hydraulic plumbing diagram must be observed here.
The brine liquid must be produced prior to charging the system. The brine concentration must be at least 25 %. Freeze protection down to
-14°C can thus be ensured. Only antifreeze products on the basis of mono-
ethylene glycol or propylene glycol may be used. The heat source system must be vented and be
checked for leaks.
The brine solution must contain at least 25 % of an antifreeze and corrosion protection agent on a monoethylene glycol or
propylene glycol basis.
8
CAUTION!
MOUNTING
COMMISSIONING
CAUTION!
power consumption of the heat pump, the technical connection requirements of the relevant electrical utility company as well as all applicable regulations. Details on the power consumption of the heat pump are contained on the product information sheet and the typeplate. The terminals are designed for a max. conductor cross-section of 10 mm˝.
COMMISSIONING
8.1 General
To ensure proper commissioning it should be carried out by an after-sales service authorized by the manufacturer. Only then can an extended warranty period of 3 years in total be granted (cf. Warranty service). Commissioning must be carried out in the heating mode.
8.2 Preparation
Prior to commissioning, the following items need to be checked:
- All connections of the heat pump must have been made as described in Chapter 7.
- The heat source system and the heating circuit must have been filled and checked.
- The strainer must have been fitted in the sole inlet of the heat pump.
- In the brine and heating circuits all valves that could impair the proper heating water flow must be open.
- The settings of the heat pump controller must be adapted to the heating installation in accordance with the instructions contained in the controller's operating manual.
8.3 Commissioning Procedure
The start-up of the heat pump is effected via the heat pump controller.
Commissioning of the heat pump must be performed in accordance with the mounting and operating manual of the heat pump controller.
Where the minimum heating water flow rate is assured by means of an overflow valve, the valve must be set to meet the requirements of the heating installation. An incorrect setting may result in various error symptoms and an increased electrical power
CAUTION!
8
9
COMMISSIONING CARE/CLEANING
consumption. To correctly set the overflow valve, the following procedure is recommended:
a) Open all heating circuits and close the overflow
valve. Determine the resulting temperature difference between supply and return flow.
b) Close all of the heating circuits that may also be
closed during operation (depending on the type of heat pump usage) so that the most unfa­vourable operating state - with respect to the water flow rate - is achieved.
c) In this operating state open the overflow valve
until approximately the same temperature difference exists that was measured under a) when the overflow valve was closed and the heating circuits open.
Any malfunctions occurring during operation are displayed on the heat pump controller and can be corrected as described in the operating manual of the heat pump controller.
CARE/CLEANING
9.1 Care
The heat pump is maintenance-free. To prevent malfunctions due to sediments in the heat ex­changers, care must be taken that no impurities can enter the heat source system and heating installa­tion. In the event that operating malfunctions due to contamination occur nevertheless, the system should be cleaned as described below.
9.2 Cleaning of Heating Side
The ingress of oxygen into the heating water circuit may result in the formation of oxidation products (rust). It is therefore important - in particular with respect to the piping of underfloor heating systems
- that the installation is executed in a diffusion-proof manner.
Also residues of lubricating and sealing agents may contaminate the heating water.
In the case of severe contamination leading to a reduction of the performance of the condenser in the heat pump, the system must be cleaned by a heating technician.
CAUTION!
CAUTION!
Based on information known to date we recommend cleaning with a 5% phosphoric acid solution or, in the case that cleaning needs to be performed more frequently, with a 5% formic acid.
In either case, the cleaning fluid should be at room temperature. It is recommended that the heat exchanger is cleaned in the direction opposite to the normal flow direction.
To prevent acidic cleaning agents from entering the circuit of the heating installation we recommend that the flushing device be fitted directly to the supply and return lines of the condenser. To prevent any damage caused by cleaning agent residues that may be present in the system it is important that the system be thoroughly flushed using appropriate neutralising agents.
The acids must be used with great care, all relevant regulations of the employers' liability insurance associations must be adhered to.
If in doubt, contact the manufacturer of the chemicals!
Caution - Heating Technicians ! Depending on the filling water quality and quantity, in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form, impairing the proper functioning of the heating installation. A reason for this is the water hardness and oxygen dissolved in the filling waters as well as additional oxygen from the air, which may penetrate via valves, fittings and plastic pipes (oxygen diffusion). As a preventive measure it is recommended that a physical water conditio-ner such as ELYSATOR be used.
9.3 Cleaning of Heat Source Side
The supplied strainer is to be install­ed in the heat source inlet of the heat pump in order to protect the evaporator against conta­mination.
The filter screen of the strainer should be cleaned one day after commissioning, thereafter every week. If no more contamination can be noticed any more, the strainer filter can be removed in order to reduce pressure losses.
9
10
CAUTION!
11
All work on the heat pump may only be performed by an authorised and qualified after-sales service.
MALFUNCTIONS/TROUBLE-
SHOOTING
DECOMMISSIONING
MALFUNCTIONS/ TROUBLESHOOTING
This heat pump is a quality product and is designed for trouble-free operation. In the event that a malfunction occurs nevertheless, you will be able to correct the problem yourself in most of the cases. Simply consult the Malfunctions and Trouble­shooting table contained in the operating manual of the heat pump controller.
Additional malfunctions can be interrogated at the heat pump controller.
If you cannot correct the malfunction yourself, please contact the after-sales service agent in charge (see Warranty Certificate).
All electrical circuits must be dis­connected from the power source prior to opening the equipment.
CAUTION!
DECOMMISSIONING
11.1 Shutdown in Summer
Shutting down the heating system in summer is effected by switching the heat pump controller to the "Summer" operating mode.
11.2 End-of-Life Decommissioning/ Disposal
Before removing the heat pump, disconnect the machine from the power source and close all valves. Environment-relevant requirements regarding the recovery, recycling and disposal of service fuels and components in accordance with all relevant standards must be adhered to. Particular attention must hereby be paid to the proper disposal of refrigerants and refrigeration oils.
10
APPENDIX
12
12.1 Dimensioned Drawing 11
12.2 Equipment Data 12
12.3 Schematics
12.3.1 Heating mode .. 5MSR 13
12.3.2 Cooling mode .. 5MSR 14
12.3.3 Heating mode .. 7MSR 15
12.3.4 Cooling mode .. 7MSR 16
12.3.5 Heating mode .. 9MSR 17
12.3.6 Cooling mode .. 9MSR 18
12.3.7 Heating mode .. 11MSR 19
12.3.8 Cooling mode .. 11MSR 20
12.4 Wiring Diagram
12.4.1 Control, standard controller 21
12.4.2 Control, cooling controller 22
12.4.3 Load 23
12.4.4 Terminal diagr., standard controller 24
12.4.5 Terminal diagr., cooling controller 25
12.4.6 Legend 26
12.5 Hydraulic Block Diagram 27
12.6 EC Declaration of Conformity 28
12.7 Warranty Certificate 29
APPENDIX
Loading...
+ 22 hidden pages