be performed by authorised and qualified
customer service technicians.
CAUTION!
connected from the power source prior to
opening the cabinet.
1.2 Legal Provisions and Directives
This heat pump conforms to all relevant DIN/VDE
regulations and EU directives. For details refer to
the EC Declaration of Conformity in the appendix.
The electrical connection of the heat pump must be
performed according to and conforming with all relevant VDE, EN and IEC standards. Beyond that, the
connection requirements of the local utility companies have to be observed.
The heat pump is to be connected to the heat source
and heat distribution systems in accordance with all
applicable provisions.
Any work on the heat pump may only
All power circuits must be dis-
CAUTION!
in the heat source inlet of the heat pump in order
to protect the evaporator against contamination.
CAUTION!
of a frost and corrosion protection agent on a
monoethylene glycol or propylene glycol basis.
CAUTION!
must be observed when connecting the load
line.
The supplied strainer is to be fitted
The brine must contain at least 25 %
The clockwise phase sequence
CAUTION!
CAUTION!
must be performed in accordance with the
mounting and operating manual of the heat
pump controller.
Commissioning of the heat pump
1.3 Energy-Efficient Use of the Heat
Pump
By operating this heat pump you contribute to the
protection of our environment. A prerequisite for an
efficient operation is the proper design and sizing of
the heating system and the heat source system. In
particular, it is important to keep water flow
temperatures as low as possible. All energy
consumers connected should therefore be suitable
for low flow temperatures. A 1 K higher heating water
temperature corresponds to an increase in power
consumption of approx. 2.5 %. Underfloor heating
systems with flow temperatures between 30 °C and
40 °C are optimally suited for energy-efficient
operation.
3
Page 4
PURPOSE OF HEAT PUMP
BASELINE UNIT
PURPOSE OF THE HEAT
PUMP
2.1 Application
The brine-to-water heat pump is designed for use
in existing or newly built heating systems. Brine is
used as the heat carrier in the heat source system.
Ground coils, ground collectors or similar systems
can be used as the heat source.
2.2 Principle of Operation
The heat generated by the sun, wind and rain is
stored in the ground. This heat stored in the ground
is collected at low temperature by the brine circulating
in the ground collector, ground coil or similar device.
A circulating pump then conveys the warmed brine
to the evaporator of the heat pump. There, the heat
is given off to the refrigerant in the refrigeration cycle.
When so doing, the brine cools so that it can again
take up heat energy in the brine circuit.
BASELINE UNIT
32
The baseline unit consists of a heat pump, ready for
connection, for indoor installation, complete with sheet
metal cabinet, control panel and integrated controller.
The refrigeration cycle contains the refrigerant R407C.
Refrigerant R407C is CFC-free, non-ozone depleting
and non-combustible.
All components required for the operation of the heat
pump are located on the control panel. The power
feed for the load and control current must be fieldinstalled by the customer.
The supply lead of the brine pump (to be provided by
the customer) must be connected to the control
panel. When so doing, a motor protecting device is
to be installed, if required.
The collector loops including brine manifold must
be provided by the customer.
123
The refrigerant, however, is drawn in by the electrically
driven compressor, is compressed and "pumped"
to a higher temperature level. The electrical power
needed to run the compressor is not lost in this
process, but most of the generated heat is transferred to the refrigerant as well.
Subsequently, the refrigerant is passed through the
condenser where it transfers its heat energy to the
heating water. Based on the thermostat setting, the
heating water is thus heated to up to 55 °C.
4
1) Condenser3) Evaporator
2) Control panel4) Compressor
4
Page 5
ACCESSORIES
TRANSPORT
ACCESSORIES
4.1 Brine Manifold
The brine manifold ties the individual collector loops
of the heat source system into a single main line
which is connected to the heat pump. Integrated ball
valves allow individual brine circuits to be shut off for
venting purposes.
TRANSPORT
54
A lift truck is suited for transporting the unit on a level
surface. If the heat pump needs to be transported
on an uneven surface or carried up or down stairs,
carrying straps may be used for this type of transport.
These straps may be passed directly underneath
the wooden pallet.
CAUTION!
wooden pallet.
The heat pump is not secured to the
CAUTION!
more than max. 45° (in either direction).
For lifting the unit without pallet, the holes provided
in the sides of the frame should be used. The side
panel assemblies must be removed for this
purpose. A commercially available pipe can be used
as a carrying aid.
CAUTION!
assemblies for lifting the unit!
The heat pump must not be tilted
Do not use the holes in the panel
5
Page 6
INSTALLATION
MOUNTING
6
INSTALLATION
6.1 General Information
As a rule, the unit must be installed indoors on a
level, smooth and horizontal surface. The entire base
frame should thereby make close contact with the
surface in order to ensure adequate sound
insulation. Failing this, additional sound insulation
measures may become necessary.
The heat pump should be located to allow safe and
easy maintenance/service access. This is ensured
if a clearance of approx. 1 m in front of and to each
side of the heat pump is maintained.
1m
1m
1m
MOUNTING
7
7.1 General
The following connections need to be established
on the heat pump:
- supply/return flow of the brine system
- supply/return flow of the heating system
- power supply
7.2 Connection on Heating Side
CAUTION!
prior to connecting the heat pump.
Before completing the heat pump connections on
the heating water side, the heating installation must
be flushed in order to remove any impurities that
may be present, as well as residues of sealing
material, and the like. Any accumulation of deposits
in the condenser may result in a total failure of the
heat pump.
Once the installation on the heating side has been
completed, the heating system must be filled, deaerated and pressure-tested.
The heating system must be flushed
6.2 Sound Emissions
The heat pump offers silent operation due to efficient
sound insulation. To prevent noise transmission to
the foundation, a suitable, sound dampening rubber
mat should be placed underneath the base frame
of the heat pump.
Any sound transmission to the heating systems is
prevented by means of flexible pressure tubing
already integrated into the heat pump.
Heating water minimum flow rate
The heating water minimum flow rate through the
heat pump must be assured in all operating states
of the heating system. This can be accomplished,
for example, by installing a differential pressure-free
manifold or an overflow valve. The procedure for
setting an overflow valve is described in the Chapter
Commissioning.
Frost protection for installations prone to frost
Provided the controllers and circulating pumps are
ready for operation, the frost protection feature of the
controller is active. If the heat pump is taken out of
service or in the event of a power failure, the system
has to be drained. In heat pump installations where
a power failure cannot be readily detected (holiday
house), the heating circuit must contain a suitable
antifreeze product.
6
Page 7
MOUNTING
7.3 Connection on Heat Source Side
The following procedure must be observed when
making the connection:
Connect the brine line to the flow and return pipe
of the heat pump.
CAUTION!
in the heat source inlet of the heat pump in order
to protect the evaporator against the ingress
of impurities.
In addition, a powerful vent must be installed at
the highest point of the heat source system. The
hydraulic plumbing diagram must be observed
here.
The brine liquid must be produced prior to
charging the system. The brine concentration
must be at least 25 %. Freeze protection down to
-14°C can thus be ensured.
Only antifreeze products on the basis of mono-
ethylene glycol or propylene glycol may be used.
The heat source system must be vented (de-
aerated) and be checked for leaks.
The supplied strainer must be fitted
An all-pole disconnecting device with a contact gap
of at least 3 mm (e.g. utility company disable contactor or power contactor) as well as a 3-pole circuit
breaker with simultaneous tripping of all external
conductors must be provided . The required crosssectional area of the conductor is to be selected
according to the power consumption of the heat
pump, the technical connection requirements of the
relevant utility company and all applicable regulations. Power consumption data of the heat pump is
provided in the product literature and on the
nameplate. The terminals are designed for a max.
conductor cross-section of 10 mm˝.
CAUTION!
must be observed when connecting the load line
(the heat pump will deliver no output and will be
very noisy when the phase sequence is incorrect).
The clockwise phase sequence
CAUTION!
least 25 % of an antifreeze and corrosion
protection agent on a monoethylene glycol or
propylene glycol basis.
The brine solution must contain at
7.4 Electrical Connection
The following electrical connections must be
established on the heat pump:
-Connection of the control wire to the control panel
of the heat pump via terminals X1: L/N/PE.
-Connection of the load wire to the control panel
of the heat pump via terminals X5: L1/L2/L3/PE.
-Connection of the brine pump (to be provided by
the customer) to the control panel of the heat
pump via terminal X1: PE and pump contactor
K2: 2/4/6 (.. 5-17CS), or motor protection F7: 2/4/
6 (.. 21CS).
All electrical components required for the operation
of the heat pump are located on the control panel.
For detailed instructions concerning the connection
and functioning of the heat pump controller refer to
the operating manual supplied with the controller.
7
Page 8
COMMISSIONING
8
COMMISSIONING
8.1 General Information
To ensure proper commissioning it should be
carried out by an after-sales service authorized by
the manufacturer. Only then can an extended
warranty period of 3 years in total be granted (cf.
Warranty service).
8.2 Preparation
Prior to commissioning, the following items need to
be checked:
- All connections of the heat pump must have been
made as described in Chapter 7.
- The heat source system and the heating circuit
must have been filled and checked.
- The strainer must have been fitted in the sole
inlet of the heat pump.
b) Close all of the heating circuits that may also be
closed during operation (depending on the type
of heat pump usage) so that the most unfavourable operating state - with respect to the water
flow rate - is achieved.
c) In this operating state open the overflow valve
until approximately the same temperature
difference exists that was measured under a)
when the overflow valve was closed and the
heating circuits open.
Any malfunctions occurring during operation are
displayed on the heat pump controller and can be
corrected as described in the operating manual of
the heat pump controller.
- In the brine and heating circuits all valves that
could impair the proper heating water flow must
be open.
- The settings of the heat pump controller must be
adapted to the heating installation in accordance
with the instructions contained in the controller's
operating manual.
8.3 Commissioning Procedure
The start-up of the heat pump is effected via the heat
pump controller.
CAUTION!
must be performed in accordance with the
mounting and operating manual of the heat
pump controller.
Where an overflow valve is fitted to assure the
minimum heating water flow rate, the valve must be
set in accordance with the requirements of the
heating installation. An incorrect setting may result
in various error symptoms and an increased electric power consumption. To correctly set the overflow
valve, the following procedure is recommended:
Commissioning of the heat pump
a) Open all heating circuits and close the overflow
valve. Determine the resulting temperature
difference between supply and return flow.
8
Page 9
9
CARE/CLEANING
9.1 Care
The heat pump is maintenance-free. To prevent
malfunctions due to sediments in the heat exchangers, care must be taken that no impurities can
enter the heat source system and heating installation. In the event that operating malfunctions due to
contamination occur nevertheless, the system
should be cleaned as described below.
9.2 Cleaning of Heating Side
The ingress of oxygen into the heating water circuit
may result in the formation of oxidation products
(rust). It is therefore important - in particular with
respect to the piping of underfloor heating systems
- that the installation is executed in a diffusion-proof
manner.
Also residues of lubricating and sealing agents may
contaminate the heating water.
CAUTION!
Depending on the filling water quality and
quantity, in particular in the case of mixed
installations and plastic pipes, mineral deposits
(rust sludge, lime) may form, impairing the proper functioning of the heating installation. A
reason for this is the water hardness and
oxygen dissolved in the filling waters as well
as additional oxygen from the air, which may
penetrate via valves, fittings and plastic pipes
(oxygen diffusion). As a preventive measure it
is recommended that a physical water conditioner such as ELYSATOR be used.
Caution - Heating Technicians !
9.3 Cleaning of Heat Source Side
CAUTION!
ed in the heat source inlet of the heat pump in
order to protect the evaporator against contamination.
The supplied strainer is to be install-
CARE/CLEANING
In the case of severe contaminations leading to a
reduction of the performance of the condenser in
the heat pump, the system must be cleaned by a
heating technician.
According to current knowledge, we recommend
cleaning with a 5% phosphoric acid solution or, in
the case that cleaning needs to be performed more
frequently, with a 5% formic acid solution.
In either case, the cleaning fluid should be at room
temperature. It is recommended that the heat
exchanger be cleaned in the direction opposite to
the normal flow direction.
To prevent acidic cleaning agents from entering the
circuit of the heating installation we recommend that
the flushing device be fitted directly to the supply
and return lines of the condenser. To prevent any
damage caused by cleaning agent residues that
may be present in the system it is important that the
system be thoroughly flushed using appropriate
neutralising agents.
The acids must be used with great care, all relevant
regulations of the employers' liability insurance
associations must be adhered to.
The filter screen of the strainer should be cleaned
one day after commissioning, thereafter every week.
If no more contamination can be noticed any more,
the strainer filter can be removed in order to reduce
pressure losses.
If in doubt, contact the manufacturer of the chemicals!
9
Page 10
MALFUNCTIONS/TROUBLESHOOTING
DECOMMISSIONING
MALFUNCTIONS/
10
CAUTION!
TROUBLESHOOTING
This heat pump is a quality product and is designed
for trouble-free operation. In the event that a
malfunction occurs nevertheless, you will be able to
correct the problem yourself in most of the cases.
Simply consult the Malfunctions and Troubleshooting table contained in the operating manual of
the heat pump controller.
Additional malfunctions can be interrogated at the
heat pump controller.
If you cannot correct the malfunction yourself, please
contact the after-sales service agent in charge (see
Warranty Certificate).
All work on the heat pump may only
be performed by an authorised and qualified
after-sales service.
DECOMMISSIONING
11
11.1 Shutdown in Summer
Shutting down the heating system in summer is
effected by switching the heat pump controller to the
"Summer" operating mode.
11.2 End-of-Life Decommissioning/
Disposal
Before removing the heat pump, disconnect the
machine from the power source and close all valves.
Environment-relevant requirements regarding the
recovery, recycling and disposal of service fuels and
components in accordance with all relevant standards
must be adhered to. Particular attention must hereby
be paid to the proper disposal of refrigerants and
refrigeration oils.
CAUTION!
connected from the power source prior to
opening the equipment.
All electrical circuits must be dis-
10
Page 11
12
APPENDIX
APPENDIX
12.1Dimensioned Drawings
12.1.1Dimens'ddrawing .. 5CS - 14CS12
12.1.2Dimens'd drawing .. 17CS - 21CS 13
12.2Equipment Data14
12.3Performance Curves/Pressure
Losses
12.3.1Performance Curves .. 5CS15
12.3.2Pressure Losses .. 5CS16
12.3.3Performance Curves .. 7CS17
12.3.4Pressure Losses .. 7CS18
12.3.5Performance Curves .. 9CS19
12.3.6Pressure Losses .. 9CS20
12.3.7Performance Curves .. 11CS21
12.3.8Pressure Losses .. 11CS22
12.3.9Performance Curves .. 14CS23
12.3.10Pressure Losses .. 14CS24
12.3.11Performance Curves .. 17CS25
12.3.12Pressure Losses .. 17CS26
12.3.13Performance Curves .. 21CS27
12.3.14Pressure Losses .. 21CS28
12.4Wiring Diagram
12.4.1Control .. 5CS to .. 17CS29
12.4.2Load .. 5CS bis .. 17CS30
12.4.3Terminal Diagram
.. 5CS to .. 17CS31
12.4.4Legend .. 5CS to .. 17CS32
12.4.5Control .. 21CS33
12.4.6Load .. 21CS34
12.4.7Terminal Diagram .. 21CS35
12.4.8Legend .. 21CS36
12.5Hydraulic Block Diagram37
12.6EC Declaration of Conformity38
12.7Warranty Certificate39
11
Page 12
APPENDIX: 12.1 DIMENSIONED DRAWINGS
12.1.1 Dimensioned Drawing.. 5CS - 14CS
Heat source supply
Heat pump outlet
Heat source return
Heat pump inlet
1" internal / 1" external thread
Connections on heating side
1 1/4" internal / 1 1/4" external thread
Connections on heat source side
Heating water return
Heat pump inlet
Heating water supply
Heat pump outlet
12
Page 13
12.1.2 Dimensioned Drawings .. 17CS - 21 CS
APPENDIX: 12.1 DIMENSIONED DRAWINGS
Heat source supply
Heat pump outlet
Heat source return
Heat pump inlet
1 1/4" internal / 1" external thread
Connections on heating side
1 1/2" internal / 1 1/2" external thread
Connections on heat source side
Heating water return
Heat pump inlet
Heating water supply
Heat pump outlet
13
Page 14
APPENDIX: 12.2 EQUIPMENT DATA
EQUIPMENT DATA for brine-to-water heat pumps for heating purposes
1
TYPE AND COMMERCIAL DESCRIPTION..5CS..7CS..9CS..11CS..14CS..17CS..21CS
2
MODEL
2.1Enclosure type acc. to EN 60 529 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
COP in the heating mode (incl. proportional pump energy)
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
8
7
6
5
4
3
2
1
0
Power consumption (incl. proportional pump power input)
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
5
4
Bedingungen:
Conditions:
Heizwasserdurchsatz 1,0 m³/h
Heating water flow rate 1,0 m3/h
Brine flow rate 3,0 m
Soledurchsatz 3,0 m³/h
3
/h
35
50
3
2
1
0
-10 -8-6-4-20246810 1214 1618 2022 2426
Soleeintrittstemperatur in [°C]
Brine inlet temperature in [°C]
21
35
Page 22
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.8 Pressure Losses .. 11CS
Pressure loss in [Pa]
40000
Druckverlust in [Pa]
35000
Druckverluste Verdampfer
Pressure losses of evaporator
at –5°C brine temperature
bei Sole -5°C
without brine accessories
ohne Solezubehör
30000
Pressure loss 13 kPa at a
Druckverlust 13 kPa bei
rated brine flow rate of 3.0 m3/h
Sole-Nenndurchfluß 3,0 m³/h
25000
20000
15000
10000
5000
0
00,511,522,533,544,55
3
/h]
Pressure loss in [Pa]
Druckverlust in [Pa]
Brine flow rate in [m
Soledurchfluß in [m³/h]
16000
14000
Druckverluste Verflüssiger
Pressure losses of condenser at
35°C heating water outlet temperature
bei HWA 35°C
12000
Pressure loss 3.5 kPa at a
Druckverlust 3,5 kPa bei
rated heating water flow rate of 1.0 m3/h
10000
Heizwasser-Nenndurchfluß 1,0 m³/h
8000
6000
4000
2000
0
00,20,40,60,811,21,41,61,82
Heizwasserdurchfluß in [m³/h]
Heating water flow rate in [m3/h]
22
Page 23
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.9 Performance Curves .. 14CS
Heating capacity in [kW]
Heizleistung in [kW]
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
Wasseraustrittstemperatur in [°C]
Water outlet temperature in [°C]
Bedingungen:
Conditions:
Heating water flow rate 1,3 m3/h
Heizwasserdurchsatz 1,3 m³/h
Brine flow rate 3,5 m3/h
Soledurchsatz 3,5 m³/h
35
50
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
COP in the heating mode (incl. proportional pump energy)
8
7
6
5
4
3
2
1
0
Power consumption (incl. proportional pump power input)
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
5
4
3
2
1
35
50
50
35
0
-10 -8-6-4-2024681012 141618 20222426
Soleeintrittstemperatur in [°C]
Brine inlet temperature in [°C]
23
Page 24
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.10 Pressure Losses .. 14CS
Pressure loss in [Pa]
30000
25000
20000
15000
Druckverlust in [Pa]
Druckverluste Verdampfer
Pressure losses of evaporator
bei Sole -5°C
at –5°C brine temperature
without brine accessories
ohne Solezubehör
Pressure loss 13 kPa at a
Druckverlust 13 kPa bei
rated brine flow rate of 3.5 m3/h
Sole-Nenndurchfluß 3,5 m³/h
10000
5000
0
00,511,522,533,544,55
3
/h]
Pressure loss in [Pa]
Druckverlust in [Pa]
Brine flow rate in [m
Soledurchfluß in [m³/h]
14000
12000
10000
Druckverluste Verflüssiger
Pressure losses of condenser at
35°C heating water outlet temperature
rated heating water flow rate of 1.3 m3/h
Heizwasser-Nenndurchfluß 1,3 m³/h
bei HWA 35°C
Pressure loss 3.5 kPa at a
Druckverlust 3,5 kPa bei
8000
6000
4000
2000
0
00,20,40,60,811,21,41,61,822,2
Heizwasserdurchfluß in [m³/h]
Heating water flow rate in [m3/h]
24
Page 25
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
50
12.3.11 Performance Curves .. 17CS
Heating capacity in [kW]
Heizleistung in [kW]
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
Wasseraustrittstemperatur in [°C]
Water outlet temperature in [°C]
Bedingungen:
Conditions:
Heating water flow rate 1,5 m3/h
Heizwasserdurchsatz 1,5 m³/h
Brine flow rate 3,8 m3/h
Soledurchsatz 3,8 m³/h
35
50
COP in the heating mode (incl. proportional pump energy)
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
8
7
6
5
4
3
2
1
0
Power consumption (incl. proportional pump power input)
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
7
6
5
4
3
2
1
35
50
35
0
-10 -8-6-4-202468101214 161820 222426
Soleeintrittstemperatur in [°C]
Brine inlet temperature in [°C]
25
Page 26
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.12 Pressure Losses .. 17CS
Pressure loss in [Pa]
24000
22000
20000
18000
16000
14000
12000
10000
Druckverlust in [Pa]
Druckverluste Verdampfer
Pressure losses of evaporator
bei Sole -5°C
at –5°C brine temperature
without brine accessories
ohne Solezubehör
Pressure loss 9 kPa at a
Druckverlust 9 kPa bei
rated brine flow rate of 3.8 m3/h
Sole-Nenndurchfluß 3,8 m³/h
8000
6000
4000
2000
0
0123456
Brine flow rate in [m3/h]
Soledurchfluß in [m³/h]
Pressure loss in [Pa]
14000
12000
10000
8000
6000
Druckverlust in [Pa]
Druckverluste Verflüssiger
Pressure losses of condenser at
35°C heating water outlet temperature
rated heating water flow rate of 1.5 m3/h
Heizwasser-Nenndurchfluß 1,5 m³/h
bei HWA 35°C
Pressure loss 4 kPa at a
Druckverlust 4 kPa bei
4000
2000
0
00,20,40,60,811,21,41,61,822,22,42,6
Heating water flow rate in [m3/h]
Heizwasserdurchfluß in [m³/h]
26
Page 27
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.13 Performance Curves .. 21CS
Heating capacity in [kW]
Heizleistung in [kW]
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
Wasseraustrittstemperatur in [°C]
Water outlet temperature in [°C]
Bedingungen:
Conditions:
Heating water flow rate 1,6 m3/h
Heizwasserdurchsatz 1,6 m³/h
Brine flow rate 6,0 m3/h
Soledurchsatz 6,0 m³/h
35
50
COP in the heating mode (incl. proportional pump energy)
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
8
7
6
5
4
3
2
1
0
Power consumption (incl. proportional pump power input)
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
7
6
5
4
3
2
1
35
50
35
0
-10 -8-6-4-20246810 121416 1820 2224 26
Soleeintrittstemperatur in [°C]
Brine inlet temperature in [°C]
27
Page 28
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.14 Pressure Losses .. 21CS
Pressure loss in [Pa]
24000
22000
20000
18000
16000
14000
12000
10000
Druckverlust in [Pa]
Druckverluste Verdampfer
Pressure losses of evaporator
rated brine flow rate of 6.0 m3/h
Sole-Nenndurchfluß 6,0 m³/h
bei Sole -5°C
at –5°C brine temperature
ohne Solezubehör
without brine accessories
Pressure loss 12 kPa at a
Druckverlust 12 kPa bei
8000
6000
4000
2000
0
012345678
Brine flow rate in [m3/h]
Soledurchfluß in [m³/h]
Pressure loss in [Pa]
14000
12000
10000
8000
6000
Druckverlust in [Pa]
Druckverluste Verflüssiger
Pressure losses of condenser at
35°C heating water outlet temperature
rated heating water flow rate of 1.6 m3/h
Heizwasser-Nenndurchfluß 1,6 m³/h
bei HWA 35°C
Pressure loss 6 kPa at a
Druckverlust 6 kPa bei
4000
2000
0
00,511,52
Heizwasserdurchfluß in [m³/h]
Heating water flow rate in [m3/h]
28
Page 29
12.4.1 Control .. 5CS to .. 17CS
NC1
3
C13
NO1
3
NC1
2
C12
NO1
2
J17J18
C
9
NO1
1
NO1
0
J16
NO9
C
9
NC8
C
8
NO8
J15
J12/NO1
J8
J5-IDC1
J7
J6
APPENDIX: 12.4 WIRING DIAGRAMS
A1
PUP
J12/NO3
Verd.1
ID14H
J12-C1
ID1
4
IDC13
ID1
3
ID13H
IDC
9
ID1
2
ID1
1
ID1
0
ID9
GND
B
8
B
7
EGS
B
6
HDND
0 VAC
R6
F4
F5
P >
P <
X4
A2
K5
A1K1A2
C
7
NO7
C
7
C
4
NO6
NO5
NO4
C
4
K5-A1F3 (L)
C
1
NO3
NO2
V2
Verdi.
NO1
V1
C
1
F2 (L)
K1-A1
N1
J13-C4
J14
J1-G0
IDC
1
0 VAC
ID8
ID7
ID6
ID5
J5
ID4
ID3
ID2
F5
J13
F4
ID1
J1-G
Y
4
J12-C1
Y
3
Y
2
Y
1
VG0
J4
V
G
Stö.-M1
Stö.-M11
SPR
EVS
X2
A3
A1
A2
24VAC
A4
4,0ATr
F2
L
BC5
J18-C13
B
J12J11
5
BC4
J3
B
4
R7
F3
4,0ATr
3
PE
12pol.
12pol.
N
230 VAC - 50Hz
+VD
C
GND
B
3
B
2
J2
B
1
J5-IDC1
G
0
G
J1
J9J10
X2-G
R2
0 VAC
24VAC
X3
24 VAC
T1
X1
Netz
Mains system
230 VAC
29
Page 30
APPENDIX: 12.4 WIRING DIAGRAMS
12.4.2 Load .. 5CS to .. 17CS
/1.8
K5
315
426
M11
L3L2
M
L1PE
PE
3
X1
F15
SSM
SSM
X2 (24 VAC)
Blatt1 / N1
Sheet 1/N1
J5 / ID5
Remove wire jumper A3 prior to connecting M11 circulating pump motor
protection (F15) (from –9CS to –17CS).
A3 is the „M11 fault“ jumper
Vor dem Einklemmen des M11 (PUP) -Motorschutzes (F15)
(ab -9CS bis-17CS) die DrahtbrückeA3 entfernen.
A3 ist die Brücke "Störung M11"
L1
X5
L2
3
Mains
PE
L3
Netz
system
3/PE 400VAC - 50Hz
No soft starter fitted in
brine-to-water units 5C and 7C
Sanftanlasser nicht vorhanden in
/1.8
K1
6
531
42
TSR
N7
Sole/Wasser 5C und 7C
W
M1
VU
M
3
30
Page 31
12.4.3 Terminal Diagram .. 5CS to .. 17CS
APPENDIX: 12.4 WIRING DIAGRAMS
M22
M15
K21
3
3
E9
M16
M21
3
230 VAC - 50Hz
Mains system
230 VAC - 50 Hz
Netz
M18
M13
Heizsta
b
E10
oder
HK
M11
Netz
4
Mains system
3L/PE 400VAC - 50Hz
NC1
3
C13
NO1
34
-N
-PE
3
MZN
NC1
2
C12
NO1
2
MAN
ID14H
ID1
4
IDC13
J8
ID1
3
ID13H
Leitungen sind bei Bedarf bauseits zu erstellen
Lines to be field-connected, if required
X1
2
-N
-PEX1
C
9
NO1
1
NO1
0
NO9
C
9
NC8
C
8
NO8
MZ
C
7
NO7
MA
C
7
L
PE
43
X1
4,0ATr
4,0ATr
F2
F3
-N
X1
-N
-PEX1
-N
-PE
X1
12pol.
N
12pol.
X1
X1
-PE
-N
X1
-N
K20
2
N10
xxxxx
P
E
L
3
L
2
L
1
X1
-PE
-N
V2
Verdi.
V1
F3 (L)
C
4
NO6
NO5
NO4
C
4
K5-A1
C
1
NO3
NO2
NO1
C
1
F2 (L)
K1-A1
X5
J14J16J15J18J17
J13
J12
J11
J9J10
N1
J5-IDC1
IDC
9
0 VAC
ID1
2
ID1
1
J7
ID1
0
ID9
GND
B
8
B
7
J6
B
6
P<
B2
X4
R6
R5
24VAC
X2
J1-G
A3
A4
J1-G0
IDC
1
0 VAC
ID8
ID7
Stö.- M1
SPR
ID6
ID5
J5
ID4
ID3
ID2
ID1
Y
4
Y
3
Y
2
Y
1
VG0
J4
V
G
BC5
B
5
BC4
J3
B
4
+VD
C
GND
B
3
B
2
J2
B
1
G
0
G
J1
Stö.- M11
EVS
T<
B4
T<
B3
7
A1(+)
A2(-)
4
A1(+)
A2(-)
N11
R7
Cod.-WP
R3
R2
R1
K23
disable input
nd
2ter Sperreingang
2
Contact open = HP disabled
Kontakt offen = WP gesperrt
K22
J14-C
J13-C
Die Funktion von E10
Function E10 is selectable
Kontakt offen = WP gesperrt
Contact open = HP disabled
L
1
M19
max.
T
1
K12
L
1
H5
max.
T
1
ist wählbar
200W
200W
K11
X1 -N
X3
31
Page 32
APPENDIX: 12.4 WIRING DIAGRAMS
12.4.4 Legend .. 5CS to .. 17CS
A1Wire jumper, must be removed if a utility company disable contactor is used
A2Wire jumper, must be removed if 2nd disable input is used
A3Wire jumper, must be removed if a motor protection contact for primary pump is used
A4Wire jumper, must be removed if a motor protection contact for the compressor is used
B2*Pressostat low pressure, brine
B3*Thermostat, hot water
B4*Thermostat, swimming pool water
E9*Electr. immersion heater, hot water
E10*Suppl. heating system (boiler or electr. heating element)
F2Load fuse for N1 relay outputs across J12 and J134.0 A slow
F3Load fuse for N1 relay outputs across J15 to J184.0 A slow
F4Pressostat high pressure
F5Pressostat low pressure (in SI 17CS, F5 is a limiter with manual reset)
F15*Motor protection M11, from SI 9CS to SI 17CS integrated in primary pump
H5*Lamp, remote fault indicator
J1...J18Terminal connector at N1
Open wire jumpers or contacts mean: lock-out or malfunction
K1Contactor, compressor
K5Contactor, primary pump
K11*Electron. relay for remote fault indicator (relay module)
K12*Electron. relay for swimming pool water circulating pump
K20*Contactor, suppl. heating system
K21*Contactor, electr. immersion heater, hot water
K22*Utility company disable contactor
K23*SPR auxiliary contactor
N1Heat pump controller
N7Soft start control (not fitted in SI 5CS and SI 7CS appliances)
N10*Remote control station
N11*Relay module
R1External sensor
R2Return sensor
R3Hot water sensor (as an alternative to hot water thermostat)
R5Sensor for heating circuit 2
R6Freeze protection sensor
R7Coding resistor 8k
T1Safety isolating transformer 230/24V AC-28V A
X1Terminal strip mains control L/N/PE-230V AC-50 Hz/fuses/N and PE-terminal block
X2Terminal strip 24V AC-terminal block
X3Terminal strip GND terminal block for sensors R1/-2 and -3 at J2
X4Terminal stripGND terminal blocl for sensors R5 and -6 at J6
X5Terminal strip power supply 3 L/PE-400V AC-50 Hz
Abbreviations:
EVSUtility company disable input
SPRSupplementary disable input
MA*Mixer OPEN
MZMixer CLOSED
*Components to be supplied by the customer
32
Page 33
12.4.5 Control .. 21CS
NC1
3
C13
NO1
3
NC1
2
C12
NO1
2
C
9
NO1
1
NO1
0
NO9
C
9
NC8
C
8
NO8
C
7
NO7
C
7
C
4
NO6
NO5
NO4
C
4
C
1
NO3
NO2
V2
Verdi.
NO1
V1
C
1
K1.2
-A1
N1
APPENDIX: 12.4 WIRING DIAGRAMS
A2
Q2
Q1
230 VAC
A1
K5
A1
A2
18
K1
16
A1
A2
K1.1
A1
A2
K1.2
T2
T1
F14
M2
11
M1
11
4,0ATr
L
4,0ATr
3
PEN
12pol.12pol.
230 VAC - 50Hz
X1
Netz
Mains system
M11
J12/NO3
J12/NO1
ID14H
J12-C1
ID1
4
IDC13
J8
ID1
3
ID13H
J17J18
J5-IDC1
IDC
9
ID1
2
ID1
1
J7
ID1
0
ID9
J12-C1
J6
J14-C7
J1-G0
J5
J4
J18-C13
J3
J2
J5-IDC1
J1
GND
B
8
B
7
EGS
B
6
J13-C4
IDC
1
ID8
ID7
ID6
ID5
ID4
ID3
EVS
ID2
ID1
J1-G
Y
4
Y
3
Y
2
Y
1
VG0
V
G
BC5
B
5
BC4
B
4
+VD
C
GND
B
3
B
2
B
1
G
0
G
J16
J15
J14
F14-T1
F3 (L)
F5
J13
F4
K5-A1
J12
F2 (L)
J11
J10J9
X2-G
SPR
A1
M1
P >
F4
15
HDND
P <
F5
0 VAC
R6
0 VAC
X4
F12
2
1
Stö.-M1
K1.2
14
14
Stö.-M11
X2
A2
24VAC
F2
R7
R2
0 VAC
24VAC
X3
F3
24 VAC
T1
33
Page 34
APPENDIX: 12.4 WIRING DIAGRAMS
12.4.6 Load .. 21CS
12 / 1.4
11
Q1
135
14
K5
I >I >I >
M11
M
246
PE
X1
3
12 / 1.5
11
Q2
135
14
I >I >I >
K1
642
M1
5
6
13
24
K1.1
L1
L2PEL3
T
RS
F12
N7
1
2
W
UV
-/1.5
M
3
F14/1.5
M2
M1
X5
3
Mains
Netz
system
3/PE 400VAC - 50Hz
34
Page 35
12.4.7 Terminal Diagram .. 21CS
APPENDIX: 12.4 WIRING DIAGRAMS
M22
M15
K21
3
3
E9
M16
M21
3
230 VAC - 50Hz
Mains system
230 VAC - 50 Hz
Netz
M18
M13E10
Heizsta
b
oder
HK
M11
Netz
4
Mains system
3L/PE 400VAC -50Hz
NC1
3
C13
J18
NO1
3
34
-N
MANMZN
-PE
NC1
2
C12
J17
NO1
2
ID14H
ID1
4
IDC13
J8
ID1
3
ID13H
X1
2
J1-G0
IDC
N1
9
0 VAC
ID1
2
ID1
1
J7
ID1
0
ID9
GND
B
8
B
7
J6
B
6
P <
B2
2
1
4
X4
R5
24VAC
X2
J1-G
J1-G0
IDC
1
0 VAC
ID8
ID7
ID6
ID5
J5
ID4
ID3
ID2
ID1
B3B4
Y
4
Y
3
Y
2
Y
1
VG0
J4
V
G
BC5
B
5
BC4
J3
B
4
+VD
C
GND
B
3
B
2
J2
B
1
G
0
G
J1
SPR
EVS
T<
T<
R7
N11
J14-C
7
A1(+)
A2(-)
J13-C
4
A1(+)
A2(-)
R3
R2
R1
disable input
nd
2ter Sperreingang
2
Contact open = HP disabled
Kontakt offen = WP gesperrt
K22K23
Utility company
disable contactor
EVU-Sperrschütz
Contact open = HP disabled
The function of the suppl.
heating system can be selected
Die Funktion des 2ten WE
ist wählbar
Kontakt offen = WP gesperrt
L
1
M19
max.
200W
T
1
K12
L
1
H5
max.
200W
T
1
K11
X1 - N
X3
-N
-PEX1X1
C
9
NO1
1
NO1
0
J16
NO9
C
9
NC8
C
8
NO8
MZ
MA
J15
C
7
NO7
C
7
J14
F3 (L)
L
PE
N
X1
4,0ATr
4,0ATr
12pol.
12pol.
34
-N
-N
-PEX1
F2
-N
F3
-PE
X1
-PE
-N
X1
-N
K20
2
X1X1X1
-PE
-N
Verdi.
C
4
NO6
NO5
J13
NO4
C
4
C
1
NO3
NO2
V2V1
J12
NO1
C
1
xxxxx
N10
P
E
L
3
L
2
L
1
F2 (L)K5-A1
K1.2
-A1
J11
J9J10
X5
35
Page 36
APPENDIX: 12.4 WIRING DIAGRAMS
12.4.8 Legend .. 21CS
A1Wire jumper, must be removed if a utility company disable contactor is used
A2Wire jumper, must be removed if 2nd disable input is used
B2*Pressostat low pressure, brine
B3*Thermostat, hot water
B4*Thermostat, swimming pool water
E9*Electr. immersion heater, hot water
E10*Suppl. heating system (boiler or electr. heating element)
F2Load fuse for N1 relay outputs across J12 and J134.0 A slow
F3Load fuse for N1 relay outputs across J15 to J184.0 A slow
F4Pressostat high pressure
F5Pressostat low pressure limiter with manual reset
F12Thermostat N7
F14Electronic motor protection, compressor 1
H5*Lamp, remote fault indicator
J1...J18Terminal connector at N1
K1Contactor, compressor
K5Contactor, primary pump
K1.1Contactor, starting current limiter
K1.2Time-delay relay for delay of K1
K11*Electron. relay, remote fault indicator (relay module)
K12*Electron. relay, swimming pool circulating pump (relay module)
K20*Contactor, suppl. heating system (boiler or electr. heating element)
K21*Contactor, electr. immersion heater for hot water
K22*Utility company disable contactor
K23*SPR auxiliary contactor
M1Compressor
M11*Primary pump
M13*Heating circulating pump
M15*Heating circulating pump heating circuit 2
M16*Suppl. circulating pump
M18*Hot water circulating pump
M19*Swimming pool water circulating pump
M21*Mixer main circuit
M22*Mixer heating circuit 2
N1Heat pump controller
N7Soft start board
N10*Remote control station
N11*Relay module
R1External sensor
R2Return sensor
R3Hot water sensor (as an alternative to hot water thermostat)
R5Sensor for heating circuit 2
R6Freeze protection sensor
R7Coding resistor 8k
T1Safety isolating transformer 230/24V AC-28V A
X1Terminal strip mains control L/N/PE-230V AC-50 Hz/fuses/N and PE-terminal block
X2Terminal strip 24V AC terminal block
X3Terminal strip GND terminal block for sensors R1/-2 and -3 at J2
X4Terminal strip GND terminal block for sensors R5 and -6 at J6
X5Terminal strip power supply 3 L/PE-400V AC-50 Hz
Abbreviations:
EVSUtility company disable input
SPRSupplementary disable input
MAMixer OPEN
MZMixer CLOSED
hereby confirm that the design and construction of the product(s) listed below, in the version(s) placed
on the market by us, conform to the relevant basic requirements of the applicable EC directives.
This declaration becomes invalidated if any modifications are made to the product(s) without our
prior authorization.