Dimplex SI 5CS, SI 21CS, SI 14CS, SI 7CS, SI 17CS User Manual

...
Page 1
MOUNTING and
OPERATING MANUAL
Brine-to-Water Heat Pump
for Indoor Installation
SI 5CS SI 7CS SI 9CS SI 11CS
SI 14CS SI 17CS SI 21CS
Order No.: 452230.67.01 FD 8404
1
Page 2
CONTENTS
1 READ IMMEDIATELY 3
1.1 Important Information
1.2 Legal Provisions and Directives
1.3 Energy-Efficient Use of the Heat Pump
2 PURPOSE OF THE HEAT
PUMP 4
2.1 Application
2.2 Principle of Operation
3 BASELINE UNIT 4
4 ACCESSORIES 5
4.1 Brine Manifold
5 TRANSPORT 5
6 INSTALLATION 6
6.1 General Information
6.2 Sound Emissions
7 MOUNTING 6/7
7.1 General
7.2 Connection on Heating Side
7.3 Connection on Heat Source Side
7.4 Electrical Connection
8 COMMISSIONING 8
8.1 General
8.2 Preparation
8.3 Commissioning Procedure
9 CARE/CLEANING 9
9.1 Care
9.2 Cleaning of Heating Side
9.3 Cleaning of Heat Source Side
10 MALFUNCTIONS/TROUBLE-
SHOOTING 10
11 DECOMMISSIONING 10
11.1 Shutdown in Summer
11.2 End-of-Life Decommissioning
12 Appendix 11
2
Page 3
READ IMMEDIATELY
READ IMMEDIATELY
1
1.1 Important Information
CAUTION!
wooden pallet.
CAUTION!
more than max. 45° (in either direction).
CAUTION!
panel assemblies!
CAUTION!
connecting the heat pump.
The heat pump is not attached to the
The heat pump must not be tilted
Do not lift unit by the holes in the
Flush the heating system prior to
CAUTION!
be performed by authorised and qualified customer service technicians.
CAUTION!
connected from the power source prior to opening the cabinet.
1.2 Legal Provisions and Directives
This heat pump conforms to all relevant DIN/VDE regulations and EU directives. For details refer to the EC Declaration of Conformity in the appendix.
The electrical connection of the heat pump must be performed according to and conforming with all re­levant VDE, EN and IEC standards. Beyond that, the connection requirements of the local utility compa­nies have to be observed.
The heat pump is to be connected to the heat source and heat distribution systems in accordance with all applicable provisions.
Any work on the heat pump may only
All power circuits must be dis-
CAUTION!
in the heat source inlet of the heat pump in order to protect the evaporator against contamina­tion.
CAUTION!
of a frost and corrosion protection agent on a monoethylene glycol or propylene glycol basis.
CAUTION!
must be observed when connecting the load line.
The supplied strainer is to be fitted
The brine must contain at least 25 %
The clockwise phase sequence
CAUTION!
CAUTION!
must be performed in accordance with the mounting and operating manual of the heat pump controller.
Commissioning of the heat pump
1.3 Energy-Efficient Use of the Heat Pump
By operating this heat pump you contribute to the protection of our environment. A prerequisite for an efficient operation is the proper design and sizing of the heating system and the heat source system. In particular, it is important to keep water flow temperatures as low as possible. All energy consumers connected should therefore be suitable for low flow temperatures. A 1 K higher heating water temperature corresponds to an increase in power consumption of approx. 2.5 %. Underfloor heating systems with flow temperatures between 30 °C and 40 °C are optimally suited for energy-efficient operation.
3
Page 4
PURPOSE OF HEAT PUMP BASELINE UNIT
PURPOSE OF THE HEAT PUMP
2.1 Application
The brine-to-water heat pump is designed for use in existing or newly built heating systems. Brine is used as the heat carrier in the heat source system. Ground coils, ground collectors or similar systems can be used as the heat source.
2.2 Principle of Operation
The heat generated by the sun, wind and rain is stored in the ground. This heat stored in the ground is collected at low temperature by the brine circulating in the ground collector, ground coil or similar device. A circulating pump then conveys the warmed brine to the evaporator of the heat pump. There, the heat is given off to the refrigerant in the refrigeration cycle. When so doing, the brine cools so that it can again take up heat energy in the brine circuit.
BASELINE UNIT
32
The baseline unit consists of a heat pump, ready for connection, for indoor installation, complete with sheet metal cabinet, control panel and integrated controller. The refrigeration cycle contains the refrigerant R407C. Refrigerant R407C is CFC-free, non-ozone depleting and non-combustible.
All components required for the operation of the heat pump are located on the control panel. The power feed for the load and control current must be field­installed by the customer.
The supply lead of the brine pump (to be provided by the customer) must be connected to the control panel. When so doing, a motor protecting device is to be installed, if required.
The collector loops including brine manifold must be provided by the customer.
1 2 3
The refrigerant, however, is drawn in by the electrically driven compressor, is compressed and "pumped" to a higher temperature level. The electrical power needed to run the compressor is not lost in this process, but most of the generated heat is trans­ferred to the refrigerant as well.
Subsequently, the refrigerant is passed through the condenser where it transfers its heat energy to the heating water. Based on the thermostat setting, the heating water is thus heated to up to 55 °C.
4
1) Condenser 3) Evaporator
2) Control panel 4) Compressor
4
Page 5
ACCESSORIES
TRANSPORT
ACCESSORIES
4.1 Brine Manifold
The brine manifold ties the individual collector loops of the heat source system into a single main line which is connected to the heat pump. Integrated ball valves allow individual brine circuits to be shut off for venting purposes.
TRANSPORT
54
A lift truck is suited for transporting the unit on a level surface. If the heat pump needs to be transported on an uneven surface or carried up or down stairs, carrying straps may be used for this type of transport. These straps may be passed directly underneath the wooden pallet.
CAUTION!
wooden pallet.
The heat pump is not secured to the
CAUTION!
more than max. 45° (in either direction).
For lifting the unit without pallet, the holes provided in the sides of the frame should be used. The side panel assemblies must be removed for this purpose. A commercially available pipe can be used as a carrying aid.
CAUTION!
assemblies for lifting the unit!
The heat pump must not be tilted
Do not use the holes in the panel
5
Page 6
INSTALLATION MOUNTING
6
INSTALLATION
6.1 General Information
As a rule, the unit must be installed indoors on a level, smooth and horizontal surface. The entire base frame should thereby make close contact with the surface in order to ensure adequate sound insulation. Failing this, additional sound insulation measures may become necessary.
The heat pump should be located to allow safe and easy maintenance/service access. This is ensured if a clearance of approx. 1 m in front of and to each side of the heat pump is maintained.
1m
1m
1m
MOUNTING
7
7.1 General
The following connections need to be established on the heat pump:
- supply/return flow of the brine system
- supply/return flow of the heating system
- power supply
7.2 Connection on Heating Side
CAUTION!
prior to connecting the heat pump.
Before completing the heat pump connections on the heating water side, the heating installation must be flushed in order to remove any impurities that may be present, as well as residues of sealing material, and the like. Any accumulation of deposits in the condenser may result in a total failure of the heat pump.
Once the installation on the heating side has been completed, the heating system must be filled, de­aerated and pressure-tested.
The heating system must be flushed
6.2 Sound Emissions
The heat pump offers silent operation due to efficient sound insulation. To prevent noise transmission to the foundation, a suitable, sound dampening rubber mat should be placed underneath the base frame of the heat pump.
Any sound transmission to the heating systems is prevented by means of flexible pressure tubing already integrated into the heat pump.
Heating water minimum flow rate
The heating water minimum flow rate through the heat pump must be assured in all operating states of the heating system. This can be accomplished, for example, by installing a differential pressure-free manifold or an overflow valve. The procedure for setting an overflow valve is described in the Chapter Commissioning.
Frost protection for installations prone to frost
Provided the controllers and circulating pumps are ready for operation, the frost protection feature of the controller is active. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained. In heat pump installations where a power failure cannot be readily detected (holiday house), the heating circuit must contain a suitable antifreeze product.
6
Page 7
MOUNTING
7.3 Connection on Heat Source Side
The following procedure must be observed when making the connection:
Connect the brine line to the flow and return pipe of the heat pump.
CAUTION!
in the heat source inlet of the heat pump in order to protect the evaporator against the ingress
of impurities.
In addition, a powerful vent must be installed at the highest point of the heat source system. The hydraulic plumbing diagram must be observed here.
The brine liquid must be produced prior to charging the system. The brine concentration must be at least 25 %. Freeze protection down to
-14°C can thus be ensured. Only antifreeze products on the basis of mono-
ethylene glycol or propylene glycol may be used. The heat source system must be vented (de-
aerated) and be checked for leaks.
The supplied strainer must be fitted
An all-pole disconnecting device with a contact gap of at least 3 mm (e.g. utility company disable contac­tor or power contactor) as well as a 3-pole circuit breaker with simultaneous tripping of all external conductors must be provided . The required cross­sectional area of the conductor is to be selected according to the power consumption of the heat pump, the technical connection requirements of the relevant utility company and all applicable regula­tions. Power consumption data of the heat pump is provided in the product literature and on the nameplate. The terminals are designed for a max. conductor cross-section of 10 mm˝.
CAUTION!
must be observed when connecting the load line (the heat pump will deliver no output and will be very noisy when the phase sequence is in­correct).
The clockwise phase sequence
CAUTION!
least 25 % of an antifreeze and corrosion protection agent on a monoethylene glycol or
propylene glycol basis.
The brine solution must contain at
7.4 Electrical Connection
The following electrical connections must be established on the heat pump:
- Connection of the control wire to the control panel of the heat pump via terminals X1: L/N/PE.
- Connection of the load wire to the control panel of the heat pump via terminals X5: L1/L2/L3/PE.
- Connection of the brine pump (to be provided by the customer) to the control panel of the heat pump via terminal X1: PE and pump contactor K2: 2/4/6 (.. 5-17CS), or motor protection F7: 2/4/ 6 (.. 21CS).
All electrical components required for the operation of the heat pump are located on the control panel.
For detailed instructions concerning the connection and functioning of the heat pump controller refer to the operating manual supplied with the controller.
7
Page 8
COMMISSIONING
8
COMMISSIONING
8.1 General Information
To ensure proper commissioning it should be carried out by an after-sales service authorized by the manufacturer. Only then can an extended warranty period of 3 years in total be granted (cf. Warranty service).
8.2 Preparation
Prior to commissioning, the following items need to be checked:
- All connections of the heat pump must have been made as described in Chapter 7.
- The heat source system and the heating circuit must have been filled and checked.
- The strainer must have been fitted in the sole inlet of the heat pump.
b) Close all of the heating circuits that may also be
closed during operation (depending on the type of heat pump usage) so that the most unfa­vourable operating state - with respect to the water flow rate - is achieved.
c) In this operating state open the overflow valve
until approximately the same temperature difference exists that was measured under a) when the overflow valve was closed and the heating circuits open.
Any malfunctions occurring during operation are displayed on the heat pump controller and can be corrected as described in the operating manual of the heat pump controller.
- In the brine and heating circuits all valves that could impair the proper heating water flow must be open.
- The settings of the heat pump controller must be adapted to the heating installation in accordance with the instructions contained in the controller's operating manual.
8.3 Commissioning Procedure
The start-up of the heat pump is effected via the heat pump controller.
CAUTION!
must be performed in accordance with the mounting and operating manual of the heat pump controller.
Where an overflow valve is fitted to assure the minimum heating water flow rate, the valve must be set in accordance with the requirements of the heating installation. An incorrect setting may result in various error symptoms and an increased elec­tric power consumption. To correctly set the overflow valve, the following procedure is recommended:
Commissioning of the heat pump
a) Open all heating circuits and close the overflow
valve. Determine the resulting temperature difference between supply and return flow.
8
Page 9
9
CARE/CLEANING
9.1 Care
The heat pump is maintenance-free. To prevent malfunctions due to sediments in the heat ex­changers, care must be taken that no impurities can enter the heat source system and heating installa­tion. In the event that operating malfunctions due to contamination occur nevertheless, the system should be cleaned as described below.
9.2 Cleaning of Heating Side
The ingress of oxygen into the heating water circuit may result in the formation of oxidation products (rust). It is therefore important - in particular with respect to the piping of underfloor heating systems
- that the installation is executed in a diffusion-proof manner.
Also residues of lubricating and sealing agents may contaminate the heating water.
CAUTION!
Depending on the filling water quality and quantity, in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form, impairing the pro­per functioning of the heating installation. A reason for this is the water hardness and oxygen dissolved in the filling waters as well as additional oxygen from the air, which may penetrate via valves, fittings and plastic pipes (oxygen diffusion). As a preventive measure it is recommended that a physical water conditio­ner such as ELYSATOR be used.
Caution - Heating Technicians !
9.3 Cleaning of Heat Source Side
CAUTION!
ed in the heat source inlet of the heat pump in order to protect the evaporator against conta­mination.
The supplied strainer is to be install-
CARE/CLEANING
In the case of severe contaminations leading to a reduction of the performance of the condenser in the heat pump, the system must be cleaned by a heating technician.
According to current knowledge, we recommend cleaning with a 5% phosphoric acid solution or, in the case that cleaning needs to be performed more frequently, with a 5% formic acid solution.
In either case, the cleaning fluid should be at room temperature. It is recommended that the heat exchanger be cleaned in the direction opposite to the normal flow direction.
To prevent acidic cleaning agents from entering the circuit of the heating installation we recommend that the flushing device be fitted directly to the supply and return lines of the condenser. To prevent any damage caused by cleaning agent residues that may be present in the system it is important that the system be thoroughly flushed using appropriate neutralising agents.
The acids must be used with great care, all relevant regulations of the employers' liability insurance associations must be adhered to.
The filter screen of the strainer should be cleaned one day after commissioning, thereafter every week. If no more contamination can be noticed any more, the strainer filter can be removed in order to reduce pressure losses.
If in doubt, contact the manufacturer of the chemicals!
9
Page 10
MALFUNCTIONS/TROUBLESHOOTING DECOMMISSIONING
MALFUNCTIONS/
10
CAUTION!
TROUBLESHOOTING
This heat pump is a quality product and is designed for trouble-free operation. In the event that a malfunction occurs nevertheless, you will be able to correct the problem yourself in most of the cases. Simply consult the Malfunctions and Trouble­shooting table contained in the operating manual of the heat pump controller.
Additional malfunctions can be interrogated at the heat pump controller.
If you cannot correct the malfunction yourself, please contact the after-sales service agent in charge (see Warranty Certificate).
All work on the heat pump may only be performed by an authorised and qualified after-sales service.
DECOMMISSIONING
11
11.1 Shutdown in Summer
Shutting down the heating system in summer is effected by switching the heat pump controller to the "Summer" operating mode.
11.2 End-of-Life Decommissioning/ Disposal
Before removing the heat pump, disconnect the machine from the power source and close all valves. Environment-relevant requirements regarding the recovery, recycling and disposal of service fuels and components in accordance with all relevant standards must be adhered to. Particular attention must hereby be paid to the proper disposal of refrigerants and refrigeration oils.
CAUTION!
connected from the power source prior to opening the equipment.
All electrical circuits must be dis-
10
Page 11
12
APPENDIX
APPENDIX
12.1 Dimensioned Drawings
12.1.1 Dimens'ddrawing .. 5CS - 14CS 12
12.1.2 Dimens'd drawing .. 17CS - 21CS 13
12.2 Equipment Data 14
12.3 Performance Curves/Pressure Losses
12.3.1 Performance Curves .. 5CS 15
12.3.2 Pressure Losses .. 5CS 16
12.3.3 Performance Curves .. 7CS 17
12.3.4 Pressure Losses .. 7CS 18
12.3.5 Performance Curves .. 9CS 19
12.3.6 Pressure Losses .. 9CS 20
12.3.7 Performance Curves .. 11CS 21
12.3.8 Pressure Losses .. 11CS 22
12.3.9 Performance Curves .. 14CS 23
12.3.10 Pressure Losses .. 14CS 24
12.3.11 Performance Curves .. 17CS 25
12.3.12 Pressure Losses .. 17CS 26
12.3.13 Performance Curves .. 21CS 27
12.3.14 Pressure Losses .. 21CS 28
12.4 Wiring Diagram
12.4.1 Control .. 5CS to .. 17CS 29
12.4.2 Load .. 5CS bis .. 17CS 30
12.4.3 Terminal Diagram .. 5CS to .. 17CS 31
12.4.4 Legend .. 5CS to .. 17CS 32
12.4.5 Control .. 21CS 33
12.4.6 Load .. 21CS 34
12.4.7 Terminal Diagram .. 21CS 35
12.4.8 Legend .. 21CS 36
12.5 Hydraulic Block Diagram 37
12.6 EC Declaration of Conformity 38
12.7 Warranty Certificate 39
11
Page 12
APPENDIX: 12.1 DIMENSIONED DRAWINGS
12.1.1 Dimensioned Drawing .. 5CS - 14CS
Heat source supply
Heat pump outlet
Heat source return
Heat pump inlet
1" internal / 1" external thread
Connections on heating side
1 1/4" internal / 1 1/4" external thread
Connections on heat source side
Heating water return
Heat pump inlet
Heating water supply
Heat pump outlet
12
Page 13
12.1.2 Dimensioned Drawings .. 17CS - 21 CS
APPENDIX: 12.1 DIMENSIONED DRAWINGS
Heat source supply
Heat pump outlet
Heat source return
Heat pump inlet
1 1/4" internal / 1" external thread
Connections on heating side
1 1/2" internal / 1 1/2" external thread
Connections on heat source side
Heating water return
Heat pump inlet
Heating water supply
Heat pump outlet
13
Page 14
APPENDIX: 12.2 EQUIPMENT DATA
EQUIPMENT DATA for brine-to-water heat pumps for heating purposes
1
TYPE AND COMMERCIAL DESCRIPTION ..5CS ..7CS ..9CS ..11CS ..14CS ..17CS ..21CS
2
MODEL
2.1 Enclosure type acc. to EN 60 529 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
2.2 Installation site indoors indoors indoors indoors indoors indoors indoors
3
PERFORMANCE DATA
3.1 Operating temperature limits:
Heating water supply °C max. 55 max. 55 max. 55 max. 55 max. 55 max. 55 max. 55
Brine (heat source) °C -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25 -5 to +25
Antifreeze agent
monoethylene glycol monoethylene glycol monoethylene glycol monoethylene glycol monoethylene glycol
Minimum brine concentration (-13°C freezing temperature)
0,25 0,25 0,25 0,25 0,25 0,25 0,25
3.2 Heating water temperature spread at B0 / W35
K 10,1 9,9 10,5 10,1 9,6 9,3 11,3
3.3 Heating capacity / coeff.of perform. at B-5 / W55
1)
kW / --- 3,8 / 1,96 5,6 / 2,2 7,7 / 2,3 9,4 / 2,4 12,5 / 2,6 14,4 / 2,6 17,9 / 2,5
at B0 / W50
1)
kW / --- 4,8 / 2,75 6,7 / 2,9 9,0 / 3,1 11,3 / 3,0 14,2 / 3,4 16,7 / 3,2 20,4 / 3,1
at B0 / W35
1)
kW / --- 5,3 / 4,3 6,9 / 4,3 9,2 / 4,4 11,8 / 4,4 14,5 / 4,5 17,1 / 4,6 21,1 / 4,3
3.4 Sound power level dB(A) 54 55 56 56 56 58 59
3.5 m³/h / Pa 0,45 / 2000 0,6 / 2500 0,75 / 4500 1,0 / 3500 1,3 / 3500 1,5 / 4000 1,6 / 6000
3.6 Brine flow rate at internal pressure difference (heat source) m³/h / Pa 1,2 / 6500 1,7 / 10000 2,3 / 16000 3,0 / 13000 3,5 / 13000 3,8 / 9000 6,0 / 12000
3.7 Refrigerant; total charge weight Type / kg R407C / 1,7 R407C / 1,5 R407C / 1,8 R407C / 2,0 R407C / 2,3 R407C / 2,8 R407C / 4,5
4
DIMENSIONS; CONNECTIONS AND WEIGHT
4.1 Equipment dimensions without connections
4)
H x W x L mm
800 × 600 × 500 800 × 600 × 500 800 × 600 × 500 800 × 600 × 500 800 × 600 × 500 1380 × 600 × 500 1380 × 600 × 500
4.2 Equipment connections for heating system inches thread 1" i/ext. thread 1" i/ext. thread 1" i/ext. thread 1" i/ext. thread 1" i/ext.
4.3 Equipment connections for heat source inches thread 1¼" i/ext. thread 1¼" i/ext. thread 1¼" i/ext. thread 1¼" i/ext. thread 1¼" i/ext. thread 1½" i/ext.
4.4 Weight of transport unit(s) incl. packaging kg 131 133 134 145 157 165 215
5
ELECTRICAL CONNECTION
5.1 Nominal voltage; fusing V / A 400 / 16 400 / 16 400 / 16 400 / 16 400 / 16 400 / 16 400 / 20
5.2 Nominal power consumption
1)
B0 W35 kW 1,23 1,6 2,07 2,66 3,22 3,72 4,91
5.3 Starting current with soft starter A 22 (w/out soft st.) 30 (w/out soft st.) 15 26 26 27 29
5.4
Nominal current B0 W35 / cosϕ
A / --- 2,22 2,89 3,77 4,84 5,81 6,35 8,86
6
COMPLIES WITH EUROPEAN SAFETY REGULATIONS
3) 3) 3) 3) 3) 3) 3)
7
OTHER DESIGN CHARACTERISTICS
7.1 Water inside equipment protected against freezing
2)
ja yes yes yes yes yes yes
7.2 Performance settings 1 1 1 1 1 1 1
7.3 Controller internal / external internal internal internal internal internal internal internal
1) 2)
4)
3) See EC Declaration of Conformity
Subject to technical modifications
Issued 24.03.2004
These data characterize the size and performance capability of the system. For economic and energetic reasons, additional factors such as balance
point and control need to be taken into consideration. Abbreviations have the following meaning, e.g. B10 / W55: heat source temperature 10 °C and
heating water supply temperature 55 °C.
Equipment Data
The heating circulating pump and the controller of the heat pump must be ready for operation at all times.
Please keep in mind that morer space is required for pipe connection, operation and maintenance.
Heating water flow rate at internal pressure difference
14
Page 15
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
50
12.3.1 Performance Curves .. 5CS
Heating capacity in [kW]
Heizleistung in [kW]
16
14
12
Water outlet temperature in [°C]
Wasseraustrittstemperatur in [°C]
10
8
6
4
2
0
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
COP in the heating mode (incl. proportional pump energy)
8
7
6
5
4
3
2
1
0
Bedingungen:
Conditions:
Heating water flow rate 0,45 m3/h
Heizwasserdurchsatz 0,45 m³/h
Brine flow rate 1,2 m3/h
Soledurchsatz 1,2 m³/h
35
50
35
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
Power consumption (incl. proportional pump power input)
4
3
2
1
0
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26
Brine inlet temperature in [°C]
Soleeintrittstemperatur in [°C]
15
50
35
Page 16
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.2 Pressure Losses .. 5CS
Pressure loss in [Pa]
40000
Druckverlust in [Pa]
35000
30000
25000
20000
15000
10000
5000
0
0 0,5 1 1,5 2 2,5 3 3,5 4
Pressure loss in [Pa]
25000
Druckverlust in [Pa]
Druckverluste Verdampfer
Pressure losses of evaporator
bei Sole -5°C
at –5°C brine temperature without brine accessories
ohne Solezubehör
Pressure loss 6.5 kPa at a
Druckverlust 6,5 kPa bei
rated brine flow rate of 1.2 m3/h
Sole-Nenndurchfluß 1,2 m³/h
Brine flow rate in [m3/h]
Soledurchfluß in [m³/h]
Druckverluste Verflüssiger
20000
15000
10000
5000
0
0 0,2 0,4 0,6 0,8 1 1,2 1,4 1,6
Pressure losses of condenser at
35°C heating water outlet temperature
rated heating water flow rate of 0.45 m3/h
Heizwasser-Nenndurchfluß 0,45 m³/h
bei HWA 35°C
Pressure loss 2 kPa at a
Druckverlust 2 kPa bei
Heizwasserdurchfluß in [m³/h]
Heating water flow rate in [m3/h]
16
Page 17
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
50
12.3.3 Performance Curves .. 7CS
Heating capacity in [kW]
Heizleistung in [kW]
16
14
Wasseraustrittstemperatur in [°C]
Water outlet temperature in [°C]
12
10
8
6
4
2
0
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
COP in the heating mode (incl. proportional pump energy)
8
7
6
5
4
3
2
1
0
Bedingungen:
Conditions:
Heating water flow rate 0,6 m3/h
Heizwasserdurchsatz 0,6 m³/h
Brine flow rate 1,7 m3/h
Soledurchsatz 1,7 m³/h
35
50
35
Power consumption (incl. proportional pump power input)
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
4
3
2
1
0
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26
Soleeintrittstemperatur in [°C]
Brine inlet temperature in [°C]
17
50
35
Page 18
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.4 Pressure Losses .. 7CS
Pressure loss in [Pa]
40000
Druckverlust in [Pa]
35000
30000
25000
20000
15000
10000
5000
0
0 0,5 1 1,5 2 2,5 3 3,5 4
Druckverlust in [Pa]
25000
Pressure loss in [Pa]
Druckverluste Verdampfer
Pressure losses of evaporator
bei Sole -5°C
at –5°C brine temperature without brine accessories
ohne Solezubehör
Pressure loss 10 kPa at a
Druckverlust 10 kPa bei
rated brine flow rate of 1.7 m3/h
Sole-Nenndurchfluß 1,7 m³/h
Brine flow rate in [m3/h]
Soledurchfluß in [m³/h]
Druckverluste Verflüssiger
20000
15000
10000
5000
0
0 0,2 0,4 0,6 0,8 1 1,2 1,4 1,6
Pressure losses of condenser at
35°C heating water outlet temperature
rated heating water flow rate of 0.6 m3/h
Heizwasser-Nenndurchfluß 0,6 m³/h
bei HWA 35°C
Pressure loss 2.5 kPa at a
Druckverlust 2,5 kPa bei
Heizwasserdurchfluß in [m³/h]
Heating water flow rate in [m3/h]
18
Page 19
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
50
12.3.5 Performance Curves .. 9CS
Heating capacity in [kW]
Heizleistung in [kW]
16
14
12
10
8
6
Wasseraustrittstemperatur in [°C]
Water outlet temperature in [°C]
35
50
4
2
0
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
COP in the heating mode (incl. proportional pump energy)
8
7
6
5
4
3
2
1
0
Power consumption (incl. proportional pump power input)
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
5
4
Bedingungen:
Conditions:
Heating water flow rate 0,75 m3/h
Heizwasserdurchsatz 0,75 m³/h
Brine flow rate 2,3 m3/h
Soledurchsatz 2,3 m³/h
35
3
2
1
0
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26
Brine inlet temperature in [°C]
Soleeintrittstemperatur in [°C]
19
50
35
Page 20
APPENDIX: 12.3 PERFORMANCE CURVES/DPRESSURE LOSSES
12.3.6 Pressure Losses .. 9CS
Pressure loss in [Pa]
40000
Druckverlust in [Pa]
35000
Druckverluste Verdampfer
Pressure losses of evaporator
at –5°C brine temperature
bei Sole -5°C
without brine accessories
ohne Solezubehör
30000
Pressure loss 16 kPa at a
Druckverlust 16 kPa bei
rated brine flow rate of 2.3 m3/h
Sole-Nenndurchfluß 2,3 m³/h
25000
20000
15000
10000
5000
0
0 0,5 1 1,5 2 2,5 3
3
/h]
Pressure loss in [Pa]
Druckverlust in [Pa]
Brine flow rate in [m
Soledurchfluß in [m³/h]
25000
Druckverluste Verflüssiger
20000
Pressure losses of condenser at
35°C heating water outlet temperature
rated heating water flow rate of 0.75 m3/h
Heizwasser-Nenndurchfluß 0,75 m³/h
bei HWA 35°C
Pressure loss 4.5 kPa at a
Druckverlust 4,5 kPa bei
15000
10000
5000
0
0 0,2 0,4 0,6 0,8 1 1,2 1,4 1,6
Heizwasserdurchfluß in [m³/h]
Heating water flow rate in [m3/h]
20
Page 21
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.7 Performance Curves .. 11CS
Heizleistung in [kW]
Heating capacity in [kW]
24,0
22,0
20,0
18,0
16,0
14,0
12,0
10,0
8,0
Wasseraustrittstemperatur in [°C]
Water outlet temperature in [°C]
35
50
6,0
4,0
2,0
0,0
COP in the heating mode (incl. proportional pump energy)
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
8
7
6
5
4
3
2
1
0
Power consumption (incl. proportional pump power input)
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
5
4
Bedingungen:
Conditions:
Heizwasserdurchsatz 1,0 m³/h
Heating water flow rate 1,0 m3/h Brine flow rate 3,0 m
Soledurchsatz 3,0 m³/h
3
/h
35
50
3
2
1
0
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26
Soleeintrittstemperatur in [°C]
Brine inlet temperature in [°C]
21
35
Page 22
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.8 Pressure Losses .. 11CS
Pressure loss in [Pa]
40000
Druckverlust in [Pa]
35000
Druckverluste Verdampfer
Pressure losses of evaporator
at –5°C brine temperature
bei Sole -5°C
without brine accessories
ohne Solezubehör
30000
Pressure loss 13 kPa at a
Druckverlust 13 kPa bei
rated brine flow rate of 3.0 m3/h
Sole-Nenndurchfluß 3,0 m³/h
25000
20000
15000
10000
5000
0
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5
3
/h]
Pressure loss in [Pa]
Druckverlust in [Pa]
Brine flow rate in [m
Soledurchfluß in [m³/h]
16000
14000
Druckverluste Verflüssiger
Pressure losses of condenser at
35°C heating water outlet temperature
bei HWA 35°C
12000
Pressure loss 3.5 kPa at a
Druckverlust 3,5 kPa bei
rated heating water flow rate of 1.0 m3/h
10000
Heizwasser-Nenndurchfluß 1,0 m³/h
8000
6000
4000
2000
0
0 0,2 0,4 0,6 0,8 1 1,2 1,4 1,6 1,8 2
Heizwasserdurchfluß in [m³/h]
Heating water flow rate in [m3/h]
22
Page 23
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.9 Performance Curves .. 14CS
Heating capacity in [kW]
Heizleistung in [kW]
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
Wasseraustrittstemperatur in [°C]
Water outlet temperature in [°C]
Bedingungen:
Conditions:
Heating water flow rate 1,3 m3/h
Heizwasserdurchsatz 1,3 m³/h
Brine flow rate 3,5 m3/h
Soledurchsatz 3,5 m³/h
35
50
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
COP in the heating mode (incl. proportional pump energy)
8
7
6
5
4
3
2
1
0
Power consumption (incl. proportional pump power input)
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
5
4
3
2
1
35
50
50
35
0
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26
Soleeintrittstemperatur in [°C]
Brine inlet temperature in [°C]
23
Page 24
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.10 Pressure Losses .. 14CS
Pressure loss in [Pa]
30000
25000
20000
15000
Druckverlust in [Pa]
Druckverluste Verdampfer
Pressure losses of evaporator
bei Sole -5°C
at –5°C brine temperature
without brine accessories
ohne Solezubehör
Pressure loss 13 kPa at a
Druckverlust 13 kPa bei
rated brine flow rate of 3.5 m3/h
Sole-Nenndurchfluß 3,5 m³/h
10000
5000
0
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5
3
/h]
Pressure loss in [Pa]
Druckverlust in [Pa]
Brine flow rate in [m
Soledurchfluß in [m³/h]
14000
12000
10000
Druckverluste Verflüssiger
Pressure losses of condenser at
35°C heating water outlet temperature
rated heating water flow rate of 1.3 m3/h
Heizwasser-Nenndurchfluß 1,3 m³/h
bei HWA 35°C
Pressure loss 3.5 kPa at a
Druckverlust 3,5 kPa bei
8000
6000
4000
2000
0
0 0,2 0,4 0,6 0,8 1 1,2 1,4 1,6 1,8 2 2,2
Heizwasserdurchfluß in [m³/h]
Heating water flow rate in [m3/h]
24
Page 25
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
50
12.3.11 Performance Curves .. 17CS
Heating capacity in [kW]
Heizleistung in [kW]
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
Wasseraustrittstemperatur in [°C]
Water outlet temperature in [°C]
Bedingungen:
Conditions:
Heating water flow rate 1,5 m3/h
Heizwasserdurchsatz 1,5 m³/h
Brine flow rate 3,8 m3/h
Soledurchsatz 3,8 m³/h
35
50
COP in the heating mode (incl. proportional pump energy)
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
8
7
6
5
4
3
2
1
0
Power consumption (incl. proportional pump power input)
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
7
6
5
4
3
2
1
35
50
35
0
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26
Soleeintrittstemperatur in [°C]
Brine inlet temperature in [°C]
25
Page 26
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.12 Pressure Losses .. 17CS
Pressure loss in [Pa]
24000
22000
20000
18000
16000
14000
12000
10000
Druckverlust in [Pa]
Druckverluste Verdampfer
Pressure losses of evaporator
bei Sole -5°C
at –5°C brine temperature
without brine accessories
ohne Solezubehör
Pressure loss 9 kPa at a
Druckverlust 9 kPa bei
rated brine flow rate of 3.8 m3/h
Sole-Nenndurchfluß 3,8 m³/h
8000
6000
4000
2000
0
0123456
Brine flow rate in [m3/h]
Soledurchfluß in [m³/h]
Pressure loss in [Pa]
14000
12000
10000
8000
6000
Druckverlust in [Pa]
Druckverluste Verflüssiger
Pressure losses of condenser at
35°C heating water outlet temperature
rated heating water flow rate of 1.5 m3/h
Heizwasser-Nenndurchfluß 1,5 m³/h
bei HWA 35°C
Pressure loss 4 kPa at a
Druckverlust 4 kPa bei
4000
2000
0
0 0,2 0,4 0,6 0,8 1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6
Heating water flow rate in [m3/h]
Heizwasserdurchfluß in [m³/h]
26
Page 27
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.13 Performance Curves .. 21CS
Heating capacity in [kW]
Heizleistung in [kW]
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2
0
Wasseraustrittstemperatur in [°C]
Water outlet temperature in [°C]
Bedingungen:
Conditions:
Heating water flow rate 1,6 m3/h
Heizwasserdurchsatz 1,6 m³/h
Brine flow rate 6,0 m3/h
Soledurchsatz 6,0 m³/h
35
50
COP in the heating mode (incl. proportional pump energy)
Leistungszahl im Heizbetrieb (incl. Der anteiligen Pumpenleistungen)
8
7
6
5
4
3
2
1
0
Power consumption (incl. proportional pump power input)
Leistungsaufnahme in [kW] (incl. Der anteiligen Pumpenleistungen)
7
6
5
4
3
2
1
35
50
35
0
-10 -8 -6 -4 -2 0 2 4 6 8 10 12 14 16 18 20 22 24 26
Soleeintrittstemperatur in [°C]
Brine inlet temperature in [°C]
27
Page 28
APPENDIX: 12.3 PERFORMANCE CURVES/PRESSURE LOSSES
12.3.14 Pressure Losses .. 21CS
Pressure loss in [Pa]
24000
22000
20000
18000
16000
14000
12000
10000
Druckverlust in [Pa]
Druckverluste Verdampfer
Pressure losses of evaporator
rated brine flow rate of 6.0 m3/h
Sole-Nenndurchfluß 6,0 m³/h
bei Sole -5°C
at –5°C brine temperature
ohne Solezubehör
without brine accessories
Pressure loss 12 kPa at a
Druckverlust 12 kPa bei
8000
6000
4000
2000
0
012345678
Brine flow rate in [m3/h]
Soledurchfluß in [m³/h]
Pressure loss in [Pa]
14000
12000
10000
8000
6000
Druckverlust in [Pa]
Druckverluste Verflüssiger
Pressure losses of condenser at
35°C heating water outlet temperature
rated heating water flow rate of 1.6 m3/h
Heizwasser-Nenndurchfluß 1,6 m³/h
bei HWA 35°C
Pressure loss 6 kPa at a
Druckverlust 6 kPa bei
4000
2000
0
0 0,5 1 1,5 2
Heizwasserdurchfluß in [m³/h]
Heating water flow rate in [m3/h]
28
Page 29
12.4.1 Control .. 5CS to .. 17CS
NC1
3
C13
NO1
3
NC1
2
C12
NO1
2
J17 J18
C
9
NO1
1
NO1
0
J16
NO9
C
9
NC8
C
8
NO8
J15
J12/NO1
J8
J5-IDC1
J7
J6
APPENDIX: 12.4 WIRING DIAGRAMS
A1
PUP
J12/NO3
Verd .1
ID14H
J12-C1
ID1
4
IDC13
ID1
3
ID13H
IDC
9
ID1
2
ID1
1
ID1
0
ID9
GND
B
8
B
7
EGS
B
6
HD ND
0 VAC
R6
F4
F5
P >
P <
X4
A2
K5
A1K1A2
C
7
NO7
C
7
C
4
NO6
NO5
NO4
C
4
K5-A1 F3 (L)
C
1
NO3
NO2
V2
Ver di.
NO1
V1
C
1
F2 (L)
K1-A1
N1
J13-C4
J14
J1-G0
IDC
1
0 VAC
ID8
ID7
ID6
ID5
J5
ID4
ID3
ID2
F5
J13
F4
ID1
J1-G
Y
4
J12-C1
Y
3
Y
2
Y
1
VG0
J4
V
G
Stö.- M1
Stö.- M11
SPR
EVS
X2
A3
A1
A2
24VAC
A4
4,0A Tr
F2
L
BC5
J18-C13
B
J12J11
5
BC4
J3
B
4
R7
F3
4,0A Tr
3
PE
12 pol.
12 pol.
N
230 VAC - 50Hz
+VD
C
GND
B
3
B
2
J2
B
1
J5-IDC1
G
0
G
J1
J9 J10
X2-G
R2
0 VAC
24VAC
X3
24 VAC
T1
X1
Netz
Mains system
230 VAC
29
Page 30
APPENDIX: 12.4 WIRING DIAGRAMS
12.4.2 Load .. 5CS to .. 17CS
/1.8
K5
31 5
426
M11
L3 L2
M
L1PE
PE
3
X1
F15
SSM
SSM
X2 (24 VAC)
Blatt1 / N1
Sheet 1/N1
J5 / ID5
Remove wire jumper A3 prior to connecting M11 circulating pump motor
protection (F15) (from –9CS to –17CS).
A3 is the „M11 fault“ jumper
Vor dem Einklemmen des M11 (PU P) -M otorschutzes (F15)
(ab -9CS bis -17CS) die Drahtbcke A3 entfernen.
A3 ist die Brüc ke "Störung M11"
L1
X5
L2
3
Mains
PE
L3
Netz
system
3/PE 400VAC - 50Hz
No soft starter fitted in
brine-to-water units 5C and 7C
Sanftanlasser nicht vorhanden in
/1.8
K1
6
5 31
4 2
T S R
N7
Sole/Wasser 5C und 7C
W
M1
VU
M
3
30
Page 31
12.4.3 Terminal Diagram .. 5CS to .. 17CS
APPENDIX: 12.4 WIRING DIAGRAMS
M22
M15
K21
3
3
E9
M16
M21
3
230 VAC - 50Hz
Mains system
230 VAC - 50 Hz
Netz
M18
M13
Heizsta
b
E10
oder
HK
M11
Netz
4
Mains system
3L/PE 400VAC - 50Hz
NC1
3
C13
NO1
34
-N
-PE
3
MZN
NC1
2
C12
NO1
2
MAN
ID14H
ID1
4
IDC13
J8
ID1
3
ID13H
Leitungen sind bei Bedar f bauseits zu erstellen
Lines to be field-connected, if required
X1
2
-N
-PE X1
C
9
NO1
1
NO1
0
NO9
C
9
NC8
C
8
NO8
MZ
C
7
NO7
MA
C
7
L
PE
43
X1
4,0A Tr
4,0A Tr
F2
F3
-N
X1
-N
-PE X1
-N
-PE
X1
12 pol.
N
12 pol.
X1
X1
-PE
-N
X1
-N
K20
2
N10
xxxxx
P
E
L
3
L
2
L
1
X1
-PE
-N
V2
Verdi.
V1
F3 (L)
C
4
NO6
NO5
NO4
C
4
K5-A1
C
1
NO3
NO2
NO1
C
1
F2 (L)
K1-A1
X5
J14 J16J15 J18J17
J13
J12
J11
J9 J10
N1
J5-IDC1
IDC
9
0 VAC
ID1
2
ID1
1
J7
ID1
0
ID9
GND
B
8
B
7
J6
B
6
P<
B2
X4
R6
R5
24VAC
X2
J1-G
A3
A4
J1-G0
IDC
1
0 VAC
ID8
ID7
Stö.- M1
SPR
ID6
ID5
J5
ID4
ID3
ID2
ID1
Y
4
Y
3
Y
2
Y
1
VG0
J4
V
G
BC5
B
5
BC4
J3
B
4
+VD
C
GND
B
3
B
2
J2
B
1
G
0
G
J1
Stö.- M1 1
EVS
T<
B4
T<
B3
7
A1(+)
A2(-)
4
A1(+)
A2(-)
N11
R7
Cod.-WP
R3
R2
R1
K23
disable input
nd
2ter Sperreingang
2
Contact open = HP disabled
Kontakt offen = WP gesperrt
K22
J14-C
J13-C
Die Funktion von E10
Function E10 is selectable
Kontakt offen = WP gesperrt
Contact open = HP disabled
L
1
M19
max.
T
1
K12
L
1
H5
max.
T
1
ist wählbar
200W
200W
K11
X1 - N
X3
31
Page 32
APPENDIX: 12.4 WIRING DIAGRAMS
12.4.4 Legend .. 5CS to .. 17CS
A1 Wire jumper, must be removed if a utility company disable contactor is used A2 Wire jumper, must be removed if 2nd disable input is used A3 Wire jumper, must be removed if a motor protection contact for primary pump is used A4 Wire jumper, must be removed if a motor protection contact for the compressor is used
B2* Pressostat low pressure, brine B3* Thermostat, hot water B4* Thermostat, swimming pool water
E9* Electr. immersion heater, hot water E10* Suppl. heating system (boiler or electr. heating element)
F2 Load fuse for N1 relay outputs across J12 and J13 4.0 A slow F3 Load fuse for N1 relay outputs across J15 to J18 4.0 A slow F4 Pressostat high pressure F5 Pressostat low pressure (in SI 17CS, F5 is a limiter with manual reset) F15* Motor protection M11, from SI 9CS to SI 17CS integrated in primary pump
H5* Lamp, remote fault indicator
J1...J18 Terminal connector at N1
Open wire jumpers or contacts mean: lock-out or malfunction
K1 Contactor, compressor K5 Contactor, primary pump K11* Electron. relay for remote fault indicator (relay module) K12* Electron. relay for swimming pool water circulating pump K20* Contactor, suppl. heating system K21* Contactor, electr. immersion heater, hot water K22* Utility company disable contactor K23* SPR auxiliary contactor
M1 Compressor M11* Primary pump M13* Heating circulating pump M15* Heating circulating pump for heating circuit 2 M16* Suppl. circulating pump M18* Hot water circulating pump M19* Swimming pool circulating pump M21* Mixer heating circuit 1 M22* Mixer heating circuit 2
N1 Heat pump controller N7 Soft start control (not fitted in SI 5CS and SI 7CS appliances) N10* Remote control station N11* Relay module
R1 External sensor R2 Return sensor R3 Hot water sensor (as an alternative to hot water thermostat) R5 Sensor for heating circuit 2 R6 Freeze protection sensor R7 Coding resistor 8k
T1 Safety isolating transformer 230/24V AC-28V A
X1 Terminal strip mains control L/N/PE-230V AC-50 Hz/fuses/N and PE-terminal block X2 Terminal strip 24V AC-terminal block X3 Terminal strip GND terminal block for sensors R1/-2 and -3 at J2 X4 Terminal stripGND terminal blocl for sensors R5 and -6 at J6 X5 Terminal strip power supply 3 L/PE-400V AC-50 Hz
Abbreviations:
EVS Utility company disable input SPR Supplementary disable input
MA* Mixer OPEN MZ Mixer CLOSED
*Components to be supplied by the customer
32
Page 33
12.4.5 Control .. 21CS
NC1
3
C13
NO1
3
NC1
2
C12
NO1
2
C
9
NO1
1
NO1
0
NO9
C
9
NC8
C
8
NO8
C
7
NO7
C
7
C
4
NO6
NO5
NO4
C
4
C
1
NO3
NO2
V2
Verdi.
NO1
V1
C
1
K1.2
-A1
N1
APPENDIX: 12.4 WIRING DIAGRAMS
A2
Q2
Q1
230 VAC
A1
K5
A1
A2
18
K1
16
A1
A2
K1.1
A1
A2
K1.2
T2
T1
F14
M2
11
M1
11
4,0A Tr
L
4,0A Tr
3
PEN
12 pol. 12 pol.
230 V AC - 50Hz
X1
Netz
Mains system
M11
J12/NO3
J12/NO1
ID14H
J12-C1
ID1
4
IDC13
J8
ID1
3
ID13H
J17 J18
J5-IDC1
IDC
9
ID1
2
ID1
1
J7
ID1
0
ID9
J12-C1
J6
J14-C7
J1-G0
J5
J4
J18-C13
J3
J2
J5-IDC1
J1
GND
B
8
B
7
EGS
B
6
J13-C4
IDC
1
ID8
ID7
ID6
ID5
ID4
ID3
EVS
ID2
ID1
J1-G
Y
4
Y
3
Y
2
Y
1
VG0
V
G
BC5
B
5
BC4
B
4
+VD
C
GND
B
3
B
2
B
1
G
0
G
J16
J15
J14
F14-T1
F3 (L)
F5
J13
F4
K5-A1
J12
F2 (L)
J11
J10J9
X2-G
SPR
A1
M1
P >
F4
15
HD ND
P <
F5
0 VAC
R6
0 VAC
X4
F12
2
1
Stö.-M1
K1.2
14
14
Stö.-M11
X2
A2
24VAC
F2
R7
R2
0 VAC
24VAC
X3
F3
24 VAC
T1
33
Page 34
APPENDIX: 12.4 WIRING DIAGRAMS
12.4.6 Load .. 21CS
12 / 1.4
11
Q1
135
14
K5
I > I > I >
M11
M
246
PE
X1
3
12 / 1.5
11
Q2
135
14
I >I > I >
K1
642
M1
5
6
13
24
K1.1
L1
L2PEL3
T
RS
F12
N7
1
2
W
UV
-/1.5
M
3
F14/1.5
M2
M1
X5
3
Mains
Netz
system
3/PE 400VAC - 50Hz
34
Page 35
12.4.7 Terminal Diagram .. 21CS
APPENDIX: 12.4 WIRING DIAGRAMS
M22
M15
K21
3
3
E9
M16
M21
3
230 VAC - 50 H z
Mains system
230 VAC - 50 Hz
Netz
M18
M13E10
Heizsta
b
oder
HK
M11
Netz
4
Mains system
3L/PE 400VAC - 50Hz
NC1
3
C13
J18
NO1
3
3 4
-N
MAN MZN
-PE
NC1
2
C12
J17
NO1
2
ID14H
ID1
4
IDC13
J8
ID1
3
ID13H
X1
2
J1-G0
IDC
N1
9
0 VAC
ID1
2
ID1
1
J7
ID1
0
ID9
GND
B
8
B
7
J6
B
6
P <
B2
2
1
4
X4
R5
24VAC
X2
J1-G
J1-G0
IDC
1
0 VAC
ID8
ID7
ID6
ID5
J5
ID4
ID3
ID2
ID1
B3 B4
Y
4
Y
3
Y
2
Y
1
VG0
J4
V
G
BC5
B
5
BC4
J3
B
4
+VD
C
GND
B
3
B
2
J2
B
1
G
0
G
J1
SPR
EVS
T<
T<
R7
N11
J14-C
7
A1(+)
A2(-)
J13-C
4
A1(+)
A2(-)
R3
R2
R1
disable input
nd
2ter Sperr eingang
2
Contact open = HP disabled
Kontakt offen = WP gesperrt
K22 K23
Utility company
disable contactor
EVU-Sperrschütz
Contact open = HP disabled
The function of the suppl.
heating system can be selected
Die Funktion des 2ten WE
ist wählbar
Kontakt offen = WP gesperrt
L
1
M19
max.
200W
T
1
K12
L
1
H5
max.
200W
T
1
K11
X1 - N
X3
-N
-PE X1X1
C
9
NO1
1
NO1
0
J16
NO9
C
9
NC8
C
8
NO8
MZ
MA
J15
C
7
NO7
C
7
J14
F3 (L)
L
PE
N
X1
4,0A Tr
4,0A Tr
12 pol.
12 pol.
34
-N
-N
-PE X1
F2
-N
F3
-PE
X1
-PE
-N
X1
-N
K20
2
X1 X1X1
-PE
-N
Verdi.
C
4
NO6
NO5
J13
NO4
C
4
C
1
NO3
NO2
V2 V1
J12
NO1
C
1
xxxxx
N10
P
E
L
3
L
2
L
1
F2 (L) K5-A1
K1.2
-A1
J11
J9 J10
X5
35
Page 36
APPENDIX: 12.4 WIRING DIAGRAMS
12.4.8 Legend .. 21CS
A1 Wire jumper, must be removed if a utility company disable contactor is used A2 Wire jumper, must be removed if 2nd disable input is used
B2* Pressostat low pressure, brine B3* Thermostat, hot water B4* Thermostat, swimming pool water
E9* Electr. immersion heater, hot water E10* Suppl. heating system (boiler or electr. heating element)
F2 Load fuse for N1 relay outputs across J12 and J13 4.0 A slow F3 Load fuse for N1 relay outputs across J15 to J18 4.0 A slow F4 Pressostat high pressure F5 Pressostat low pressure limiter with manual reset F12 Thermostat N7 F14 Electronic motor protection, compressor 1
H5* Lamp, remote fault indicator
J1...J18 Terminal connector at N1
K1 Contactor, compressor K5 Contactor, primary pump K1.1 Contactor, starting current limiter K1.2 Time-delay relay for delay of K1 K11* Electron. relay, remote fault indicator (relay module) K12* Electron. relay, swimming pool circulating pump (relay module) K20* Contactor, suppl. heating system (boiler or electr. heating element) K21* Contactor, electr. immersion heater for hot water K22* Utility company disable contactor K23* SPR auxiliary contactor
M1 Compressor M11* Primary pump M13* Heating circulating pump M15* Heating circulating pump heating circuit 2 M16* Suppl. circulating pump M18* Hot water circulating pump M19* Swimming pool water circulating pump M21* Mixer main circuit M22* Mixer heating circuit 2
N1 Heat pump controller N7 Soft start board N10* Remote control station N11* Relay module
Q1 Power protection switch, brine pump Q2 Power protection switch, compressor
R1 External sensor R2 Return sensor R3 Hot water sensor (as an alternative to hot water thermostat) R5 Sensor for heating circuit 2 R6 Freeze protection sensor R7 Coding resistor 8k
T1 Safety isolating transformer 230/24V AC-28V A
X1 Terminal strip mains control L/N/PE-230V AC-50 Hz/fuses/N and PE-terminal block X2 Terminal strip 24V AC terminal block X3 Terminal strip GND terminal block for sensors R1/-2 and -3 at J2 X4 Terminal strip GND terminal block for sensors R5 and -6 at J6 X5 Terminal strip power supply 3 L/PE-400V AC-50 Hz
Abbreviations:
EVS Utility company disable input SPR Supplementary disable input MA Mixer OPEN MZ Mixer CLOSED
* Components to be supplied by the customer
36
Page 37
Hydraulic Block Diagram
Shut-off valve
Shut-off valve with drain
Overflow valve
Safety valve
Circulating pump
Expansion vessel
Thermostat/manual valve
Shut-off valve with check valve
Heat consumer
Strainer
Temperature sensor
Flexible connecting hose
Brine circulating pump
APPENDIX: 12.5 HYDRAULIC BLOCK DIAGRAM
Heating circulating pump
Hot water circulating pump
External wall sensor
Return sensor
Hot water sensor
Cold water
Hot water
Heat pump
Buffer tank
Heat pump controller
Electric distribution
Hot water storage tank
Ground collectors
Ground loops
Brine manifold
Brine collector
37
Page 38
APPENDIX: 12.6 EC DECLARATION OF CONFORMITY
EC Declaration of Conformity
Declaration of Conformity
The undersigned
KKW Kulmbacher Klimageräte-Werk GmbH, Division Dimplex Am Goldenen Feld 18 D-95326 Kulmbach
hereby confirm that the design and construction of the product(s) listed below, in the version(s) placed on the market by us, conform to the relevant basic requirements of the applicable EC directives.
This declaration becomes invalidated if any modifications are made to the product(s) without our prior authorization.
Designation of the product(s): EC Directives:
Brine-to-water heat pumps EC Low Voltage Directive
for indoor installation withR407C (73/23/EEC)
EC EMC Directive (89/336/EEC)
Water-to-water heat pumps Pressure Equipment Directive
for indoor installation withR407C (97/23/EEC)
Type(s): Harmonized EN Standards:
SI 5CS SI 7CS SI 9CS SI 11CS SI 14CS SI 17CS SI 21CS
WI 9CS WI 14CS WI 22CS WI 27CS
Order No.: National Standard/Directives:
Requirements of category II
337 280 337 290 337 300 337 310 337 320 337 330 337 340
Kulmbach, 07.05.2002
338 720 337 350 337 360 337 370
General Manager Technical Director
38
Page 39
Notes
39
Page 40
KKW Kulmbacher Klimageräte-Werk GmbH Subject to technical modifications Division Dimplex Fax (0 92 21) 709-589 Am Goldenen Feld 18 www.dimplex.de D-95326 Kulmbach
40
Loading...