Dimplex SI 5CS, SI 21CS, SI 14CS, SI 7CS, SI 17CS User Manual

...
MOUNTING and
OPERATING MANUAL
Brine-to-Water Heat Pump
for Indoor Installation
SI 5CS SI 7CS SI 9CS SI 11CS
SI 14CS SI 17CS SI 21CS
Order No.: 452230.67.01 FD 8404
1
CONTENTS
1 READ IMMEDIATELY 3
1.1 Important Information
1.2 Legal Provisions and Directives
1.3 Energy-Efficient Use of the Heat Pump
2 PURPOSE OF THE HEAT
PUMP 4
2.1 Application
2.2 Principle of Operation
3 BASELINE UNIT 4
4 ACCESSORIES 5
4.1 Brine Manifold
5 TRANSPORT 5
6 INSTALLATION 6
6.1 General Information
6.2 Sound Emissions
7 MOUNTING 6/7
7.1 General
7.2 Connection on Heating Side
7.3 Connection on Heat Source Side
7.4 Electrical Connection
8 COMMISSIONING 8
8.1 General
8.2 Preparation
8.3 Commissioning Procedure
9 CARE/CLEANING 9
9.1 Care
9.2 Cleaning of Heating Side
9.3 Cleaning of Heat Source Side
10 MALFUNCTIONS/TROUBLE-
SHOOTING 10
11 DECOMMISSIONING 10
11.1 Shutdown in Summer
11.2 End-of-Life Decommissioning
12 Appendix 11
2
READ IMMEDIATELY
READ IMMEDIATELY
1
1.1 Important Information
CAUTION!
wooden pallet.
CAUTION!
more than max. 45° (in either direction).
CAUTION!
panel assemblies!
CAUTION!
connecting the heat pump.
The heat pump is not attached to the
The heat pump must not be tilted
Do not lift unit by the holes in the
Flush the heating system prior to
CAUTION!
be performed by authorised and qualified customer service technicians.
CAUTION!
connected from the power source prior to opening the cabinet.
1.2 Legal Provisions and Directives
This heat pump conforms to all relevant DIN/VDE regulations and EU directives. For details refer to the EC Declaration of Conformity in the appendix.
The electrical connection of the heat pump must be performed according to and conforming with all re­levant VDE, EN and IEC standards. Beyond that, the connection requirements of the local utility compa­nies have to be observed.
The heat pump is to be connected to the heat source and heat distribution systems in accordance with all applicable provisions.
Any work on the heat pump may only
All power circuits must be dis-
CAUTION!
in the heat source inlet of the heat pump in order to protect the evaporator against contamina­tion.
CAUTION!
of a frost and corrosion protection agent on a monoethylene glycol or propylene glycol basis.
CAUTION!
must be observed when connecting the load line.
The supplied strainer is to be fitted
The brine must contain at least 25 %
The clockwise phase sequence
CAUTION!
CAUTION!
must be performed in accordance with the mounting and operating manual of the heat pump controller.
Commissioning of the heat pump
1.3 Energy-Efficient Use of the Heat Pump
By operating this heat pump you contribute to the protection of our environment. A prerequisite for an efficient operation is the proper design and sizing of the heating system and the heat source system. In particular, it is important to keep water flow temperatures as low as possible. All energy consumers connected should therefore be suitable for low flow temperatures. A 1 K higher heating water temperature corresponds to an increase in power consumption of approx. 2.5 %. Underfloor heating systems with flow temperatures between 30 °C and 40 °C are optimally suited for energy-efficient operation.
3
PURPOSE OF HEAT PUMP BASELINE UNIT
PURPOSE OF THE HEAT PUMP
2.1 Application
The brine-to-water heat pump is designed for use in existing or newly built heating systems. Brine is used as the heat carrier in the heat source system. Ground coils, ground collectors or similar systems can be used as the heat source.
2.2 Principle of Operation
The heat generated by the sun, wind and rain is stored in the ground. This heat stored in the ground is collected at low temperature by the brine circulating in the ground collector, ground coil or similar device. A circulating pump then conveys the warmed brine to the evaporator of the heat pump. There, the heat is given off to the refrigerant in the refrigeration cycle. When so doing, the brine cools so that it can again take up heat energy in the brine circuit.
BASELINE UNIT
32
The baseline unit consists of a heat pump, ready for connection, for indoor installation, complete with sheet metal cabinet, control panel and integrated controller. The refrigeration cycle contains the refrigerant R407C. Refrigerant R407C is CFC-free, non-ozone depleting and non-combustible.
All components required for the operation of the heat pump are located on the control panel. The power feed for the load and control current must be field­installed by the customer.
The supply lead of the brine pump (to be provided by the customer) must be connected to the control panel. When so doing, a motor protecting device is to be installed, if required.
The collector loops including brine manifold must be provided by the customer.
1 2 3
The refrigerant, however, is drawn in by the electrically driven compressor, is compressed and "pumped" to a higher temperature level. The electrical power needed to run the compressor is not lost in this process, but most of the generated heat is trans­ferred to the refrigerant as well.
Subsequently, the refrigerant is passed through the condenser where it transfers its heat energy to the heating water. Based on the thermostat setting, the heating water is thus heated to up to 55 °C.
4
1) Condenser 3) Evaporator
2) Control panel 4) Compressor
4
ACCESSORIES
TRANSPORT
ACCESSORIES
4.1 Brine Manifold
The brine manifold ties the individual collector loops of the heat source system into a single main line which is connected to the heat pump. Integrated ball valves allow individual brine circuits to be shut off for venting purposes.
TRANSPORT
54
A lift truck is suited for transporting the unit on a level surface. If the heat pump needs to be transported on an uneven surface or carried up or down stairs, carrying straps may be used for this type of transport. These straps may be passed directly underneath the wooden pallet.
CAUTION!
wooden pallet.
The heat pump is not secured to the
CAUTION!
more than max. 45° (in either direction).
For lifting the unit without pallet, the holes provided in the sides of the frame should be used. The side panel assemblies must be removed for this purpose. A commercially available pipe can be used as a carrying aid.
CAUTION!
assemblies for lifting the unit!
The heat pump must not be tilted
Do not use the holes in the panel
5
INSTALLATION MOUNTING
6
INSTALLATION
6.1 General Information
As a rule, the unit must be installed indoors on a level, smooth and horizontal surface. The entire base frame should thereby make close contact with the surface in order to ensure adequate sound insulation. Failing this, additional sound insulation measures may become necessary.
The heat pump should be located to allow safe and easy maintenance/service access. This is ensured if a clearance of approx. 1 m in front of and to each side of the heat pump is maintained.
1m
1m
1m
MOUNTING
7
7.1 General
The following connections need to be established on the heat pump:
- supply/return flow of the brine system
- supply/return flow of the heating system
- power supply
7.2 Connection on Heating Side
CAUTION!
prior to connecting the heat pump.
Before completing the heat pump connections on the heating water side, the heating installation must be flushed in order to remove any impurities that may be present, as well as residues of sealing material, and the like. Any accumulation of deposits in the condenser may result in a total failure of the heat pump.
Once the installation on the heating side has been completed, the heating system must be filled, de­aerated and pressure-tested.
The heating system must be flushed
6.2 Sound Emissions
The heat pump offers silent operation due to efficient sound insulation. To prevent noise transmission to the foundation, a suitable, sound dampening rubber mat should be placed underneath the base frame of the heat pump.
Any sound transmission to the heating systems is prevented by means of flexible pressure tubing already integrated into the heat pump.
Heating water minimum flow rate
The heating water minimum flow rate through the heat pump must be assured in all operating states of the heating system. This can be accomplished, for example, by installing a differential pressure-free manifold or an overflow valve. The procedure for setting an overflow valve is described in the Chapter Commissioning.
Frost protection for installations prone to frost
Provided the controllers and circulating pumps are ready for operation, the frost protection feature of the controller is active. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained. In heat pump installations where a power failure cannot be readily detected (holiday house), the heating circuit must contain a suitable antifreeze product.
6
MOUNTING
7.3 Connection on Heat Source Side
The following procedure must be observed when making the connection:
Connect the brine line to the flow and return pipe of the heat pump.
CAUTION!
in the heat source inlet of the heat pump in order to protect the evaporator against the ingress
of impurities.
In addition, a powerful vent must be installed at the highest point of the heat source system. The hydraulic plumbing diagram must be observed here.
The brine liquid must be produced prior to charging the system. The brine concentration must be at least 25 %. Freeze protection down to
-14°C can thus be ensured. Only antifreeze products on the basis of mono-
ethylene glycol or propylene glycol may be used. The heat source system must be vented (de-
aerated) and be checked for leaks.
The supplied strainer must be fitted
An all-pole disconnecting device with a contact gap of at least 3 mm (e.g. utility company disable contac­tor or power contactor) as well as a 3-pole circuit breaker with simultaneous tripping of all external conductors must be provided . The required cross­sectional area of the conductor is to be selected according to the power consumption of the heat pump, the technical connection requirements of the relevant utility company and all applicable regula­tions. Power consumption data of the heat pump is provided in the product literature and on the nameplate. The terminals are designed for a max. conductor cross-section of 10 mm˝.
CAUTION!
must be observed when connecting the load line (the heat pump will deliver no output and will be very noisy when the phase sequence is in­correct).
The clockwise phase sequence
CAUTION!
least 25 % of an antifreeze and corrosion protection agent on a monoethylene glycol or
propylene glycol basis.
The brine solution must contain at
7.4 Electrical Connection
The following electrical connections must be established on the heat pump:
- Connection of the control wire to the control panel of the heat pump via terminals X1: L/N/PE.
- Connection of the load wire to the control panel of the heat pump via terminals X5: L1/L2/L3/PE.
- Connection of the brine pump (to be provided by the customer) to the control panel of the heat pump via terminal X1: PE and pump contactor K2: 2/4/6 (.. 5-17CS), or motor protection F7: 2/4/ 6 (.. 21CS).
All electrical components required for the operation of the heat pump are located on the control panel.
For detailed instructions concerning the connection and functioning of the heat pump controller refer to the operating manual supplied with the controller.
7
COMMISSIONING
8
COMMISSIONING
8.1 General Information
To ensure proper commissioning it should be carried out by an after-sales service authorized by the manufacturer. Only then can an extended warranty period of 3 years in total be granted (cf. Warranty service).
8.2 Preparation
Prior to commissioning, the following items need to be checked:
- All connections of the heat pump must have been made as described in Chapter 7.
- The heat source system and the heating circuit must have been filled and checked.
- The strainer must have been fitted in the sole inlet of the heat pump.
b) Close all of the heating circuits that may also be
closed during operation (depending on the type of heat pump usage) so that the most unfa­vourable operating state - with respect to the water flow rate - is achieved.
c) In this operating state open the overflow valve
until approximately the same temperature difference exists that was measured under a) when the overflow valve was closed and the heating circuits open.
Any malfunctions occurring during operation are displayed on the heat pump controller and can be corrected as described in the operating manual of the heat pump controller.
- In the brine and heating circuits all valves that could impair the proper heating water flow must be open.
- The settings of the heat pump controller must be adapted to the heating installation in accordance with the instructions contained in the controller's operating manual.
8.3 Commissioning Procedure
The start-up of the heat pump is effected via the heat pump controller.
CAUTION!
must be performed in accordance with the mounting and operating manual of the heat pump controller.
Where an overflow valve is fitted to assure the minimum heating water flow rate, the valve must be set in accordance with the requirements of the heating installation. An incorrect setting may result in various error symptoms and an increased elec­tric power consumption. To correctly set the overflow valve, the following procedure is recommended:
Commissioning of the heat pump
a) Open all heating circuits and close the overflow
valve. Determine the resulting temperature difference between supply and return flow.
8
9
CARE/CLEANING
9.1 Care
The heat pump is maintenance-free. To prevent malfunctions due to sediments in the heat ex­changers, care must be taken that no impurities can enter the heat source system and heating installa­tion. In the event that operating malfunctions due to contamination occur nevertheless, the system should be cleaned as described below.
9.2 Cleaning of Heating Side
The ingress of oxygen into the heating water circuit may result in the formation of oxidation products (rust). It is therefore important - in particular with respect to the piping of underfloor heating systems
- that the installation is executed in a diffusion-proof manner.
Also residues of lubricating and sealing agents may contaminate the heating water.
CAUTION!
Depending on the filling water quality and quantity, in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form, impairing the pro­per functioning of the heating installation. A reason for this is the water hardness and oxygen dissolved in the filling waters as well as additional oxygen from the air, which may penetrate via valves, fittings and plastic pipes (oxygen diffusion). As a preventive measure it is recommended that a physical water conditio­ner such as ELYSATOR be used.
Caution - Heating Technicians !
9.3 Cleaning of Heat Source Side
CAUTION!
ed in the heat source inlet of the heat pump in order to protect the evaporator against conta­mination.
The supplied strainer is to be install-
CARE/CLEANING
In the case of severe contaminations leading to a reduction of the performance of the condenser in the heat pump, the system must be cleaned by a heating technician.
According to current knowledge, we recommend cleaning with a 5% phosphoric acid solution or, in the case that cleaning needs to be performed more frequently, with a 5% formic acid solution.
In either case, the cleaning fluid should be at room temperature. It is recommended that the heat exchanger be cleaned in the direction opposite to the normal flow direction.
To prevent acidic cleaning agents from entering the circuit of the heating installation we recommend that the flushing device be fitted directly to the supply and return lines of the condenser. To prevent any damage caused by cleaning agent residues that may be present in the system it is important that the system be thoroughly flushed using appropriate neutralising agents.
The acids must be used with great care, all relevant regulations of the employers' liability insurance associations must be adhered to.
The filter screen of the strainer should be cleaned one day after commissioning, thereafter every week. If no more contamination can be noticed any more, the strainer filter can be removed in order to reduce pressure losses.
If in doubt, contact the manufacturer of the chemicals!
9
MALFUNCTIONS/TROUBLESHOOTING DECOMMISSIONING
MALFUNCTIONS/
10
CAUTION!
TROUBLESHOOTING
This heat pump is a quality product and is designed for trouble-free operation. In the event that a malfunction occurs nevertheless, you will be able to correct the problem yourself in most of the cases. Simply consult the Malfunctions and Trouble­shooting table contained in the operating manual of the heat pump controller.
Additional malfunctions can be interrogated at the heat pump controller.
If you cannot correct the malfunction yourself, please contact the after-sales service agent in charge (see Warranty Certificate).
All work on the heat pump may only be performed by an authorised and qualified after-sales service.
DECOMMISSIONING
11
11.1 Shutdown in Summer
Shutting down the heating system in summer is effected by switching the heat pump controller to the "Summer" operating mode.
11.2 End-of-Life Decommissioning/ Disposal
Before removing the heat pump, disconnect the machine from the power source and close all valves. Environment-relevant requirements regarding the recovery, recycling and disposal of service fuels and components in accordance with all relevant standards must be adhered to. Particular attention must hereby be paid to the proper disposal of refrigerants and refrigeration oils.
CAUTION!
connected from the power source prior to opening the equipment.
All electrical circuits must be dis-
10
12
APPENDIX
APPENDIX
12.1 Dimensioned Drawings
12.1.1 Dimens'ddrawing .. 5CS - 14CS 12
12.1.2 Dimens'd drawing .. 17CS - 21CS 13
12.2 Equipment Data 14
12.3 Performance Curves/Pressure Losses
12.3.1 Performance Curves .. 5CS 15
12.3.2 Pressure Losses .. 5CS 16
12.3.3 Performance Curves .. 7CS 17
12.3.4 Pressure Losses .. 7CS 18
12.3.5 Performance Curves .. 9CS 19
12.3.6 Pressure Losses .. 9CS 20
12.3.7 Performance Curves .. 11CS 21
12.3.8 Pressure Losses .. 11CS 22
12.3.9 Performance Curves .. 14CS 23
12.3.10 Pressure Losses .. 14CS 24
12.3.11 Performance Curves .. 17CS 25
12.3.12 Pressure Losses .. 17CS 26
12.3.13 Performance Curves .. 21CS 27
12.3.14 Pressure Losses .. 21CS 28
12.4 Wiring Diagram
12.4.1 Control .. 5CS to .. 17CS 29
12.4.2 Load .. 5CS bis .. 17CS 30
12.4.3 Terminal Diagram .. 5CS to .. 17CS 31
12.4.4 Legend .. 5CS to .. 17CS 32
12.4.5 Control .. 21CS 33
12.4.6 Load .. 21CS 34
12.4.7 Terminal Diagram .. 21CS 35
12.4.8 Legend .. 21CS 36
12.5 Hydraulic Block Diagram 37
12.6 EC Declaration of Conformity 38
12.7 Warranty Certificate 39
11
APPENDIX: 12.1 DIMENSIONED DRAWINGS
12.1.1 Dimensioned Drawing .. 5CS - 14CS
Heat source supply
Heat pump outlet
Heat source return
Heat pump inlet
1" internal / 1" external thread
Connections on heating side
1 1/4" internal / 1 1/4" external thread
Connections on heat source side
Heating water return
Heat pump inlet
Heating water supply
Heat pump outlet
12
Loading...
+ 28 hidden pages