Dimplex SCxn175si, SCxn215sd, SCxn215si, SCxn255si, SCxn305si Installation And Operating Instructions Manual

...
Page 1
Page 1 of 28
ST0109 – C 05/09
WATER
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Installation and operating instructions
Page 2
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 2 of 28
ST0109 – C 05/09
WATER
0 Overall view
Figure 1 – Overall view of proposed installation sequence SCxn…d/i
SCxn80/130/150/175/215/255/305d
01
02
03
04
05
06
07
SCxn80/130/150/175/215/255/305i
11
08
Standard SCxn cylinder
01
02
03
04
05
07
09
10
Page 3
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 3 of 28
ST0109 – C 05/09
WATER
Figure 2 – Overall view of proposed installation sequence SCxn…sd/si
SCxn175/215/255/305sd
SCxn175/215/255/305si
18
01 02 03 04 05 07 08 09 10 11 12 13 14 15 16 17 18 01 02 03 04 05 07 12 13 14 15 16 17 06
Solar SCxn cylinder
Page 4
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 4 of 28
ST0109 – C 05/09
WATER
1 Contents
0 OVERALL VIEW 2
1 CONTENTS 4
2 BEFORE YOU START 5
G
ENERAL 5
C
OMPETENCE 5
H
EALTH AND SAFETY 5
R
ISK ASSESSMENT 6
3 SCOPE OF DELIVERY 6
4 PRODUCT FEATURES AND DESCRIPTIONS 7
5 INSTALLATION 9
5.1
GENERAL ADVICE 9
5.2
SITING CONSIDERATIONS 10
5.3
COLD WATER SUPPLY AND DISCHARGE PIPE WORK 10
5.4
HOT WATER OUTLET 12
5.5
IMMERSION HEATER 12
5.6
INDIRECT HEATING LOOP 13
5.7
SOLAR LOOP 14
5.8
SECONDARY RETURN 15
5.10
INSTALLATION EXPANSION VESSEL 15
5.11
WIRING SCHEMATIC AUXILIARY LOOP 16
5.12
WIRING SCHEMATIC SOLAR LOOP 19
5.13
SOLAR SENSOR INSTALLATION 19
6 COMMISSIONING 21
6.1
SCXN D/I RANGE 21
6.2
SCXN SD/SI RANGE 21
7 OPERATION 22
7.1
WATER TEMPERATURE DIRECT ELECTRIC HEATING 22
7.2
WATER TEMPERATURE AUXILIARY HEATING 23
8 MAINTENANCE 23
9 TROUBLESHOOTING 24
10 TECHNICAL DATA 25
10.1
SCXN D/I 25
10.2
SCXN SD/SI 26
Page 5
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 5 of 28
ST0109 – C 05/09
WATER
2 Before you start
General
Thank you for choosing a Dimplex product. We ensure you that every effort was made at design, manufacture and delivery stages of this product to meet your expectations. We ensure you of our best possible support throughout the product’s lifespan. As part of ongoing product development and improvement Dimplex reserves the right to undertake changes to the product without prior notice. Great care has been taken to ensure this manual was correct at the time of print. Should you however discover any issues with the information contained therein please do not hesitate to contact your vendor. We strongly recommend you read the whole contents of this manual before commenc­ing the work.
Competence
Dimplex products have been designed and manufactured to the current relevant stan­dards and under stringent quality control. It is therefore imperative that the product is only installed by a:
- trained and
- competent person as defined in the relevant regulations. Dimplex does not accept any liability for damage done to persons or property resulting from undue handling and usage of this product. All regulations current at the time of installation are to be considered alongside the con­tent of this manual as they form the code of best practice.
The guarantee of this product is linked to the ability of proving that the product was installed, commissioned and maintained:
- by a competent person
- in accordance with Dimplex instructions and the current relevant regulations and leg­islation
- the product being registered with Dimplex at the time of installation using the form in the Dimplex On Site Guide
- records showing the date of maintenance in accordance with the maintenance sched­ule as detailed in the On Site Guide
Health and Safety
The installation of this product is subject to the Health and Safety at Work Act. It is your responsibility to ensure that the transport, storage, installation and operation of the product is carried out in a safe manner. Dimplex will not accept any liability due to damage caused to people or property result­ing from negligence or not adhering to the relevant Health and Safety practises.
Page 6
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 6 of 28
ST0109 – C 05/09
WATER
Risk assessment
The compilation of a risk assessment is strongly recommended before installing the product. The following areas require particular consideration in addition to the informa­tion required by the Health and Safety at Work Act.
- scalding: where appropriate or required by law a thermostatic mixing valve is to be fitted to the hot water outlet of the cylinder
- explosion: the unit is fully equipped with all relevant safety equipment to comply with current regulations. The correct design and function has been verified by independent third party testing. The correct application thereof is the responsibility of the compe­tent installer.
- water borne organisms (i.e. Legionella): if applicable a risk assessment should be carried out following the recommendations outlined in the Approved Code of Practise L8.
- the user preference must be considered when commissioning the system, in particular when adjusting the solar and auxiliary system temperature and timer settings.
3 Scope of delivery
Please check the contents and condition of your delivery before signing the delivery documentation. Contact your supplier immediately for any missing or damaged compo­nents. Claims for missing or damaged parts after signing for the delivery will not be accepted.
SCxn
175/215/255/305
SCxn
80/150/175/215/255/305
d i sd si
Unvented stainless steel cylinder including:
- cold water inlet
- hot water outlet
- ½” sensor pockets
- ½” secondary return
- auxiliary heating coil
- solar coil
- twin thermostat
- 3kW immersion
- T&P Valve
x1 x1
-
-
-
-
-
x1(SCxn80)/x2
x1
x1
x1
-
-
x1
-
x1
x1 x1
x1
x1 x2 x1
-
x1
x1 x2 x1
x1
x1 x2 x1 x1 x1 x2 x1 x1
Page 7
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 7 of 28
ST0109 – C 05/09
WATER
Figure 3 – Scope of delivery
4 Product features and descriptions
The Dimplex® unvented stainless steel cylinder range incorporates many features to ensure the highest level of comfort in providing hot water while minimising energy re­quirements and environmental impact during manufacturing, operation and disposal. The range covers storage volumes from 80 litres to 305 litres in various designs from direct electric heated units, indirect units to a range of units allowing the use of renew­able energy sources such as solar thermal. A complete list of features provided by the whole range of cylinders is given in Figure 4.
Expansion vessel: 18 l: 175 l, 215 l 24 l: 255 l, 305 l
-
-
-
-
x1
x1
Expansion vessel fixing kit
-
- x1
x1
Inlet control group
2ba
r
6bar
2ba
r
6bar
3ba
r
6bar
3ba
r
6bar
Tundish 15mm – 22mm
x1
x1 x1 x1
Two port motor­ised valve 22mm
-
x1 - x1
Instructions x1
x1 x1 x1
Benchmark card x1
x1 x1 x1
SCxn…d
SCxn…i
SCxn…sd
SCxn…si
Pres. red. Pres. rel.
Page 8
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 8 of 28
ST0109 – C 05/09
WATER
Feature
SCxn
d i si
sd
80
-
305
80 130 150 175 215 255 305
175
-
305
175
-
305
Materials
- inner cylinder
- outer cylinder
- inlet/outlet
- coils
- insulation
Duplex stainless steel Dove grey leather grain coated steel Stainless steel Corrugated stainless steel 60mm PU foam (GWP=1, ODP=0)
Maximum operating conditions
- potable water temperature
- heating water temperature
- operating pressure
70°C 95°C 6bar
Cold water supply
- minimum dynamic pressure
- maximum pressure
- minimum flow rate
1.5bar 25bar 15 l/min
Connections
- cold water inlet
- hot water outlet
- secondary return
- coil flow and return
- sensor pocket
22mm stainless steel 22mm stainless steel ½”F BSP 22mm stainless steel ½”F BSP
Coil specification
- surface area [m²]
- rating [kW]
-
-
0.3 7
0.5 14
0.75 17
0.75/1.1 17/-
Immersion heater 1/
2
1 1 2
Thermostatic control
- direct input
- indirect input
- integral immersion heater thermostat and cut out
- external twin thermostat and cut out
Safety components
- pressure reducing valve and strainer
- expansion relief valve
- temperature and pressure relief valve
- factory pressure test
2bar
6bar 7bar / 90°C
10bar
3bar
6bar 7bar / 90°C 10bar
Other features Water inlet diffuser – prevents cold and hot water from mix-
ing
Water outlet sloped – improves stratification during draw off
and reduces heat loss Light weight – easy handling No anode – reduced service requirements
Approvals KIWA
BBA
Guarantee
- inner cylinder
- immersion heaters
- other components
25 years 2 years – excluding the effects of lime scale 5 years – excluding expansion vessel membrane pressure
Figure 4 – Product features
Page 9
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 9 of 28
ST0109 – C 05/09
WATER
5 Installation
5.1 General advice
Please read the following section carefully before commencing installation. If in any doubt, please call the appropriate help desk. Disregarding the instructions given in this manual in its entirety and any relevant regulations, standards and codes of practice will void the guarantee of this product.
Please note: the following instructions are structured in such a way that individual steps are described. Not all steps will apply to all products. Figure 5 shows which steps apply to which cylinder types.
Figure 5 – Chapter reference
Handling – depending on the size of the unit and access to its installation location con­sideration must be given to the handling of the unit. Please note that handling, installa­tion and use of this product is subject to the Health and Safety at Work Act. If the unit is not installed immediately, it should remain in its protective packaging with all pipe protectors/end caps applied to prevent damage and dirt deposit inside the cyl­inder and the coils.
Pipe work – the pipe runs should be executed as short as possible, unused pipe work should be removed and all remaining pipe work should be lagged in accordance with regulatory requirements to prevent heat loss and the formation of condensation.
Taps and fittings – all taps and fittings incorporated in the unvented system should have a rated operating pressure of 6 bar or above.
Page 10
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 10 of 28
ST0109 – C 05/09
WATER
5.2 Siting considerations
When choosing a suitable location for the cylinder the following aspects should be con­sidered:
- structural integrity
- access for installation, operation, maintenance and replacement
- routing of discharge pipe work
- access to water mains supply, hot and cold water distribution pipe work
- access to suitable electricity supply
- location in relation to remaining system components such as auxiliary and solar heat­ing system
- frost protection
The Dimplex SCxn cylinder range is designed to be floor standing, vertically mounted, indoors and in a frost free environment. The cylinder may be located on any flat and level surface, provided it is sufficiently robust to support the weight of the cylinder when full of water (see chapter 10).
The position and orientation of the cylinder should be such that easy access is provided for servicing the controls and replacing the immersion heater should the need arise. Ensure that no pipe work hinders any work to be carried out on the various cylinder components. Particular care must be taken when placing the cylinder in a garage or outbuilding. All exposed pipe work must be correctly insulated to avoid frost damage. If required the occurrence of frost has to be avoided by means of heating the space in which the cylin­der is located.
5.3 Cold water supply and discharge pipe work
The required operating conditions of the Dimplex SCxn cylinder range are summarised in Figure 4. The following instructions have to be followed when installing the cold water mains supply to the cylinder.
1 The cold water supply to the cylinder must come directly from the cold water mains
after the mains stop valve to the property.
2 The inlet group supplied with the cylinder contains a line strainer, pressure reducing
valve, pressure relief valve, check valves, balanced cold water supply port and a connection point for the expansion vessel (required for SCxn solar only).
3 The cold water inlet pipe work should have at least an inside diameter of 19mm and
meeting the requirements of the water regulations for the supply of wholesome wa­ter.
4 The discharge pipe work from the expansion relief valve must be installed constantly
falling to an open point of discharge. It is recommended to combine it with the dis­charge of the temperature and pressure relief valve as illustrated in Figure 6.
When completing the installation of the discharge pipe work ensure the valve itself is
secured by tightening the screw on the side of the assembly. Loosening the screw allows the best possible orientation of the valve.
Page 11
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 11 of 28
ST0109 – C 05/09
WATER
5 It is recommended to install a drain valve in the lowest point of the cold water feed
to the cylinder. This allows the cylinder to be drained in a controlled manner should this become necessary.
Note: Between the inlet group and the cold water inlet on the cylinder NO
isolating
device should be fitted as by doing so important safety devices could be isolated!
6 The temperature and pressure relief valve must be discharged into the tundish. The
sizing of the discharge pipe work is regulated through building regulation G3. An ex­tract is shown in Figure 6.
01
02 03 04 05
Discharge pipe constantly falling to safe discharge location.
max. 500mm
06
min. 300mm
Page 12
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 12 of 28
ST0109 – C 05/09
WATER
Figure 6 – Cold water supply and discharge pipe work installation
5.4 Hot water outlet
The hot water pipe work is to be directly connected to the how water outlet connections of the cylinder as indicated in Figures 1 and 2.
Should a thermostatic mixing valve be required the valve is to be installed following the manufacturers instructions. When fitting the thermostatic mixing valve ensure that none of the safety relevant devices of the unit can be isolated (see 5.3).
It is recommended to insulate the hot water pipe work from the cylinder to the outlets to reduce the energy requirements for providing hot water.
5.5 Immersion heater
The immersion heater has to be connected in accordance with IEE Wiring Regulations and the installer carrying out the work has to be suitably qualified. It must be con­nected through a double pole isolating switch or suitable controller which must have a contact separation of at least 3mm in all poles. The wiring diagram for the immersion heater is shown in Figure 7. For further details please see instructions provided with immersion heater.
The immersion heater incorporates an independent non-self resetting over temperature cut-out. Should the over temperature cut-out operate, the rest pin will be pushed up­wards, and become level or slightly proud of the cover at the position marked “Safety”. Use a suitable sized implement to reset the pin by pushing it hard into its original posi­tion.
Figure 7 – Wiring diagram immersion heater
Page 13
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 13 of 28
ST0109 – C 05/09
WATER
Note: The cylinder must be filled with water before switching on the immersion heater. Failure to do so will damage the element and void any guarantee on the product.
5.6 Indirect heating loop
The indirect heating source can be connected to the cylinder in various ways as de­scribed by the chosen control system supplier. The wiring and installation principles for two typical integration methods are detailed in chapter 5.11.
Figure 8 – indirect heating loop installation
To conform with building regulations it is imperative that the motorised two port valve is installed in the indirect heating loop and connected into the control circuit as required.
08
SCxn…i
SCxn…si
09
11 10 08 09 11 10
Page 14
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 14 of 28
ST0109 – C 05/09
WATER
The port connections for the indirect heating flow and return are identified in Figure 1 for the SCxn…i range and in Figure 2 for the SCxn…si range. Should the flow connection be the highest point in the indirect heating loop an adequate device for de-aeration has to be installed. Equally, should the return connection be the lowest point in the indirect heating loop, a suitable drain device should be installed in the lowest point.
When installing the motorised two port valve ensure the direction of flow is adhered to as marked on the body of the device. Connecting the control loop ensure the correct thermostat on the cylinder is chosen for the respective loop.
The fittings used to connect to the cylinder must be suitable for stainless steel. Not all push fit fittings can be used – please check with your supplier. Should compression fit­tings be used ensure that the connection is not being over-tightened, always countering the force with a second spanner.
5.7 Solar loop
The solar loop has to be completely installed:
- in metal pipe work
- insulated with high temperature insulation
- connected with compression fittings only (or other means which are suitable for solar)
Figure 9 – Solar loop installation
13
SCxn…sd / SCxn…si
12
14
Page 15
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 15 of 28
ST0109 – C 05/09
WATER
The wiring schematic for the solar loop is detailed in chapter 5.12. Please note: the so­lar loop does not require a motorised two port valve as long as:
- the Dimplex SOLPU1/2 pump unit is being used (non return valves in flow and return)
- the cylinder is located lower than the solar panels
- all other connection requirements in this manual are being adhered to To conform with building regulations it is imperative that the solar circulation pump is installed in the solar loop through the twin thermostat and not directly from the solar control unit.
The port connections for the solar flow and return connections are identified in Figure 2 for the SCxn…sd and the SCxn…si range. Should the flow connection be the highest point in the solar loop an adequate device for de-aeration has to be installed should the system not be commissioned using a flush a fill pump. Equally, should the return connection be the lowest point in the solar loop, a suitable drain device should be installed in the lowest point.
5.8 Secondary return
A ½” boss is provided on the SCxn…sd/si cylinder range to connect a secondary return loop to avoid:
- stagnant water in long pipe runs
- long waiting times at draw off point for hot water
- undue water wastage To minimise the energy consumption of the secondary return circuit and to ensure reli­able operation it is important to consider:
- the control of the circulation pump to be time and temperature controlled
- the secondary return circuit pipe work to be insulated
- the secondary return pump to be of suitable material
The location of the secondary return connection on the cylinder is highlighted in Figure
2.
5.10 Installation expansion vessel
Optional for standard SCxn d/i cylinders, mandatory for solar SCxn d/I cylinders.
The expansion vessel can be connected directly to the cold water inlet group utilising the flexible hose supplied with the vessel. It is important not to install any isolating de­vices between the vessel and the cold water inlet group.
Further it is recommended to mount the vessel higher than the cylinder to avoid having to drain the cylinder when maintaining and replacing the expansion vessel. The connec­tion of the expansion vessel to the inlet group is shown in Figure 10.
Page 16
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 16 of 28
ST0109 – C 05/09
WATER
Figure 10 – Installation expansion vessel
(optional for standard SCxn d/i cylinders, mandatory for solar SCxn d/I cylinders)
It is important to check the pre-charge pressure of the expansion vessel mem­brane before filling the cylinder. The pre-charge should be >2bar.
5.11 Wiring schematic auxiliary loop
The auxiliary heating system can be interfaced with the Dimplex SCxn cylinder in vari­ous. Two common examples are given in Figures 11 and 12.
Before adapting one of the proposed systems ensure the system is compatible with the remaining control equipment installed in the system.
Page 17
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 17 of 28
ST0109 – C 05/09
WATER
Figure 11 – Auxiliary loop integration 2x motorised two port valve
Page 18
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 18 of 28
ST0109 – C 05/09
WATER
Figure 12 - Auxiliary loop integration 1x motorised two port valve and mid-position valve
Page 19
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 19 of 28
ST0109 – C 05/09
WATER
5.12 Wiring schematic solar loop
The integration of the Dimplex solar SCxn cylinder is shown in Figures 11 and 12. The wiring schematic for the solar loop is shown in Figure 13.
Figure 13 – Solar loop integration
5.13 Solar sensor installation
The Dimplex solar SCxn range cylinders allow for the installation of two sensors. The lower sensor is required to control the solar circulation pump. The upper sensor is for information only to indicate the actual available hot water temperature.
Two ½” sensor pockets are supplied with the pump unit. The sensor pockets are to be used to install the sensors in the cylinders.
The location of the sensor bosses is indicated in Figure 14, also showing the methodol­ogy of installing the sensor into the sensor pocket. A suitable sealant is to be used such as Loctite 577.
Page 20
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 20 of 28
ST0109 – C 05/09
WATER
Figure 14 – Solar sensor boss positions and sensor installation
01
02 03
Page 21
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 21 of 28
ST0109 – C 05/09
WATER
6 Commissioning
The following commissioning procedure only details the required steps to be taken for the potable water loop and not for the direct heating, auxiliary or solar loops. Please refer to relevant manuals for these operations.
6.1 SCxn … d/i range
1 Check all connections and joints to ensure they have been tightened and se-
cured correctly.
2 Before turning on the mains supply to the cylinder a hot water tap should be
opened, preferable on the same floor or the floor below where the cylinder is located.
3 Turn on the supply to the cylinder and fill until water runs from the open hot
water tap.
4 Turn off the mains supply to the cylinder and wait for the water to stop run-
ning from the hot water tap.
5 Operate the temperature and pressure relief valve until water stops flowing.  6 Close the hot water tap and temperature and pressure relief valve.  7 Connect an air pump to the Schrader valve (valve with blue cap) located on
the pressure reducing valve (inlet group).
8 Pump air into the Schrader valve until a pressure of 1 bar is reached.  9 Remove the pump and replace the blue cap.  10 Turn the mains supply back on and bring the cylinder up to working pressure.  11 Check all joints for leaks, even those not having been altered especially when
replacing a vented cylinder.
12 Open temperature and pressure relief valve to ensure proper discharge and
check after closing that valve is not dripping.
13 Open pressure relief valve to ensure proper discharge and check after closing
that valve is not dripping.
14 Check all shower outlets, toilet cisterns and other draw off points for leaks or
dripping (especially when replacing a vented unit).
15 Open all water outlets to purge air from pipe work and ensure proper opera-
tion.
16 Adjust timer programmer and cylinder thermostat settings in accordance with
client requirements.
17 Instruct user in the operation of the unit and hand over manuals and bench-
mark card, advising the owner of annual service requirement.
6.2 SCxn … sd/si range
1 Check all connections and joints to ensure they have been tightened and se-
cured correctly.
2 Before turning on the mains supply to the cylinder a hot water tap should be
opened, preferable on the same floor or the floor below where the cylinder is located.
3 Check the pre-charge in the expansion vessel and ensure it is at least 2bar.
Note actual pressure on label on expansion vessel.
Page 22
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 22 of 28
ST0109 – C 05/09
WATER
4 Turn on the supply to the cylinder and fill until water runs from the open hot
water tap.
5 Close the hot water tap.  6 Check all joints for leaks, even those not having been altered especially when
replacing a vented cylinder.
7 Open temperature and pressure relief valve to ensure proper discharge and
check after closing that valve is not dripping.
8 Open pressure relief valve to ensure proper discharge and check after closing
that valve is not dripping.
9 Check all shower outlets, toiler cisterns and other draw off points for leaks or
dripping (especially when replacing a vented unit).
10 Open all water outlets to purge air from pipe work and ensure proper opera-
tion.
11 Adjust timer programmer and cylinder thermostat settings in accordance with
client requirements.
12 Instruct user in the operation of the unit and hand over manuals and bench-
mark card, advising the owner of annual service requirement.
7 Operation
Once the system has been fully commissioned, no user interference should be required to fully enjoy the comfort and benefits of the Dimplex SCxn hot water cylinder. The hot water temperature can be set to various requirements. Ideally it should be around 60°C. Higher temperature can cause tripping of the high limit thermostat, intro­duces more heat loss from the unit and increases the risk of scalding significantly.
When turning on a hot tap for the first time after a heat up period there might be a short surge of water. This is normal in unvented systems and does not constitute a fault. Sometimes the water may appear milky – this is due to very fine air bubbles in the wa­ter which will clear quickly.
7.1 Water temperature direct electric heating
Before removing the cover from immersion heater isolate appliance on isolating switch! Danger of electrical shock! Never enter immersion heater housing with blank metal objects!
Figure 15 – Adjustment water temperature direct electric heating element
Dial to adjust wa­ter temperature.
Page 23
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 23 of 28
ST0109 – C 05/09
WATER
The hot water temperature achieved by the direct electric heating element can be ad­justed by removing the cover from the immersion heater and adjusting the dial up or down as indicated in Figure 15.
7.2 Water temperature auxiliary heating
The water temperature achieved by the auxiliary heating system depends on the setting of the thermostat on:
- the cylinder AND
- the auxiliary heating source. The adjustment at the cylinder is being carried out on the twin thermostat fitted to the cylinder as shown in Figure 16. The manual high limit re-set is behind the black screw.
Figure 16 – Adjustment water temperature auxiliary source
8 Maintenance
The maintenance of this appliance must be carried out by a suitably qualified person only. Isolate all electrical supplies from the unit before commencing work. Danger of electrical shock!
1 Draw some water from cold water tap and retain in container.  2 Isolate cold water mains supply from cylinder.  3 Briefly open temperature and pressure relief valve, assure safe discharge and
check that valve is not dripping when closed.
4 Briefly open pressure relief valve, assure safe discharge and check that valve
is not dripping when closed.
5 Open hot water tap and release remaining pressure from unit.  6 Note the set pressure of pressure reducing valve. Remove cartridge and
clean strainer in water provided in container. Re-assemble pressure reducing valve ensuring the correct pressure is set.
7 Periodically the immersion heaters should be removed, cleaned and the unit
flushed out. The immersion heater seal should be replaced when fitting the element to the cylinder.
8 Check electrical wiring connections and the condition of the cable of the im-
mersion heater and the thermostat.
9 Re-commission unit.
Dial to adjust wa­ter temperature.
Page 24
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 24 of 28
ST0109 – C 05/09
WATER
9 Troubleshooting
Fault Cause Solution A No water
from hot
water taps
A.1 Stop valve closed A.2 Strainer blocked
A.3 Pressure reducing valve fitted
against flow
A.1 Open stop valve A.2 Turn water supply off,
clean strainer and re­commission
A.3 Re-fit with arrow showing
in direction of flow
B No hot water B.1 Timer/Programmer not set
correctly
B.2 Auxiliary heating mal function
B.3 Direct heating mal function
B.4 Auxiliary/direct heating high
limit thermostat has tripped
B.1 Set timer/programmer
correctly
B.2 Consult auxiliary heating
system instructions
B.3 Call for qualified person
to check immersion heater
B.4 Reset limit thermostat(s)
C Intermittent
water dis­charge through tun­dish on warm-up
C.1 Bubble depleted
C.2 Expansion vessel lost charge
C.1 See commissioning for
creation of bubble
C.2 Check expansion vessel
(see commission­ing/maintenance), top up or replace
D Continuous
discharge
D.1 Pressure reducing valve not
working
D.2 Pressure relief or T&P valve
not seating correctly
D.3 Mal function of high limit
thermostat or appliance
D.1 Check pressure after
valve and replace if faulty
D.2 Manually lift valve once
or twice to clear debris, otherwise replace
D.3 Check function of ther-
mostats and appliances
E Leakage from
casing
E.1 Compression/threaded joints
not formed correctly
E.1 Re-seal joints with care
F Hot water
from cold tap
F.1 Hot pipe work being routed
adjacent to cold pipe work
F.2 Leaking seal in mixer tap
F.1 Insulate hot pipe work or
re-route
F.2 Replace seals in mixer
tap
G Metallic noise
from system
G.1 Pipe work not sufficiently
supported
G.1 Add extra pipe work fix-
ings
Page 25
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 25 of 28
ST0109 – C 05/09
WATER
10 Technical data
10.1 SCxn … d/i
SCxn Capacity 80
130
150
175
215
255
305
Weight [kg]
d 27
30 32 37 43 50
59
i 29
32 35 40 48 55
65 Heat loss [kWh]
d/i 1.12 1.50 1.82 2.10 2.59 2.73 2.88
Heat up [mns]
d 64
115
138
167
212
263
313
i 33
28 33 27 35 42
50 Re-heat [mns]
d 53
90
104
124
153
184
220
i 23
21 24 24 30 35
42 A [mm] d/i 182 B [mm] d/i 196 C [mm] d -
570
648
753
821
1269
1526
D [mm] d/i 356
626
745
891
1116
1365
1620
E [mm] d/i 645
958
1086
1243
1485
1753
2029
F [mm] d/i 574
G [mm] i 339
380
369 H [mm] i 445 I [mm] i 182
B
F
F
A/I
D
E
G
E
A
C
D
B
H
Page 26
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 26 of 28
ST0109 – C 05/09
WATER
10.2 SCxn … sd/si
SCxn Capacity 175
215
255
305
Weight [kg] sd
44
52 59
69 si 48
56 63
73
Heat loss [kWh] sd/si
1.78
2.19 2.31
2.51
Heat up [mns] sd
20
24 29
34 si 18
22 25
30
Re-heat [mns] sd
14
17 20
24 si 13
18 19
22
A [mm] sd/si
182
B [mm] sd/si
531/589
C [mm] sd
846
1087 1355
1631
D/N/P [mm] sd/si
1017
1259 1527
1804
E [mm] sd/si
1243
1485 1753
2029
F [mm] sd/si
574
G [mm] si
711
H [mm] si
842
I [mm] si
580
J [mm] sd/si
346
K [mm] sd/si
480
L/0 [mm] sd/si
213
M [mm] sd
803
879 1057
1196
si
774
1116 1029
1167
Aux. vol. [l] sd
90
130 170
220
si 80
120 160
210
A
K
M
D/N
E
F
O
J
B
C
P
I
G
H
Page 27
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 27 of 28
ST0109 – C 05/09
WATER
Page 28
Unvented hot water cylinder – SCxn…d/i, SCxn…sd/si
Page 28 of 28
ST0109 – C 05/09
WATER
Dimplex UK Limited