3
1. Introduction
The SCX Solar cylinder is a high quality stainless steel unvented cylinder designed for use with all
solar systems to provide hot water from a cold mains water supply of between 3bar and 12bar.
Reduced performance is available at lower pressures but the units are not suitable for pressures
lower than 1.5bar and flow rate of less than 20 litres per minute. The indirect heat exchange surfaces
are designed to provide a rapid heat up time. The unit comes complete with all the necessary safety
equipment to comply with legislation governing the installation of such systems.
1.1 Cylinder Suitability:
The
SCX Solar cylinder should only be used as part of a solar installation and configured as shown in
figure 1.2. Additional safety devices may be required if the cylinder is operated with other heat sources.
2. Technical Specifications
Model Number SCx175sd SCx215sd SCx255sd SCx305sd SCx175si SCx215si SCx255si SCx305si
Storage capacity (litres)
175 215 255 305 175 215 255 305
Cylinder diameter (mm)
574 574 574 574 574 574 574 574
Aux Water volume (l)
90 130 170 215 105 140 180 230
Overall height (mm)
1300 1542 1809 2085 1300 1542 1809 2085
T&P Valve (mm)
1080 1322 1589 1865 1080 1322 1589 1865
Lower Immersion (mm)
593 593 593 593 593 593 593 593
Top Immersion (mm)
908 1150 1417 1693 - - - -
Solar Flow (mm)
542 542 542 542 542 542 542 542
Solar Return (mm)
380 380 380 380 380 380 380 380
Cold Inlet (mm)
300 300 300 300 300 300 300 300
solar Coil size sqm
1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1
Aux Coil size sqm
- - - - 0.75 0.75 0.75 0.75
Auxiliary Flow (mm)
- - - - 904 904 904 904
Auxiliary Re turn (mm)
- - - - 742 742 742 742
Weight when full (kg)
219 267 314 374 223 271 318 378
Heat-up time* (m)
20 24 28.5 34 18 21.5 25 30
Re-heat time* (m)
14 17 20 24 13 16 19 22
Heat Loss in 24hr (kw)
1.78 2.19 2.31 2.51 1.78 2.19 2.31 2.51
Secondary Return •• ••••• •
Primary flow/return connections (mm)
22 22 22 22 22 22 22 22
Cold feed/hot draw off connections (mm)
22 22 22 22 22 22 22 22
Maximum water supply pressure (bar)
12 12 12 12 12 12 12 12
System operating pressure (pre-set) (bar)
33 333333
Expansion vessel charge pressure (bar)
33 333333
Maximum primary working pressure (bar)
33 333333
Package includes:
Expansion vessel ltr 18 18 25 25 18 18 25 25
Inlet Valve Group (pressure reducing valve, non
return valve, 6 bar expansion relief valve, line
•• ••••• •
T/P valve 7bar 90degC (factory fitted) •
2.1 Heat-up & Reheat Times*
*Heat-up and reheat times are for a guide only and are based on a primary flow temperature of 60oC
and heating water from 15
o
C to 60oC. The immersion of the cylinder or external boiler must be used
to raise the temperature to 60
o
C from the maximum temperature achieved at any time by the solar
system,.
Reheat times are those to heat 70% of the cylinder from cold.