The product complies with the European Safety Standards EN13240 for Room heaters red by solid fuel.
08/51568/0 - Issue 2
Please hand these instructions to the stove user when installation is complete.
Leave the system ready for operation and instruct the user in the correct use of the
appliance and operation of controls.
Installation should only be carried out by a suitably qualied installer that is registered
with HETAS (UK) or with the Irish Nationwide Fireplace Organisation (INFO).
Installation must comply with Building Regulations.
Langbrook 5kW (LBK5)

1
Table 1 - Dimensions A B C D E F G H J K
Langbrook 5kw 600 500 30 250 105 368 23 110 472 127
Note: All Dimensions in mm. Dimensions stated may be subject to a slight ± variation. ( 25.4mm = 1”)
Table 2 - Technical Specication Langbrook 5kw
Nominal heat output
Wood kW 5.0
Solid Fuel (Ancit) kW 5.3
Efciency
Wood % 77.0
Solid Fuel (Ancit) % 82.5
CO Emission (@13% O2)
Wood % 0.32
Solid Fuel (Ancit) % 0.38
Flue Gas Temp
Wood °C 306
Solid Fuel (Ancit) °C 249
Flue Gas Mass Flow
Wood g/s 4.0
Solid Fuel (Ancit) g/s 3.3
Refuel Period hr 1
Safe Distance to Combustibles
Sides mm 500
Rear mm 650
Flue Outlet Size mm / inch 127 / 5
Product Weight kg 98.7
Additional Room Ventillation Required cm² see table 4
A
B
D
E
C
J
H
F
K (Dia)
G

45°
Max
150 Max
Seal with fire
proof lagging
3
4
5 6
Table 3 - Position of Hearth & Appliance from adjacent walls
Hearth distance ‘X’ from wall Appliance distance from walls Min Wall Thickness ‘T’ Min Wall height ‘H’
0mm 0 - 50mm 200mm Height of appliance +300mm
or 1200mm from hearth
(whichever is greater)
0mm 51 - 150mm 75mm
0 - 150mm 150 - 300mm 75mm
+150mm +300mm No Minimum Requirement
H
MIN
150mm
X
X
T
T
MIN
150mm
MIN
125mm
See Table 3
Solid, non-combustible
material e.g. masonary
or concrete
300mm
150
150
150
300
FREESTANDING ON
NON COMBUSTIBLE HEARTH
MIN 12mm THICK
MIN 840mm
MIN 840mm

150 max
Seal gap with
fire-proof lagging
150 max