Dimplex LA16ASR User Manual

CE
MOUNTING and OPERATING MANUAL
Reversible Air-to-Water Heat Pump
for Outdoor Installation
LA 16ASR
Order No.: 452158.66.21 FD 8507
CONTENTS
1 READ IMMEDIATELY 3
1.2 Legal Provisions and Guidelines
1.3 Energy-Efficient Use of Heat Pumps
2 PURPOSE OF HEAT PUMP 4
2.1 Application
2.2 Principle of Operation
3 SCOPE OF DELIVERY 4/5
3.1 Baseline Unit
3.2 Control Box
3.3 Heat Pump Controller
4 TRANSPORT 5
5 INSTALLATION 6
5.1 General
5.2 Condensate Line
6 MOUNTING 6/7
6.1 General
6.2 Heating and Hot Water Connection
6.3 Electrical Connection
7 COMMISSIONING 7/8
7.1 General
7.2 Preparation
7.3 Procedure During Heating Period
7.4 Procedure During Cooling Period
8 CLEANING / MAINTENANCE 8/9
8.1 Maintenance
8.2 Cleaning of Heating Side
8.3 Cleaning of Air Side
9 MALFUNCTIONS, TROUBLE-
SHOOTING 9
10 DECOMMISSIONING 9
10.1 Placing Out of Service in Summer
10.2 End-of-Life Decommissioning / Disposal
11 APPENDIX FF
2
READ IMMEDIATELY
READ IMMEDIATELY
1
1.1 Important Information
CAUTION!
ensured that all electrical circuits are disconnected from the power source.
CAUTION!
not be tilted more than 45° (in either direction).
CAUTION!
only connected by the packaging film.
CAUTION!
must not be restricted nor obstructed.
CAUTION!
observed: Damage to the compressor may be incurred if it is operated in the wrong sense of rotation.
CAUTION!
containing sand, soda, acid or chloride as these may attack the surface.
CAUTION!
is imperative that the water circuit be neutralized after cleaning using appropriate agents.
CAUTION!
with a frequency converter.
CAUTION!
be performed by qualified persons only.
Prior to opening the unit it must be
During transport, the heat pump must
Heat pump and transport pallet are
The intake and outlet duct openings
Clockwise phase sequence to be
Do not use any cleaning agents
To prevent consequential damage it
The unit is not suitable for operation
Work on the refrigeration circuit may
1.2 Legal Provisions and Guidelines
This heat pump was designed and built in compliance with all relevant EU directives, DIN and VDE regulations (see CE Declaration of Conformity).
The electrical connection of the heat pump must be performed according to and conforming with all relevant VDE, EN and IEC standards. Beyond that, all technical connection requirements of the local electrical utility company have to be observed.
On connecting the heating and cooling system, all relevant regulations have to be complied wit.
1.3 Energy-Efficient Use of the Heat Pump
By purchasing this heat pump you contribute to the protection of the environment. A prerequisite for energy-efficient operation is the proper design of the heat source system and the heat utilization/cooling system.
One of the most important factors of heat pump efficiency is keeping the temperature difference between the heating water and the heat source as small as possible. It is therefore strongly recommended that the design of both the heat source system and the heat distribution system be carried out with great care. A 1 Kelvin (1°C) higher
temperature difference corresponds to an increase in power consumption of approx. 2.5%.
When designing the heating system care must be taken that special applications such as domestic water heating are taken into consideration and dimensioned for low temperature operation. Heat pumps are optimally suited for underfloor heating (surface/radiant heating) applications due to the low supply temperatures (30 °C to 40 °C).
During operation it is essential that the heat exchanger is not contaminated as this would increase the temperature difference resulting in an inferior coefficient of performance.
A considerable contribution to the economical operation is made by the heat pump controller provided it is set correctly. For more detailed information refer to the operating manual of the heat pump controller.
3
PURPOSE OF HEAT PUMP SCOPE OF DELIVERY
PURPOSE OF HEAT
2
PUMP
2.1 Application
The air-to-water heat pump is designed for use in existing or newly built heating systems.
The heat pump is designed exclusively for the heating and cooling of heating water!
In the heating mode, the heat pump is suitable both for mono-energetic and bivalent operation at outdoor air temperatures down to -20
In the continuous mode of operation, a heating water return temperature of more than 18 °C must be maintained in order to ensure proper defrosting of the evaporator.
The heat pump is not designed for any increased heat demand during the drying phase of new buildings; the additional heat demand must be met by special appliances to be supplied on site. For the structural drying of new buildings in the autumn or winter it is recommended that an additional electric heating element (available as accessory) be installed.
In the cooling mode, the heat pump is suited for air temperatures ranging from +15 °C ... +40 °C.
It can be used for passive and dynamic cooling applications alike. The minimum water temperature is +7 °C.
CAUTION!
with a frequency converter.
The unit is not suited for operation
o
C.
valve as well as the low-noise compressor, a desuperheater, a condenser and the electric control unit.
In the case of low ambient temperatures, air humidity may accumulate on the evaporator in the form of frost impairing the heat transfer. The evaporator is automatically defrosted by the heat pump, if required.
Cooling
In the "cooling" mode, the operating process of evaporator and condenser is reversed
The heating water transfers the heat to the refrigerant via the condenser that is now working as the evaporator. In the compressor the temperature of the refrigerant is raised, and the heat is rejected to the ambient air via the condenser (in the heating mode the evaporator).
Via the additional heat exchanger, the waste heat can also be used for hot water consumers such as domestic hot water, swimming pool or bathroom heating applications.
SCOPE OF DELIVERY
3
3.1 Baseline Unit
The heat pump is delivered as a compact unit containing the components listed below.
The refrigerant used is R404A.
12
..
2.2 Principle of Operation
Heating
Ambient air is drawn in by the fan and passed over the evaporator (heat exchanger). The evaporator cools the air, i.e. it extracts the heat it contains. In the evaporator, the heat removed is transferred to the working fluid (refrigerant).
With the aid of an electrically driven compressor, the absorbed heat is "pumped" to a higher temperature level through pressure increase and given off to the heating water via the condenser (heat exchanger).
The desuperheater, mounted upstream, enables domestic hot water to be produced simultaneously or separately.
In so doing, electrical energy is used to raise the heat of the environment to a higher temperature level. Due to the fact that the energy extracted from the air is transferred to the heating water, this type of appliance is referred to a air-to-water heat pump.
The air-to-water heat pump consists of the following main components: evaporator, fan and expansion
65 43
1) Evaporator 4) Pressostats
(heating mode) 5) Condenser
2) Fan (heating mode)
3) Control box 6) Compressor
4
SCOPE OF DELIVERY
TRANSPORT
3.2 Control Box
The control box is integrated in the heat pump. It can be
folded downward after removing the lower front
panel and loosening the fastening screws located at the top on the right.
The control box houses the mains terminals as well as the power contactors and the soft start unit.
The plug connector for the control lead is located at the bottom of the unit in the immediate vicinity of the line feed-through through the bottom of the unit.
3.3 Heat Pump Controller
For the operation of your reversible air-to-water heat pump, the reversible heat pump controller included in the scope of delivery is to be used.
he heat pump controller is a comfortable electronic regulating and control unit. It controls and monitors the entire heating/cooling system as a function of the outdoor air temperature, the hot water preparation and the safety devices.
The external temperature sensor, to be mounted by the customer, incl. fastening hardware is shipped with the controller.
Method of functioning and operation of the heat pump controller are described in the enclosed operating manual.
TRANSPORT
4
CAUTION!
must not be tilted more than 45° (in either direction).
The unit should be transported to the final installation site on a wooden pallet. The baseline unit can be transported either by means of a lift truck, a sack trolley, or the like, or using 3/4" pipes to be put through the openings provided in the base plate or the frame.
During transport, the heat pump
CAUTION!
are only connected by the packaging film.
It is necessary to remove the lower cover panel to be able to access the transport openings in the frame. For this purpose, loosen two screws each in the base, retract the panels and disengage them at the
3.
1.
1.
Opening the cover Closing the cover
top. When reinstalling the panels, they should be pushed upward by exerting slight pressure.
When slipping the carrying pipes through the frame, care must be taken that no components are damaged.
The heat pump and transport pallet
1.
3.
2.
2.
1.
2.
1.
5
INSTALLATION MOUNTING
INSTALLATION
5
5.1 General
The unit should always be installed on a permanently level, smooth and horizontal floor. The entire base frame surface should thereby make close contact with the floor in order to ensure adequate sound insulation and to prevent water-carrying parts from cooling out. If this is not the case, additional insulation measures may become necessary. It must be possible to carry out servicing work without any problems. This is ensured if a clearance of 1.2 m to solid walls is maintained.
1,2 m
1,2 m
CAUTION!
must not be restricted nor obstructed.
5.2 Condensate Line
The condensation water that may collect during operation must be drained in a place protected from frost. The heat pump must be positioned horizontally so that proper discharge can be ensured. The condensation water pipe must have a minimum diameter of 50 mm and should be discharged to the sewer drain in a frost-proof location.
The intake and discharge openings
MOUNTING
6
6.1 General
The following connections need to be established on the heat pump:
- supply/return flow of heating system
- supply/return flow of hot water circuit
- condensate drain
- control lead to the heat pump controller
- power supply
6.2 Heating and Hot Water Connection
The connections on the heating side of the heat pump are provided with 1"external thread. The hoses to be connected exit the unit through its bottom. When carrying out the connections, use a wrench to counterhold at the transitions.
Before completing the heat pump connections on
1,2 m1,2 m
the heating water side, the heating installation must be flushed in order to remove any impurities that may be present and to ensure trouble-free operation of the heat pump. On systems equipped with heating water flow shut-off devices such as radiator or thermostat valves, an overflow valve to be provided by the customer needs to be installed behind the heating pump in a heating system bypass. This guarantees a minimum heating water flow through the heat pump and prevents any malfunctions from occurring.
Once the installation on the heating side has been completed, the heating system must be filled, de­aerated and pressure-tested.
Frost Protection
As a precaution against frost, manual drain valves should be provided. If the heat pump is placed out of service or in the event of a power failure, the system has to be drained at three points (see figure) and blown out. In heat pump installations where a power failure cannot be readily detected (holiday house), the heating circuit must contain a suitable antifreeze product.
6
Wärmepumpe
Heat pump
3
1
2
MOUNTING
COMMISSIONING
6.3 Electrical Connection
The power connection of the heat pump is effected via a commercially available 4-core cable.
The cable has to be supplied by the client and the wire cross-section to be selected according to the power consumption of the heat pump (see Equip­ment Data in the appendix) as well as the relevant VDE (EN) and VNB regulations.
The power supply of the heat pump must be equipped with an all-pole disconnecting device with a contact gap of at least 3 mm (e.g. utility company shut-off contactor, power contactor) as well as a 3­pole circuit breaker with simultaneous tripping of all external conductors (tripping current as stated on the device data plate).
When making the electrical connection, the clockwise phase sequence of the power supply must be ensured.
Phase sequence: L1, L2, L3.
CAUTION!
observed: Damage to the compressor may be incurred if it is operated in the wrong sense of rotation.
The control voltage is supplied via the heat pump controller.
The 230V AC-50 Hz power supply of the heat pump controller is effected as described in its instruction manual (fusing 16 A).
The control lead (not included in the scope of delivery) is connected to the heat pump controller via a multi-pole plug connector. In the heat pump, the plug connector located at the bottom of the unit in the immediate vicinity of the line feed-through through the base of the unit. More detailed instructions are contained in the instruction manual of the heat pump controller.
For more detailed information refer to the wiring diagrams in the appendix.
Clockwise phase sequence to be
COMMISSIONING
7
7.1 General
To ensure proper commissioning it should be carried out by an after-sales service authorized by the manufacturer. Only then can an extended warranty period of 3 years in total be granted (cf. Warranty service).
7.2 Preparatory Steps
Prior to commissioning, the following items need to be checked:
- All connections of the heat pump must have been made as described in Chapter 6.
- In the heating circuit all valves that could impair the proper heating water flow must be open.
- The air intake/discharge path must be unobstructed.
- The sense of rotation of the fan must correspond to the direction of the arrow.
- The settings of the heat pump controller must be adapted to the heating installation in accordance with the instructions contained in its instruction manual.
- Proper condensate drainage must be ensured.
7.3 Procedure During Heating Season
The start-up of the heat pump is effected via the heat pump controller. The settings must be made in accordance with its instruction manual.
Malfunctions during operation are displayed on the heat pump controller and may be corrected as described in the heat pump controller's instruction manual.
n the case of outdoor temperatures below 10 °C and heating water temperatures below 16 °C, the buffer tank has to be heated to at least 30 °C using the second heat generator.
The following procedure has to be observed so that the commissioning activities can be carried out without any problems:
a) Close all heating circuits. b) Open the overflow valve all the way. c) Select the automatic mode on the controller. d) Wait until the buffer tank has reached a
temperature of 25-30 °C.
e) Subsequently, slowly reopen the valves of the
heating circuits, one after the other, in such a way that the heating water flow rate is continually increased by slightly opening the related heating circuit valve. When so doing, the heating water temperature in the buffer tank must not fall below 25 °C so that the heat pump can be defrosted at any time.
7
COMMISSIONING CLEANING / MAINTENANCE
f) Once all heating circuit are fully open and a
heating water temperature of approx. 25 °C is maintained in the buffer tank, the minimum flow rate must be set on the overflow valve and the heating circulating pump.
g) New buildings have an increased heat demand
due to the energy required for structural drying. This increased heat demand may result in insufficiently dimensioned heating installations not attaining the desired room temperature at all times. In this case it is therefore recommended that the second heat generator be kept ready for operation in the first heating season. The limit temperature on the heat pump controller should therefore be raised to 15°C.
7.4 Procedure During Cooling Season
In this case, all heating circuits can be fully opened.
The setting described in 7.3 f) must be carried out during the heating season.
CLEANING /
8
MAINTENANCE
8.1 Maintenance
To protect the paint finish, avoid placing objects against or on the unit. The external parts of the heat pump can be wiped with a damp cloth and commercially available cleaning agents.
CAUTION!
containing sand, soda, acid or chloride as these may damage the surface.
To prevent malfunctions in the heat exchanger of the heat pump caused by dirt deposits, care must be taken that the heat exchanger cannot become contaminated in the heating installation. In the event that operating malfunctions due to contamination occur nevertheless, the system should be cleaned as described below.
Do not use any cleaning agents
8.2 Cleaning of Heating Side
The ingress of oxygen into the heating water may result in the formation of oxidation products. An ad­ditional contamination of the heating water caused by residues of lubricating and sealing agents occurs in many cases.
Both of the above causes may lead to a reduction in the performance of the heat pump condenser. In these cases the installer needs to clean the condenser. Based on information known to date we recommend cleaning with a 5% phosphoric acid solution or, in the case that cleaning needs to be performed more frequently, with a 5% formic acid solution. In both cases the
cleaning fluid should be at room temperature. Thorough flushing is necessary to ensure that all cleaning agent residues are removed from the system. It is recommended that the heat exchanger is cleaned in the direction opposite to the normal flow direction. Owing to their acid content flushing agents must be used with caution. To prevent acidic flushing agents from entering the heating installation when cleaning the condenser, we recommend that the flushing device should be mounted directly to
8
CLEANING / MAINTENANCE
MALFUNCTIONS / TROUBLESHOOTING
DECOMMISSIONING
the supply and return line of the heat pump. The regulations of the trade associations must be adhered to. If in doubt, contact the manufacturers of the chemicals!
CAUTION!
is imperative that the water circuit be neutralized after cleaning using appropriate agents.
Caution - Heating Engineers
Depending on the water quality and quantity, in particular in the case of mixed installations and plastic pipes, mineral deposits (rust sludge, lime) may form impairing the proper functioning of the heating installation. A cause of this is the water hardness as well as oxygen dissolved in the filling water as well as additional oxygen from the air which may penetrate via valves, fittings and plastic pipes (oxygen diffusion). As a preventive measure it is recommended that a physical water conditioner such as ELYSATOR be used.
To prevent consequential damage it
8.3 Cleaning of Air Side
Evaporator, fan and condensate drain should be cleaned of debris (leaves, branches, etc.) from time to time. To this end, the front panel of the heat pump should be opened first at the bottom and then at the top.
CAUTION!
ensured that all electrical circuits are disconnected from the power source.
The removal and reinstallation of the panel assemblies to be performed as described in Chapter 4.
When cleaning do not use any sharp or hard objects so as to prevent any damage to the evaporator and the condensate pan.
Prior to opening the unit it must be
MALFUNCTIONS /
9
TROUBLESHOOTING
This heat pump is a quality product and is designed for troublefree and maintenance-free operation. In the event that a malfunction occurs nevertheless, you will be able to correct the problem easily yourself. Simply consult the Malfunctions and Troubleshooting table in the operating manual of the controller. Malfunctions can be interrogated at the heat pump controller. If the problem cannot be corrected by the user, please contact the after-sales service in charge (see Warranty Card).
CAUTION!
be performed by an authorized and qualified after­sales service.
Any work on the heat pump may only
DECOMMISSIONING
10
10.1 Placing Out of Service in Summer
Placing the heat pump out of service in summer can be effected by switching the heat pump controller to the "Summer" operating mode.
10.2 End-of-Life Decommissioning /
Disposal
Before removing the heat pump, disconnect the machine from the power supply and close all valves. Environment-relevant requirements regarding the recovery, recycling and disposal of service fuels and components in accordance with all relevant standards must be adhered to. In this context, particular attention must be paid to the proper disposal of refrigerants and refrigeration oils.
9
11
APPENDIX
APPENDIX
11.1 DIMENSION DRAWING 11
11.2 EQUIPMENT DATA 12
11.3 SCHEMATICS
11.3.1 Heating Mode 13
11.3.2 Cooling Mode 14
11.4 WIRING DIAGRAMS
11.4.1 Control 15
11.4.2 Load 16
11.4.3 Terminal Diagram 17
11.4.4 Legend 18
11.5 HYDRAULIC BLOCK DIAGRAM 19
11.6 EC DECLARATION OF CONFORMITY 20
11.7 WARRANTY CERTIFICATE AFTER-SALES SERVICE 21
10
Dimension Drawing
APPENDIX: 11.1 DIMENSION DRAWING
11
APPENDIX: 11.2 EQUIPMENT DATA
Equipment Data
12
11.3.1 Heating Mode
APPENDIX: 11.3 SCHEMATICS
13
APPENDIX: 11.3 SCHEMATICS
11.3.2 Cooling Mode
14
11.4.1 Control
(8)
X6-8
X7-8
G (24VAC)
(14)
(7)
X6-14
X6-7
X7-14
X7-7
HG
AE
(18)
X6-18
X7-18
KD
APPENDIX: 11.4 WIRING DIAGRAMS
24pol.
X4
X5
(20)
(2)
(4)
(6)
(9)
X6-9
X6-6
X7-6
X7-9
ND
HD
(16)
(1)
X6-16
X6 -1
X7-16
X7 -1
COD
WSV
16-X2
R11
(5)
(17)
X6-5
X6-17
X7-17
COD
17-X2
5k6
X6-4
X7-5
X7-4
FRO
FRO
5-X2
4-X2
R9
(3)
(13)
(12)
X6-2
X6-3
X7-2
X7-3
RLF
RLF
2-X2
3-X2
R10
X6-12
X6-13
X7-13
X7-12
4-WMV
Verd1
(10)
(11)
X6-11
X7-11
VENTI
(19)
2
X6-24
X6-10
X6-21
X7-24
X7-10
X7-21
Steuerleitung 20x1,0mm2
Control lead 20x1,0mm
N
L (23oV)
G0(0 VAC)
11-X2
10-X2
A1
A2
K2
Wärmpumpenregler
Heat pump controller
/-.2
/2.4
/2.4
/2.4
462
135
21 22
12-X213-X2
Y1
/-.2
/-.2
/2.4
/2.4
7-X2
C (4)
8-X2
A (1)
E3
P>
(2) B
8-X2
1-X2
21
22
K1
21
13
K1
4
1
2
T>
F5
A (1)
C (4)
P>
P>
E4
8-X2
F2
(2) B
8-X2
<
P<
F3
8-X2
8-X2
22
14
K2
TK
M2/
F23
10-X2 10-X2
A1
A2
K1
1-X3
E1
2-X3
E2
TK
N-X3
N-X3
9-X2
6-X2
18-X2
14-X2
/2.4
462
135
21 22
13 14
2
15
Alle Querschnitte 0,75mm2
Cable diameters all 0,75mm
APPENDIX: 11.4 WIRING DIAGRAMS
11.4.2 Load
/1.5
K2
5
6
3
4
1
2
M
3
M2
F23/1.2
/1.4
K1
6
135
24
T
RS
N3
VUW
M
M1
PE
distributor
PE-
Verteiler
P
E
L
3
L
2
L
1
X1
3
ge/gn
ye/gn
3
2
1
4
ge/gn
ye/gn
3
2
1
P
E
L
3
Netz
L
2
Mains
L
1
3/PE 400VAC - 50Hz
16
2
Alle Quer schnitte 0,75mm2
Cable diameters all 0,75mm
APPENDIX: 11.4 WIRING DIAGRAMS
11.4.3 Terminal Diagram
Terminal connection diagram and connector assignment
Klemmenplan und Steckverbinderbelegung
in the reversible air-to-water outdoor unit
im reversiblen Luft/Wasser-Außengerät LA 16 ASR
E
X1
L1L2L
1 2
3
P
n g
/ e g
ye/gn
3
X7
X6
X7
9
7
5
3
1
0
6
4
2
1
8
9
3
1
1
1
2 1
7
5 1
6
4
1
1
1
1
8
0
1
2
3
1
2
2
2
4
2
2
g n u
t
i
t
e
s
l
a
s
L
s
Load
u
l h
4
c s
Connecting lead
n A
n g
/ e
Mains
Netz
g
ye/gn
E
132
L1L2L3P
3/PE 400VAC - 50Hz
Wärmepumpenregler
Heat pump controller
X6
g n u
t
i e
l
r e u e
t
Control lead
S
X5
X4
1
3
2
4
)
)
)
) 1
(
Wire () and pin numbers
Ader- () und Pinnummern
4
3
2
(
(
(
7
5
6
)
)
5
6
(
(
9
0 1
8
) 0
)
)
)
1
8
7
9
(
(
(
(
X5
) 1
(
1
4
3
2
(
(
(
2
4
3
)
)
)
)
)
)
7
6
5
(
(
(
6
7
5
)
)
0
)
8
1
9
(
(
(
0 1
8
9
3
1
1
1
2 1
)
)
)
2
3
1 1
1
1
(
(
(
g n u
t
i e
l
r e u e
Control lead
t S
)
)
)
2
3
1
1
1
1
(
(
(
2 1
3
1
1
1
5
7
1
1
6
4
1
1
)
)
)
)
5
7
6
4
1
1
1
1
(
(
(
(
1
9
2
1
2
0
8 1
) 8 1
(
2
2
) 9 1
(
X5 / X6
1
5
10
16
21
Ader- () und Pinnummern
Wire () and pin numbers
)
)
4
5
1
1
(
(
4 1
5 1
)
)
)
8
7
6
1
1
1
(
(
(
6
8
1
1
7 1
4
9
20
24
)
)
)
)
0
9
2
1
2
1
2
2
(
(
(
(
2
0
2
2
9
1
1
2
3 2
4 2
) 0 2
(
15
)
)
4
3
2
2
(
(
4 2
3 2
Heat pump controller
Wärmepumpenregler
17
X4 / X7
9
15
20
24 21
14
5
10
16
APPENDIX: 11.4 WIRING DIAGRAMS
11.4.4 Legend
E1 Crankcase heater, compressor E2 Fan for nozzle ring heater E3 Defrost end pressostat E4 Condensing pressure pressostat
F2 High-pressure pressostat F3 Low-pressure pressostat F5 Thermostat HG F23 Winding shield, fan
K1 Compressor contactor K2 Fan contactor
M1 Compressor M2 Fan
N1 Heat pump controller N3 Soft start control
R9 Frost protection sensor for heating water R10 Heating water return flow sensor R11 Coding resistor (5k6)
X1 Terminal strip: load terminal X2 Terminal strip: internal wiring X3 Terminal strip: heaters X4 Plug connector, heat pump controller X5 Plug connector, control lead X6 Plug connector, control lead X7 Plug connector, heat pump
Y1 4-way reversing valve
18
Hydraulic Block Diagram
N1-N05
(HUP)
N1-N06
(WUP)
N2-N02
(SUP)
N1-N010
EV
N1-B3
(WWF)
KW
T
WW
EV
N2-N01
(HUPR)
N1-B6
(NKF)
N1-N04 (2.WE)
N1-N012/N013
(MAN/MZN)
M
N1-N011
(HPN)
X8/X11
N1-B1
(AUF)
T
T
1
5
6
2
4
3
Standardregler (mit Display)
Kühlregler (ohne Display)
Außenwandfühler
Elektroverteilung
Heizungsumwälzpumpe
Umwälzpumpe für Heiz- und Kühlbetrieb
Heizungspumpe 2ter Heizkreis
Kaltwasser
Mischer AUF - 2ter Heizkreis
Mischer ZU - 2ter Heizkreis
2ter Heizkreis Rücklauffühler
Schwimmbadpumpe
Wärmeerzeuger
Warmwasserumwälzpumpe
Warmwasser
Warmwasserfühler
Flexibler Anschlußschlauch
Temperaturfühler
Dreiwegemischer
Absperrventil
Ausdehnungsgefäß
Thermostat-/ Handventil
Umwälzpumpe
Überströmventil
Wärmeverbraucher
Absperrventil mit Rückschlagventil
Sicherheitsventilkombination
Absperrventil mit Entwässerung
M
N1
N2
AUF
EV
HUP
HUPR
HPN
KW
MAN
MZN
NKF
SUP
WE
WUP
WW
WWF
Wärmepumpe
Pufferspeicher
Warmwasserspeicher
Pufferspeicher für Abwärme
Wärmepumpenregler
Elektroverteilung
1
2
3
4
5
6
Heat pump
Buffer tank
Hot water tank
Buffer tank for waste heat
Heat pump controller
Electric distribution
APPENDIX: 11.5 HYDRAULIC BLOCK DIAGRAM
Standard controller (with display)
Cooling regulator (without display)
External sensor
Electric distribution
Heating water circulating pump
Circulating pump for heating and cooling mode
heating circuit
nd
heating circuit
nd
Circulating pump 2
Cold water
Mixer OPEN – 2
heating circuit
nd
heating circuit return sensor
nd
2
Mixer CLOSED – 2
Swimming pool pump
Heat generator
Hot water circulating pump
Hot water
Hot water sensor
Shut-off valve
Overflow valve
Safety assembly
Circulating pump
Expansion vessel
Thermostat/manual valve
Shut-off valve with non-return valve
Shut-off valve with drain
Heat consumers
3-way mixing valve
Temperature sensor
Flexible connecting hose
19
APPENDIX: 11.6 EC DECLARATION OF CONFORMITY
EC Declaration of Conformity
Declaration of Conformity
The undersigned
KKW Kulmbacher Klimageräte-Werk GmbH, Geschäftsbereich Dimplex Am Goldenen Feld 18 D-95326 Kulmbach
hereby confirm that the design and construction of the product(s) listed below, in the version(s) placed on the market by us, conform to the relevant requirements of the applicable EC directives.
This declaration becomes invalidated if any modifications are made to the product(s) without our prior authorization.
Designation of the product(s): EC Directives:
Air-to-water heat pumps EC Directive for Low Voltage
for outdoor installation, (73/23/EEC) containing R404A EC Directive for Electromagnetic Compatibility (EMC)
(89/336/EEC) Pressure Equipment Directive (97/23/EEC)
Type(s): Harmonized EN Standards:
LA 16ASR
Requirements of category II
Order No.: National Standard/Directives:
342 070
Kulmbach, 25.07.2003
General Manager Technical Director
20
Notes
21
Notes
22
Notes
23
KKW Kulmbacher Klimageräte-Werk GmbH Technical data subject to change without notice Geschäftsbereich Dimplex Fax +49 (0) 92 21 709-589 Am Goldenen Feld 18 www.dimplex.de D-95326 Kulmbach