Dimplex KSS 2504, KSS 3204, KSS 4504, KSS 6004 Installation And Operating Instructions Manual

KSS 2504 KSS 3204 KSS 4504 KSS 6004
Split Air Conditioner for Wall Mounting
Installation and Operating Instructions 453322.66.11 06/07/B
Contents: Page
Installation Instructions
Device-Specific Safety Regulations ................................................................................................................... 2
Check List .......................................................................................................................................................... 3
Technical Data ...................................................................................................................................................4
Device Construction ........................................................................................................................................... 6
Installation Notes for Split Air Conditioners ....................................................................................................... 7
Minimum Clearances .................................................................................................................................... 9
Assembling the Outdoor Unit ........................................................................................................................... 10
Connecting the Cooling System....................................................................................................................... 11
Pre-filled Refrigerant Pipes .............................................................................................................................. 12
Installation Notes – Laying a Split Pipe ........................................................................................................... 15
Electrical Connection .......................................................................................................................................17
Start-Up – Function Test .................................................................................................................................. 18
Refrigeration Plan ............................................................................................................................................ 19
Circuit Diagrams............................................................................................................................................... 20
Operating Instructions
Important Notes on Operation.......................................................................................................................... 23
Direction of Air Flow .................................................................................................................................... 24
Cleaning and Maintenance ......................................................................................................................... 24
Remote Control ................................................................................................................................................ 25
Battery for Remote Control .........................................................................................................................25
Functions of Remote Controls KSS 2504 / 3204 / 4504 / 6004.................................................................. 26
Cooling ........................................................................................................................................................ 27
Heating........................................................................................................................................................ 28
Dehumidification ......................................................................................................................................... 29
Auto............................................................................................................................................................. 30
Timer Function ............................................................................................................................................ 31
Sleep Function ............................................................................................................................................ 32
Faults ..........................................................................................................................................................33
2
General Safety Requirements
Please read these installation and operating instructions carefully and fully before commencing installation! They contain important information about assembly, use and maintenance as well as the safety instructions to be observed!
After unpacking it, please inspect the device for any damage. In case of doubt, do not put the
device into use but have it examined by a qualified technician.
Before connecting the device, please ensure that the mains supply network corresponds to that
required by the device according to the type plate data (observe your utility company’s local connection conditions).
The device must not be operated in rooms where highly inflammable substances are used (e.g.
solvents, etc.).
The device must be unplugged from the mains before any cleaning or maintenance work is
carried out.
This device may be used only for the purpose for which it was made, i.e. for heating, cooling,
dehumidification and air recirculation. All other purposes are not those for which it was intended and must therefore be regarded as hazardous.
In the case of a fault and / or functional defect, please switch the device off (disconnect from the mains). Do not try to repair the device yourself. Necessary repairs must be carried out by the after-sales service.
The power supply cable may be replaced only by a qualified electrician. The manufacturer is not liable for damage caused by improper or incorrect use or the
incorrect installation of the device.
Device-Specific Safety Regulations
The device must be installed according to the manufacturer’s specifications. Incorrect
installation can cause injury to persons or animals and damage to property.
Where possible, the outdoor unit is to be installed in such a way that it is not exposed to direct
sunlight.
The inlet and outlet vents of the room air conditioner must not be covered or closed. No objects may be pushed into the air inlet and outlet vents. Disconnect the air conditioner from the power supply if it is out of use for some time. The air conditioner should be inspected at regular intervals (e.g. before the cooling season). The condensation which collects in or runs out of the air conditioner should not be drunk. Do not operate the room air conditioner without an air filter. The air filters should be cleaned at regular intervals (depending on user and room). Do not place any objects on the room air conditioner. The indoor unit of the room air conditioner may be operated in dry rooms only. Do not pour or spray any liquids into or onto the room air conditioner. Do not use hairsprays, solvents etc (e.g. aerosols) in the vicinity of the air conditioner.
The air conditioner should be switched off immediately in the case of a fault (e.g. if smoke is
created or an unusual smell is noticed). Disconnect the device from the power supply (switch off the fuse or pull out the plug) and contact an authorized after-sales service.
Keep persons, particularly small children, pets and plants away from the direct air flow, it could
damage their health or general condition.
The device may be assembled and disassembled by a qualified technician only.
3
Check List
Has a calculation of the cooling load been made?
Is the cooling capacity of the device sufficient for the room to be cooled?
Are the operating limits sufficient for the purpose for which the air conditioner is intended?
Are the walls or the foundation for the installation of the outdoor unit strong enough?
The indoor unit should be installed in a position where it ensures uniform cooling.
Minimum clearances must be observed.
Planning the installation of the outdoor unit.
Consider noise emission and free air circulation, avoid direct sunlight, ensure unimpeded access to
the unit; the unit should be installed in a place to which the public does not have access.
Is a wall bracket required for the outdoor unit?
Plan the power cable and connection, ensure adequate fuses.
Check the maximum length and feasibility of the refrigerant pipes.
Refrigerant pipes should be as straight and short as possible.
When laying refrigerant pipes it is essential to maintain a bend radius of 3.5 x diameter.
Excess piping should be wound up at a downward angle to the outdoor unit in order to avoid residues of
refrigerant oil.
Take account of differences in height between the room unit and the outdoor unit; if the outdoor unit is
higher than the room unit then one or more oil siphons should be provided as necessary.
Plan condensation drainage.
If the condensation pipe cannot be laid with a downward slope, the room unit must be provided with a
condensation pump.
Condensation is always formed on the “cold” side of the air-conditioning plant, i.e. for cooling in the
room unit and for heating in the outdoor unit.
Do you require permission from the local utility company?
4
Technical Data
Split room air conditioners with rapid refrigerant coupling
Indoor unit Outdoor unit
KSS 2504 AB
KSS 2504 A
KSS 2504AI KSS 2504AA
KSS 3204 AB KSS 3204 A
KSS 3204AI KSS 3204AA
Cooling capacity / heat output 1) kW 2.5 / 2.8 3.2 / 3.5 Air volume, indoor unit m³/h 420 460 Connection voltage
1/N/PE a230 V Nominal power consumption for cooling / heating
kW 0.79 / 0.97 1.09 / 1.24
Sound power level, outdoor / indoor unit (approx.)
dB(A) 52 / 36 55 / 39
Refrigerant R 410A Net weight outdoor / indoor unit kg 32 / 8.5 32 / 8.5 Dimensions, outdoor unit (W x H x D) mm 848 x 540 x 260 848 x 540 x 260 Dimensions, indoor unit (W x H x D) mm 770 x 250 x 180 770 x 250 x 180 Difference in height between device units, maximum
M 10
Length of refrigerant pipe, maximum M 20 Temperature range, cooling Indoor unit (adjustable range) Upper operating limit +30 °C / lower operating limit + 16 °C Outdoor unit (fixed-setpoint conditions) Upper operating limit +43 °C / lower operating limit -5 °C Temperature range, heating Indoor unit (adjustable range) Upper operating limit +30 °C / lower operating limit +16 °C Outdoor unit (fixed-setpoint conditions) Upper operating limit +43 °C / lower operating limit -7 °C Electrical connection lines Mains cable (dimension / length) mm² 3 x 1.0 / 5.2 m 3 x 1.5 / 5.2 m Control line (dimension / length) mm² 2 x 0.75 / 6.0 m 2 x 0.75 / 6.0 m Energy efficiency class 3) A B Coefficients of performance (cooling / heating)
4)
3.2 / 2.9 3.0 / 2.8
Refrigerant pipe accessories
3)
(essential)
consisting of a suction and pressure pipe, insulated and pre-filled with refrigerant
Pre-filled refrigerant pipes, length 2.5 m
KMSL 1438A-2 KMSL 1412A-2
Pre-filled refrigerant pipes, length 5.0 m
KMSL 1438A-5 KMSL 1412A-5
Split room air conditioners for wall mounting
with flanged connections, not for use with KMSL refrigerant pipes
(technical data see above) Indoor unit KSS 2504A IB KSS 3204A IB Outdoor unit KSS 2504A AB KSS 3204A AB Pipe for liquid mm
© 6 x 1 © 6 x 1
Suction gas pipe mm
© 10 x 1 © 12 x 1
Split pipes max. length / max. height m 20 / 10 20 / 10
Special accessories
comprising 2 brackets for wall mounting of outdoor unit Wall bracket
WKS 357 WKS 357
Condensation pump
KSI 3100 KSI 3100
1) Nominal data acc. to ISO 5151
2) Refrigerant pipes may be joined to extend them. The maximum permitted length of pipe must be observed.
3)
In compliance with 92/75/EC, Directive 2002/31/EC
4) Acc. to EN 14511
5
Split room air conditioners with rapid refrigerant coupling
Indoor unit Outdoor unit
KSS 4504 CB
KSS 4504 C
KSS 4504CI KSS 4504CA
KSS 6004 CB KSS 6004 C
KSS 6004CI KSS 6004CA
Cooling capacity / heat output 1) kW 4.5 / 5.2 6.0 / 6.5 Air volumes, indoor unit m³/h 700 720 Connection voltage
1/N/PE a230 V Nominal power consumption for cooling / heating
kW 1.75/ 1.75 2.30 / 2.30
Sound power level, outdoor / indoor unit (approx.)
dB(A) 58 / 46 59 / 48
Refrigerant R 407C Net weight outdoor / indoor unit kg 58 / 12 59 / 12 Dimensions, outdoor unit (W x H x D) mm 950 x 700 x 412 950 x 700 x 412 Dimensions, indoor unit (W x H x D) mm 907 x 290 x 195 907 x 290 x 195 Difference in height between device units, maximum
m 10
Length of refrigerant pipe, maximum m 20 Temperature range, cooling Indoor unit (adjustable range) Upper operating limit +30 °C / lower operating limit +16 °C Outdoor unit (fixed-setpoint conditions) Upper operating limit +43 °C / lower operating limit 0 °C Temperature range, heating Indoor unit (adjustable range) Upper operating limit +30 °C / lower operating limit +16 °C Outdoor unit (fixed-setpoint conditions) Upper operating limit +43 °C / lower operating limit -7 °C Electrical connection lines Mains cable (dimension / length) mm² 4 x 2.5 / 5.2 m 4 x 2.5 / 5.2 m Control line (dimension / length) mm² 5 x 1.0 / 6.8 m 5 x 1.0 / 6.8 m Energy efficiency class 3) D D Coefficients of performance
(cooling/heating)
4)
2.57 / 2.97 2.6 / 2.8
Refrigerant pipe accessories
3)
(essential)
consisting of a suction and pressure pipe, insulated and pre-filled with refrigerant
Pre-filled refrigerant pipe, length 2.5 m
KMSL 3858-2 KMSL 3858-2
Pre-filled refrigerant pipe, length 5.0 m
KMSL 3858-2 KMSL 3858-2
Split room air conditioners for wall mounting
with flanged connections, not for use with KMSL refrigerant pipes
(technical data see above) Indoor unit KSS 4504C IB KSS 6004C IB Outdoor unit KSS 4504C AB KSS 6004C AB Pipe for liquid mm
© 10 x 1 © 10 x 1
Suction gas pipe mm
© 16 x 1 © 16 x 1
Split pipes max. length / max. height m 20 / 10 20 / 10
Special accessories
comprising 2 brackets for wall mounting of outdoor unit Wall bracket
WKS 357 WKS 357
Condensation pump
KSI 3100 KSI 3100
1) Nominal data acc. to ISO 5151
2) Refrigerant pipes may be joined to extend them. The maximum permitted length of pipe must be observed.
3) In compliance with 92/75/EC, Directive 2002/31/EC
4) Acc. to EN 14511
6
Device Construction
Outdoor
component
Room
component
(1) Casing flap
(2) Air filter
(3) Air filter Element A (option only)
(4) Air filter Element B (option only)
(5) Cover
(6) Airflow fins
(7) Connection cable
(8) Condensation drain
(9) Air outlet grid
(10) Remote control
A
ir intake
A
ir outlet
Timer
7
Installation Notes for Split Air Conditioners
Before choosing a room air conditioner, we recommend carrying out a cooling load calculation according to the standard, or on the basis of a relevant standard. Forms for cooling load calculation complete with instructions can be obtained from the manufacturer or wholesaler or in the Internet at www.dimplex.de.
Note: Indoor or outdoor units which are not installed according to instructions may cause a reduction or loss
of warranty in the case of repair.
Choosing the installation location
It is very important to install split devices in suitable locations, as it is difficult, and thus expensive, to move them after installation. If possible, decide on the installation location in agreement with the final customer. The installation must be suitable for bearing the weight and the operational vibration of the indoor or outdoor unit on a permanent basis.
Notes on the installation of the indoor unit
- The circulating air should flow through the whole of the room to be cooled.
- The flow of cold air should not be directed at persons or their place of work.
- The condensation formed during cooling must be drained off without impairing functioning. If
condensation can only be led off upwards or without a downward slope, then the installation of a condensation pump is necessary.
- The unit may not be installed in rooms subject to high humidity in which the device is in contact with
moisture or water.
- The device may not be installed in rooms in which oil vapour is emitted or could be emitted.
Notes on the installation of the outdoor unit
- The outdoor unit should be installed in a place where it will not become soiled.
- When there is a danger of condensation freezing (heating operation when outside temperatures are low),
the condensate drain stubs should be removed and additional insulation be provided for the drainage area. Freezing condensation (e.g. the formation of ice on the heat exchanger) can impede the fan function of the outdoor unit.
- The outdoor unit must be installed in compliance with the regulations regarding the assessment of
operational noise in the neighbourhood. In particular, a suitable distance from bedrooms and similar rooms should be maintained.
- The device may not be installed in areas of aggressive air!
Scope of supply
Please check that the delivery is complete and that the devices are undamaged. The scope of supply includes:
1. Split air conditioner consisting of an indoor and an outdoor unit (two VPE - for a complete order)
2. Mounting plate for wall mounting of the indoor unit, slotted into it (incl. screws)
3. Remote control (incl. 2 batteries)
4. Condensation drain plug for draining condensation in the outdoor unit
5. Assembly and operating instructions
6. Length of insulating tube (approx. 250 mm x diam.
i
20 mm)
7. Control line with connection plug and a connection cable to the power supply (see Technical Data)
8. Sealant (in box – for sealing the wall around the pipes)
8
Assembling the Indoor Unit
Mounting plate:
The mounting plate for the indoor unit must be positioned horizontally and attached firmly. Minimum clearances must be observed. Please use the screws provided.
Wall opening:
One opening in the wall with a minimum diameter of 70 mm is necessary for the passage
of the condensation pipe and the refrigerant and electrical leads from the indoor unit to the outdoor unit (for adapted refrigerant connection pipes for the indoor unit or for KSS split pipes) A smaller opening, approx. diam. 55 mm, may be sufficient for non-adapted devices [without refrigerant couplings]. A sleeve should be placed in the wall opening in order to prevent damage to the pipes (in particular to the insulation of the split pipes)! It is better to pass the refrigerant connection pipes of the indoor unit through the wall than the split pipes themselves as some of these have a larger diameter and are thus difficult to lay in a small space (at the rear of the indoor unit).
1 Insulated suction pipe 2 Pressure pipe 3 Control line 4 Condensation pipe 5 Electric connecting cables (not in diagram)
Important: The opening must slope downward at an angle of about 5° so that the condensation formed during de-humidification and cooling can run away. (The end of the condensation pipe may not be standing in water or be below the water line!)
Position for wall opening
The diagram below shows the recommended position for the wall opening in relation to the mounting plate if the pipes are not to be visible in the room after installation.
In combination with KMSL split pipes only the position shown on the right, where dimensions are given, is suitable for the rear!
If you use your own split leads you may be able to use the position shown on the left (of the mounting plate) in relation to the wall opening.
Please note that the bends in the refrigerant pipes may not be positioned immediately in front of or after the refrigerant couplings or the screw fastenings for the leads!
If it does not matter whether the pipes are visible in the room, they can all be led out of the side of the indoor unit to the left (in the direction of the pipe connections of the indoor unit; the perforated areas in the casing of the indoor unit should be cut out for this) and led through the wall in some other suitable place.
Indoor unit:
Slot the indoor unit into the mounting plate and close the clips provided in the lower part of the casing.
Sealing the wall opening:
This is not done until the outdoor unit has been installed and all necessary connections between the indoor and the outdoor unit have been made. The wall opening, or the remaining openings in the wall opening sleeve, can be sealed using the sealant provided, using mortar or a mineral fibre plug with a silicone coating. In the case of fire protection walls, the provisions of DIN 4102 must be observed.
Hanging slots
ca. 50
ca. 50
70
ca. 50
ca. 60
70
KSS 4504C / 6004C
9
Minimum Clearances
Indoor unit
The following minimum clearances (A and B) from walls are essential for the trouble-free operation of the room air conditioner and for servicing and repairs.
The clearance between the ceiling and the lower edge of the room air conditioner must be at least 2.30 m. For device dimensions see Technical Data.
For all devices: A 100 mm B 180 mm
Outdoor unit
Clearance from walls (see Technical Data for device dimensions)
(If mounted close to the ground: 50 mm + necessary bend radius, if a condensation pipe is used)
300 mm (air intake side)
2 m
Condensation outflow
10
Assembling the Outdoor Unit
The outdoor unit should be attached firmly to a suitable surface or a suitable wall of sufficient strength (see also “Wall bracket accessory”).
It should be installed in a place where there is unimpeded air inflow and outflow An air short circuit must be avoided. Please observe minimum clearances and the sound power levels given in the technical data (distances from bedrooms or third-party rooms etc.).
Condensation drainage in the outdoor unit
When the heat pump is in operation, condensation is formed in the outdoor unit, which must be drained off in a manner appropriate to the location. There is a hole (diam. 25) for condensation drainage in the base plate of the outdoor unit into which the condensation drainage plug supplied is inserted. If the installation location allows it, the condensation formed can simply drip away, otherwise it must be led off through a pipe attached to the drainage plug.
Caution:
During heating operation at temperatures below +4 °C the condensation outlet can freeze up under unfavourable conditions and this can block the condensation fan. If temperatures below +4 °C are to be expected at the condensation outlet during heating operation, appropriate measures, e.g. insulation (insulation of the base of the casing and the condensation drainage area) should be taken, or, if possible, the drainage plug should not
be installed. If a condensation pipe is used, it must always slope downwards.
Distances between the drilling holes for mounting the outdoor unit
Type Dim. A (mm) Dim. B (mm) Dim. C (mm)
KSS 2504A/3204A 275 540 848 KSS 4504C 375 572 950 KSS 6004C 375 572 950
Connecting the cooling system for devices with pre-filled refrigerant pipes KMSL… .
The refrigerant pipes of the indoor and outdoor units are pre-filled with refrigerant R407C or R410A.
Please observe the safety regulations for handling CFC (HCFC) in the section “Pre-filled refrigerant pipes KMSL…” when installing the air conditioners and the split pipes.
(see page 12f.)
Split pipes of the KMSL series
Care must be taken to connect the refrigerant pipes correctly. It is particularly important to observe the torques specified (see page 14). Incorrect connection of the split pipes, which can be ordered as accessories, is impossible, because each half of the coupling fits only to its other half in the indoor or outdoor unit.
Ready-to-use refrigerant pipes in various lengths are available (see Essential Accessories in “Technical Data”). Excessively long pipes should be avoided when selecting split pipes (loss of cooling capacity). Reductions or extensions to length may be made by the authorised after-sales service only.
Please observe the assembly steps and the notes in the section “Pre-filled refrigerant pipes KMSL” on page 12ff. for installation and the connection of the cooling system.
View from
above
11
Connecting the Cooling System
First, unwind the refrigerant pipes carefully to their full length. The pipes may not have more than 3 bends in succession and a total of 12 bends over their entire length.
The number of bends should be kept to a minimum. The radius of the bends must be at least 3.5 times the external diameter. If necessary, a suitable bending device should be used.
Connecting the refrigerant pipes:
See the section “Pre-filled refrigerant pipes KMSL” for this.
Lay the suction and pressure pipes between the indoor and outdoor unit. We recommend laying the thicker suction pipes first, as the thinner pressure pipes are more easily fitted in.
Excess piping should be wound up at a downward angle to the outdoor unit in order to avoid residues of refrigerant oil.
Remove the dust caps and dust plugs from the two halves of the coupling.
The thread of the coupling and the seals should be cleaned with a clean cloth to avoid trapping dust and moisture in the system.
The membranes of the coupling and the rubber seals of the male halves of the couplings should be moistened with a few drops of refrigerant oil.
The matching halves of the couplings should be screwed together by hand until the thread is well engaged (or until the inner halves of the coupling membrane meet – turning then becomes much more difficult) and then tightened using a spanner (see Torques for refrigerant pipe couplings). A hissing noise during joining is normal. Caution! When torque is applied, the two halves of the coupling should always be held firm with spanners. Screw locks should then be applied to stop the connection loosening unintentionally through vibration.
After joining, the coupling connections must not be opened (Refrigerant could escape! Repairs must be carried out by an authorised after-sales service only).
Torques for refrigerant pipe couplings
The necessary torques for the secure (leak-proof) connection of the refrigerant pipe couplings are given below:
Split pipes with refrigerant couplings with 3/8“ and 1/4" UNF threads (spanner values SW 19 und SW
21) 15 – 20 Nm.
Split pipes with refrigerant couplings with 5/8“ and 1/2" UNF threads (spanner values SW 27 und SW
34) 47 – 54 Nm.
All refrigerant pipes and connections must be tested for leaks before first use (e.g. using a leak search spray).
wrong
right
Loading...
+ 25 hidden pages