Dimplex KBE 50, KBE 75, KBE 100, KBE 125, KBE 175 Operating And Installation Instructions

...
1
Operating and Installation Instructions KBE Wall Convectors 453321.66.85gb 07/04/A
1. Important Information
Please read with care all of the information provided in these instructions in a safe place for future reference. Pass them on to any subsequent purchaser of the unit.
The unit is suitable solely for heating the air in a closed room.
Only a qualified electrician should install or repair this unit.
In the event of a fault, disconnect the unit from the main power supply (switch off or unscrew fuse)
Do not cover the unit - fire hazard!
Caution! The unit is hot to the touch when in operation.
Do not operate the unit unattended if there are small
children in the vicinity.
Do not insert objects of any kind through the apertures in the unit.
The unit should be installed so that its controls are out of reach of anyone in the bathtub or under the shower. VDE 0100 Part 701 specifies that the unit may not be installed in the protection zone. Keep the flap over the controls closed.
An isolating device must be provided in the electrical wiring specified (for example, a miniature circuit­breaker). It must have a contact gap of at least 3 mm at each pole.
Substances which could lead to ignition or thermal decomposition inside the unit (for example, carpet or floor tile adhesives) must not be used unless you are certain the unit has cooled down to room temperature.
2. Installation, Wiring, Minimum Clearances
The convector may only be installed in a horizontal position (the control panel must always be at the top). The convector must be installed in such a way that flammable objects cannot ignite. It is permissible to mount the convector on a wooden wall. The convector must not be mounted directly beneath a wall power socket. It is essential that you observe the minimum clearances A, B and C specified in the installation diagram, particularly as regards clearances from easily flammable objects. Make sure that air can flow into or out of the convector without being obstructed.
Minimum clearances A B C mm 150 150 150
The convector is not mounted directly on the wall but installed in a wall frame.
- Drill the mounting holes for the wall frame.
- Screw the wall frame to the wall.
- Fit the convector in the wall frame using the slots on the back of the unit.
- Swing the unit up and against the wall, latching it into the top part of the wall frame.
3. Electrical Connection
In addition to the leads for the electrical power supply (L1 = brown, N = blue, PE = green / yellow) a marked control wire (black) is provided for external temperature reduction via an external timer or pilot unit, for example.
See section 8 for circuit diagram.
4. Heating
Switch On/Off
A = Off, no function. M = On. Thermostat regulates the room temperature to the
value specified at the thermostat knob.
Thermostat
The Heater is equipped with a thermostat which you can use to set the room temperature you want. The ∗ setting of the thermostat is for frost protection. Here the thermostat keeps the room temperature at around 7°C. A room temperature of about 21 °C corresponds to a ‘6’ setting on the thermostat knob.
BA500BA
Min.
C
GB
Switch On/Off Thermostat
2
4a. Restricting the Temperature Range
With the aid of the two pins on the back of the unit you can set the range of the thermostat wheel. One pin determines the upper value and the other pin the lower value. Move the pins back and forth to loosen them.
5. Overheating Cut-out
For your protection the heater is equipped with an overheating cut-out. If the outgoing flow of air is obstructed (for example, the air grille is covered or is closed), the heater will cut out automatically.
Do not put the heater back into operation until you have corrected what caused the overheating cut-out to trip. You should also switch off the power supply to the unit for a few minutes (mode switch to OFF).
Once the unit has cooled down enough you can switch it back on. For you to enjoy the full power of the heater the air intakes and outlets must be kept free of dust. Clean the heat with your vacuum cleaner before the cold season of the year.
6. Faults
If no heat is coming out of the convector make sure that the On/Off switch is set to position "M" (see Section 4) and that the thermostat is set to the temperature you want. Check that the circuit-breaker has not tripped or that the fuse has not blown. In the event of malfunctions in your heater, please contact your local electrician or the nearest customer service point for Dimplex appliances. The E number and the FD code are required before servicing can be carried out. You will find them on the rating plate.
Any examination of the heater or repair work may only be carried out by a qualified electrician or after-sales service technician.
7. Cleaning
Before attempting any cleaning operation, switch off the heater and wait until it has fully cooled down. The heater can be swung away from the wall to allow access for cleaning: Undo the fastening and pull the top of the heater forwards.
Use a soft damp cloth to wipe off the outside surfaces of the heater. Do not use abrasives or furniture polishes for cleaning as these can damage the surfaces of the heater.
8. Technical Data, Dimensions, Weights
Supply voltage 1/N/PE~ 230V, 50Hz Thermostat 7-29°C Protection class l With protective earth terminal Degree of protection IP 21 Drip proof
Rating Model Weight Dimensions in mm W kg A B
500 KBE 50 3,4 360 400 750 KBE 75 3,7 360 400 1000 KBE 100 4,3 440 400 1250 KBE 125 4,9 520 400 1500 KBE 150 5,5 600 400 1750 KBE 175 6,0 760 400 2000 KBE 200 6,6 840 400
9. Warranty
Authorized dealers can provide information on the terms and conditions of warranty. The warranty is not valid without a sales receipt marked with the date of purchase.
KKW Kulmbacher Klimagerätewerk GmbH Geschäftsbereich Dimplex Tel. +49 (0) 9221 / 709-564 Am Goldenen Feld 18 Fax +49 (0) 9221 / 709-565 D-95326 Kulmbach www.dimplex.de Kundendienst@dimplex.de
A
PE
N
Control wire black
L1
105
83
B
Restriction pins
Loading...