Dimplex EWa-C 1 kW, EWa-C 1.5 kW, EWa-C 2 kW Installation Instructions Manual

Down-Flo Wall Heater
1-888-346-7539
Installation Instructions
Wiring Two conductor non-metallic sheath cable with ground wire is recommended
for recessed installation of these heaters while two conductor, metallic sheath cable (BX) is recommended for surface installations. Use number 12 gauge wire for all models. Each heater should be on an individual, properly fused circuit.
Recessed Installation
2. Cut a wall opening 14 9/16” (37cm) high by 11 1/4” (28.5cm) wide (see Fig 1). Allow a minimum of 2” (5cm) clearance around wall opening to accomodate heater frame. Depth of wall opening must be 3 1/4” (8.3cm) minimum, measured from finished wall surface.
3. Remove the screws securing heater assembly to the wall box and separate. Keep all screws for heater reassembly.
4. Remove rear knockout at top corner of wall box and insert 1/2 cable connector. Bring service leads through connector and secure end of cable to the connector.
5. For safety, each wall heater is provided with a grounding screw located in the upper right corner of the wall box. Connect ground lead and tighten screw for good electrical connection.
6. Place wall box in wall opening so the welded side brackets rest on finished wall surface, and secure box with four #10 Philips head wood screws, 1 1/2” long (not provided). Insert the wood screws through the inner set of flange holes at both top and bottom.
Alternate holes are provided in sides of box for mounting to wood framing. (If wall box is installed prior to application of finished wall surface, set box to allow for wall thickness).
NOTE: When mounting wall box to hard wall surface, predrill mounting
and clearance holes to prevent splitting wall surface.
7. Check nameplate on heater to make sure you are connecting to the
Series EWA-C, 1, 1.5 & 2 KW
proper voltage. Remove any packing material or debris from the heater assembly and wall box. Then connect service leads.
8. Place heater assembly into the wall box. Check fan to see that it turns freely, and service leads are clear of fan area. Secure heater assembly to the wall box with four sheet metal screws (provided).
9. Carefully position grille over heater assembly so that protruding switch and thermostat shaft do not bind against grille. Secure grille to heater assembly using two Phillips head sheet metal screws (provided). Push press-fit thermostat knob on shaft.
10. Install the frame to the grille, securing its upper back edge behind the lip on the top of the wall box, and its lower edge with the single screw.
11. Energize heater circuit and test heater (see operating instructions).
Surface Installation
1. Allow 25” (63cm) of service cable for connecting the heater (see Fig. 2). Remove all but 2” (5cm) of outer jacket and strip individual conductors 1/4” (6mm) from end.
2. Mount surface box to the wall using the four provided #8 - 3/4” Philips head wood screws, inserted through mounting holes on the back side flanges. (For hard wall surfaces, pre-drill mounting holes to prevent splitting wall surface.)
3. Install 1/2 cable connector in hole on bottom of surface box near right side. Feed service leads through and secure end of cable to the connector.
4. Remove the rear knockout on top of heater wall box near right side and insert bushing (provided). Feed service wires through bushing. Secure wall box to surface box with four sheet metal screws (provided with the surface box). Screws are inserted through the inside holes on the flanges.
5. Proceed with steps 7 through 11 inclusive in recessed heater installation instructions.
Operating Instructions
These heaters are operated by an on/off switch and also a temperature control with a knob.
RECESSED
FRAME
THERMOSTAT
KNOB
GRILL
PHILLIPS
HEAD
SCREW
3 1/4”MINIMUM
GROUNDING SCREW
OVERTEMP LIGHT
120/208/240V
WALL OPENING
HEATER
ASSEMBLY
Fig. 1
11 1/4”
REMOVE THIS
KNOCKOUT
12” CABLE
WALL OPENING
14 9/16”
PHILLIPS HEAD
SCREW
WALL BOX
1. Turn the switch ON. Remember there is a fan delay.
2. Set thermostat by turning the knob to desired room comfort level (clockwise to increase heat output). Once you have determined the proper setting to provide the heat level you prefer, you need not touch the knob again.
3. Turn the switch OFF to turn off heater. To reuse, simply turn the switch ON - the temperature level you wish has been previously set. NOTE: This heater is equipped with a fan delay switch which delays the fan operation until the heating grid has heated sufficiently to assure the circulation of only warm air. This same switch permits the fan to operate after power to the grid has been shut off by thermostat action, thus utilizing all the heat remaining in the grid. When the heater is shut down by turning the switch OFF, power to both fan motor and element is diconnected and the fan motor will not continue to operate.
WARNING: Should the OVERTEMP light come on, disconnect power to
the heater, turn the switch OFF or turn down the thermostat fully counterclockwise and call a licenced electrician. DO NOT USE HEATER UNTIL PROBLEM IS DETERMINED AND FIXED.
SPECIFICATIONS AND ORDERING INFORMATION
CATALOG No. SUPPLY VOLTS AMPS. CFM
1.0 kW EWA10C11 120V 8.3 50 3413 BTU EWA10C21 208V 4.8 50
EWA10C31 240V 4.2 50 EWA10C41 277V 3.6 50
1.5 kW EWA15C11 120V 12.5 50 5122 BTU EWA15C21 208V 7.2 50
EWA15C31 240V 6.2 50 EWA15C41 277V 5.4 50
Tamper Proof Models The ON/OFF switch and the temperature regulating thermostat are
recessed so that the continuous grille front panel can be installed concealing both controls. The thermostat is operated by removing the front panel. The ON/OFF switch can be operated by inserting a slender non metallic rod between grill louvers and turning the switch ON or OFF.
Maintenance
This heater requires no maintenance other than a cleaning at least once a year.
CAUTION: Before removing heater parts, open branch service switch or remove fuses. These are located at the distribution panel.
To clean, remove frame, grille and heater assembly. Remove any dust and dirt from wall box and heater assembly with a soft cloth or brush, then re-install heater assembly making sure that the fan turns freely and service leads are away from fan area. The frame and grille may be washed with a mild detergent, however make sure they are thoroughly rinsed and dried before re-installation.
SURFACE
WOOD SCREW
BUSHING
GROUNDING
SCREW
SURFACE WALL
BOX
25” SERVICE
LEADS
2.0 kW EWA20C21 208V 9.6 50 6830 BTU EWA20C31 240V 8.3 50
Wall Box Opening: 14 9/16” (37cm) height, 11 1/4” (28.5cm) Front Plate: 16 3/8” (41.6cm) height, 13” (33cm) width, Field Installed Accessories:
1. When installing optional wall thermostat, unit mounted thermostat must be set at it’s highest setting.
2. All external control equipment (shown with dashed lines) furnished by customer. Control wiring must be suitable for 600V.
3. Heater branch circuits shall have a carrying capacity of no less than 125% of maximum load served.
4. All external wiring to the heater shall be in compliance with the National Electrical Code pr the Appliance Codes.
EWA20C41 277V 7.2 50
width, 3 1/2” (8.5cm) depth
extends 1 3/4” (4.5cm) from wall (recessed)
8754 - Surface Mounting Box Kit TGKSB - Tamper Proof Grille/Controls Kit
WALL STAT
(OPTIONAL)
SHEET METAL
SCREW
REMOVE THIS
KNOCKOUT
SERVICE CABLE
HEATER WALL BOX
ELECTRICAL SERVICE PER NAMEPLATE
SWITCH
CAPACITOR
THERMOSTAT
Fig. 2
THERMOSTAT
M
GRID
FAN
CONTROL
LIMIT
CONTROL
7204380100 REV04
Loading...
+ 1 hidden pages