Dimplex EUH03B31T, EUH03B11T, EUH03B34CT, EUH03B41CT, EUH03B51CT Quick Manual

...
ELECTRIC UNIT HEATERS
MODEL EUH-B
Installation/ Start-up/ Maintenance
FOR HORIZONTAL OR VERTICAL AIRFLOW PERMANENT OR SUPPLEMENTARY ELECTRIC FORCED AIR HEATING FROM THE SAME VERSATILE UNIT
1. HEATER LOCATION: Unit heaters should be located along outside walls to provide perimeter air circulation. The discharge air should wipe the walls without blowing directly on them. (Figure 1) a. Small rooms - can be heated by one or two units. Locate the unit heater(s) to provide circular air movement within the space. b. Large rooms - requiring multiple unit installations. Units should be located so that the discharge air from one unit supports the discharge from another unit and provides a circular air movement. c. Remote thermostats - should be located on interior walls or posts away from heat sources, cold drafts, and away from heater discharge streams.
2. MOUNTING UNIT HEATER(S): Heater should be mounted a minimum of ten (10) inches from walls and six (6) feet above fl oor (8 feet for vertical air fl ow) with the discharge parallel to or away from wall. (See Table A for recommended mounting heights) a. MOUNTING BRACKET - The heater is shipped with a mounting bracket packed separately in the carton. Secure the bracket to threaded attachment points on the sides of the heater with two bolts (provided). Select desired angle of tilt (Horizontal, 15, 30, 45, 60, 75, or Vertical), remove corresponding knockouts on sides of the heater, then screw the remaining two bolts into the threaded holes in the bracket so that the bolts pass through the knockout holes. The unit is now ready for hanging. b. CEILING MOUNTING - Fasten the heater securely to the ceiling using the center hole in the bracket or the two holes on either side of the center hole. The Unit mounting bracket may be attached directly to the ceiling. c.WALL MOUNTING - The heater may also be mounted to a wall with accessory wall bracket, (Part # EUHWB). The wall bracket attaches to the center hole of the unit mounting bracket.
EXPOSED OUTSIDE WALL
SMALL ROOM LARGE ROOM
FIGURE 1
EXPOSED OUTSIDE WALL
WALL
EXPOSED OUTSIDE
1-888-346-7539
7202450001R05
Heater is now ready for wiring
3. WIRING:
a. Connect the heater only to the voltage and frequency specifi ed on the nameplate. b. All wiring to be in accordance with local and national electric codes. c. Remove two screws securing the access door (See Figure 2) and swing the door down to expose the wiring and control compartment. d. Three knockouts are provided at the back of the heater for power and control wiring. (See Figure 2) e. Rough-in branch circuit wiring to the heater using wire rated for 75 degrees C. Wire heater supply according to diagram attached to the access door.
REMOVE SCREW, EACH SIDE
FIGURE 2
SUPPLY ENTRY KNOCKOUTS
4. CONTROLS: Factory installed. a. Fan delay - The heater is equipped with a fan delay delay control. The fan will remain on for a few moments after the elements are de-energized. b. Automatic High Limit - Each heater is equipped with automatic reset thermal cutouts located above the elements. Should these safety switches operate, they will automatically reset once the element reaches a safe operating temperature, however the cause of the high limit condition should be determined and corrected to insure satisfactory operation. c.Thermostat - All heaters are equipped with a hydraulic type thermostat which has a nominal operating range of 40F (low) to 100F (high).
5. OPTIONAL CONTROLS: Field installed. a. Remote line voltage thermostat - An optional remote line voltage thermostat may be used to control the unit. Field connections may simply be connected to the control terminal block located in the wiring compartment in accordance with with the wiring diagram attached to the access door.
CAUTION - Disconnect the built-in thermostat
b. Remote Low voltage thermostat with relay - An optional low voltage thermostat/relay kit may be used to control the unit (Catalogue #EUAR11, 120V primary; EUAR21, 208V primary; EUAR31, 240V primary; EUAR41, 277V primary). The relay is installed through the hole provided in the back left corner of the blower deck. Power connections are made to the control terminal block located in the wiring compartment in accordance with the wiring diagram attached to the access door. A knockout is provided on the left side of the heater for the 24 volt thermostat control wiring. It is important that the plastic insulation bushing be installed into the knockout hole before running low voltage control wiring. The thermostat is installed and wired in accordance with the instructions packaged with the kit.
CAUTION - Disconnect the built-in thermostat