Dimplex ECS150HP40A-580, ECS210HP40A-580, ECS250HP40A-580 Installation And User Instructions Manual

Important - This Manual Must Be Left With The User After
Installation!
EC-Eau Cylinder Range
A Class Heat Pump Cylinders
Up to 250L
A Class HP Installation a
nd User Instructions R02583
-13 05/17
Page
2
The HWA Charter requires that all members adhere to the following:
supply fit for purpose products clearly and honestly described supply products that meet, or exceed appropriate standards and building and water regulations provide pre and post sales technical support provide clear and concise warranty details to customers
For further information on the HWA Charter Membership, please refer to the HWA website
www.hotwater.org.uk
All Glen Dimplex cylinders are certified by KIWA, for further information on this regulation body please refer
to the KIWA website www.kiwa.co.uk
Dimplex is a licensed member of the Benchmark Scheme which aims to improve the standards of installation and commissioning of domestic heating and hot water systems in the UK and to encourage regular servicing
to optimise safety, efficiency and performance.
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate
compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hot Water Industry Council who manage
and promote the Scheme. Visit www.centralheating.co.uk for more information.
Overall View
A Class HP Installation a
nd User
Instructions R02583
-13 05/17
Page
3
0 Overall View
Figure 1: Overall View of A Class Heat Pump Cylinder Installation Process
08
02
03
01
05
04
06
07
09
Contents
A Class HP Installation a
nd User Instructions R02583
-13 05/17
Page
4
1 Contents
0 Overall View ............................................................................................................. 3
1 Contents ................................................................................................................... 4
2 Introduction ............................................................................................................. 7
3 Scope of Delivery ..................................................................................................... 7
4 Pre-Installation Advice ............................................................................................. 8
4.1 Risk Assessment ..................................................................................................8
4.2 Siting Considerations ............................................................................................8
4.3 Cold Water Supply ................................................................................................9
4.4 Building Regulation G3 Discharge Requirements .......................................................9
4.4.1 Discharge Pipe D2 ..........................................................................................9
4.4.2 Worked Example .......................................................................................... 11
4.4.3 Termination of Discharge Pipe ....................................................................... 11
4.5 Limitations ........................................................................................................ 11
5 Installation ............................................................................................................ 12
5.1 Cold Water Inlet with Inlet Control Group .............................................................. 12
5.1.1 Correctly Site the Cylinder ............................................................................ 12
5.1.2 Install the Inlet Group .................................................................................. 12
5.1.3 Expansion Vessel ......................................................................................... 12
5.1.4 Balanced Cold Water Supply .......................................................................... 12
5.1.5 Drain Valve ................................................................................................. 12
5.2 Hot Water Outlet ................................................................................................ 13
5.2.1 Thermostatic Mixing Valve ............................................................................ 13
5.2.2 Pipe Insulation ............................................................................................ 13
5.3 Discharge Pipes from Safety Devices ..................................................................... 13
5.3.1 Discharge Pipe D1 ........................................................................................ 13
5.3.2 Discharge Pipe D2 ........................................................................................ 13
5.3.3 Tundish ...................................................................................................... 13
5.4 HP Flow to Buffer Connection ............................................................................... 13
5.5 Buffer Flow to HP Connection ............................................................................... 13
5.6 Coil Return Connections ...................................................................................... 14
5.7 Coil Flow Connections ......................................................................................... 14
5.8.1 Temperature Sensor Connection .................................................................... 16
5.9 Water Module Wiring ........................................................................................... 19
5.9.1 Primary Electrical Connections ....................................................................... 19
5.9.2 Modbus Connection ...................................................................................... 20
5.9.3 Zone Connections ........................................................................................ 20
5.9.4 Digital Inputs & Temperature Sensors ............................................................ 21
5.10 Bivalent System ................................................................................................. 23
5.11 Connection of Secondary Return ........................................................................... 23
6 Commissioning ....................................................................................................... 24
Contents
A Class HP Installation a
nd User Instructions R02583
-13 05/17
Page
5
7 Maintenance ........................................................................................................... 25
8 Spare Parts ............................................................................................................ 26
9 Technical Data and Product Fiche ........................................................................... 27
9.1 A Class Heat Pump Buffer Range .......................................................................... 27
9.2 Cylinder Heat Exchanger Pressure Drop ................................................................. 30
9.3 Cylinder Attainable Temperature .......................................................................... 31
10 User Instructions................................................................................................ 31
10.1 General ............................................................................................................. 31
10.2 Operation .......................................................................................................... 31
10.3 Water Temperature Direct Electric Heating ............................................................ 31
10.4 Maintenance ...................................................................................................... 32
10.5 Troubleshooting ................................................................................................. 32
Scope of Delivery
A Class HP Installation a
nd User Instructions R02583
-13 05/17
Page
6
Precaution: This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understanding the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
Note: Between the inlet group and the cold water inlet on the cylinder NO isolating device may be fitted, as by doing so important safety devices could be isolated!
It is important to check the pre­charge pressure of the expansion vessel membrane before filling the cylinder. This has been factory set to 3 bar. The pre-charge should be greater than or equal to 3 bar.
It is important that the tundish is positioned away from any electrical components.
Note: Means for electrical disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
Before removing the cover from the immersion heater isolate appliance using isolating switch! Danger of electrical shock! Only use suitable electrically insulated equipment when working inside immersion housing.
The maintenance of this appliance must be carried out by a suitably qualified person only. It is recommended to maintain the unit on an annual basis. Isolate all electrical supplies from the unit before commencing work. Danger of electrical shock!
CLEANING INSTRUCTIONS: Clean outer cladding of cylinder with a soft cloth dampened with warm water only. Do not use abrasive or aggressive cleaning materials, such as alcohol or petroleum based solvents, as this may damage the surface of the product.
Temperature setting: A high level cutout is fitted to the product for each heat source. This should never activate under normal operation. The maximum possible cylinder temperature attainable by the heat pump is 65°C as set on the User Interface. The back-up immersion heater can produce up to 72°C at its maximum setting, i.e. 5. For convenience the immersion heater is preset to produce 60°C.
If an electronic copy of this manual should be required, please contact the manufacturer at the address at the back of this manual.
Scope of Delivery
A Class HP Installation a
nd User Instructions R02583
-13 05/17
Page
7
2 Introduction
Thank you for choosing a Dimplex product. The EC-Eau heat pump cylinders are specified with large, high surface area heat exchangers, specifically sized to match the requirements of Dimplex “A” Class Heat Pumps. They boast 60mm of low GWP insulation foam, together with 100% recyclable stainless steel inner components and a sleek black, hard wearing outer shell manufactured from completely recycled materials.
NOTE: This product has been designed specifically for the purpose of delivering heated, domestic and sanitary hot water as part of a pressurised water heating system. The package is provided with fittings that comply with Section G3 of Building Regulations.
WARNING: Dimplex cannot take responsibility for ensuring safe operation of the appliance outside of the scope of intended use.
For more detailed information on product features, please see the Technical Data section in this manual.
3 Scope of Delivery
Please ensure you check the scope of delivery below before signing any delivery documentation. Claims for missing or damaged parts after signing for the delivery will not be accepted.
Table 1: Scope of Delivery for A Class Heat Pump Cylinders
* These items are supplied factory fitted
** Supplied with Dimplex heat pump hydraulic pack
Pre-Installation
A Class HP Installation a
nd User Instructions R02583
-13 05/17
Page
8
4 Pre-Installation Advice
Please read the following section carefully before commencing installation. If in any doubt, please call the appropriate help desk. Disregarding the instructions given in this manual in its entirety and any relevant regulations, standards and codes of practice will void the guarantee of this product.
Handling – depending on the size of the
unit and access to its installation location, consideration must be given to the handling of the unit. Please note that handling, installation and use of this product is subject to the Health and Safety at Work Act. If the unit is not installed immediately, it should remain in its protective packaging with all pipe protectors/end caps applied to prevent damage and dirt deposit inside the cylinder and the coils.
Pipe Work – the pipe runs should be
executed as short as possible, unused pipe work should be removed and all remaining pipe work should be lagged in accordance with regulatory requirements to prevent heat loss and the formation of condensation.
Taps and Fittings – all taps and fittings
incorporated in the unvented system should have a rated operating pressure of 0.6 MPa (6 bar) or above.
4.1 Risk Assessment
The compilation of a risk assessment is strongly recommended before installing the product. The following areas require particular consideration in addition to the information required by the Health and Safety at Work Act.
scalding: where appropriate or required by
law a thermostatic mixing valve is to be fitted to the hot water outlet of the cylinder (see also water borne organisms).
explosion: the unit is fully equipped with all
relevant safety equipment to comply with current regulations. The correct design and function has been verified by independent third party testing. The correct application thereof is the responsibility of the competent installer.
water borne organisms (i.e. Legionella): if
applicable a risk assessment should be carried out following the recommendations outlined in the Approved Code of Practice L8.
the user preference must be considered
when commissioning the system, in particular when adjusting the temperature and timer settings.
4.2 Siting Considerations
When choosing a suitable location for the cylinder the following aspects should be considered:
structural integrity access for installation, operation,
maintenance and replacement
routing of discharge pipe work access to water mains supply, hot and cold
water distribution pipe work
access to suitable electricity supply location in relation to remaining system
components such as auxiliary system
frost protection
The heat pump cylinder range is designed to be floor standing, vertically mounted, indoors and in a frost free environment. The cylinder may be located on any flat and level surface, provided it is sufficiently robust to support the weight of the cylinder when full of water (please see technical data) and suitably accessible for replacement/maintenance without specialist tools or lifting equipment as this will void the warranty conditions.
The position and orientation of the cylinder should be such that easy access is provided for servicing the controls. A minimum distance of 400mm in front of the immersion is recommended, to allow the replacement of the immersion heater should the need arise. When installing the cylinder all labels should be clearly visible and ensure that no pipework hinders any work to be carried out on the various cylinder components.
Particular care must be taken when placing the cylinder in a garage or outbuilding. All exposed pipe work must be correctly insulated to avoid frost damage.
Pre-Installation
A Class HP Installation a
nd User Instructions R02583
-13 05/17
Page
9
CLEANING INSTRUCTIONS: Clean outer cladding of cylinder with a soft cloth dampened with warm water only. Do not use abrasive or aggressive cleaning materials, such as alcohol or petroleum based solvents, as this may damage the surface of the product.
4.3 Cold Water Supply
For satisfactory and safe performance of the unvented cylinder the water supply must meet the following criteria:
Minimum dynamic pressure
150 kPa (1.5 bar)
Maximum inlet supply pressure
1200 kPa (12 bar)
Minimum flow rate
15 l/min
Max. chlorine content
250mg/L
Max. water hardness
200mg/L
The following instructions have to be followed when installing the cold water mains supply to the cylinder:
The cold water supply to the cylinder must
come directly from the cold water mains after the mains stop valve to the property.
The cold water inlet pipe work should have
at least an inside diameter of 19mm and should meet the requirements of the water regulations for the supply of wholesome water.
Dimplex recommend an annual maintenance inspection is carried out on the domestic hot water cylinder. In hard water areas this should include inspection of the heat exchanger and immersion heater, [above 120ppm or 120mg/l]. A local water treatment company should be able to offer free water quality testing. The heating elements may require periodic de-scaling. The installer should do this as part of a maintenance agreement.
If required, precautions can be taken to minimise effects of water hardness, i.e. installation of water conditioner or water softener. These devices should be installed in hard water areas where high water storage temperatures are required, i.e. greater than 60°C storage temperatures, particularly when water hardness exceeds 200ppm. Should the water cylinder require de-scaling, this must be performed by a qualified technician.
4.4 Building Regulation G3 Discharge
Requirements
As part of the requirements of Building Regulation G3 any discharge from an unvented system should be conveyed to where it is visible, but will not cause danger to persons in or about the building. The tundish and the discharge pipes should be fitted in accordance with the requirements of Building Regulation approved document G3, (England and Wales), Part P of Northern Ireland and Standard 4.9 of Scotland.
4.4.1 Discharge Pipe D2
The discharge pipe (D2) from the Tundish should:
“have a vertical section of pipe at least
300mm long below the tundish before any elbows or bends in the pipework and be installed with a continuous fall of at least 1 in 200 thereafter.”
The discharge pipe (D2) should be made of:
“metal; or other material that has been
demonstrated to be capable of safely withstanding temperatures of the water discharged and is clearly and permanently marked to identify the product and performance standard.
Dimplex strongly recommends the use of metal pipework only and Dimplex does not take responsibility for any damage caused from discharges.
The discharge pipe d2 should be at least one pipe size larger than the nominal outlet size of the safety device unless its total equivalent hydraulic resistance exceeds that of a straight pipe 9m long, i.e. For discharge pipes between 9m and 18m the equivalent resistance length should be at least two sizes larger than the nominal outlet size of the safety device; between 18 and 27m at least 3 sizes larger, and so on; bends must be taken into account in calculating the flow resistance. See Figure 2: Typical Discharge Pipe ArrangementFigure 2, Table 2 and the worked example.
Note: An alternative approach for sizing discharge pipes would be to follow Annex D, section D.2 of BS 6700:2006 + A1:2009).
Pre-Installation
HP Installation and User Instructions R00918
-6 01/13
Page
10
Figure 2: Typical Discharge Pipe Arrangement
Table 2: Sizing of Copper Discharge Pipe “D2for Common Temperature Relief Valve Outlet Sizes
Pre-Installation
A Class HP
Installation a
nd User Instructions R02583
-13 05/17
Page
11
4.4.2 Worked Example
This example is for a G½ temperature relief valve with a discharge pipe (D2) (as fitted on 125 to 300L cylinders) having 4 No. 22mm elbows and length of 7m from the tundish to the point of discharge.
From Table 2, the maximum resistance allowed for a straight length of 22mm copper discharge pipe
(D2) from a G½ temperature relief valve is 9.0m. Subtract the resistance for 4 No. 22mm elbows at 0.8m each = 3.2m.
Therefore the maximum permitted length
equates to 5.8m, which is less than the actual length of 7m, therefore calculate the next largest size.
Maximum resistance allowed for a straight length of 28mm copper discharge pipe (D2) from a G½ temperature relief valve is: 18m
Subtract the resistance for 4 No. 28mm elbows at 1.0m each = 4m
Therefore the maximum permitted length equates to 14m.
As the actual length is 7m, a 28mm (D2) copper pipe will be satisfactory.
Where a single common discharge pipe
serves more than one system, it should be at least one pipe size larger than the largest individual discharge pipe (D2) to be connected.
The discharge pipe should not be connected
to a soil discharge stack unless the soil discharge stack is capable of safely withstanding temperatures of the water discharged, in which case, it should:
contain a mechanical seal, which allows
water into the branch pipe without allowing foul air from the drain to be ventilated through the tundish.
there should be a separate branch pipe with
no sanitary appliances connected to it.
if plastic pipes are used as branch pipes
carrying discharge from a safety device,
they should be either polybutalene (PB) or cross-linked polyethylene (PE-X) complying with national standards.
be continuously marked with a warning that
no sanitary appliances should be connected to the pipe.
4.4.3 Termination of Discharge Pipe
“The discharge pipe (D2) from the tundish
should terminate in a safe place where there is no risk to persons in the vicinity of the discharge.”
Examples of acceptable discharge arrangements are:
“to a trapped gully with the end of the pipe
below a fixed grating and above the water seal;
downward discharges at low level; i.e. up to
100mm above external surfaces such as car parks, hard standings, grassed areas etc. are acceptable providing that a wire cage or similar guard is positioned to prevent contact, whilst maintaining visibility; and,
discharges at high level: e.g. into a metal
hopper and metal downpipe with the end of the discharge pipe clearly visible or onto a roof capable of withstanding high temperature discharges of water and 3m from any plastic guttering system that would collect such discharges.”
Note: As the discharge would consist of high temperature water and steam, asphalt, roofing felt and non-metallic rainwater goods may be damaged by such discharges.
4.5 Limitations
The heat pump must be specified correctly,
to ensure it is compatible with the model of cylinder installed. This is to prevent the heat pump malfunctioning when preparing domestic hot water.
The heat exchangers in this range of
cylinders have been specifically designed for heat pump applications. Great care must be taken if using these cylinders with other heat sources, due to the heat exchange capacity of the product.
Installation
A Class HP Installation a
nd User Instructions R02583
-13 05/17
Page
12
5 Installation
5.1 Cold Water Inlet with Inlet Control
Group
5.1.1 Correctly Site the Cylinder
Install the cylinder in an appropriate location, ensuring all of the recommendations have been considered (see chapter 4.2).
5.1.2 Install the Inlet Group
The inlet group regulates the pressure of the incoming mains water supply to the cylinder and removes any debris that might be water borne.
Note: Between the inlet group and the cold water inlet on the cylinder NO isolating device may be fitted, as by doing so important safety devices could be isolated!
5.1.3 Expansion Vessel
The expansion vessel is mandatory on all EC-Eau cylinders and can be connected directly to the cold water inlet group, utilising the flexible hose supplied with the vessel. The expansion vessel should always be fitted in accordance with the manufacturer’s instructions. Isolating device/s must not be fitted between the water cylinder, the expansion vessel and the cold water inlet group.
Furthermore, it is recommended to mount the vessel higher than the cylinder to avoid having to drain the cylinder when maintaining and replacing the expansion vessel.
Figure 3: Connection Of The Expansion Vessel To The
Inlet Group
It is important to check the pre-charge pressure of the expansion vessel membrane before filling the cylinder. This has been factory set to 3 bar. The pre­charge should be greater than or equal to 3bar.
Note: The expansion vessel must be installed to the side of the expansion relief valve on the inlet group. To do this the blanking plug must be removed and the expansion vessel connected, as shown in Figure 4.
Figure 4: Detail Showing The Connection Of The
Expansion Vessel To The Inlet Group
5.1.4 Balanced Cold Water Supply
If a balanced cold water supply is required (recommended) a connection can be taken from the bottom of the inlet group.
5.1.5 Drain Valve
It is also recommended to install a drain valve in the lowest point of the cold water feed to the cylinder. This allows the cylinder to be drained in a controlled manner should this become necessary.
Expansion
Vessel
Connection
Balanced
Cold Water
Supply
Expansion
Relief
Valve
Cold
Water to
Cylinder
Cold
Water from
Mains
Loading...
+ 27 hidden pages