Dimplex A8M, A16M, A12M Installation Manual

Page 1
A-Class Heat Pumps
A8M, A12M & A16M Installation Manual
dimplex.co.uk
8/60472/0
Issue 1.07
Page 2
Page 3
1. Introduction 5
1.1 Manual Information 5
1.2 Important Safety Information 6
1.3 Intended Use 8
1.4 Legal 8
1.5 Heat Pump Labels and Pipe Connections 9
1.6 Heat Pump Dimensions 9
1.7 Scope of Delivery 10
1.7.1 Installation pack 1 - Space heating and Dimplex A-Class cylinder 11
1.7.2 Installation pack 2 - Space heating and Dimplex standard cylinder 12
1.7.3 Installation pack 3 - Space heating only 13
2. Important pre-installation information 14
2.1 Connection to the Grid - Notifying the DNO 14
2.1.1 Heat Pump Sizing 14
2.2 Heat Pump Location 14
3. Installation instructions 16
3.1 16
3.1.1 Temperature Control Devices 18
3.1.2 Space Heating Zones 19
3.1.3 Location of Wiring Centre 19
4. Installation 20
4.1 Important - Plumbing Information 20
4.1.1 Pipe Sizing Information 22
4.1.2 Buffer tank 23
4.1.3 Adjusting the spring loaded by-pass valve (if fitted) 23
4.1.4 Metering for the Domestic Renewable Heat Incentive - UK 24
4.2 Electrical Information 25
4.2.5 Access to Electrical Connections - Opening the heat pump 25
4.2.6 Electrical Connections - power and Modbus cable heat pump connections 26
4.2.7 Modbus Cable Information 28
4.2.8 Opening and Installing the User Interface 28
4.3 Heat Pump Controller / Commissioning 30
4.3.1 Important pre-startup information 30
4.4 Commissioning 31
4.4.1 Starting the heat pump in cold weather 31
4.4.2 General / Schematic 31
4.4.3 Waterside Check 33
Page 4
4.4.4 Temperature Check 34
4.4.5 Electrical connections 34
4.4.6 Water Flow Check 34
4.4.7 DHW set-up 36
4.4.8 Electrical connections (DHW) 36
4.4.9 DHW Test 36
4.4.10 Disinfection (thermal) 38
4.4.11 Weather compensation 39
4.4.12 Heating curves 39
4.4.13 Comfort level 40
4.4.14 Setup complete 40
4.5 Additional Installer Menu Options 40
4.5.1 Service menu 40
4.5.2 Message log 40
4.5.3 Output Tests 41
4.5.4 Defrost 41
4.5.5 Operating data 41
4.5.6 History 41
5. System Health Check / Maintenance 42
5.1 Heat pump: 42
5.2 Electrical: 42
5.3 Hydraulics: 42
5.4 Indoor settings: 42
6. Appendices 43
6.1 44
6.2 Refrigeration cycle 45
6.3 Schematics - Example 1 46
6.4 Schematics - Example 2 47
6.5 Schematics 1, 2, 3 & 4 : Space Heating Only 48
6.6 Schematics 5, 6, 7, 8 : Zone space heating + DHW 49
6.7 Schematics 9, 10, 11, 12 : Bivalent space heating 50
6.8 Schematics 13, 14, 15, 16 - Bivalent zone space heating + DHW 51
6.9 52
6.10 53
6.11 54
6.12 Controller cable connections 55
6.13 56
6.14 Installer hand-over form 57
6.15 58
Page 5
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
5
1. Introduction
1.1 Manual Information
NOTE: This manual is intended for electricians and qualied installers only!
This manual is intended for installers and electricians installing Dimplex A-Class air-source heat pumps.
All installers must have prior knowledge regarding the installation of Dimplex A-Class air-source heat pump
systems, and must be competent to install the system safely and successfully.
Installers must have knowledge of any local or national standards, codes or regulations that may apply, as
well as safe methods of practice. Dimplex accept no responsibility for compliance with these codes and
regulations on the part of the installer.
All electrical installations must be carried out in accordance with local and national standards and
regulations, including BS 7671.
NOTE: Repair should not be attempted by unqualied persons.
NOTE: Retain this manual for information
The instructions included in this manual are important for the correct installation and use of Dimplex
A-Class air-source heat pumps. Please ensure that you retain this manual for reference.
The specications and information supplied in this manual may be subject to change without notice at the
discretion of Dimplex. All attempts have been made to ensure that this document is complete and that the
information supplied is correct at the time of publication, however Dimplex will assume no responsibility
for damages (including consequential and indirect / accidental damages) resulting from reliance on the
information presented in this document.
NOTE: Check that you have the latest issue of this manual before installation.
NOTE: Go to http://www.dimplex.co.uk/customer_support/downloads and enter your A-Class heat
pump model number for the latest PDF download of this manual.
These original instructions must be left with the user after installation, including the hand-over form at the
back, where the installer should record key information during commissioning.
Unauthorised reproduction of this document is prohibited.
Page 6
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
6
1.2 Important Safety Information
Do not tilt the heat pump by more than 45° in any
direction.
Do not lift without using correct lifting devices.
Ensure that all clearance dimensions are observed - this
is important for correct heat pump operation and air ow.
Use a suitable lifting device in accordance with any
relevant health and safety regulations.
Do not move or transport the heat pump at.
WARNING: When using lifting rods to lift the heat pump, straps must also be used to prevent toppling.
Figure 1: Maximum tilt angle
NOTE: Leaving a clear pathway for delivery will allow the heat pump to be delivered as close to the installation site as possible to minimize moving / lifting.
• Never use cleaning agents containing sand, soda, acid or chloride as these can damage surfaces
/ components.
• Do not use muddy or dirty water to ll the heating system. This can cause components to
malfunction and poses a corrosion risk to the system.
• If the heat pump may be disconnected from the power supply for long periods of time, or where
power supplies are susceptible to failure, antifreeze must be added to the system.
Example: Mono ethylene glycol at 25% volume to protect down to -14°C in a holiday home.
• Use a suitable ltration protection system and a corrosive additive to prevent the formation of
oxides or solids in the heat pump condenser.
• This appliance can be used by children aged from 8 years and above and persons with reduced
physical, sensory or mental capabilities or lack of experience and knowledge if they have been
given supervision or instruction concerning use of the appliance in a safe way and understand
the hazards involved.
• Children shall not play with the appliance.
• Cleaning and user maintenance shall not be made by children without supervision.
NOTE: The heat pump contains refrigerant at high pressure. Safety measures are in place to avoid system pressure build up;
Stage 1: Pressure transducer stops compressor. Stage 2: Pressure switch switches heat pump off. All safety devices reset automatically.
Page 7
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
7
WARNING: Before removing the cover of the heat pump, cylinder or wiring centre, ensure that all electrical circuits are isolated.
NOTE: The heat pump has a multi-layered, software generated alarm management system, which prevents it from running outside its operating limits.
NOTE: If an alarm / message occurs, the heat pump will attempt to take remedial action before causing the system to stop completely if the problem persists. However, the overriding safety feature is the high pressure switch, which de-energises the main contactor supplying power, in accordance with EN378.
NOTE: This device is suitable for mains connection only (230V, 1P&N, 50Hz) and is not suitable for operation with an electrical generator or power modulator, due to possible effects on the quality of the electrical supply. Any attempt to do so will void warranty.
• Means for disconnection from the supply mains must be incorporated into the xed wiring in
accordance with the national wiring regulations.
• This device must be installed in accordance with national wiring regulations.
• The local wiring regulations should always be followed paying particular attention to the mixing of
low voltage and extra low voltage cabling.
• Ensure the incoming power supply and the distribution board are suitably rated.
• Ensure that the regulations specied by the local electricity supplier have been adhered to.
• All fuse rating and protective overload device information is provided in the wiring label located
on the inside of the front bottom panel of the heat pump. For instruction on how to remove this
panel please see section 3.1.
• The installation of a heat pump designated residual current device (type B RCD) having a rated
residual operating current not exceeding 30mA is recommended, in accordance with local
regulations (BS7671 for UK installations).
• The correct earthing (grounding) of the heat pump is of the utmost importance.
CAUTION: The heat pump has a high leakage current and must be properly grounded for safety in accordance with local and national regulations regarding equipment with a leakage current exceeding
3.5ma.
CAUTION: Two separate, designated RCD devices should be tted - one for the heat pump and one for the cylinder. The heat pump system must not share an already existing domestic RCD device.
Page 8
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
8
1.3 Intended Use
This product is designed to extract heat from outside air to provide energy for a water-based heating
system, and is intended for domestic and light commercial use. Any other use beyond that intended by
the manufacturer is prohibited. This requires the user to abide by the manufacturer’s product information.
Please refrain from tampering with or altering the device.
NOTE: Additional heating may be required if the heat pump is intended to dry out a new or renovated building, as the initial heat load may be higher than the design load.
1.4 Legal
The construction and design of the heat pump complies with all relevant EU directives (see CE declaration
of conformity in Appendices section).
When connecting the heat pump to the power supply, the relevant EN and IEC standards must be adhered
to. Any further connection requirements stipulated by the network operation must also be observed.
When connecting to the heating system all applicable regulations must also be adhered to.
NOTE: Products not installed with the Dimplex hydraulics packs will not be supported by Dimplex. This includes but is not limited to thermal stores.
NOTE: Installation and any service work on the heat pump may only be performed by an authorised and qualied installer and after-sales service technicians.
Page 9
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
9
1.5 Heat Pump Labels and Pipe Connections
Figure 2:Heat pump connections and labels
1.6 Heat Pump Dimensions
Figure 3:Heat pump dimensions
1
3
2
4
1
2
Water outlet connection
Water inlet connection
Water connection label
3
Rating label
4
Model:
Serial No. 001
8.0
R410A 2.0 kg
bar
C20 A
h/³m0073riA
aPk1.4h/³m1.2
Protection: IP 24 kg
12.30 kW COP 4.72
12.90 kW COP 2.20
1/75733/0
The refrigeration cycle is hermetically sealed.
Contains Kyoto-Protocol defined fluorinated greenhouse gases.
All work to be carried out on this unit is to be carried out by a competent person.
Power Factor
A-2W55
P
Heating
Air to Water Variable Speed Heat Pump
Max Op. Pressure
Revision:
Single Phase 230V/50Hz
45
kW
Δp
Electrical Power (Max)
P
Heating
A7W35
Heating Water:
EN14511-2 Conditions
A16T
Fabrication Date:
0.99
Fuse Protection
Min. Flow
T
y
pical
Flow
-20 / +35
+25/+65
Min / Max
Op. Temp.
Min / Max Op. Temp.
Weight 130
GDC Group Greenbank Industrial Estate, Rampart Road, Newry Northern Ireland BT34 2QU
Tilt angle
Do not clamp
on sides
MCS HP0017 HEAT PUMPS
Page 10
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
10
1.7 Scope of Delivery
Please ensure you check the scope of delivery before signing any delivery documentation.
Below is a guideline checklist for what should be contained in each pack.
Claims for missing or damaged parts after signing for the delivery will not be accepted.
There are 3 options to select from when installing a Dimplex Heat Pump:
Pack 1 - Space heating and Dimplex A-Class Cylinder
This pack should contain four boxes;
• Heat Pump
• ACCHYPK Hydraulics Kit A (contains all of the necessary hydraulic components)
• Cylinder
• Cylinder Accessories
A separate wiring centre is not required as the wiring centre is built into the cylinder.
Pack 2 - Space heating and Dimplex Standard Heat Pump Cylinder
This pack should contain ve boxes;
• Heat Pump
• ACCHYPK Hydraulics Kit A (contains all of the necessary hydraulic components)
• Cylinder
• Cylinder Accessories
• Wiring Centre
A separate wiring centre is required as the wiring centre is not built into the standard cylinder.
Pack 3 – Space heating only
This pack should contain three boxes;
• Heat Pump
• ACSHYPK Hydraulics Kit B (contains all of the necessary hydraulic components)
• Wiring Centre
• Accessories
A separate wiring centre is required to wire the circulation pumps and controls.
NOTE: Details for each installation pack are shown on pages 11-13.
All hydraulic kits listed in the following tables include the following documents;
ASHP Installation manual, part number 8/60472/0 A8M, A12M, A16M
ASHP User manual, part number 8/60476/0 A8M, A12M, A16M
Please ensure that these manuals are left with the end user. Manuals must be stored safely for future reference.
Page 11
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
11
1.7.1 Installation pack 1 - Space heating and Dimplex A-Class cylinder
No.
Description Part No.
1 A-Class heat pump A8M / A12M / A16M
10 Blanking plugs (x4, stored inside heat pump) 4592624105
Hydraulics Kit A ACCHYPK
2 User interface (UI) 1754600
3 ERES spring loaded by-pass valve (22mm comp. tting) 1755780
4 3-port diverting valve (28mm comp. ttings) 1755750
5 Pump - UPM GEO 25-85 180 (1500mm cable) 1755740
6 Isolation valves (1” swivel BSP to 28mm comp.) - Flow 1755760
7 Isolation valves (1” swivel BSP to 28mm comp.) - Return with strainer 1755770
13
2 x Circulation Pump Gate Valve 11/2” swivel to 28mm comp
2 x Washer 30.1x21x2mm
1756090
Dimplex A-Class cylinder kit, which includes;
8 A-Class cylinder with integrated buffer
9
Safety group DHW side; expansion vessel, hose and bracket, inlet group,
tundish
11 Drain
12 3x copper pipes - Pump to buffer / cylinder
14 Air vent
Pipe connections to coil, pipe, drain and vent.
Pipe connections to pump.
q
w
e
r t
y u
i
o
a
s
d
f
g
Page 12
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
12
1.7.2 Installation pack 2 - Space heating and Dimplex standard cylinder
NOTE: Cylinder required for pack 2 installation; please see Dimplex EC-EAU cylinder manual for range of non A-Class cylinders.
No. Description Part No.
1 A-Class heat pump A8M / A12M / A16M
10 Blanking plugs (x4, stored inside heat pump) 4592624105
Hydraulics Kit A ACCHYPK
2 User interface (UI) 1754600
3 ERES spring loaded by-pass valve (22mm comp. tting) 1755780
4 3-port diverting valve (28mm comp. ttings) 1755750
5 Pump - UPM GEO 25-85 180 (1500mm cable) 1755740
6 Isolation valves (1” swivel BSP to 28mm comp.) - Flow 1755760
7 Isolation valves (1” swivel BSP to 28mm comp.) - Return with strainer 1755770
12
2 x Circulation Pump Gate Valve 11/2” swivel to 28mm comp
2 x Washer 30.1x21x2mm
1756090
8 Dimplex standard cylinder
Wiring centre module, which includes;
9 Wiring centre module
049162
11 1 x Temperature probe (NTC10) for DHW
q
w
e
r t
y u
i
o
a
d
s
Page 13
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
13
1.7.3 Installation pack 3 - Space heating only
q
w
r
t
y
u
o
a
s
i
No. Description Part No.
1 A-Class heat pump A8M / A12M / A16M
10 Blanking plugs (x4, stored inside heat pump) 4592624105
Hydraulics Kit B ACCHYPK
2 User interface (UI) 1754600
5 Pump - UPM GEO 25-85 180 (1500mm cable) 1755740
6 Isolation valves (1” swivel BSP to 28mm comp.) - Flow 1755760
7 Isolation valves (1” swivel BSP to 28mm comp.) - Return with strainer 1755770
4
2 x Circulation Pump Gate Valve 11/2” swivel to 28mm comp
2 x Washer 30.1x21x2mm
1756090
Wiring centre module, which includes;
9 Wiring centre module
049162
11 1 x Temperature probe (NTC10) for DHW
Accessories
8 100L / 200L / 300L buffer tank (depending on installation) 025586
3 2kW buffer immersion element 363610
e
Page 14
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
14
2. Important pre-installation information
CAUTION: You must read and understand all of the information in this section before attempting an installation!
2.1 Connection to the Grid - Notifying the DNO
Before you connect a heat pump to the grid, the necessary permissions must be granted by the
distribution network operator. Not obtaining the necessary permissions may result in an unexpected
network upgrade charge, and may compromise the integrity of the local supply if a ‘disturbing load’ is
connected to the network.
The required forms are supplied by Dimplex and must be lled in by the heat pump installer alongside the
client. We recommend notifying the DNO as early as possible in the planning stage to discuss the project
and any additional information. Further information can be found on the Energy Networks website
(www.energynetworks.org) or from your local DNO.
2.1.1 Heat Pump Sizing
NOTE: Ensure that the correct size heat pump has been selected in accordance with the latest version of MIS3005 (for UK installations).
If a non A-Class heat pump cylinder is being used, ensure that it has been accurately sized with the
appropriate coil surface area of the cylinder to match the heat pump’s output and ow rate requirements,
and that all necessary hydraulic connections have been considered in connecting it to the heat pump
system.
Ensure that suitable heat emitters have been sized in accordance with the BRE publication Design of low-
temperature domestic heating systems: A guide for system designers and installers. To maximise
system efciency it is important to design the system with the lowest ow temperature possible.
For more information on sizing heat emitters or to order BRE publications, please visit the BRE bookshop
website: www.brebookshop.com
2.2 Heat Pump Location
• The heat pump must be installed outdoors.
• The fan should not face prevailing winds to ensure correct air ow through the evaporator.
• The minimum clearance distances provided in this manual must be followed.
• NO obstructions in front of the heat pump fan for at least 1m.
• Clearance is important for good air ow and service access to the heat pump.
• Do not position the heat pump close to bedroom windows, as the fan and compressor may be
operational at night.
Page 15
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
15
Figure 4: Poor air ow
CAUTION: Ensure that there are no obstructions in front of the heat pump fan for at least 1m - however, 2m is recommended. ANY type of obstruction in front of the heat pump, even small shrubs, can block the air ow and cause cold air recirculation.
Figure 5: Good air ow with recommended clearances
Page 16
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
16
3. Installation instructions
3.1 Positioning and xing the heat pump
• The heat pump must be xed onto a level, stable concrete plinth of minimum dimensions approx.
1000mm x 500mm.
• The concrete plinth must be able to withstand the unit’s weight of 110-140kg (depending on
model).
• A minimum distance of 50mm between the heat pump and the edge of the plinth is required on
all sides.
CAUTION: The minimum clearance distances around the heat pump are shown in gure 3; 300mm at the rear for air ow, 500mm each side for service and at least 1000mm in front of the fan to avoid air recirculation.
Figure 6: Required service and air ow clearance dimensions
Page 17
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
17
1) Check that plinth dimensions are within the required clearances, as per figure 6.
Positioning the heat pump in a conned space, frost hollow or well will result in reduced heat pump
efciency.
The cold air which is expelled by the fan cannot disperse and may be drawn back into the system.
This means that the heat pump may be operating using a lower inlet temperature than what is actually
available from the ambient air.
Figure 7: Removing the panels to t xing bolts and condensate pipe
CAUTION: Ensure that the condensate pipe is uncoiled and is running to a drain
2) Remove the heat pump panels to mark drilling holes on plinth.
The heat pump panels must be removed so that the base panel is visible. To do this, remove the screws
and slide the panels downwards and out.
Once the panels are removed, mark the holes for the xing bolts (gure 6), then lift or slide the heat pump
out of the way to drill the holes. Leave the panels off until all xing and positioning of the heat pump, bolts
and condensate pipe have been carried out (steps 3 -4).
3) Run the condensate pipe to an appropriate drain
The condensate drain pipe is coiled up inside the heat pump for protection during transportation. In order
to access this for installation, the panels will need to be removed (see gure 7). The condensate pipe must
be uncoiled and run through the condensate pipe hole in the base panel to the drain.
Page 18
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
18
• The pipe should be prevented from exposure to the elements, as this may contribute to freezing
issues. The condensate pipe must run through the base panel and underground to the drain. Freezing
of this pipe due to incorrect installation can result in irreparable damage and void warranty.
• Approximately 2 litres of condensate water are drained from the system every time a defrost cycle
occurs (approximately once every hour in cold and humid weather). Therefore, it is essential that the
condensate pipe is fed into a rain water drain or soak away to allow for safe disposal of the excess
water, away from footpaths or patios.
• The removal of condensate must be secured and the condensate pipe must be kept free from debris
and frost.
• The condensate pipe should not run into sewer pipe as fumes may travel into the heat pump and
cause corrosion to the evaporator coil.
4) Inserting the fixing bolts
Once the holes for the xing bolts are drilled, place the heat pump back onto the plinth and x in place
using the M10 bolts supplied in the installation pack.
5) Positioning and Fixing Indoor Components
The controller and thermostats should be installed on internal walls in living area to reect the correct
room temperature, and away from direct sunlight, drafts (windows and doors) and heat emitters.
3.1.1 Temperature Control Devices
• The controller/user interface that is supplied with the Dimplex A-Class heat pump is used as a
heat pump controller as well as a space heating and domestic hot water (DHW) controller.
The preferred option is to use the user interface as a room temperature control device.
• The user interface and room thermostats should be installed indoors in a location that is out of
reach of children, but where the LCD display can be easily seen (usually 1.2m – 1.7m from the
oor).
While only one user interface is currently available per system, there are additional options
of either temperature probes or mechanical thermostats, which can be used to control the
temperature in up to four zones.
• Mechanical thermostats provide less control over the heating system, while the temperature
probe option allows the heat pump to sense changes in demand and adjust accordingly. The
temperature probe option is generally recommended over the mechanical thermostat option.
Page 19
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
19
3.1.2 Space Heating Zones
A zone is dened as the physical area of the home in which temperatures are controlled by each individual
device. For example, there might be a user interface installed in the living area, in which case this may be
referred to as zone 1. There may also be a temperature probe installed upstairs in the sleeping/bedroom
area, which would then be designated as zone 2, and so on.
Extra zones are an additional, optional feature of the heating system. The standard package comes with
one user interface and the possibility of four separate zones. Each heating zone can be assigned a heat
curve specic to the type of heat emitters.
3.1.3 Location of Wiring Centre
If a Dimplex A-Class cylinder is used, the wiring centre is built in to the A-class cylinder and pre-wired.
If a non A-Class cylinder is used, the wiring centre module must be installed.
The wiring centre module is designed to be wall mounted, and it is recommended that it is installed in
close proximity to the cylinder to allow for installation of components which require a control cable
(modbus) connection, i.e. pump, DHW probe, 3-port valve and heat pump connections.
Page 20
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
20
4. Installation
4.1 Important - Plumbing Information
NOTE: To simplify underoor heating initial screed heating, it is essential to have a thermostatic mixing valve on the underood heating (UFH) manifold. This allows the heat pump to run at higher temperature and capacity when the screed is cold.
• If multiple heat emitter circuits are installed, operating at different ow and return temperatures (such
as under oor heating and standard radiators), a mixing valve must be used on low temperature
circuits to prevent high temperature water from entering the under oor heating manifold.
• Isolation valves (non-return valve and ball valve with strainer), supplied in the Dimplex heat pump
hydraulics pack, allow the strainer to be removed and cleaned without having to drain the system.
• Existing hot water systems should be ushed prior to connection to the heat pump to remove all
contaminants and impurities, in accordance with the latest version of MIS3005.
• Flow and return isolation valves and piping must be tted to each of the heat pump water connections
on the back of the heat pump, as shown in gure 1.
• The isolation valve on the return is also tted with a non-return valve and a strainer (included in the
Dimplex heat pump hydraulics pack). This means that in order to clean the strainer, the system does
not have to be drained. Instead, it is possible just to close the isolation valves on the return and
remove the strainer. This way, the only water that will be lost from the system is that between the non-
return valve and strainer.
• The strainer must be tted in order to prevent contamination of the condenser heat exchanger. If an
alternative strainer is used, it must be at least 7 microns in size.
• System should be pressurised and the system pressure must be checked once valves are re-opened.
• Direct condensate drain pipe to soak away or drain.
• All piping must be properly insulated and external length kept to a minimum.
• The return isolation valve provided in the hydraulics pack has a built in strainer to help prevent debris
entering the condenser and must be tted.
• The system must be lled and ushed with clean fresh water to ensure the removal of all the air from
the installation.
CAUTION: When lling the system, always ensure that clean, fresh water is used. Using dirty or untreated water may cause severe damage to components and may affect the efciency of the system when operating.
• Air bleed points must be installed at the highest point in the system; in particular, the installer must
remember to install an air bleed on the heat pump pipe if it is a local high point since there is no air
bleed point on the heat pump itself. Dimplex recommend the use of a power ush and purge cart to
facilitate this process.
Page 21
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
21
• Flow and return isolation valves and piping must be tted to each of the heat pump water connections
on the back of the heat pump, as shown in gure 8.
• The isolation valve on the return is also tted with a non-return valve and a strainer (included in the
Dimplex heat pump hydraulics pack). This means that in order to clean the strainer, the system does
not have to be drained. Instead, it is possible just to close the isolation valves on the return and
remove the strainer. This way, the only water that will be lost from the system is that between the non-
return valve and strainer.
• The strainer must be tted in order to prevent contamination of the condenser heat exchanger. If an
alternative strainer is used, it must be at least 7 microns in size.
• System should be pressurised and the system pressure must be checked once valves are re-opened.
• Direct condensate drain pipe to soak away or drain.
• All piping must be properly insulated and external length kept to a minimum.
• The return isolation valve provided in the hydraulics pack has a built in strainer to help prevent debris
entering the condenser and must be tted.
Figure 8: Details of ow and return isolation valves
CAUTION: The quality of the water used to ll the heating system is of vital importance. Muddy or dirty water, for example, from a freshly drilled well, is not suitable, as this can lead to the incorrect functioning of some components and poses a corrosion risk to the system.
Page 22
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
22
4.1.1 Pipe Sizing Information
When selecting piping to install w ith the heat p ump please ensure that:
The safety group and expansion vessel (space heating side) are accurately sized by the installer
based on the system volume (these are not supplied by Dimplex).
External pipework and valves should be adequately insulated with vapour resistant insulation and
protected against damage to prevent excessive heat losses. All joints should be suitably sealed
and exposed pipework must be avoided.
Ensure the water out and water in pipes are positioned correctly for connection to the heat pump
NOTE: The hydraulic installation information provided in this manual applies only to the components provided in the Glen Dimplex hydraulics pack (see Scope of Delivery for information).
A8M A12M / A16M
Space heating only
DHW with A-Class cylinder
Water ow rate
@ 1100 l/h
(nominal)
@ 2100 l/h
(nominal)
@ 1800 l/h (nominal)
Associated head available 60kPa 14kPa 18kPa
Pipe diameter
(mm)
Internal diameter
(mm)
Maximum equivalent pipe length
90 N/A N/A
300 23 38
22
28
32
19.8
25.6
29.6
0.31 l/m
0.51 l/m
0.69 l/m 600 46 77
Table 1: Maximum equivalent length for copper pipe - water only
CAUTION: Table 1 above is provided as a guideline when using water only. Any percentage of anti-freeze added will affect the pressure drop of the system greatly and will render this table invalid.
Not all types of pipe will have the same internal diameter, e.g. multi-layered/plastic pipes will have
a thicker wall so the guidelines set out in table 1 will not apply. Microbore (8mm) and 15mm pipe is
not suitable.
As a rule of thumb, the equivalent straight length (L [mm]) of each elbow is found by multiplying
the outer diameter of the pipe (D [mm]) by 30, e.g. 4 elbows of diameter 22mm pipe is equivalent to
2.5m of 22mm pipe.
Volume of
water per
metre of pipe
Page 23
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
23
4.1.2 Buffer tank
The heat pump uses a reverse cycle defrost in order to defrost the evaporator by taking heat from the
heating system. It is therefore necessary to connect a buffer tank in series with the heat pump, as shown
in the hydraulic schematic diagrams (Appendices). The Dimplex A-Class cylinder range come with an
integrated buffer tank, which;
• Provides some energy storage for the unit to carry out successful defrost.
• Increases compressor life due to reduction in the number of starts.
It is recommended that a buffer with a heating element/immersion is used as it may be required if initial
start-up and commissioning are carried out in very cold weather.
Buffer Tank Sizing
The minimum total system water volume (including water in heat emitters) should be no less than 100l.
Water volume in pipework, heat emitters and the built-in 40l buffer tank included in the A-Class cylinder
must all be taken into account. This is particularly important when using Smartrads, as their water content
is low compared to standard radiators (0.6l for SRX180 model).
4.1.3 Adjusting the spring loaded by-pass valve (if tted)
CAUTION: If an externally controlled zone pump is connected when using any schematic, the spring loaded bypass must not be used and instead must be replaced by an open bypass tted with a gate valve. This is to ensure that the zone pump(s) is/are not running against a dead head when the heat pump is idle or in DHW mode
The bypass valve is used to maintain a minimum ow rate and prevents faulty operation of the heat pump,
as well as allowing it to run efciently. The bypass valve must be adjusted correctly after commissioning
the heat pump.
Please ensure that the following steps are taken when adjusting the bypass valve;
1. Ensure that the bypass valve is open fully and begin running the heat pump.
2. Close all of the heating circuits that may be closed during the operation of the heating system so
that the least favourable ow rate can be achieved. This should cause all of the ow to go through the
bypass valve. To check that all of the water ow is going through the bypass valve, feel the pipe after the
valve to check its temperature (it should be getting heat from the heat pump).
3. Slowly close the valve until the water is no longer owing through it, then turn the valve back
slightly (approx. 0.5 to 1 turn) to allow some ow and prevent the heat pump from tripping.
4. Open the zone valves while the heat pump is still running, and again check the ow through the
bypass valve by feeling the pipe after the valve and checking its temperature (it should not be as hot as
ow temperature). The bypass setting should allow hot water to ow through the bypass valve when some
of the heating circuits are closed.
Page 24
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
24
4.1.4 Metering for the Domestic Renewable Heat Incentive - UK
Please take note of the following requirements if the installation is to be fitted with a meter;
• Leave sufcient space for appropriate meters to be tted in dened locations.
• For Dimplex installations using 22mm pipe, please leave 440mm of straight pipework on the
meter inlet pipe and 175mm of straight pipework on the outlet pipe;
• For installations using 28mm pipe, please leave 560mm of straight pipework on the meter inlet
pipe and 175mm of straight pipework on the outlet pipe.
• Install low pressure-drop isolation valves to avoid the need to drain systems when tting heat
meters. See the schematics (Appendices) for more information on valve locations.
• Leave sufcient pipework accessible, i.e. not boxed in or under oor boards, to enable meters to
be tted.
• Guidelines for tting an MCS approved meter can be found in the Domestic Renewable Heat
Incentive essential guide to metering, available on the Ofgem website: www.ofgem.gov.uk
Page 25
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
25
4.2 Electrical Information
The heat pump system consists of the heat pump, wiring centre and user interface. If a Dimplex A-Class
cylinder is also used, the wiring centre is built into the cylinder.
The user interface acts as a thermostat and is sufcient if one heating zone is present. Optional, additional
temperature probes or room thermostats are required for additional heating zones.
The wiring diagrams in the Appendices section show the different possible wiring congurations for
systems with and without a Dimplex A-Class cylinder.
WARNING: Before opening the heat pump, ensure all circuits are isolated.
WARNING: Ensure that the components in the electrical box do not get wet when the electrical box is
opened.
WARNING: The main 230V power cable must be supplied via a suitable sized exterior isolator, lockable in the OFF position.
4.2.5 Access to Electrical Connections - Opening the heat pump
Figure 9: Access to the electrical box
Page 26
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
26
To open the heat pump, follow the procedure shown in gure 9;
1) Unscrew 2 screws (1) holding front bottom panel (2) using a PZ2 screwdriver
2) Pull the front bottom panel (2) down then out to remove
3) Unscrew 5 screws (3) holding the front cover (4) of the electrical box to open and then pull down
4) Remove 2 PZ2 screws (6) holding the door ap in place to access cable connections.
5) Cable access cover (7) only used on some models.
For model cable connection congurations for your heat pump model, please see gure(s) 11/12.
6) The cable access covers (5 and 7) can be opened by removing a screw to allow access to cables.
CAUTION: Ensure that cable access covers are closed correctly when not in use.
CAUTION: Follow steps in reverse order to close the heat pump. When closing the heat pump front
panel, ensure that the top and bottom panels are interlocked.
4.2.6 Electrical Connections - power and Modbus cable heat pump connections
The electrical connections to the heat pump may have one of two congurations, depending on the model.
Please see diagrams 11/12 for your conguration.
Figure 10: Heat pump electrical connections
NOTE: ‘S’ as shown in gure 10 above is the earth shield and must be connected during installation.
Controller Cable (RS485 MODBUS) to be connected to S, OV, B, A
Mains power supply cable to be connected to PE, L, N
Connections on this side are pre-wired
EARTH SHIELD
WHITE / Orange
BLUE / White
WHITE / Blue
Page 27
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
27
• For conguration 1, the cables are fed through the holes at the back of the heat pump and directly
inside the electrical box through the base of the heat pump (see gure 11).
Figure 11: Electrical cabling conguration 1
• For conguration 2, the cables are fed through the holes at the back of the heat pump, up through the
holes in the base of the heat pump and then from outside the electrical box through the cable glands
(see gure 12).
Figure 12: Electrical cabling conguration 2
M16X1.5 Cable Gland
RS485 Modbus Cable
M16 Lock Nut
M25x1.5 Cable Gland
Armoured Power Cable
M25 Lock Nut
Page 28
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
28
Allow sufcient cable length to ensure the connections are not strained when the cover is opened.
Once cables have been routed through the cable glands, close the access cover.
Connect power cable and controller cable as shown in gure 10. Do not strip the cables before pulling
them through the glands in the access panel. Where stranded cable is being used, a ferrule must be tted
before inserting into the push connections.
The controller (Modbus) cable is then connected from the heat pump to the wiring centre (see wiring
diagrams in Appendices).
4.2.7 Modbus Cable Information
Table 2: Recommended cable specications/electrical characteristics for Modbus cable
4.2.8 Opening and Installing the User Interface
It is recommended to connect the Modbus cable in daisy-chain series (as shown in gure 13) from the
heat pump on to the wiring centre and then on to the UI. The jumpers will be in the correct factory setting
for this wiring conguration by default. If using the recommended conguration, the jumper position does
not need to be changed.
Figure 13: Recommended MODBUS cable conguration
If it is deemed necessary to install the Modbus cable in a different order, please see Appendices.
The cover of the UI must be removed in order to move the jumper. To remove the cover, unscrew the
screw at the bottom of the UI and lift the cover and rotary dial.
Belden Cable 9842 Typical Equivalent Cable
Nominal Characteristic Impedance 120Ω 120Ω
Nominal Conductor DC Resistance
24.0Ω/1000ft
78.7401 Ω/km*
78.80 Ω/km*
Nominal Capacitance Core to Core
12.8pF/ft
41.99pF/m
42pF/m
*Conversion factor for ft to m = 3.28 ft = 1m
1km of Belden cable would have a resistance of 78.74 Ω/km
1km of Equivalent cable has a resistance of 78.8 Ω/km
Start
End
Page 29
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
29
To replace the cover, position the rotary dial over the holding pin on the board, ensuring the two are lined
up correctly. Replace the cover and bottom screw. Ensure that rotary dial is tested and working once cover
has been replaced.
Page 30
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
30
4.3 Heat Pump Controller / Commissioning
4.3.1 Important pre-startup information
When starting up the heat pump, you must rst ensure that;
• All covers are replaced.
• The heat pump isolator switch is switched on.
• The heat pump is connected to the mains power supply via a separate suitable circuit breaker and
RCD protection.
• The wiring centre or DHW cylinder is connected to the mains power supply.
The Modbus network is complete and the UI and the heat pump are connected to the wiring centre or
DHW cylinder.
Once the connections have been made and the power supplies have been switched on, the system may
take a couple of minutes to start up.
When switching on the heat pump for the rst time, and after the start up sequence, you will be greeted by
the main menu or screensaver if the heat pump is idle (use the Esc button to return to the main menu).
To access the Installer Menu, you must select the
information menu, represented by the ‘i’ icon on the
main menu (shown in gure 14).
Use the rotary dial to select the ‘Login’ option and to
scroll through numbers from 0 - 999.
Input the code to access the installer settings (22),
then the code to bring up the installer menu (55).
NOTE: You will not be able to access any other options on the main menu, except the information menu, until the heat pump has been fully commissioned.
Figure 14: Starting up the user interface
NOTE: Some of the commissioning checks are functional and will require physically starting pumps, valves. etc. rather than inputting information on the UI only.
NOTE: The model no. displayed on the information screen will be 8, 12 or 16 depending on your heat pump model. The serial number displayed will be specic to your heat pump.
CAUTION: Access to functions by unatuhorised personnel negates warranty and may cause damage to the system.
Page 31
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
31
When you enter the installer menu, select the Language Selection option, which will bring you to the Start
Guide screen. Selecting UK will bring you back to the installer menu, which will now display
Commissioning as an option.
Figure 15: Installer and commissioning menu options (when complete)
4.4 Commissioning
Select Commissioning to begin and follow the instructions on the system controller.
The commissioning routine will take you through a number of checks and tests to complete the
installation.
When you nish using each submenu in the commissioning process, selecting Next will take you back to
the main commissioning menu, where a new submenu will be available.
4.4.1 Starting the heat pump in cold weather
When carrying out a commissioning and setting a heat pump to work in conditions where defrosting is
required (≤12°C) and/or the space heating return temperature is ≤18°C, start by heating the buffer tank.
There is not currently a software function to close down the heating circuits, so to do this the rest of the
heating circuit must be closed down manually to allow the buffer tank to heat up (well above 25°C).
Once this temperature has been achieved, individual heating circuits (i.e. zones) can be opened gradually.
During this procedure, DO NOT:
• Allow excess volumes of cold water to return from the heating circuit
• Allow the heat pump return temperature to drop below 18°C
• Bivalent Mode (Alternative back-up heat sources)
• If the heat pump cannot meet the heating load (if it is undersized for extreme conditions), the system
must call on an alternative, back-up heat source. This bivalence feature is automatically triggered by
the controller and allows a backup heater to help the heat pump in reaching its set point.
4.4.2 General / Schematic
Accessing General/Schematic menu allows you to set the date and time, and the level of access allowed.
It is recommended that the Standard user access level is selected for most installations.
Page 32
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
32
Selecting Next will bring you to the Schematic menu, as shown in gure 16.
The schematic number refers to one of the plumbing schematics described in
the Appendices section.
Please ensure that your plumbing reects the diagram set up to ensure correct
operation. The schematic coding is explained below.
Numbers that are shaded grey do not change. These are determined by the type
of device being installed.
Numbers not shaded are determined by the type of installation being used.
Figure 16: Schematics
Table 3: Explanation of digits of schematic codes
The example schematics 1 and 2 (appendix) would
therefore both use the schematic code 10220290, as
they are both;
mono-energy systems
using an immersion heater
two zones
space heating and DHW functions
The difference between examples 1 and 2 is that
example 1 shows an example of a system requiring an
open by-pass while example 2 requires the installation
of a spring by-pass.
Table 4: Schematic codes information
1 0 0 0
3rd Digit
2: mono-energy (heat pump + electric back-up)
3: bivalent (heat pump with boiler as back-up)
4th Digit
0: no DHW function
2: using immersion heater (for top-ups above the
maximum achievable temperature of the heat
pump)
6th Digit
number of zones (up to 4 zones with UI and
temperature probe instead of thermostat)
7th Digit
1: space heating only
9: space heating + DHW
No. on UI Code Appendix No.
1 10200110 6.5 2 10200210 6.5 3 10200310 6.5 4 10200410 6.5 5 10220190 6.6 6 10220290 6.6 7 10220390 6.6 8 10220490 6.6
9 10300110 6.7 10 10300210 6.7 11 10300310 6.7 12 10300410 6.7 13 10310190 6.8 14 10310290 6.8 15 10310390 6.8 16 10310490 6.8
Page 33
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
33
4.4.3 Waterside Check
The ‘Waterside Check’ menu allows you to select whether temperature control is based on the ow or
return temperature. This will apply to heating curves, as discussed in section 4.4.12.
It is generally always recommended to set the temperature control based on the return temperature
(the default selection on the UI), unless it is absolutely necessary to use ow temperature instead for a
particular set up.
CAUTION: Flow control may lead to unnecessary stopping and starting of the heat pump.
Selecting Next will bring you to the waterside checks menu (gure 17).
A number of waterside checks must be carried out as part of commissioning, and must be ticked as
completed. In the Waterside check menu:
• The system must be ushed.
• The strainer must be tted to the return pipe and checked to ensure that it is
clean.
• The system must be pressurized (you must enter the system pressure).
• The system must be fully bled.
• The expansion vessel must be tted
• Membrane pressure of the expansion vessel must be checked and adjusted
Figure 17: Waterside Check
When checks are completed and ‘Next’ is selected, the type of temperature measurement devices to be
used in each heating zone must also be selected by scrolling across and pressing conrm. The following
options are available;
User Interface (usually in zone 1 – heating system controller)
Temperature probe (option for temperature probe 1 to 3, for additional
zones).
Mechanical thermostat (option for mechanical stat 1 to 3, for additional
zones).
Using a mechanical stat limits the level of heating control on the zone from
the UI. Heating in zones using temperature probes can be fully controlled using
the UI. Selecting ‘Next’ will bring you to the ‘Temperature check’ menu.
Figure 18: Temperature device selection
NOTE: If any changes must be made to the commissioning conguration (e.g. selecting a different probe), it is strongly advised that a factory reset is performed and that the heat pump is recommissioned entirely. Changing individual settings during the commissioning process may cause commands to be ignored or cause the heat pump to stop working correctly.
Page 34
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
34
NOTE: If you leave the commissioning menu before you successfully complete commissioning, all previous information entered will be saved and completed menus will be highlighted in green. You can then return at a later stage to complete the process.
4.4.4 Temperature Check
This screen displays the temperatures currently being read by all temperature
probes. It is the duty of the installer to ensure that all sensors are installed and
working correctly.
CAUTION: The boxes on this menu should not be ticked unless all displayed temperatures have been conrmed to be within an acceptable and expected range.
Figure 19: Temperature check
4.4.5 Electrical connections
This menu provides a list of electrical connections that should be made prior
to commissioning for space heating. The list is based on the schematic zone
diagram selected and also the type of temperature devices that will be used in
each zone.
Once you have conrmed all checks and select Next, you will return to the
commissioning menu where you can now access the ‘Water ow check’ menu.
Figure 20: Electrical connections
4.4.6 Water Flow Check
Select ‘Run Test’ to start the circulation pump. Ensure that all valves are
open to allow ow. The circulation pump will be tested rst by running for 30
seconds. When the timer reaches zero, the pump will continue to run until
ow is conrmed, which allows time for the installer to check that the pump is
working.
Figure 21: Pump check
Once you are condent that the pump is on and that there is water ow, select Continue to conrm that
the pump is working correctly. Do not conrm that the pump is working in this menu unless you have
physically checked it, as the UI requires your input and does not detect this automatically.
Page 35
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
35
Once this is successful, the compressor will run for 5 minutes. As the test runs,
the screen will give you information on the status of the heat pump and the time
remaining on the test.
If you do not have ow or if there is a problem, you can stop the test. If you
stop the test, there is a 5 minute delay before you can attempt to run the test
again. It is not possible to bypass the test, as good water ow is critical to the
operation of the heat pump.
Figure 22: Compressor test
If there is no ow at all, a high pressure fault will appear on the UI screen and the commissioning will be
aborted. Once the test is completed, you will see one of three messages:
1. No ow detected
2. Flow too low
3. Flow detected
If you see message 1 or 2, this might be an indication of an air-lock, dirty strainer, ow restriction or pump
too small for the required pipework. Please check for these issues and if present, rectify to ensure that
there is sufcient ow then repeat the test. There will be a time delay before you can restart the test.
When you seea screen with the pump highlighted in green, ow has been detected and the compressor
‘ow check’ test is complete. You will receive the status ‘Waterside is OK’ when the waterside checks are
completed. Selecting Next brings you to the Electrical Connections menu.
Figure 23: Good ow detected and water side OK conrmation screens
If carrying out start up in cold weather, commission the heat pump heating only the buffer. Once it reaches
the required temperature open each zone slowly and in series, especially for under oor heating. If you
have selected Schematic 1 or 3 (Space heating only or Bivalent space heating), move now to section
4.4.12 Heating Curves to complete the commissioning process.
Page 36
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
36
CAUTION: For safety reasons, if the heat pump pressure exceeds 38 bar/temperature exceeds 60°C, the commissioning will be aborted. Under these conditions, measures should be taken to allow the temperature to drop below 60°C, i.e. a zone should be opened.
4.4.7 DHW set-up
Before commissioning the DHW, a number of checks must be carried out, as
shown in gure 24. When you have ticked each box to conrm each DHW
check, Next will bring you back to the installer menu, where you can now select
Electrical Connections (DHW).
Figure 24: DHW set-up
NOTE: It is possible to use space heating without completing the DHW setup. This can be done by selecting ‘N’ on the DHW setup screen where it asks if the cylinder is connected (see gure 24).
This may be necessary where the DHW is not yet connected or where the cylinder has not yet been lled. When the cylinder is ready, it will be necessary to return to this step of the commissioning and select ‘Y’ instead for “Cylinder Connected?” to set up domestic hot water.
4.4.8 Electrical connections (DHW)
This menu provides a list of electrical connections that should be made prior to
commissioning the domestic hot water cylinder. You must check and conrm all
connections in order to make the DHW Test available in the installer menu.
The numbers listed on the LHS of the screen refer to the connections which are
labelled in the wiring diagrams included in this manual.
Figure 25: DHW electrical
connections
4.4.9 DHW Test
Before you run the DHW test, which consists of heating up the cylinder to maximum temperature from
the heat pump, you will be asked to check that the valve (gure 27) is in the DHW position (A position), as
shown on the screen in gure 26. Check that the red actuator marker changes to the correct position (the
default position is B).
NOTE: If the 3-port valve head is removed and the valve moved by hand, the valve must be power cycled (switched off and on again) in order to ensure normal operation.
Page 37
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
37
Figure 26: Valve check
Figure 27: Valve positions
When you have completed the valve check and select Next, you will see the
DHW test screen, which informs that the test can take up to 90 minutes (based
on a 300L cylinder). Selecting ‘Run test’ begins the DHW cycle and shows you
the time remaining (see gure 28).
The DHW test is important for non A-class cylinders to ensure that the cylinder
is compatible with the heat pump. If the coil in the cylinder is too small, the
maximum achievable temperature might be too low for comfort (e.g. < 40°C)
Figure 28: DHW Test
For system with A-class cylinders, the “Finish” button (gure 29) can be used before 60°C temperature has
been reached, as the compatibility doesn’t have to be proven.
Once the DWH cylinder is showing signs of being heated up then the Finish function allows to shorten the
DHW test without having to wait until temperature achieves 60°C.
This Finish function should be used in cold humid conditions to avoid defrost issues (defrost is currently
not enabled during DHW test).
It is recommended to pre-heated the cylinder rst by using normal function and then do a DHW test to
top-up the cylinder. Please refer to technical bulletin for detailed procedure.
NOTE: During the DHW test, the defrost function will be disabled. If the coil starts frosting due to external conditions, it is possible to postpone the test by selecting Finish while the test is still running. Even if this test is postponed, the DHW function may be used.
Page 38
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
38
NOTE: Selecting ‘Stop test’ will cancel the test completely. If the DHW test has been cancelled rather than postponed, the information regarding the immersion displayed on the set temperature menu for DHW will not be correct (the immersion will not be used until the maximum temperature achievable by the heat pump has been reached).
Figure 29: DHW test
nish function
Figure 30: DHW test fail and DHW test completed
If the test fails, you will see the screen shown on the left in gure 30, which provides information on why
the test failed, and advice on checks to carry out.
If the test is complete and has been successful, you will see the screen shown on the right in gure 30,
which shows the maximum temperature that the cylinder can achieve.
4.4.10 Disinfection (thermal)
Thermal disinfection is a function which keeps the level of legionella bacteria
in the cylinder under acceptable levels. This is carried out by heating the hot
water in the cylinder to a high temperature for a minimum set time.
The temperature and frequency of the disinfection cycle can be adjusted in this
menu.
Figure 31: Disinfection setup
If the temperature is set to above what the heat pump can achieve, text on the screen will appear which
noties that the immersion heater will be used at the end of the cycle to top up to the required disinfection
temperature.
39
39
Page 39
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
39
4.4.11 Weather compensation
The biggest factor in dening the heat demand required for a building is typically the weather. Which
affects the required heat load for a building. Weather compensation works by adjusting the set point
temperature of the heating system to reect changes in the outside (external) temperature, allowing the
heat pump to operate more efciently.
Weather compensation is determined by the heat curve settings for the system. The pre-dened heating
curves should only be modied by an installer to best match the heat emitters used.
4.4.12 Heating curves
Each zone is associated to a pre-set heat curve. Selecting the zone and pressing Next will allow you to
assign a pre-set curve for typical heat emitters.
The four pre-set heating curves are shown the table below.
Each curve can be reviewed and modied to meet the requirements of the heating system by selecting
Edit.
This will bring you to a default heating curve for the selected emitter. Selecting Next will select the default.
The pre-dened curves have recommended temperature ranges for each heat emitter;
Table 5: Heating Curve Parameters
The values that generate the heating curve graph can be changed, by scrolling through the temperature
value to adjust and setting it.
This is validated using the Set button when complete (see gure 32).
• The green line on the right indicates the maximum outdoor temperature at
which space heating stops running (DHW is still adjusted independently).
• The yellow line on the left indicates the minimum outdoor temperature at
which the bivalent heating system starts working and may need to be adjusted
depending on the location/property.
• The red line indicates the temperature that the water will be heated to, based
on the outdoor temperatures.
• The Def option will reset the pre-dened values. Nxt will save entered values.
Figure 32: SmartRad
Heating Curve
Heat Emitter Type Max. Water Temp. At Low External Temp. Min. Water at High External Temp.
SmartRad 48°C -10°C 35°C 10°C
Underoor Heating 30°C -10°C 25°C 12°C
Standard Radiator 55°C -10°C 40°C 15°C
Custom (at line) 55°C -15°C 55°C 15°C
Page 40
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
40
NOTE: If the heat pump is in heating “ON” mode and the maximum outside temperature is reached, the heat pump will revert to and maintain the set back temperature until the heating is turned off and on again. To prevent this, it is recommended to set your summer temperature (see heat curves section
4.4.12), at a higher value (the default outside ambient setting is 18°C).
4.4.13 Comfort level
For end-users, the preferred method of modifying the heating system comfort level is by using the comfort
level function rather than modifying the heat curve. Here, it is possible to raise or lower the water input
temperature within a range of 9K (-3 to +6) by accessing the comfort level.
For more information please see the A-Class User Manual
4.4.14 Setup complete
NOTE: To complete commissioning and allow the heat pump to operate, you must select the ‘Setup complete’ submenu in the installer menu, as shown in gure 33. if you do not see this screen, commissioning has not been successful and the heat pump will not operate correctly.
Once all of these steps have been carried out successfully, you will see the
screen shown in gure 33.
Figure 33: Setup complete
Selecting Auto will activate all settings, where as selecting Off will enable the heat pump only to carry out
frost protection (i.e. no heating is required but the heat pump is protected from freezing conditions).
The default setting for the heat pump is Off. To turn on the heat pump, you must return to the home screen
to access the user menu.
For further information on end user controller instructions please see A-Class Air Source Heat Pump User
Guide supplied in the hydraulics pack.
4.5 Additional Installer Menu Options
Once the commissioning process has been completed, additional menus will be available to the installer,
as outlined in this section. These options must be accessed through the service menu.
4.5.1 Service menu
The service menu can be accessed, in a similar manner to the installation menu, by inputting the installer
menu code (22) and then using the ’Login’ access code 998. Access to this menu may be required for fault
nding or servicing.
4.5.2 Message log
The message log menu provides a list of all errors that have taken place, including the date and time when
they occurred. Selecting an individual error code will provide more information on the type of error that
occurred if an SD card is present. Active error messages will show a ticked box.
Page 41
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
41
Figure 34 shows an example of the messages shown in the message list menu.
When a new error occurs, it will appear at the top of the list.
Up to 20 errors can be shown on the list at once, then, if another error occurs, the
oldest error will be pushed off the list to make room for the new error. If the same
error message is being displayed more than once, it may be necessary to check
back through some of the older error messages in order to nd the cause of the
problem.
Figure 34: Message log
NOTE: If a major fault occurs many times, the compressor will go into lock-out mode to prevent any further damage to the heat pump. In order to resolve this, the power to the compressor will have to be turned off for at least 2 minutes and turned on again.
4.5.3 Output Tests
The output tests menu allows you to turn ON/OFF tests on individual
components of the system, as shown in gure 35, and can be accessed once
Electrical Connections (Space Heating) are conrmed.
The relays which control the immersion and backup heater/buffer use
an electric interlocking system, and therefore R7 and R8 must be used
together in order for the backup heater to function. Testing these relays
individually will not reflect this.
Figure 35: Output tests
4.5.4 Defrost
Before running a manual defrost cycle you must ensure the buffer has been isolated from the heating, as
stated by the message on the UI. Selecting ‘Start Defrost’ begins the defrost cycle. The defrost screen will
state the time remaining in the defrost cycle.
A heating water return temperature of 18°C is required for proper defrosting of the evaporator.
4.5.5 Operating data
The operating data menu provides a list of all the system parameters, such as all temperatures, including
each zone set and actual temperatures, ow rate, and heat pump status. If an SD card is present, this data
will be recorded to every message listed.
4.5.6 History
The History menu shows the temporary and permanent run time history of the system. These values
can be reset in order to record run times over a certain time period. Selecting ‘Next’ brings you to the
permanent run time history which cannot be reset unless a software update is installed.
Page 42
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
42
5. System Health Check / Maintenance
NOTE: These are checks that should be carried out regularly to ensure that your Dimplex product performs at its best.
5.1 Heat pump:
• Is the fan grille clear from debris? - Visual check
• Is the tray clear from debris and water owing freely? - Visual check
• Is the condensate drain clear from debris?
• Is the evaporator coil clean and free from damage? E.g. attened ns
• Are all of the outer panels secure?
5.2 Electrical:
• Is the power cable rmly xed?
• Is the earth wire connection secure?
• Is the supply voltage correct?
5.3 Hydraulics:
• Is the system correctly pressurized?
• Are there any water leaks in the system? Is the required pressure holding?
• Is the strainer on the return pipe clear of debris?
See section 4.1.3 for details on isolating and cleaning the strainer.
5.4 Indoor settings:
• Are the set temperatures and heating times suitable for the occupants?
• Is the building warm enough for the occupants or does the heating curve need to be adjusted?
NOTE: It is recommended that the strainer is checked and cleaned 24 hours after commissioning, and each time the system is modied or has service work carried out thereafter.
Page 43
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
43
6. Appendices
6.1 Technical Specications
6.2 Refrigeration Cycle diagram
6.3 Schematics - Example 1
6.4 Schematics - Example 2
6.5 Schematics 1, 2, 3 & 4 : Space Heating Only
6.6 Schematics 5, 6, 7 & 8 : Zone Space Heating & Domestic Hot Water
6.7 Schematics 9, 10, 11 & 12 : Bivalent Space Heating
6.8 Schematics 13, 14, 15 & 16 : Bivalent Zone Space Heating & Domestic Hot Water
6.9 Wiring Centre Electrical Connections - with A-Class Cylinder
6.10 Jumper Information for Alternative Wiring Conguration
6.11 Controller Cable Connections
6.12 Installer Menu Flow Chart
6.13 Installer Hand-Over Form
6.14 Certicate of Conformity
Page 44
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
44
6.1 Technical Specications
1
According to EN 12102.
2
Fan is variable speed, rated input relates to nominal input power.
T
ECHNICAL SPECIFICATIONS
1 T
YPEAND ORDER CODE U NITS A8M A12M A16M
2 DESIGN
2.1 Degree of protection according to EN 60529 for compact unit or heating element
IP 24
2.2 Installation Location Outside
3 PERFORMANCE DATA
3.1 Heating Water Operating Temperature Range (min 56/52 )xam /
Outside Air Operating Temperature Range (min / max) 03/02-
3.2 Heat Output / COP
Heating Water Temperature Difference @ Standard Rating Condition
These figures characterise the size and performance of the system according to EN 14511. Abbreviations have the following meaning, e.g. A7 W35: Outside temperature 7°C and heating water supply temperature 35°C .
@ A7W35 kW/--- 6.30 / 4.42
12.30 / 4.72 12.30 / 4.72
@ A7W55 kW/--- 6.2 / 3.1 12.5 / 3.2 12.5 / 3.2
@ A7W65 kW/--- 6.3 / 2.7 12.4 / 2.6 12.4 / 2.6
@A-2W35 kW/--- 6.7 / 2.9 12 / 3.3 15.5 / 3.2
@A-2W55 kW/--- 7.1 / 2.1 12.0 / 2.5 15.6 / 2.4
@ A-7W35 kW/--- 7.0 / 2.9 12.0 / 3.0 13.2 / 3.0
@ A-7W55 kW/--- 7.1 / 2.1 12.0 / 2.2 15.3 / 2.2
3.3 Sound Power Level
1
dB(A) 63 63.5 63.5
3.4 Sound Pressure Level @ 10m (Heat Pump positioned against wall)
dB(A) 41.5 38.5 38.5
3.5 Heating Water Flow Rate @ A7W35, nominal / minimum m³/h 1.15 / 0.85 2.1 / 1.2 2.1 / 1.2
3.6 Condenser Pressure Drop @ nominal flow rate (A7W35) kPa 3 4 4
3.7 Air Flow @ A7W35 m³/h 2600 3700 3700
3.8 Refrigerant; total filling weight Type/kg R410A / 1.75 R410A / 2.0 R410A /
2.0
3.9 Water Capacity of Stainless Steel Heat Exchanger litre 0.85 1 1
3.10 Polyol Ester Oil in Compressor 81.1 ertil
4 DIMENSIONS, CONNECTIONS & WEIGHT
4.1 Device Dimensions Without Connections H x W x L (mm) 1260 x 932 x 401 1571 X 932 X 401
4.2 Physical Volume 95.0 5.0 ³m
xe ”1 hcni metsyS gnitaeH ot snoitcennoC eciveD 3.4 t. thread
4.4 Weight of the Transportable Unit (Excluding Pac 031 011 gk )gnigak
5 ELECTRICAL CONNECTIONS (HEAT PUMP)
1 / V032 - ycneuqerF / esahP / egatloV lanimoN 1.5 ph / 50 Hz 230V / 1ph / 50 Hz
5.3 Nominal Power Consumption / Nominal Current @ A7W35
kW/A 1.4 / 6.3 2.6 / 11
5.4 Maximum Power Consumption / Maximum Current @ A-2W55
kW/A 4 / 16 6.9 / 30 8.1 / 35
5.5 Maximum Starting Current - Inverter Ramp Up
A5.2 tnerruC gnitratS laudarG A
5.6 Power Factor A7W35 / (cos )
-
0.94 0.95 0.95
5.7 Power Input of Integral Fan @ A7W35
2
06 06 05 W
6 OTHER DESIGN CHARACTERISTICS
6.1 Defrosting Mode / Type Automatic / Reverse Cycle
6.3 Device Freeze Protection Yes : Heating Water in Device Protected Against Freezing by Software
5.2 Fuse Protection 04 C 02 C
Page 45
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
45
6.2 Refrigeration cycle
PTH
PTL
FLOW
RETURN
essor
eceiver
e
essure transducer
essure switch
essure transducer
essure transducer
1. Coil temp
2. External air temp
3. Flow temp
4. Retur
n temp
5. Compressor suction temp
6. V
apor injection temp
7. Liquid line temp
1
2
3
4
5
678
9
10
12
14
9
7
14
16
15
13
Ø10
Ø18
Ø12
Ø12
Ø18
Ø12
Ø10
REFRIGERANT CYCLE
EVI
11
T3
T4
T1
T2
T5
T6
T7
Direction
of air ow
Page 46
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
46
A1
A1
A1
A2
A2
10A RELAY
10A RELAY
20A RELAY
20A
RELAY 4A fuse 4A fuse 2A fuse
A2
NTC-Zone4
NTC-Zone3
NTC-Zone2
NTC-Zone1
NTC-DHW
DI 01
DI 03
DI 04
DI 05
N
N
N
E
E
E
DI 02
E
E
N
N
B' A' Common B A 0Volt Comm +12V
+230V Comm
+230V Comm
Relay-8 Relay-7 Relay-6
Relay-5 Relay-4 Relay-3 Relay-2 Relay-1
EARTH
NEUTRAL LIVE
MAINS
POWER
Modbus
Status
MODBUS
SD
System
Status
Refer to Appendices for
detailed wiring of Wiring
centre
Water Module
Mains Supply:
Single Phase
230-240V
50Hz
Heat Pump Mains Supply:
Single Phase
230-240V
50Hz
DHW Immersion
DHW NTC
Back Up Heater
Alternatives:
- NTC10
- Mechanical Thermostat
if UI Controller NOT used
[
]
Zone 1
Room Thermostat
Max. 1 Meter
Isolation Switch*
6mm²
6mm²
6mm²
16Amp
Isolation
Switch
ENL
LNE
*Isolation switch to suit heat pump model: 20Amp for
8kW heat pumps or 40 Amp for 12-16kW.
Optional
Zone
Valve**
** Additional relay required if pump is controlled by
water module
T
Logic
T
Gate valve for flow adjustment on open
by-pass
If multiple heat emitter circuits are installed, operating
at diff
erent flow and return temperatures (such as
under floor heating and standard radiators), a mixing
valve must be used on low temperature circuits to
prevent high temperature water from entering the
under floor heating manifold.
See
Note
Note
NOTE: If ANY of the zones are using an externally
controlled circulating pump, the open by-pass must
be fitted.
NOTE: Fill & Flush connections are not supplied
by Dimplex and must be sourced separately.
T
T
Normally Open
Example 1: Schematic for zones with circulating pump and open by-pass
ZONE 1: UFH
Mains Cold Feed
Expansion Vessel
Depending on
system volume
UI Controller
Heat Pump
to Heating
A
B
AB
Isolating Valve
Isolating Valve with Filter & NRV
Expansion Vessel
Safety Valve Combination
Motorised 3-Way Valve
Immersion heater
Air Vent
Drain Off Valve
Pump
Heat Load
Room Thermostat
Drain
Flow
Return Flow
Electrical Connections
3-Way Mixing Valve
Fill & Flush connections
ZONE 2: Radiators
Volt-free contact on UFH
electronic / logic switch;
To connect to mechanical
thermostat input on the
water module
NTC10 or
mechanical stat.
BUFFER
Drain to Soak Away
SYMBOL
HYDRAULIC SYMBOL
6.3 Schematics - Example 1
Page 47
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
47
6.4 Schematics - Example 2
A1
A1
A1
A2
A2
10A RELAY
10A RELAY
20A RELAY
20A
RELAY 4A fuse 4A fuse 2A fuse
A2
NTC-Zone4
NTC-Zone3
NTC-Zone2
NTC-Zone1
NTC-DHW
DI 01
DI 03
DI 04
DI 05
N
N
N
E
E
E
DI 02
E
E
N
N
B' A' Common B A 0Volt Comm +12V
+230V Comm
+230V Comm
Relay-8 Relay-7 Relay-6
Relay-5 Relay-4 Relay-3 Relay-2 Relay-1
EARTH NEUTRAL
LIVE
MAINS
POWER
Modbus
Status
MODBUS
SD
System
Status
Refer to Appendices for
detailed wiring of Wiring
centre
Water Module Mains
Supply:
Single Phase
230-240V
50Hz
Heat Pump
Mains Supply:
Single Phase
230-240V
50Hz
DHW Immersion
DHW NTC
Back Up Heater
Alternatives:
- NTC10
- Mechanical Thermostat
if UI Controller NOT used
[
]
Max. 1 Meter
Isolation Switch*
6mm
6mm
6mm
16Amp
Isolation
Switch
ENL
LNE
*Isolation switch may be 20 Amp for 8kW heat pumps or 40
Amp for 12-16kW heat pumps.
Zone Valve
NOTE: Please ensure that the heat pump circulation
pump is correctly sized for the installation, e.g. minimum
ow is maintained through heat pump at all times
Zone Valve
Zone 1
Room Thermostat
T
NOTE: Fill & Flush connections are not supplied
by Dimplex and must be sourced separately.
T
T
Normally Open
Example 2: Schematic for zones without cir
culating pumps and with a spring-loaded by-pass tted
ZONE 1: Radiators or SmartRads
Mains Cold Feed
Expansion Vessel
Depending on
system volume
Heat Pump
to Heating
A
B
AB
Fill & Flush connections
Spring-loaded by-pass
ZONE 2: Radiators
UI Controller
NTC10 or
mechanical stat.
Isolating Valve
Isolating Valve with Filter & NRV
Expansion Vessel
Safety Valve Combination
Motorised 3-Way Valve
Immersion heater
Air Vent
Drain Off Valve
Pump
Heat Load
Room Thermostat
Drain
Flow
Return Flow
Electrical Connections
3-Way Mixing Valve
Spring-Loaded By-Pass Valve
BUFFER
Drain to Soak Away
SYMBOL
HYDRAULIC SYMBOL
Page 48
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
48
6.5 Schematics 1, 2, 3 & 4 : Space Heating Only
Mains Supply:
Single Phase
230-240V
50Hz
A1
A1
A1
A2
A2
10A RELAY
10A RELAY
20A RELAY
20A
RELAY 4A fuse 4A fuse 2A fuse
A2
NTC-Zone4
NTC-Zone3
NTC-Zone2
NTC-Zone1
NTC-DHW
DI 01
DI 03
DI 04
DI 05
N
N
N
E
E
E
DI 02
E
E
N
N
B' A' Common B A 0Volt Comm +12V
+230V Comm
+230V Comm
Relay-8 Relay-7 Relay-6
Relay-5 Relay-4 Relay-3 Relay-2 Relay-1
EARTH
NEUTRAL LIVE
MAINS
POWER
Modbus
Status
MODBUS
SD
System
Status
Mains Supply:
Single Phase
230-240V
50Hz
Max. 1 Meter
Isolation Switch*
6mm²
6mm²
6mm²
]
Back Up
Heater
Refer to Appendices for detailed wiring of Wiring centre
Alternatives:
- NTC10
- Mechanical Thermostat
if UI Controller NOT used
[
Zone 1
Room Thermostat
User Interface or
NTC10 or
Mechanical T'stat
User Interface or
NTC10 or
Mechanical T'stat
User Interface or
NTC10 or
Mechanical T'stat
20Amp
Isolation Switch
ENL
LNE
See example 1
or 2 for by-pass
options
For details of different types
of zone set up (with / without
circulating pump), see
example schematics
*Isolation switch may be 20Amp for 8kW heat pumps or
40 Amp for 12-16kW heat pumps.
NOTE: Fill & Flush connections are not supplied
by Dimplex and must be sourced separately.
UI Controller
10200110
10200210
10200310
10200410
SINGLE ZONE
TWO ZONES
THREE ZONES
FOUR ZONES
Heat Pump
BUFFER
Expansion Vessel
Depending on
system volume
ZONE 2
ZONE 3
ZONE 4
ZONE 1
By-Pass
123
4
Drain to Soak Away
SCHEMATIC
DESCRIPTION
RELAY CONNECTIONS
RELAY 3 FOR ZONE 1
RELAY 4 FOR ZONE 2
RELAY 5 FOR ZONE 3
RELAY 6 FOR ZONE 4
ON WIRING CENTRE
Fill & Flush Connections
NO. ON UI
Isolating Valve
Isolating Valve with Filter & NRV
Expansion Vessel
Safety Valve Combination
Immersion heater
Air Vent
Drain Off Valve
Pump
Room Thermostat
Drain
Flow
Return Flow
Electrical Connections
Page 49
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
49
6.6 Schematics 5, 6, 7, 8 : Zone space heating + DHW
A1
A1
A1
A2
A2
10A RELAY
10A RELAY
20A RELAY
20A RELAY 4A fuse 4A fuse 2A fuse
A2
NTC-Zone4
NTC-Zone3
NTC-Zone2
NTC-Zone1
NTC-DHW
DI 01
DI 03
DI 04
DI 05
N
N
N
E
E
E
DI 02
E
E
N
N
B' A' Common B A 0Volt Comm +12V
+230V Comm
+230V Comm
Relay-8 Relay-7 Relay-6
Relay-5 Relay-4 Relay-3 Relay-2 Relay-1
EARTH
NEUTRAL LIVE
MAINS
POWER
Modbus
Status
MODBUS
SD
System
Status
Refer to
Appendices for
detailed wiring of
Wiring centre
Mains Supply:
Single Phase
230-240V
50Hz
Mains Supply:
Single Phase
230-240V
50Hz
DHW Immersion
DHW NTC
Back Up Heater
Alternatives:
- NTC10
- Mechanical Thermostat
if UI Controller NOT used
[
]
Zone 1
Room Thermostat
User Interface or
NTC10 or
Mechanical T'stat
User Interface or
NTC10 or
Mechanical T'stat
User Interface or
NTC10 or
Mechanical T'stat
Max. 1 Meter
Isolation Switch*
6mm²
6mm²
6mm²
ENL
LNE
For details of different types
of zone set up (with / without
circulating pump), see
example schematics
See example 1 or 2 for by-pass options
*Isolation switch may be 20Amp for 8kW heat pumps or 40
Amp for 12-16kW heat pumps.
NOTE: Fill & Flush connections are not supplied
by Dimplex and must be sourced separately.
Signal
20Amp
Isolation
Switc
h
T
T
Normally Open
ZONE 2 ZONE 3
ZONE 4
ZONE 1
10220190
10220290
10220390
10220490
SINGLE ZONE
TWO ZONES
THREE ZONES
FOUR ZONES
Mains Cold Feed
Expansion Vessel
Depending on
system volume
UI Controller
Heat Pump
to Heating
A
B
AB
By-Pass
567
8
BUFFER
SCHEMATIC
DESCRIPTION
RELAY CONNECTIONS
RELAY 3 FOR ZONE 1
RELAY 4 FOR ZONE 2
RELAY 5 FOR ZONE 3
RELAY 6 FOR ZONE 4
ON WIRING CENTRE
Drain to Soak Away
NO. ON UI
Fill & Flush Connections
Isolating Valve
Isolating Valve with Filter & NRV
Expansion Vessel
Safety Valve Combination
Immersion heater
Air Vent
Drain Off Valve
3 Port Valve
Pump
Room Thermostat
Drain
Flow
Return Flow
Electrical Connections
Page 50
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
50
6.7 Schematics 9, 10, 11, 12 : Bivalent space heating
A1
A1
A1
A2
A2
10A RELAY
10A RELAY
20A RELAY
20A RELAY 4A fuse 4A fuse 2A fuse
A2
NTC-Zone4
NTC-Zone3
NTC-Zone2
NTC-Zone1
NTC-DHW
DI 01
DI 03
DI 04
DI 05
N
N
N
E
E
E
DI 02
E
E
N
N
B' A' Common B A 0Volt Comm +12V
+230V Comm
+230V Comm
Relay-8 Relay-7 Relay-6
Relay-5 Relay-4 Relay-3 Relay-2 Relay-1
EARTH NEUTRAL LIVE
MAINS
POWER
Modbus
Status
MODBUS
SD
System
Status
User Interface or
NTC10 or
Mechanical T'stat
User Interface or
NTC10 or
Mechanical T'stat
User Interface or
NTC10 or
Mechanical T'stat
Max. 1 Meter
Isolation Switch*
6mm²
6mm²
6mm²
Mains Supply:
Single Phase
230-240V
50Hz
Mains Supply:
Single Phase
230-240V
50Hz
Refer to
Appendices for
detailed wiring of
Wiring centre
Alternatives:
- NTC10
- Mechanical Thermostat
if UI Controller NOT used
[
]
Zone 1
Room Thermostat
Back Up
Heater
ENL
LNE
See examples 1 or 2 for
by-pass options
Expansion
Valve
Depending on system volume
For details of different types
of zone set up (with / without
circulating pump), see
example schematics
*Isolation switch may be 20Amp for 8kW heat pumps or 40
Amp for 12-16kW heat pumps.
20Amp
Isolation Switch
NOTE: Fill & Flush connections are not supplied
by Dimplex and must be sourced separately.
Signal
BUFFER
UI Controller
ZONE 2
ZONE 3
ZONE 4
ZONE 1
10300110
10300210
10300310
10300410
SINGLE ZONE
TWO ZONES
THREE ZONES
FOUR ZONES
Boiler
Heat Pump
91011
12
By-Pass
Drain to Soak Away
SCHEMATIC
DESCRIPTION
RELAY CONNECTIONS
RELAY 3 FOR ZONE 1
RELAY 4 FOR ZONE 2
RELAY 5 FOR ZONE 3
RELAY 6 FOR ZONE 4
ON WIRING CENTRE
NO. ON UI
Fill & Flush Connections
Isolating Valve
Isolating Valve with Filter & NRV
Expansion Vessel
Safety Valve Combination
Immersion heater
Air Vent
Drain Off Valve
Non-return Valve
Pump
Room Thermostat
Drain
Flow
Return Flow
Electrical Connections
Page 51
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
51
6.8 Schematics 13, 14, 15, 16 - Bivalent zone space heating + DHW
DHW Immersion
DHW NTC
Zone 1
Room Thermostat
Alternatives:
- NTC10
- Mechanical Thermostat
if UI Controller NOT used
[
]
A1
A1
A1
A2
A2
10A RELAY
10A RELAY
20A RELAY
20A
RELAY 4A fuse 4A fuse 2A fuse
A2
NTC-Zone4
NTC-Zone3
NTC-Zone2
NTC-Zone1
NTC-DHW
DI 01
DI 03
DI 04
DI 05
N
N
N
E
E
E
DI 02
E
E
N
N
B' A' Common B A 0Volt Comm +12V
+230V Comm
+230V Comm
Relay-8 Relay-7 Relay-6
Relay-5 Relay-4 Relay-3 Relay-2 Relay-1
EARTH NEUTRAL
LIVE
MAINS
POWER
Modbus
Status
MODBUS
SD
System
Status
Refer to Appendices for detailed wiring of Wiring centre
Back Up
User Interface or
NTC10 or
Mechanical T'stat
User Interface or
NTC10 or
Mechanical T'stat
User Interface or
NTC10 or
Mechanical T'stat
Max. 1 Meter
40Amp
Isolation Switch
6mm²
6mm²
6mm²
Mains Supply:
Single Phase
230-240V
50Hz
Mains Supply:
Single Phase
230-240V
50Hz
Heater
20Amp
Isolatio
n
Switch
ENL
LNE
See example 1 or 2 for by-pass options
*Isolation switch may be 20Amp
for 8kW heat pumps or 40 Amp for
12-16kW heat pumps.
For details of different types
of zone set up (with / without
circulating pump), see
example schematics
NOTE: Fill & Flush connections are not supplied
by Dimplex and must be sourced separately.
Signal
Expansion Vessel
Depending on
T
Mains Cold Feed
T
Normally Open
Heat Pump
UI Controller
to Heating
Boiler
ZONE 2 ZONE 3
ZONE 4
ZONE 1
system volume
10310190
SINGLE ZONE
TWO ZONES
THREE ZONES
FOUR ZONES
10310290
10310390
10310490
A
B
AB
By-Pass
13
141516
Drain to Soak Away
SCHEMATIC
DESCRIPTION
RELAY CONNECTIONS
RELAY 3 FOR ZONE 1
RELAY 4 FOR ZONE 2
RELAY 5 FOR ZONE 3
RELAY 6 FOR ZONE 4
ON WIRING CENTRE
BUFFER
NO. ON UI
Fill & Flush Connections**
Isolating Valve
Isolating Valve with Filter & NRV
Expansion Vessel
Safety Valve Combination
Immersion heater
Air Vent
Drain Off Valve
Non-return Valve
3 Port Valve
Pump
Room Thermostat
Drain
Flow
Return Flow
Electrical Connections
Page 52
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
52
6.9 Wiring centre electrical congurations - with non A Class cylinder / no cylinder
SH Zone 1 - Valve
DHW Immersion 3kW
NTC-Zone4
NTC-Zone3
NTC-Zone2
NTC-Zone1
NTC-DHW
DI 01
DI 03
DI 04
DI 05
DI 02
B'A'CommonBA
0Volt Comm
+12V
+230V Comm
+230V Comm
Relay-8
Relay-7
Relay-6
Relay-5
Relay-4
Relay-3
Relay-2
Relay-1
EARTH
NEUTRAL
LIVE
MAINS
POWER
Modbus
Status
MODBUS
SD
System
Status
Circulating Pump
N
PE
L
2A fuse
21
24
22
11
14
12
A2 A1
COIL
NC
NO
COM
21
24
22
11
14
12
A
A1
COIL
NC
NO
COM
21
24
22
11
14
12
A2 A1
NC
NO
COM
4A fu
230V ~50-60HZ
4A fuse
4A fuse
230V ~50-60HZ
4000
BELDEN 9842 Modbus In
Factory pre-wired
PEPEPE
NNN
BLACK
BROWN
Circulating Pump
DHW/SH Live
DHW/SH Black
Buffer IMMERSION
DHW IMMERSION
NEUTRAL
EARTH
230V Supply
N
P
L
1
234
5
123
4
5
L
BELDEN 9842 Modbus Out
DI 01 & DI 02
NOT IN USE
OPTIONAL NTC ZONES
SEE CONTROLLER CABLE
CONNECTIONS DIAGRAM
FOR DETAILS
Buffer Immersion 3kW
DHW/SH Valve
WHITE / blue
EARTH SHIELD
WHITE / Orange
BLUE / white
CONNECTIONS
ARE LOCATED INSIDE THE UI CASING
(SEE BELOW)
WHITE / orange
ORANGE / white
BLUE / white
WHITE / blue
EARTH SHIELD
GND
+12V
A
B
S
CONNECTIONS ARE LOCATED INSIDE THE ELECTRICAL BO IN THE HEAT PUMP
N
P
SH Zone 2 - Valve
L
N
P
SH Zone 3 - Valve
L
N
P
S
B
A
0V
230V SUPPL
L
N
P
L
N
P
PWM Control Cable
(not used)
L
N
P
L
L
N
P
L
N
P
ZONE PUMPS IF REUIRED NEED A SUITABLE ETERNAL RELA TO
BE INSTALLED TO ENERGISE THE PUMP
PUMPS CANNOT BE POWERED DIRECTL FROM PCB RELAS (1 - 8 )
A 16A HI-INRUSH RELA NEEDS TO BE USED
NOTE THE PRIMAR PUMP UMP GEO 25-85 180 HAS AN ETRA PWM
CABLE THIS CABLE IS FOR AN ETRA FUNCTION THAT IS NOT CURRENTL
AVAILABLE AND SHOULD BE LEFT ELECTRICALL SAFE
NOTE DIGITAL INPUTS (DI01 - DI05) ARE VOLT
FREE IF AN VOLTAGE (SUCH AS A SWITCH
LIVE 230V) IS CONNECTED IRREPARABLE
DAMAGE WILL BE CAUSED TO THE WIRING
CENTRE
WARNING
SCREENS FROM BOTH COMMUNICATION
(MODBUS) CABLES MUST BE GROUNDED /
EARTHED
SH Zone 4 - Valve
L
N
P
OPTIONAL DIGITAL INPUTS
SEE CONTROLLER CABLE
CONNECTIONS DIAGRAM FOR DETAILS
Page 53
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
53
6.10 Wiring centre electrical congurations - with A Class cylinder
LLLLLLLL
SH Zone 1 - Valve
NTC-Zone4
NTC-Zone3
NTC-Zone2
NTC-Zone1
NTC-DHW
DI 01
DI 03
DI 04
DI 05
DI 02
B'A'CommonBA
0Volt Comm
+12V
+230V Comm
+230V Comm
Relay-8
Relay-7
Relay-6
Relay-5
Relay-4
Relay-3
Relay-2
Relay-1
EARTH
NEUTRAL
LIVE
MAINS
POWER
Modbus
Status
MODBUS
SD
System
Status
Circulating Pump
BELDEN 9842 Modbus In
BLACK
BROWN
NEUTRAL
EARTH
230V Supply
N
P
L
L
ZONE PUMPS, IF REQUIRED, NEED A SUITABLE EXTERNAL
RELAY TO BE INSTALLED TO ENERGISE THE PUMP.
PUMPS CANNOT BE POWERED DIRECTLY FROM PCB RELAYS
(1 - 8 ).
A 16A HI-INRUSH RELAY NEEDS TO BE USED.
BELDEN 9842 Modbus Out
DI 01 & DI 02
NOT IN USE
DHW/SH Valve
WHITE / blue
EARTH SHIELD
WHITE / Orange
BLUE / white
CONNECTIONS ARE LOCATED INSIDE THE UI CASING
(SEE BELOW)
WHITE / orange
ORANGE / white
BLUE / white
WHITE / blue
EARTH SHIELD
GND
+12V
A
B
S
CONNECTIONS ARE LOCATED INSIDE THE ELECTRICAL BOX IN THE HEAT PUMP
N
P
SH Zone 2 - Valve
L
N
P
SH Zone 3 - Valve
L
N
P
S
B
A
0V
230V SUPPLY
L
N
P
L
N
P
PWM Control Cable
(not used)
L
N
P
L
NOTE: DIGITAL INPUTS (DI01 - DI05) ARE
VOLT FREE. IF ANY VOLTAGE (SUCH AS A
SWITCH LIVE 230V) IS CONNECTED,
IRREPARABLE DAMAGE WILL BE CAUSED TO
THE WIRING CENTRE.
NOTE: THE PRIMARY PUMP UMP GEO 25-85 180 HAS AN EXTRA
PWM CABLE. THIS CABLE IS FOR AN EXTRA FUNCTION THAT IS
NOT CURRENTLY AVAILABLE AND SHOULD BE LEFT
ELECTRICALLY SAFE.
DHW/SH Valve
DHW/SH Valve
Circulating Pump
2A Fuse
4A Fuse
4A Fuse
4A Fuse
X1
N Block
(BLUE)
X1
E Block
(GREEN)
WARNING:
SCREENS FROM BOTH COMMUNICATION (MODBUS)
CABLES MUST BE GROUNDED/EARTHED
SH Zone 4 - Valve
L
N
P
OPTIONAL NTC ZONES
SEE CONTROLLER CABLE
CONNECTIONS DIAGRAM FOR
DETAILS
OPTIONAL DIGITAL OUTPUTS
SEE CONTROLLER CABLE
CONNECTIONS DIAGRAM FOR
DETAILS
Page 54
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
54
6.11 Jumper congurations
Master board Jumper OFF
SEC Board Jumper ON
Water Module Jumper OFF
User Interface Jumper ON
NOTE: The diagram above shows the ON/OFF positions of jumpers for the recommended conguration.
NOTE: The alternative wiring conguration is shown below, but should only be used if absolutely
necessary.Wiring centre electrical congurations - with A Class cylinder
Figure 36: Jumper in ON
position on SEC board
Figure 37: Jumper in OFF
position on water module
Figure 38: Jumper in ON position
on user interface (UI)
Start
End
Page 55
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
55
6.12 Controller cable connections
Page 56
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
56
DHW Setup
D HW Tes t
Electrical Connec tio ns (DHW)
Wate rf low Checks
Language Selection
Commissioning
General/Sch ematic
Wate rsid e Checks
Message List
Histo ry
Electrical Connec tio ns
(Space Heating Only)
Operating Data
Input/Outp ut Tests
Disinf ection
Heati ng
Zone Selection
Heati ng Circuit Typ e
Setup Comp lete
ON/Automatic
6.13 Installer menu ow chart
Page 57
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
57
6.14 Installer hand-over form
Installer InformatIon
Name:
Phone No.
Company:
Address:
Email:
MCS No.
InstallatIon InformatIon
Date of Installation / Commissioning:
Heat Pump Model:
Heat Pump Serial No.:
Cylinder Model:
Cylinder Serial No.:
Accessories Installed:
Schematic No. Used in Commissioning:
Temperature Devices Used for Zone Control:
Zone 1:
Zone 2:
Zone 3:
Zone 4:
Heat Emitters Installed:
temperatures recorded at commIssIonIng:
Flow Temperature °C
Return Temperature °C
Outside Temperature °C
Spread K
Flow Rate m3/h
Refrigeration:
High Pressure
Low Pressure
Heat Exchanger
Temp. Refrigeration
Temp. Water
Running Amps
DHW SH
Pressure Temperature
IN (T1) OUT (T2)
Page 58
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
58
EC Declaration of Conformity
GDC Group Limited, Millbrook House, Grange Drive, Hedge End, Southampton, Hants, SO302DF, United Kingdom
Manufacturer: GDC Group,
Greenbank Industrial Estate, Rampart Road, Newry, Co. Down, BT34 2QU
Description: Heat Pump Type: Air – to – Water Model: A16M
Model: A12M Model: A8M
EC Directives:
Low voltage directive 2006/95/EC EMC directive 2004/108/EC Pressure equipment directive 97/23/EC
Applied Standards:
EN 60335-1:2002+A11+A1+A12+corr.+A2:2006; EN60335-1/A13:2008; EN60335-2­40:2003+A11+A12+A1+corr.+A2:2009 EN55014-1:2006; EN55014-2:1997+A1:2001 EN61000-3-2:2006; EN61000-3-3:1995+A1:2001+A2:2005 EN378-1:2008; EN378-2:2008+A1:2009; EN378-3:2008; EN378-4:2008 EN 14511-1:2007; EN14511-2:2007; EN14511-3:2007+EN14511-3:2007/AC:2008; EN14511-4:2007
Conformity assessment procedure according to pressure equipment directive:
Module A
CE mark added:
2013
EC declaration of conformity issued on:
25th September 2014
Ireland, 25.09.14
Issue: 1.03
6.15
Page 59
Millbrook House, Grange Drive, Hedge End, Southampton, SO30 2DF
0844 879 3587
dimplex.co.uk | gdcgroup.co.uk
59
Loading...