Dimplex A12M, A16M Installation Manual

8/60472/0
Issue 1
A12M / A16M: Installation Manual
ii
Overall view
Figure 1 (a): Outer dimensions of heat pump, (b) position of heat pump registration plate and details
(c) Internal components of heat pump
(a)
(b)
(c)
iii
Contents
1 Introduction .......................................................................................... 1
2 Scope of delivery ................................................................................... 1
3 Pre-Installation advice .......................................................................... 5
3.1 Warnings .......................................................................................... 5
3.2 Intended use ..................................................................................... 6
3.3 Legal ................................................................................................ 6
3.4 Heat pump sizing ............................................................................... 6
3.5 Site selection ..................................................................................... 6
3.5.1 Location of heat pump ................................................................... 6
3.5.2 Heat pump placement and fixing ..................................................... 7
3.6 Plumbing –Preparation ........................................................................ 8
3.6.1 Buffer tank ................................................................................... 9
3.7 Electrical connections - Preparation ...................................................... 9
4 Installation .......................................................................................... 10
4.1 Handling and transport ..................................................................... 10
4.2 Plumbing......................................................................................... 10
4.3 Electrical connections ....................................................................... 11
4.4 Opening the heat pump for electrical connections ................................. 15
4.4.1 Heat pump electrical connection .................................................... 16
5 Set to work .......................................................................................... 17
5.1 Location of indoor components .......................................................... 17
5.2 Set to work ..................................................................................... 17
5.3 Opening the UI ................................................................................ 17
5.4 Using the User Interface ................................................................... 18
6 Pre-commissioning .............................................................................. 18
6.1.1 General/Schematic ...................................................................... 19
6.1.2 Message log ............................................................................... 19
6.1.3 Output Tests .............................................................................. 19
6.1.4 Defrost ...................................................................................... 19
6.1.5 Operating data ........................................................................... 19
6.1.6 History ...................................................................................... 19
iv
7 Commissioning .................................................................................... 20
7.1.1 Waterside check.......................................................................... 20
7.1.2 Temperature check ..................................................................... 21
7.1.3 Electrical connections (SH) ........................................................... 21
7.1.4 Water flow check ........................................................................ 21
7.1.5 DHW setup ................................................................................. 22
7.1.6 Electrical connections (DHW) ........................................................ 22
7.1.7 DHW Test................................................................................... 22
7.1.8 Disinfection ................................................................................ 23
7.1.9 Heating curves............................................................................ 23
8 System health checks .......................................................................... 24
9 Troubleshooting, FAQ .......................................................................... 25
9.1 Table of error codes and descriptions .................................................. 25
10 Technical Specifications ................................................................... 24
Appendices:
A Refrigeration cycle................................................................................A
B Schematic zone diagrams......................................................................B
Schematic 1: 10200110 - Space Heating Only .......................................... B
Schematic 2: 10220290 - Zone Space Heating & DHW ............................... C
Schematic 3: 10300110 - Bivalent Space Heating ..................................... D
Schematic 4: 10310290 - Bivalent Zone Space Heating & DHW .................. E
C Wiring centre electrical connections.........................................................F
D Installer controller cable connections...................................................... G
E Installer menu flow chart.......................................................................H
1
1 Introduction
Thank you for choosing a Dimplex Heat Pump. The Dimplex A class heat pump combines outstanding performance to maximise year-round efficiency no matter what the weather conditions. It can also deliver high output and high temperatures even at outside air temperatures of -7. The sophisticated controller makes the system easy to use and there are many more technological innovations including a scroll compressor that uses enhanced vapour injection.
2 Scope of delivery
Please ensure you check the scope of delivery before signing any delivery documentation. Claims for missing or damaged parts after signing for the delivery will not be accepted.
There are 3 options to select from when installing a Dimplex Heat Pump:
Pack 1 - Space heating and Dimplex
A Class Cylinder
To install the heat pump and Dimplex A class cylinder together you must purchase Pack 1 which contains necessary components shown in the tables below. A separate wiring centre is not required as the wiring centre is built into the cylinder. The ACCHYPK Hydraulics pack contains the all of the necessary hydraulic components.
Pack 2 - Space heating and Dimplex
Standard Heat Pump Cylinder
To install the heat pump for space heating and domestic hot water but not using an A class cylinder you must purchase Pack 2 which contains the necessary components shown in the tables below. A separate wiring centre is required to wire the circulation pumps and zone controls since this is not supplied on the cylinder. The ACCHYPK Hydraulics pack contains the all of the necessary hydraulic components.
Pack 3 – Space heating only
To install the heat pump for space heating only, you must purchase Pack 3 which contains the necessary components shown in the tables below. A separate wiring centre is required to wire the circulation pumps and zone controls. The ACSSHYPK Hydraulics pack contains the all of the necessary hydraulic components.
2
PACK 1:
SPACE HEATING AND DIMPLEX A CLASS CYLINDER
Heat pump
A12M / A16M
Hydraulics Kit A which includes:
ACCHYPK
User interface (UI)
049179
Pump - UPM GEO 25-85 180 (70mm cable)
049148
2 x Pump Valve Gate 1"1/2 – 28mm 2 x Washer 30.1x21x2mm
By pass valve (22mm) Spring loaded
050557
3 port diameter valve
050564
Isolation valves - (1) Flow (2) Return with strainer
Flow 062801
Return
062815CR
4 x Blanking plugs for lifting holes
624105
Installation and User manuals
Dimplex DHW Cylinder Kit
Cylinder
Air vent Drain
Safety group DHW side - expansion vessel, hose and bracket, inlet group, tundish
3 x Copper pipes – Pump to buffer/cylinder
Pipe connections to coil, pipe, drain and vent
Pipe connections to pump
3
PACK 2:
SPACE HEATING AND DIMPLEX STANDARD HEAT PUMP
CYLINDER
Heat pump
A12M / A16M
Hydraulics Pack A which includes:
ACCHYPK
User interface (UI)
049179
Pump - UPM GEO 25-85 180 (70mm cable)
049148
2 x Pump Valve Gate 1"1/2 – 28mm 2 x Washer 30.1x21x2mm
Altecnic ERES straight by pass valve (22mm 22mm) Spring loaded
050557
3 port diameter valve
050564
Isolation valves - (1) Flow (2) Return with strainer
Flow 062801
Return
062815CR
4 x Blanking plugs for lifting holes
624105
Installation and User manuals
Wiring centre Kit
Wiring centre module
049162
1 x Temperature probe (NTC10) for DHW
4
PACK 3:
SPACE HEATING ONLY
Heat pump
A12M / A16M
Hydraulics Pack B which includes:
ACSSHYPK
User interface (UI)
049179
Pump - UPM GEO 25-85 180 (70mm cable)
049148
2 x Pump Valve Gate 1"1/2 – 28mm 2 x Washer 30.1x21x2mm
Altecnic ERES straight by pass valve (22mm 22mm) Spring loaded
050557
Isolation valves - (1) Flow (2) Return with strainer
Flow 062801
Return
062815CR
4 x Blanking plugs for lifting holes
624105
Installation and User manuals
Wiring centre Kit
Wiring centre module
049162
1 x Temperature probe (NTC10) for DHW
5
3 Pre-Installation advice
3.1 Warnings
When transporting the heat pump,
ensure that it is not tilted more than 45° (in any direction), for any prolonged period of time.
Do not attempt to lift the heat pump
manually. It weighs 130kg and should only be lifted using the appropriate lifting devices.
Installation and any service work on
the heat pump may only be performed by authorised and qualified installer and after-sales service technicians.
This device is suitable for mains
connection only: 230V, 1P&N, 50Hz, and is not suitable for operation with any electrical generator and any attempt to do so will void warranty.
This device shall be installed in
accordance with national wiring regulations. The digital inputs are volt free, if any voltage, such as a switch live 230V is connected irreparable damage will be caused to the wiring centre. The local wiring regulations should always be followed paying particular attention to mixing of low voltage and extra low voltage cabling.
Before removing the cover of the
heat pump, cylinder or wiring centre, ensure that all electrical circuits are isolated.
Means for disconnection from the
supply mains must be incorporated
in the fixed wiring in accordance with the national wiring regulations.
The heat pump contains refrigerant
at high pressure. Safety measures are in place to avoid system pressure build up:
Stage 1: Pressure transducer
stops compressor
Stage 2: Pressure switch switches
heat pump off.
The installation of a residual current
device (RCD) having a rated residual operating current not exceeding 30mA is advisable.
Additional heating may be required
if heat pump is intended to dry out a new or renovated building, as the initial heat load will be higher than the calculated load.
If the heat pump can be
disconnected from power supply for prolonged periods of time or where power supplies are susceptible to failure, antifreeze must be added to the system.
Never use cleaning agents
containing sand, soda, acid or chloride as these can damage the surfaces/components.
We recommend the installation of a
suitable filtration protection system and a corrosion additive for the heating system to prevent the formation of deposits (e.g. oxide and solids) in the condenser of the heat pump. The return isolation valve provided in the hydraulics pack has a built in strainer for this purpose.
6
Products not installed with the
Dimplex hydraulics packs will not be supported by Dimplex. This includes but is not limited to thermal stores.
During the commissioning of the
domestic hot water cylinder, ensure that the cylinder is full and no water is drawn from the cylinder as this will adversely affect the heat pumps operation.
This appliance can be used by
children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
3.2 Intended use
This device is only intended for domestic use, as specified by the manufacturer. Any other use beyond that intended by the manufacturer is prohibited. This requires the user to abide by the manufacturers product information. Please refrain from tampering with or altering the device.
3.3 Legal
The construction and design of the heat pump complies with all relevant EU directives (see CE declaration of conformity).
When connecting the heat pump to the power supply, the relevant EN and IEC standards are to be adhered to. Any further connection requirements
stipulated by the network operation must also be observed.
When connecting to the heating system all applicable regulations must also be adhered to.
3.4 Heat pump sizing
Ensure that the correct size heat
pump has been selected in accordance with the latest version of MIS3005 (UK only) and with the Dimplex Heat Pump Planning Manual.
If a non A-Class heat pump cylinder
is being used, ensure that it has been accurately sized with the appropriate coil surface area of the cylinder to match the heat pump’s output, flow rate requirements and that all necessary hydraulic connections have been considered in connecting it to the heat pump system.
Ensure that suitable heat emitters
have been sized in accordance with the Heat Emitter Guide (UK only) and selected ensuring a low flow temperature design. To maximise system efficiency it is important to design the system with the lowest flow temperature possible.
3.5 Site selection
3.5.1 Location of heat pump
The heat pump must be installed
outdoors with adequate clearances for ventilation and maintenance as shown in figure 2. It is recommended that the heat pump is installed along the property wall, as shown below.
There must be a minimum distance
of 1000mm in front of the fan to
7
prevent air re-circulation. Positioning the heat pump in a confined space, frost hollow or well will result in reduced heat pump operating efficiency.
The fan should preferably not face
prevailing winds to ensure correct air flow through the evaporator.
Figure 2: Required free space around heat
pump for ventilation and maintenance
Although the heat pump is within
noise and vibration regulations outlined in MCS 007, it is recommended to avoid positioning it close to bedroom windows, as the fan and compressor may be operational at night.
3.5.2 Heat pump placement and fixing
Approximately 2 litres of condensate
water is drained from the system every time a defrost cycle occurs. Therefore, it is essential that the condensate pipe is fed into a drain or soak away to allow for safe disposal of the excess water, away from footpaths or patios.
The condensate pipe must be kept
frost free. Freezing of this pipe due to incorrect installation can result in irreparable damage and void warranty.
Figure 3: Position of fixing holes and condensate drain
8
The condensate pipe should not run
into sewer pipe as fumes may travel into the heat pump and cause corrosion to the evaporator coil.
The heat pump must be fixed onto a
level, stable base that is capable of withstanding the unit’s weight of 130kg, with a minimum of 30mm clearance around all sides of the heat pump (recommended minimum L x W x D = 1000 x 470 x 100mm). It can be secured with M10 anchor bolts, using the fixing holes shown in figure 3.
Ideally the heat pump should be
located close to the property. Positioning of the heat pump at a distance from the property will result in the need for extra insulated pipe, which will lead to extra cost, and result in additional heat losses.
3.6 Plumbing –Preparation
When selecting piping to install with the heat pump please ensure:
The pipe sizes are adequate to allow
correct minimum water flow rate through the heat pump.
Table 1: Maximum length of copper pipe
Nominal
Minimum
@ 2050 l/h
@ 1200 l/h
18 kPA
60 kPa
Diameter
(mm)
Max length
(m)
Max length
(m)
15 1 10
22
10
80
28
30
265
32
60
525
The pipe lengths given in table 1
include the straight length of the piping and all elbows. The equivalent straight length (L) of each elbow is found by multiplying the outer diameter of the pipe (D) by 30:
External pipes should be adequately
insulated with vapour resistant insulation and protected against damage to prevent excessive heat losses. All joints should be suitably sealed and exposed pipework must be avoided.
Existing hot water systems should
be flushed prior to connection to the heat pump to remove all contaminants and impurities, in accordance with the latest version of MIS 3005.
Make the water flow and return
pipes positioned correctly for connection to the heat pump as shown on the label in figure 4 and on the back of the heat pump.
Isolation valves, supplied in the
Dimplex heat pump hydraulics pack, allow the strainer to be removed and cleaned without having to drain the system (non-return valve and ball valve with strainer). Installation of these valves is discussed in more detail section 5.2.
If heat emitters consist of underfloor
heating and higher temperature heat emitters, a mixing valve must be used to prevent high temperature water entering the underfloor heating manifold.
L = D x 30
Loading...
+ 27 hidden pages