Dimplex A12M, A16M Installation Manual

Page 1
8/60472/0
Issue 1
A12M / A16M: Installation Manual
Page 2
ii
Overall view
Figure 1 (a): Outer dimensions of heat pump, (b) position of heat pump registration plate and details
(c) Internal components of heat pump
(a)
(b)
(c)
Page 3
iii
Contents
1 Introduction .......................................................................................... 1
2 Scope of delivery ................................................................................... 1
3 Pre-Installation advice .......................................................................... 5
3.1 Warnings .......................................................................................... 5
3.2 Intended use ..................................................................................... 6
3.3 Legal ................................................................................................ 6
3.4 Heat pump sizing ............................................................................... 6
3.5 Site selection ..................................................................................... 6
3.5.1 Location of heat pump ................................................................... 6
3.5.2 Heat pump placement and fixing ..................................................... 7
3.6 Plumbing –Preparation ........................................................................ 8
3.6.1 Buffer tank ................................................................................... 9
3.7 Electrical connections - Preparation ...................................................... 9
4 Installation .......................................................................................... 10
4.1 Handling and transport ..................................................................... 10
4.2 Plumbing......................................................................................... 10
4.3 Electrical connections ....................................................................... 11
4.4 Opening the heat pump for electrical connections ................................. 15
4.4.1 Heat pump electrical connection .................................................... 16
5 Set to work .......................................................................................... 17
5.1 Location of indoor components .......................................................... 17
5.2 Set to work ..................................................................................... 17
5.3 Opening the UI ................................................................................ 17
5.4 Using the User Interface ................................................................... 18
6 Pre-commissioning .............................................................................. 18
6.1.1 General/Schematic ...................................................................... 19
6.1.2 Message log ............................................................................... 19
6.1.3 Output Tests .............................................................................. 19
6.1.4 Defrost ...................................................................................... 19
6.1.5 Operating data ........................................................................... 19
6.1.6 History ...................................................................................... 19
Page 4
iv
7 Commissioning .................................................................................... 20
7.1.1 Waterside check.......................................................................... 20
7.1.2 Temperature check ..................................................................... 21
7.1.3 Electrical connections (SH) ........................................................... 21
7.1.4 Water flow check ........................................................................ 21
7.1.5 DHW setup ................................................................................. 22
7.1.6 Electrical connections (DHW) ........................................................ 22
7.1.7 DHW Test................................................................................... 22
7.1.8 Disinfection ................................................................................ 23
7.1.9 Heating curves............................................................................ 23
8 System health checks .......................................................................... 24
9 Troubleshooting, FAQ .......................................................................... 25
9.1 Table of error codes and descriptions .................................................. 25
10 Technical Specifications ................................................................... 24
Appendices:
A Refrigeration cycle................................................................................A
B Schematic zone diagrams......................................................................B
Schematic 1: 10200110 - Space Heating Only .......................................... B
Schematic 2: 10220290 - Zone Space Heating & DHW ............................... C
Schematic 3: 10300110 - Bivalent Space Heating ..................................... D
Schematic 4: 10310290 - Bivalent Zone Space Heating & DHW .................. E
C Wiring centre electrical connections.........................................................F
D Installer controller cable connections...................................................... G
E Installer menu flow chart.......................................................................H
Page 5
1
1 Introduction
Thank you for choosing a Dimplex Heat Pump. The Dimplex A class heat pump combines outstanding performance to maximise year-round efficiency no matter what the weather conditions. It can also deliver high output and high temperatures even at outside air temperatures of -7. The sophisticated controller makes the system easy to use and there are many more technological innovations including a scroll compressor that uses enhanced vapour injection.
2 Scope of delivery
Please ensure you check the scope of delivery before signing any delivery documentation. Claims for missing or damaged parts after signing for the delivery will not be accepted.
There are 3 options to select from when installing a Dimplex Heat Pump:
Pack 1 - Space heating and Dimplex
A Class Cylinder
To install the heat pump and Dimplex A class cylinder together you must purchase Pack 1 which contains necessary components shown in the tables below. A separate wiring centre is not required as the wiring centre is built into the cylinder. The ACCHYPK Hydraulics pack contains the all of the necessary hydraulic components.
Pack 2 - Space heating and Dimplex
Standard Heat Pump Cylinder
To install the heat pump for space heating and domestic hot water but not using an A class cylinder you must purchase Pack 2 which contains the necessary components shown in the tables below. A separate wiring centre is required to wire the circulation pumps and zone controls since this is not supplied on the cylinder. The ACCHYPK Hydraulics pack contains the all of the necessary hydraulic components.
Pack 3 – Space heating only
To install the heat pump for space heating only, you must purchase Pack 3 which contains the necessary components shown in the tables below. A separate wiring centre is required to wire the circulation pumps and zone controls. The ACSSHYPK Hydraulics pack contains the all of the necessary hydraulic components.
Page 6
2
PACK 1:
SPACE HEATING AND DIMPLEX A CLASS CYLINDER
Heat pump
A12M / A16M
Hydraulics Kit A which includes:
ACCHYPK
User interface (UI)
049179
Pump - UPM GEO 25-85 180 (70mm cable)
049148
2 x Pump Valve Gate 1"1/2 – 28mm 2 x Washer 30.1x21x2mm
By pass valve (22mm) Spring loaded
050557
3 port diameter valve
050564
Isolation valves - (1) Flow (2) Return with strainer
Flow 062801
Return
062815CR
4 x Blanking plugs for lifting holes
624105
Installation and User manuals
Dimplex DHW Cylinder Kit
Cylinder
Air vent Drain
Safety group DHW side - expansion vessel, hose and bracket, inlet group, tundish
3 x Copper pipes – Pump to buffer/cylinder
Pipe connections to coil, pipe, drain and vent
Pipe connections to pump
Page 7
3
PACK 2:
SPACE HEATING AND DIMPLEX STANDARD HEAT PUMP
CYLINDER
Heat pump
A12M / A16M
Hydraulics Pack A which includes:
ACCHYPK
User interface (UI)
049179
Pump - UPM GEO 25-85 180 (70mm cable)
049148
2 x Pump Valve Gate 1"1/2 – 28mm 2 x Washer 30.1x21x2mm
Altecnic ERES straight by pass valve (22mm 22mm) Spring loaded
050557
3 port diameter valve
050564
Isolation valves - (1) Flow (2) Return with strainer
Flow 062801
Return
062815CR
4 x Blanking plugs for lifting holes
624105
Installation and User manuals
Wiring centre Kit
Wiring centre module
049162
1 x Temperature probe (NTC10) for DHW
Page 8
4
PACK 3:
SPACE HEATING ONLY
Heat pump
A12M / A16M
Hydraulics Pack B which includes:
ACSSHYPK
User interface (UI)
049179
Pump - UPM GEO 25-85 180 (70mm cable)
049148
2 x Pump Valve Gate 1"1/2 – 28mm 2 x Washer 30.1x21x2mm
Altecnic ERES straight by pass valve (22mm 22mm) Spring loaded
050557
Isolation valves - (1) Flow (2) Return with strainer
Flow 062801
Return
062815CR
4 x Blanking plugs for lifting holes
624105
Installation and User manuals
Wiring centre Kit
Wiring centre module
049162
1 x Temperature probe (NTC10) for DHW
Page 9
5
3 Pre-Installation advice
3.1 Warnings
When transporting the heat pump,
ensure that it is not tilted more than 45° (in any direction), for any prolonged period of time.
Do not attempt to lift the heat pump
manually. It weighs 130kg and should only be lifted using the appropriate lifting devices.
Installation and any service work on
the heat pump may only be performed by authorised and qualified installer and after-sales service technicians.
This device is suitable for mains
connection only: 230V, 1P&N, 50Hz, and is not suitable for operation with any electrical generator and any attempt to do so will void warranty.
This device shall be installed in
accordance with national wiring regulations. The digital inputs are volt free, if any voltage, such as a switch live 230V is connected irreparable damage will be caused to the wiring centre. The local wiring regulations should always be followed paying particular attention to mixing of low voltage and extra low voltage cabling.
Before removing the cover of the
heat pump, cylinder or wiring centre, ensure that all electrical circuits are isolated.
Means for disconnection from the
supply mains must be incorporated
in the fixed wiring in accordance with the national wiring regulations.
The heat pump contains refrigerant
at high pressure. Safety measures are in place to avoid system pressure build up:
Stage 1: Pressure transducer
stops compressor
Stage 2: Pressure switch switches
heat pump off.
The installation of a residual current
device (RCD) having a rated residual operating current not exceeding 30mA is advisable.
Additional heating may be required
if heat pump is intended to dry out a new or renovated building, as the initial heat load will be higher than the calculated load.
If the heat pump can be
disconnected from power supply for prolonged periods of time or where power supplies are susceptible to failure, antifreeze must be added to the system.
Never use cleaning agents
containing sand, soda, acid or chloride as these can damage the surfaces/components.
We recommend the installation of a
suitable filtration protection system and a corrosion additive for the heating system to prevent the formation of deposits (e.g. oxide and solids) in the condenser of the heat pump. The return isolation valve provided in the hydraulics pack has a built in strainer for this purpose.
Page 10
6
Products not installed with the
Dimplex hydraulics packs will not be supported by Dimplex. This includes but is not limited to thermal stores.
During the commissioning of the
domestic hot water cylinder, ensure that the cylinder is full and no water is drawn from the cylinder as this will adversely affect the heat pumps operation.
This appliance can be used by
children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
3.2 Intended use
This device is only intended for domestic use, as specified by the manufacturer. Any other use beyond that intended by the manufacturer is prohibited. This requires the user to abide by the manufacturers product information. Please refrain from tampering with or altering the device.
3.3 Legal
The construction and design of the heat pump complies with all relevant EU directives (see CE declaration of conformity).
When connecting the heat pump to the power supply, the relevant EN and IEC standards are to be adhered to. Any further connection requirements
stipulated by the network operation must also be observed.
When connecting to the heating system all applicable regulations must also be adhered to.
3.4 Heat pump sizing
Ensure that the correct size heat
pump has been selected in accordance with the latest version of MIS3005 (UK only) and with the Dimplex Heat Pump Planning Manual.
If a non A-Class heat pump cylinder
is being used, ensure that it has been accurately sized with the appropriate coil surface area of the cylinder to match the heat pump’s output, flow rate requirements and that all necessary hydraulic connections have been considered in connecting it to the heat pump system.
Ensure that suitable heat emitters
have been sized in accordance with the Heat Emitter Guide (UK only) and selected ensuring a low flow temperature design. To maximise system efficiency it is important to design the system with the lowest flow temperature possible.
3.5 Site selection
3.5.1 Location of heat pump
The heat pump must be installed
outdoors with adequate clearances for ventilation and maintenance as shown in figure 2. It is recommended that the heat pump is installed along the property wall, as shown below.
There must be a minimum distance
of 1000mm in front of the fan to
Page 11
7
prevent air re-circulation. Positioning the heat pump in a confined space, frost hollow or well will result in reduced heat pump operating efficiency.
The fan should preferably not face
prevailing winds to ensure correct air flow through the evaporator.
Figure 2: Required free space around heat
pump for ventilation and maintenance
Although the heat pump is within
noise and vibration regulations outlined in MCS 007, it is recommended to avoid positioning it close to bedroom windows, as the fan and compressor may be operational at night.
3.5.2 Heat pump placement and fixing
Approximately 2 litres of condensate
water is drained from the system every time a defrost cycle occurs. Therefore, it is essential that the condensate pipe is fed into a drain or soak away to allow for safe disposal of the excess water, away from footpaths or patios.
The condensate pipe must be kept
frost free. Freezing of this pipe due to incorrect installation can result in irreparable damage and void warranty.
Figure 3: Position of fixing holes and condensate drain
Page 12
8
The condensate pipe should not run
into sewer pipe as fumes may travel into the heat pump and cause corrosion to the evaporator coil.
The heat pump must be fixed onto a
level, stable base that is capable of withstanding the unit’s weight of 130kg, with a minimum of 30mm clearance around all sides of the heat pump (recommended minimum L x W x D = 1000 x 470 x 100mm). It can be secured with M10 anchor bolts, using the fixing holes shown in figure 3.
Ideally the heat pump should be
located close to the property. Positioning of the heat pump at a distance from the property will result in the need for extra insulated pipe, which will lead to extra cost, and result in additional heat losses.
3.6 Plumbing –Preparation
When selecting piping to install with the heat pump please ensure:
The pipe sizes are adequate to allow
correct minimum water flow rate through the heat pump.
Table 1: Maximum length of copper pipe
Nominal
Minimum
@ 2050 l/h
@ 1200 l/h
18 kPA
60 kPa
Diameter
(mm)
Max length
(m)
Max length
(m)
15 1 10
22
10
80
28
30
265
32
60
525
The pipe lengths given in table 1
include the straight length of the piping and all elbows. The equivalent straight length (L) of each elbow is found by multiplying the outer diameter of the pipe (D) by 30:
External pipes should be adequately
insulated with vapour resistant insulation and protected against damage to prevent excessive heat losses. All joints should be suitably sealed and exposed pipework must be avoided.
Existing hot water systems should
be flushed prior to connection to the heat pump to remove all contaminants and impurities, in accordance with the latest version of MIS 3005.
Make the water flow and return
pipes positioned correctly for connection to the heat pump as shown on the label in figure 4 and on the back of the heat pump.
Isolation valves, supplied in the
Dimplex heat pump hydraulics pack, allow the strainer to be removed and cleaned without having to drain the system (non-return valve and ball valve with strainer). Installation of these valves is discussed in more detail section 5.2.
If heat emitters consist of underfloor
heating and higher temperature heat emitters, a mixing valve must be used to prevent high temperature water entering the underfloor heating manifold.
L = D x 30
Page 13
9
Figure 4: Plumbing with isolation valve with strainer to be fitted to return pipe
3.6.1 Buffer tank
The heat pump uses reverse cycle defrost in order to defrost the evaporator, which will happen automatically when required in cold/moist weather conditions. Therefore, it is necessary to connect a buffer tank in series with the heat pump, as shown in the hydraulic schematic diagrams (Appendix B). The Dimplex A-Class cylinder range come with an integrated buffer tank, which:
Provides sufficient energy for the
unit to carry out successful defrost.
Increases compressor life due to the
extension of minimum starts
It is recommended that a buffer with a heating element is used as it may be required if initial start-up and commissioning are carried out in cold weather.
3.7 Electrical connections -
Preparation
Ensure the incoming power supply
and the distribution board are suitably rated.
Ensure that the regulations specified
by the local electricity supplier have been adhered to.
The supply cable must be sized to
meet the requirements of national wiring regulations for current carrying capacity and disconnection, a minimum cross sectional area of 6mm² steel wire armoured (SWA) cable is recommended.
The required controller cable is a
shielded MODBUS cable RS485, for example a 4 core 1mm² 24 AWG (Nominal impedance 120Ω) Foil and Braid, which can be purchased from Dimplex as an accessory.
Page 14
10
The user interface acts as the
temperature probe in the primary zone. For multiple zones, mechanical thermostats or NTC10 temperature probes may be used.
4 Installation
4.1 Handling and transport
Remember that the heat pump
should never be tilted by more than 45° during handling and transport, as depicted on the registration plate and in figure 5.
Figure 5: Tilt angle
Ensure that there is a clear pathway
for a truck to deliver the heat pump as close to the selected location as possible.
The heat pump weighs 130kg and
therefore should only be lifted by means of a lift truck, hand truck or lifting rods with straps that can be fed through the holes in the base plate and frame, shown in figure 6.
The installer must use a suitable
lifting method, in accordance with in accordance with health and safety regulations.
Straps must also be used with the
lifting rod to prevent the heat pump from toppling.
Figure 6: Handling of heat pump
4.2 Plumbing
The system must be flushed, filled
and all trapped air should be removed. Air bleeds must be installed at every high point; in particular, the installer must remember an air bleed on the flow pipe if it is a local high point since there is no air bleed point on the condenser.
The dirt strainer, supplied in the
Dimplex heat pump hydraulics pack, is built into the return isolation valve and must be installed on the return pipe to prevent contamination of the condenser heat exchanger
If an alternative strainer is used, it
must be at least 7 microns in size and connected with ball valves.
Fit flow and return isolation valves
(Flow 062801, Return 062815CR) and piping to each of the water ports on the back of the heat pump, as shown in figure 7.
Page 15
11
Figure 7: Flow and return valves
The non-return valve built into
‘1062815CR’ allows the strainer to be cleaned without draining the system, by simply closing the flow and return valves and removing the strainer. The only water that is lost will be that in the return valve. System pressure must be checked once valves are re-opened.
Direct condensate drain pipe to soak
away or drain, as illustrated in figure 3 in section 3.5.2.
All piping must be properly
insulated.
4.3 Electrical connections
The heat pump system consists of the heat pump, wiring centre and user interface. If a Dimplex A Class cylinder is also purchased, the wiring centre is built into the cyinder. The user interface contains a thermostat and is sufficient if one heating zone is present.
Optional, additional UI’s, temperature
probes or room thermostats are required for additional heating zones. Figure 8 (a) – (c) shows the wiring configuration of the 3 different installation options (outlined in section 2: Scope of Delivery, at the beginning of this manual).
Page 16
12
Figure 8 (a): Wiring configuration of space heating and hot water - Dimplex A Class cylinder
Page 17
13
Figure 8 (b): Wiring configuration of space heating and hot water – Dimplex standard
cylinder
Page 18
14
Figure 8 (c): Wiring configuration of space heating only
Page 19
15
4.4 Opening the heat pump for
electrical connections
To open the heat pump, follow the procedure shown in figure 9:
1. Unscrew 2 screws holding bottom
panel, using a PZ2 screwdriver.
2. Pull the front panel down and then
out to remove.
3. Unscrew 5 screws holding the front
cover of the electrical box to open and pull down towards you.
4. Remove 2 hex screws holding the
door flap in place to access cable connections.
NOTE: Follow steps in reverse order to
close the heat pump. When closing the heat pump front panel, ensure that the top and bottom panels are interlocked.
Figure 9: Opening the casing to fit electrical connections
WARNINGS:
Before opening the heat
pump, ensure all circuits are isolated.
Ensure that the components in
the electrical box do not get wet when the electrical box is opened.
Page 20
16
4.4.1 Heat pump electrical connection
To make electrical connections to the heat pump:
1. Feed power cable and controller
cable through gland at the back of the base panel.
2. Remove the cable access cover and
using the opening in the base panel for access, pull power cable and controller cable through the two cable glands in base panel and through the two glands on the side of the electric box.
3. Allow sufficient cable to ensure the
connections are not strained when the cover is opened. Armoured cable must be stripped once it has been pulled through the base cable gland in order to pass through cable gland in the side panel of the electrical box.
4. Connect power cable and controller
cable as shown in figure 10. Stranded cable must be ferruled to insert into push in connections.
5. The controller cable is then
connected from the heat pump to the wiring centre (see wiring diagrams in Appendix C and D).
Figure 10: Heat pump electrical connections
Page 21
17
5 Set to work
5.1 Location of indoor components
Location of UI and room thermostats:
The user interface and room thermostats should be installed indoors in a location that is out of reach of children, but where the screen can be easily seen (usually 1.2m – 1.7m from the floor).
The controller and thermostats should be installed on internal walls in living area to reflect the correct temperature, and away from direct sunlight, drafts (windows and doors) and heat emitters.
Location of wiring centre:
If a Dimplex A Class cylinder is used, the wiring centre is built in and pre wiring. If a non A Class cylinder is used, it is recommended to install the wiring centre in close proximity to the cylinder.
5.2 Set to work
When starting up the heat pump you must first ensure:
The isolator switch is switched on. The heat pump is connected to the
mains power supply.
The wiring centre or DHW cylinder is
connected to the mains power supply.
The UI and the heat pump are
connected to the wiring centre or DHW cylinder.
Once the connections have been made and the UI has been switched on, the system may take a couple of minutes to start up.
5.3 Opening the UI
It is recommended to install the heat pump, wiring centre and UI in that order. If additional UI’s are required, or if it is necessary to install the system in a different order, a jumper must be moved on the UI’s PCB board to the ON pin, as shown in figure 11.
The cover of the UI must be removed in order to mover the jumper. To remove and replace the cover:
To remove:
Unscrew the screw at the bottom of
the UI and lift the cover and rotary dial.
To replace:
Position the rotary dial over the
holding pin on the board, ensuring the two on lined up correctly.
Replace cover and bottom screw.
Figure 11: Jumper on UI board
Page 22
18
5.4 Using the User Interface
Figure 12: Main user interface (UI)
Select – click middle of the rotary
dial (Enter/Confirm)
Change selected value – turn the
rotary dial to desired value
Confirm change – click middle of
rotary dial (Enter/Confirm)
Back up one level – click small
button (Escape)
6 Pre-commissioning
When switching on the heat pump for the first time, and after start up sequence, you will be greeted with the welcome screen, shown in figure 13.
Figure 13: Home screen
To access the Installer Menu, you must click into the messages menu. Once in the messages menu, you must select
‘Login’ as shown in figure 14, and turn
the dial to 55 in order to access the Installer Menu.
Figure 14: Home screen
When you enter the installer menu, you will see the Start guide screen, as
shown in figure 15 (a). Selecting ‘UK’
will bring you to the Installer Menu.
Select ‘Commissioning’ to begin and
follow the step by step guide on the user interface, which will take you through all necessary steps of commissioning. For commissioning instructions, move to Section 7 now.
(a) (b)
Figure 15: (a) Welcome screen
(b) Installer menu
Messages menu
Login = 55
Page 23
19
6.1.1 General/Schematic
In some cases, it may be necessary to carry out checks on individual components of the heating system before beginning the commissioning routine. Accessing General/Schematic menu allows you to set the date and time, and the level of access allowed. Selecting ‘Next’ will bring you to the Schematic menu, as shown in figure 16, Once you have selected a schematic zone diagram, a number of other options will become available in the main Installer menu, as described in Table 2.
Figure 16: Schematic zone diagram
selection
Table 2: Description of submenus in the Installer Main Menu
Menu option
Content
Message log
Provides log of message – error code, date, time, description
Output tests
Allows ON/OFF tests for individual components and zones
Defrost
Allows defrost cycle to be manually started
Operating data
Provides full list of system parameters
History
Provides temporary and permanent history of run times of different components
6.1.2 Message log
The message log menu provides a list of all errors that have taken place, including the date and time that they occurred. Selecting an individual error code will provide more information on the type of error that occurred.
6.1.3 Output Tests
The output tests menu allows you to run ON/OFF tests on individual components of the system such as the zone pumps, valves, immersion, backup heater, fan and defrost.
6.1.4 Defrost
Before running a manual defrost cycle you must ensure the buffer has been isolated from the heating, as stated by the message on the UI. Selecting ‘Run
Defrost’ begins the defrost cycle. The
defrost screen will state the time
remaining in the defrost cycle. When the cycle is finished, the screen will tell you that the defrost cycle is complete.
A heating water return temperature
of 18°C ensures proper defrosting of the evaporator.
6.1.5 Operating data
The operating data menu provides a list of all the system parameters such as all temperatures including each zone set and actual temperatures, flow rate, and heat pump status.
6.1.6 History
The History menu shows the temporary run time history of the components of the system. These values can be reset in order to record run times over a certain time period. Selecting ‘Next’ brings you to the permanent run time history which cannot be reset.
Page 24
20
7 Commissioning
Select ‘Commissioning’ to begin and
follow the instructions on the system controller. The commissioning routine will take you through a number of checks and tests to complete the installation, as outlined in table 3. When you finish each submenu in the commissioning process, selecting ‘Next
will take you back to the main Commissioning menu, where a new submenu will be available.
The first menu you will be asked to complete is the General/Schematic menu. General menu allows you to set the date and time.
Table 3: Description of each submenu in the Commissioning Menu
Menu option
Content
General / Schematic
Selection of time, date and appropriate plumbing schematic
Waterside checks
Checks that must be carried out on the water circuit
Water flow check
Ensures the circulation pump flow rate is okay
Electrical connections
Ensures all the necessary electrical connections to the wiring centre have been made correctly
DHW Setup
Ensures the cylinder is full and connected correctly
DHW Test
Runs DHW cylinder test to find maximum achievable temperature (may take up to 90 minutes depending on heat pump and cylinder size)
Disinfection
Setting frequency and time of disinfection
Heating curve
Selection of heating curve for each zone depending on type of heat emitters in place
In the ‘Schematic’ menu, shown in figure 16 above, you can select the relevant schematic zone diagram, in accordance with those in Appendix B. Once you select the relevant schematic zone diagram, more options will appear on the installer menu, depending on the zone diagram you have selected. As each menu is completed, more options will become available, as outlined in the flow chart in Appendix E.
7.1.1 Waterside check
The ‘Waterside check’ menu allows you
to select if temperature control is based on the flow or return temperature, as shown in figure 17. This will apply to heating curves, as discussed in section
6.1.8 below.
Figure 17: Temperature control
It is recommended to set the temperature control based on the flow temperature for radiators and smart rads, and on the return temperature for
underfloor heating. Selecting ‘Next’ will
bring you to the waterside checks menu.
Page 25
21
A number of waterside checks must be carried out as part of commissioning, and must be ticked as completed in the Waterside check menu:
The system must be flushed. The strainer must be fitted to the
return pipe.
The system must be pressurized
(You must enter the system pressure).
The system must be fully bled. The expansion vessel must be fitted Membrane pressure must be
checked and adjusted if required.
When checks are completed and ‘Next is selected, the type of temperature measurement devices to be used in each heating zone must also be selected:
User Interface Temperature probe Mechanical thermostat
Selecting ‘Next’ will bring you to the ‘Temperature check’ menu.
7.1.2 Temperature check
This screen displays the temperatures being read by all temperature probes. Tick each box once you have ensured that all the temperatures are as expected.
7.1.3 Electrical connections (SH)
This menu provides a list of electrical connections that should be made prior to commissioning for space heating. The lists based on the schematic zone diagram selected and also the type of temperature devices that will be used in
each zone. Once you have confirmed all checks and select ‘Next’, you will return to the commissioning menu where you
can now access the ‘Water flow check’
menu.
7.1.4 Water flow check
Select ‘Run Test’ to begin water flow
check. The circulation pump will be tested first by running it for 30 seconds. Once you check that flow is
detected, click ‘Continue’ to confirm
that the pump is working correctly.
Once this is successful, the compressor will be run for 5 minutes. As the test runs, the screen will give you information on the status of the heat pump and the time remaining on the test. If you do not have flow or if there is a problem, you can stop the test. Once the test is completed, you will see one of three messages:
1. No flow detected
2. Flow too low
3. Flow detected
If you see message 1 or 2, you must carry out the changes recommended on the screen and repeat the test. There will be a time delay before you can restart the test. When you see the screen shown in figure 18, with the pump highlighted in green, flow has been detected and the compressor test is complete.
You will receive the status ‘Waterside is OK’ when the waterside checks are completed. Selecting ‘Next’ brings you
to the Electrical Connections menu.
If carrying out start up in cold weather, start by heating the buffer. Once it reaches the required temperature open each zone slowly and in series, especially for underfloor heating.
NOTE: If these options are ticked but
haven’t been carried out, any failure in
the system will be outside of warranty.
Page 26
22
Figure 18: Green symbol on successful
compressor test
If you have selected Schematic 1 or 3 (Space heating only or Bivalent space heating), move now to section 7.1.9
‘Heating Curves’ to complete the
commissioning process.
7.1.5 DHW setup
Before commissioning the DHW side, a number of checks must be carried out, as shown in figure 19.
Figure 19: DHW checks
When you have ticked each box to confirm each DHW check, ‘Next’ will bring you back to the installer menu,
where you can now select ‘Electrical Connections (DHW)’.
7.1.6 Electrical connections (DHW)
This menu provides a list of electrical connections that should be made prior to commissioning the domestic hot water cylinder. You must check and confirm all connections in order to
make the ‘DHW Test’ available in the
installer menu.
7.1.7 DHW Test
Before you run the DHW test, you will be asked to check that the valve is in the DHW position, as shown in the screen in figure 20. Check that the red actuator marker changes to the correct position.
Figure 20: Valve check screen
When you have completed the valve
check and select ‘Next’, you will see the
DHW test screen, which informs that the test can take up to 90 minutes.
Selecting ‘Run test’ begins the DHW
test and shows you the time remaining.
If the test fails, you will see the screen shown in figure 21, which provides information on why the test failed, and advice on checks to carry out.
If the test is complete and has been successful, you will see the screen shown in figure 22, which shows the maximum temperature that the cylinder can achieve.
NOTE: If you leave the commissioning
menu before you successfully complete commissioning, all previous information entered will be saved and completed menus will be highlighted in green.
Page 27
23
Figure 21: DHW test failed
Figure 22: DHW test complete
7.1.8 Disinfection
The temperature and frequency of the disinfection cycle can be adjusted in this menu. If the temperature is set to higher than the heat pump can achieve, the screen shown in figure 23 will appear which notifies that the immersion heated will be used to reach the disinfection temperature.
Figure 23: Disinfection setup
7.1.9 Heating curves
When selecting heating curves, you will do so zone by zone. Selecting the zone
and pressing ‘Next’ will allow you to
select the kind of heat emitters that are in place in the selected zone. The four heating curves are for:
Smart Rad Under floor Standard Rad Custom
Selecting Smart Rad, Under floor or Standard Rad will bring you to a default heating curve for the selected emitter.
The pre-defined curves have recommended temperature ranges for each heat emitter.
Smart Rad Max 48 Min 35 Under floor Max 30 Min 25 Standard Rad Max 55 Min 45 A fourth option ‘Custom’ provides a
flat line curve.
The values that generate the heating curve graph can be changed, by selecting the corresponding temperature box and adjusting the temperature, as shown in figure 24.
Figure 24: Heating curve for Smart Rad
NOTE: Pre-defined heating curves
should only be changed if the heat pump does not achieve the pre-defined, recommended temperatures.
Page 28
24
The green line on the right indicates the maximum outdoor temperature at which the heat pump stops running. The yellow line on the left indicates the minimum outdoor temperature at which the bivalent heating system starts working.
The red line indicates the temperature that the water will be heated to, based on the outdoor temperatures. The ‘Default’ option will reset the pre­defined values. Set will save entered values.
To complete commissioning, you must
select the ‘Setup complete’ submenu in
the installer menu, as shown in figure 25:
Figure 25: Full Commissioning menu
When commissioning has been successfully completed, you will see the screen shown in figure 26. Selecting ‘Automatic’ will activate all settings. The default setting for the heat pump is OFF. To turn on the heat pump, you must return to the home screen to access the user menu.
Figure 26: Commissioning complete
For further information on end user controller instructions please see:
‘A Class Air Source Heat Pump User Guide’ supplied in the Hydraulics Pack
with this manual.
8 System health checks
Heat pump:
Is the fan clear from debris?
Electrical:
Is the power cable firmly fixed? Is the earth wire connection secure? Is the supply voltage correct?
Hydraulics:
Is the water pressure higher than
XXbar?
Are there any leaks in the system? Is the filter clear of debris?
Note: It is recommended that the strainer is checked and cleaned 24 hours after commissioning, and regularly within the first week of operation.
Indoor settings:
Are the set temperatures and
heating times suitable for the occupants?
Is the building warm enough for the
occupants or does the heating curve need to be adjusted?
Is the UI screen working correctly?
NOTE: For successful commissioning
you MUST follow through the menu until you see the screen shown in figure 24. If you do not see this screen, commissioning has not been successful and will void warranty of the heat pump.
Page 29
25
9 Troubleshooting, FAQ
If the heat pump is being installed in a holiday home or temporary domestic dwelling, antifreeze must be added to
the system in case of unattended power cuts.
9.1 Table of error codes and
descriptions
Page 30
24
10 Technical Specifications
1
Type and order code
A 12
A16
2
Design
2.1
Degree of protection according to EN 60529 for compact unit or heating element
IP 24
IP 24
2.2
Installation location
Outdoors
Outdoors
3
Performance data
3.1
Operating temperature limits:
Min / Max
Min / Max
Heating water flow and return temperature
°C
25 / 65
25 / 65
Outside air temperature
°C
-20 / 35
-20 / 35
Seasonal Performance Factor (SPF) for Under floor at 35°C1
3.9
3.9
Seasonal Performance Factor (SPF) for Radiators at 55°C1
3.6
3.6
3.2
Heating water temperature difference at standard rating condition
A7 W352 K 5
5
Heat output / COP
at A7 W352
kW / ---
12 / 4.7
12 / 4.7 *
at A-2 W352
kW / ---
12 / 3.5
15.5 / 3.2
at A-7 W352
kW / ---
12 / 3
14.3 / 3
at A7 W552
kW / ---
12 / 3
12 / 3 *
at A-2 W552
kW / ---
12 / 2.5
15.6 / 2.4
at A-7 W552
kW / ---
12 / 2.2
15.3 / 2.2
at A7 W652
kW / ---
12 / 2.5
12 / 2.5*
at A-2 W652
kW / ---
12 / 2.0
15 / 1.99
at A-7 W652
kW / ---
12 / 1.8
15 / 1.8
* Performance at this point is optimised to match the building heat load and maximise the Seasonal performance factor.
3.3
Sound power level3
(Provisional)
dB(A)
64
64
3.4
Sound pressure level at 10m (Heat pump against wall)
dB(A)
40
40
3.5
Heating water flow rate @ A7 W35 (nominal)
m³/h, l/min
2.1 / 35
2.1 / 35
3.6
Air flow @ A7 W35
m³/h
3700
3700
3.7
Refrigerant; total filling weight
Type / kg
R410A / 2.0
R410A / 2.0
3.8
Water capacity of stainless steel heat exchanger
litre 1 1
3.9
Polyol ester oil in compressor
litre
1.18
1.18
4
Dimensions, connections and weight
4.1
Device dimensions without connections
H x W x L mm
1571 x 932 x 401
1571 x 932 x 401
4.2
Physical volume
0.59
0.59
4.3
Device connections to heating system
inch
1" ext. thread
1" ext. thread
4.4
Weight of the transportable unit(s) excluding packaging
kg
130
130
5
Electrical connection (Heat pump)
5.1
Nominal voltage; fuse protection
V / A
230 / C 40
230 / C 40
5.2
Nominal power consumption / current A7 W35
kW / A
2.6 / 11
2.6 / 11
5.3
Maximum power consumption / current A-2 W65
kW / A
6.9 / 30
8.1 / 35
5.4
Power factor A7 W35 / cosϕ
A / ---
11 / >0.95
11 / >0.95
5.5
Power input of integral fan @ A7 W354
W
60
60
6
Other design characteristics
6.1
Defrosting
Automatic
Automatic
Type of defrosting
Reverse cycle
Reverse cycle
6.2
Heating water in device protected against freezing by software
Yes
Yes
1.)
Calculated to EN15316 excluding hot water
2.)
These data characterise the size and performance of the system according to EN 14511 with clean heat exchangers. Abbreviations have the following meaning, e.g. A2 / W35: outside temperature 2°C and heating water supply temperature 35°C. A2 / W35 test, takes into account defrosting as per EN 14511.
3.)
According to EN 12102.
4.)
Fan is variable speed, rated input relates to nominal input power.
Page 31
A
Appendices
A Refrigerant cycle
Page 32
B
B Schematic zone diagrams –
Schematic 1: 10200110 - Space Heating Only
Page 33
C
Schematic 2: 10220290 - Zone Space Heating & DHW
Page 34
D
Schematic 3: 10300110 - Bivalent Space Heating
Page 35
E
Schematic 4: 10310290 - Bivalent Zone Space Heating & DHW
Page 36
F
C Wiring centre electrical connections
Page 37
G
D Controller cable connections
Page 38
H
E Installer Menu Flow Chart
Page 39
I
EC Declaration of Conformity
GDC Group Limited, Millbrook House, Grange Drive, Hedge End, Southampton, Hants, SO302DF, United Kingdom
Manufacturer: Glen Electric Ltd
Greenbank Industrial Estate, Rampart Road, Newry, Co. Down, BT34 2QU
Hereby certified that the following device(s) complies/comply with the applicable EU directives. This certification loses its validity if the device(s) is/are modified.
Description: Heat Pump Type: Air – to – Water Model: A16M
Model: A12M
EC Directives:
Low voltage directive 2006/95/EC EMC directive 2004/108/EC Pressure equipment directive 97/23/EC
Applied Standards:
EN 60335-1:2012; EN60335-2-40:2003+A11+A12+A1+corr.+A2:2009+AC:2010 EN55014-1:2006; EN55014-2:1997+A1:2001 EN61000-3-2:2006; EN61000-3-3:1995+A1:2001+A2:2005 EN378-1:2008+A1:2010; EN378-2:2008+A1:2009; EN378-3:2008; EN378-4:2008 EN 14511-1:2011; EN14511-2:2011; EN14511-3:2011; EN14511-4:2011
Conformity assessment procedure according to pressure equipment directive:
Module A
CE mark added:
2013
EC declaration of conformity issued on:
XX June 2013
Ireland, XX.06.13 Technical Director Martin Betz: __________________
Issue: 1
Loading...