Di-log PU260 User guide

Page 1
Instruction Manual
PU260
Voltage Tester Proving Unit
with Continuity Tester
Page 2
Contents
1.0 Introduction/scope of supply
2.0 Transport and storage
4.0 Control elements and connections
References marked on the instrument or in instruction manual:
Warning of a potential danger, follow instructions in this manual.
Reference ! Please use utmost attention.
Caution ! Dangerous voltage. Danger of electrical shock.
Continuos double or reinforced insulation category II IEC 536 / DIN EN 61140
Conformity symbol, the instrument complies with the relevant directives. It complies with EMC Directive (2004/108/EEC), Standards EN 61326 – 1 : 2006. It also complies with the Low Voltage Directive (2006/95/EEC), Standards EN 61010­1 and EN 61010-031 are fulfilled.
The PU260 meets the standard (2002/96/EEC) WEEE. This marking indicates that this product should not be disposed with other household wastes throughout the EC. To prevent possible harm to the environment or human health from uncontrolled waste disposal, recycle it responsibly to promote the sustainable reuse of material resources. To return your used device, please use the return and collection systems or contact the retailer where the product purchased. They can take this product for environmental safe recycling.
2
Page 3
The instruction manual contains information and references, necessary for safe operation and maintenance of the instrument. Prior to using the instrument the user is kindly requested to thoroughly read the instruction manual and comply with it in all sections.
Failure to read the instruction manual or to follow with the warnings and references contained herein can result in serious bodily injury or instrument damage. The respective accident prevention regulations established by the professional associations are to be strictly enforced at all times.
1.0 Introduction / Scope of supply
You have purchased a high quality test instrument which will allow you to carry out tests over a long time period.
The instrument is characterised by the following features:
Portable, battery powered Proving Unit for testing Two Pole Voltage Testers up to 690 V
Continuity Tester for testing: fuses, fused test leads etc.
Additional touch electrode for quick testing of fused leads
Optical and acoustical continuity indication
Low Battery indication
Incl. rubber holster.
Scope of Supply:
1 pc proving unit 10 pc batteries 1.5V AA 1 pc. Instruction Manual
3
Page 4
2.0 Transport and Storage
Please keep the original packaging for later transport. Any transport damage due to faulty packaging will be excluded from warranty claims.
In order to avoid instrument damage, it is recommended to remove batteries when not using the instrument over a certain time period. However, should the instrument be contaminated by leaking battery cells, you are kindly requested to return it to Di-Log for cleaning and inspection.
Instruments must be stored in dry and closed areas. In the case of an instrument being transported in extreme temperatures, a recovery time of minimum 2 hours is required prior to instrument operation.
3.0 Safety References
The operator’s safety is no longer ensured, the instrument is to be put out of service and protected against use. Safety may be compromised if the instrument:
Shows obvious damage
Does not carry out the desired measurements
Has been stored for too long under unfavourable conditions
Has been subjected to mechanical stress during transport.
The instrument may only be used within the operational ranges a specified in the technical data section.
Avoid any heating up of instrument by direct sunlight to ensure perfect functioning and long instrument life.
4
Page 5
4.0 Control Elements and Connections
LED Output Voltage On
LED Output Current higher than
3.5mA acc. IEC61243-3
LED Low Battery
Output 690V DC sockets
Touch Electrode for Continuity Test
Input Sockets for Continuity Test
LED Continuity < 100Ω
5
Page 6
Continuity Testing
Connect test leads across the input sockets for continuity testing. If the lead resistance is below 100Ω the continuity LED will illuminate and the buzzer will be audible. The touch electrode enables quick testing of fused leads.
Proof Testing
Insert the voltage tester probes into the output sockets (690V DC). Apply sufficient pressure to ensure a good connection. Check the voltage indication on the voltage tester under test. Ensure the output voltage LED is on during the test.
N.B.
Please note the output voltage may not be 690V and will depend upon the load applied by the voltage indicator.
6
Page 7
TECHNICAL DATA
LED DISPLAY
Voltage 690V DC
Output Current higher than 3.5 mA
Low Battery
Continuity Test
VOLTAGE TEST
Output Voltage 690V DC /
≥ 200 kΩ load
Test Current ≤ 3,5 mA
CONTINUITY TEST
Continuity Range < 100 Ω
Test Current approx. 1 mA
Temp. Range: 0.40°C/max.70% r.H.
Power Supply: 10 x 1.5 V IEC LR6
Dimension: 220x110x40mm (approx)
Weight: 650g. (approx)
7
Page 8
www.dilog.com