Digiplex DGP-NE96 Reference And Installation Manual

DigiplexNE Control Panel - V1.4
Sabotage-Proof High-Security System
DGP-NE96
Reference and Installation Manual
www.paradox.ca
DIGIPLEXNE CONTROL PANEL 1
INTRODUCTION............................................................... 4
Features................................................................................... 4
Specifications........................................................................... 4
Keypad Specifications........................................ ... ................... 4
INSTALLATION ............................................................... 5
Recommended Installation Procedure..................................... 5
Location & Mounting ................................................................ 5
Earth Ground............................................................................ 5
AC Power.............................................................. ... ................ 5
Backup Battery......................................................................... 5
Battery Test..................................................................................... 5
Auxiliary Power Terminals........................................................ 5
Bell/siren Output.................................................... ................... 5
Programmable Outputs............................................................ 5
Keyswitch Connections............................................................ 5
Access Control Connections.................................................... 5
Calculating Power Requirements............................................. 7
Keypad Zone Connections....................................................... 8
Addressable Zone Connections............................................... 8
Double Zone Connections........................................................ 9
Connecting the DGP2-ZX4 ...................................................... 9
Combus Connections............................................................. 10
Connecting the Combus in Noisy Environments........................... 10
Fire Circuits........................................................ ... ................. 10
Smoke Detector Installation (2-Wire)............................................. 10
ESL CleanMe® Installation ........................................................... 10
Smoke Detector Installation (4-Wire)............................................. 10
Telephone Line Connections ................................................. 10
Built-in RTC......................................................................... ... 11
PROGRAMMING METHODS ......................................... 12
WinLoad Uploading/Downloading Software........................... 12
Paradox Memory Key............................................................. 12
Module Broadcast .................................................................. 12
Programming Through a Keypad........................................... 12
Feature Select Programming ........................................................ 12
Decimal Programming................................................................... 12
Hexadecimal Programming........................................................... 12
Module Programming Mode................................................... 12
ZONE PROGRAMMING ................................................. 13
Zone Numbering .................................................................... 13
Clearing a Zone’s Numbering........................................................ 14
Zone Doubling (ATZ).............................................................. 14
Zone Definitions..................................................................... 14
Zone Disabled ............................................................................... 14
Entry Delays 1 and 2..................................................................... 14
Follow Zones................................................................................. 14
Instant Zones................................................................................. 14
24Hr Buzzer Zones ...................................................................... 14
24Hr Burglary Zones ..................................................................... 14
24Hr Hold-up Zones...................................................................... 14
24Hr Gas Zones............................................................................ 14
24Hr Heat Zones........................................................................... 14
24Hr Water Zones......................................................................... 15
24Hr Freeze Zones ....................................................................... 15
Delayed 24Hr Fire Zone................................................................ 15
Standard 24Hr Fire Zone...................................... ......................... 15
Stay Delay Zone............................................................................ 15
Zone Partition Assignment..................................................... 15
Zone Options.......................................................................... 15
Auto Zone Shutdown ..................................................................... 15
Bypass Zones ................................................................................ 15
Stay Zones..................................................................................... 16
Force Zones................................................................................... 16
Alarm Types................................................................................... 16
Intellizone....................................................................................... 16
Delay Before Alarm Transmission ................................................. 16
Input Speed ........................................................................... 16
EOL on Hardwire Zones........................................................ 16
Keypad Numbering................................................................ 16
KEYSWITCH PROGRAMMING...................................... 17
Keyswitch Numbering............................................................ 17
Keyswitch Definitions............................................................. 17
Keyswitch Disabled........................................................................ 17
Momentary Keyswitch.................................................................... 17
Maintained Keyswitch.................................................................... 17
Generates a Utility Key Event on Open ......................................... 18
Generates a Utility Key Event on Open and Close........................ 18
Keyswitch Partition Assignment............................................. 18
Keyswitch Options................................................................. 18
Stay/Instant Disarm Option (Keyswitch) ........................................ 18
Arm Only (Keyswitch) .................................................................... 18
Regular Arming (Keyswitch) .......................................................... 18
Stay Arming (Keyswitch)................................................................ 18
Force Arming (Keyswitch).............................................................. 18
Instant Arming (Keyswitch)............................................................ 18
ARMING & DISARMING OPTIONS................................ 19
Arming Follows Partition........................................................ 19
Restrict Arming on Supervision Loss..................................... 19
Restrict Arming on Tamper.................................................... 19
Restrict Arming on AC Failure ............................................... 19
Restrict Arming on Battery Failure......................................... 19
Restrict Arming on Bell or Auxiliary Failure ........................... 19
Restrict Arming on TLM Failure............................................. 19
Restrict Arming on Module Troubles ..................................... 19
Timed Auto-Arming................................................................ 19
Auto-Arm Timer.............................................................................. 20
No Movement Auto-Arming ................................................... 20
No Movement Timer ...................................................................... 20
Auto-Arming Options ............................................................. 20
Switch To Stay Arming .......................................................... 20
Always Force Arm when Regular Arming.............................. 20
Follow Zone Switches to Entry Delay 2 ................................. 20
One-touch Features............................................................... 20
Exit Delay.................................................. ... .. ........................ 20
Exit Delay Termination................................................................... 20
No Exit Delay on Remote Arm....................................................... 21
Keypad Lock-out Feature ...................................................... 21
Bell Squawk......... .................................................................. 21
Ring-back............................................................................... 21
Maximum Bypass Entries...................................................... 21
Display “Bypass” If Armed................................... ... ... .. .......... 21
ALARM OPTIONS.......................... ... ... ... ... .... ... ... ... .... ... . 22
Bell/alarm Output............................................................... ... . 22
Bell Cut-off Timer................................................................... 22
No Bell Cut-Off on Fire Alarm ........................................................ 22
Recycle Alarm Rate....................................................................... 22
Recycle Delay................................................................................ 22
Wireless Transmitter Supervision Options............................. 22
Supervision Bypass Options.......................................................... 22
2 REFERENCE & INSTALLATION MANUAL
Police Code Timer............................ ... ... ............................... 22
Tamper Recognition Options................................................. 22
Tamper Bypass Options................................................................ 23
Keypad Panic Options........................................................... 23
EVENT REPORTING...................................................... 24
Reporting Enabled................................................................. 25
Report Codes......................................................................... 25
Zone Alarm and Alarm Restore Report Codes.............................. 25
Tamper and Tamper Restore Report Codes................................. 25
Keyswitch Arming.......................................................................... 25
Keyswitch Disarming..................................................................... 25
Access Codes Arming ................................................................... 25
Access Codes Disarming .............................................................. 25
Special System Reporting Codes.................................................. 25
Special Arming Report Codes....................................................... 25
Special Disarming Report Codes .................................................. 26
Special Alarm Report Codes......................................................... 26
System Trouble Codes.................................................................. 26
System Trouble Restore Codes .................................................... 26
Report Arming and Disarming ............................................... 26
Enable Arming and Disarming Report Schedules ......................... 26
Arming and Disarming Report Schedules ..................................... 27
Arming/Disarming Schedule Tolerance Window ........................... 27
Monitoring Station Phone # ................................................... 27
Partition Account #................................................................. 27
Partition Account Number Transmission ............................... 27
Reporting Formats................................................................. 28
Standard Pulse Formats................................................................ 28
Ademco Express ........................................................................... 28
Contact ID Pager........................................................................... 28
Ademco Contact ID ....................................................................... 28
SIA FSK......................................................................................... 28
Pager Reporting Format................................................................ 28
Event Call Direction....................... ... ... .................................. 28
Maximum Dialing Attempts............................................................ 28
Delay Between Dialing Attempts ................................................... 28
Alternate Dialing Option................................................................. 28
Pager Delay........................................................................... 29
Recent Close Delay................................................... ............ 29
Power Failure Report Delay................................................... 29
Auto Test Report.................................................................... 29
Disarm Reporting Options ..................................................... 29
Zone Restore Report Options................................................ 29
Auto Report Code Programming ........................................... 29
Closing Delinquency Timer.................................................... 29
DIALER OPTIONS.......................................................... 30
Telephone Line Monitoring.................................................... 30
TLM Fail Timer .............................................................................. 30
Tone/pulse Dialing........................................................ ......... 30
Pulse Ratio ............................................................................ 30
Busy Tone Detection ............................................ .. ............... 30
Switch To Pulse..................................................................... 30
Bell On Communication Fail.................................................. 30
Keypad Beep on Successful Arm or Disarm Report.............. 30
Dial Tone Delay.......................... ........................................... 30
PROGRAMMABLE OUTPUTS....................................... 31
PGM Activation Event............................................................ 31
PGM Deactivation Option.................... .................................. 31
Flexible PGM Deactivation Option......................................... 31
PGM Deactivation Event.................................... ... ................. 31
PGM Timer ............................................................................ 31
PGM Time Base Selection ............................................................ 31
PGM1 Becomes a 2-wire Smoke Detector Input................... 31
PGM Test Mode.................................................................... 31
SYSTEM SETTINGS & COMMANDS............................. 32
Hardware Reset .................................................................... 32
Software Reset ...................................................................... 32
Installer Code Lock................................................................ 32
Daylight Savings Time........................................................... 32
Battery Charge Current......................................................... 32
Combus Speed........................................... ........................... 32
Transmit Zone Status on Serial Port..................................... 32
Serial Port Baud Rate.......................................... ... .. ............. 32
Partitioning ............................................................................ 32
Panel Partition Assignment........................................................... 33
Shabbat Feature.................................................................... 33
Installer Function Keys.......................................................... 33
Module Reset........................................................................ 33
Locate Module....................................................................... 33
Module Programming............................................................ 33
Module and Label Broadcast................................................. 33
System Date & Time ............................................................. 34
Clock Compensation Value................................................... 34
Remove Module........................... ... ...................................... 34
Serial Number Viewing.......................................................... 34
Power Save Mode................................................................. 34
Auto Trouble Shutdown......................................................... 34
No AC Fail Display................................................................ 34
Multiple Action Feature.......................................................... 34
System Labels....................................................................... 34
ACCESS CODES............................................................ 36
Installer Code........................................................................ 36
Access Code Length............................................................. 36
System Master Code............................................................. 36
Programming Access Codes................................................. 36
User Options ......................................................................... 36
Partition Assignment ............................................................. 37
Access Control.......................... ........................................ .... 37
Access Level Assignment............................................................. 37
Schedule Assignment ................................................................... 37
Access Control Options................................................................. 37
Access Card Assignment.............................................................. 37
ACCESS CONTROL: SYSTEM FEATURES ................. 38
Common Access Control Terms ........................................... 38
Programming Overview......................................................... 38
Enable Access Control.......................................................... 38
Door Numbering.......................................................... .......... 38
Access Levels ..................................................... ... ............... 38
Access Schedules................................................................. 38
Backup Schedules......................................... ... ... .................. 39
Holiday Programming............................................................ 39
Schedule Tolerance Window................................................. 39
Door Access Mode................................................................ 39
Code Access......................................................................... 39
Card and Code Access ......................................................... 39
Skip Exit Delay When Arming With Access Card.................. 40
Restrict Arming on Door........................................................ 40
Restrict Disarming on Door................................................... 40
Door Access During Clock Loss............................................ 40
Burglar Alarm On Forced Door or Door Left Open................ 40
Logging Access Control Events ............................................ 40
Log Request For Exit In Event Buffer............................................ 40
Log Door Left Open Restore In Event Buffer................................ 40
DIGIPLEXNE CONTROL PANEL 3
Log Door Forced Open Restore In Event Buffer ........................... 40
WINLOAD SOFTWARE.................................................. 41
Panel Identifier.................................. ..................................... 41
PC Password .................................................. ... .................... 41
PC Telephone Number .......................................................... 41
Call Back Feature............................................... .................... 41
Call WinLoad........................................ ... ............................... 41
Answer WinLoad.................................................................... 41
Answering Machine Override Delay.............................. ... ...... 41
Ring Counter.......................................................................... 41
Event Buffer Transmission..................................................... 41
USER FEATURES .......................................................... 42
Regular Arming...................................................................... 42
Stay Arming............................................................................ 42
Stay Arming with Delay ................................................................. 42
Instant Arming........................................................................ 42
Instant Arming with Delay.............................................................. 42
Force Arming........................................... ............................... 42
How to Arm ............................................................................ 42
Disarming.............................................................. ................. 42
Bypass Programming............................................................. 42
Chime Zones..................................... ..................................... 43
Keypad Settings..................................................................... 43
Event Record Display....................................................... ... ... 43
Scroll Restart.......................................................................... 43
Trouble Display.............................. ........................................ 43
Trouble Latch........................................................... .. ............ 44
Clear Bell Current Limit Trouble............................................. 44
APPENDIX 1: PGM PROGRAMMING TABLE............... 45
APPENDIX 2: AUTOMATIC REPORT CODE LIST ....... 52
APPENDIX 3: CONTACT ID REPORT CODE LIST....... 54
INDEX........................................... ... .... ... ... ...................... 55
WARNINGS.. ... ....................................... ... ... .... ... ............ 62
1.0
4 REFERENCE & INSTALLATION MANUAL
1 INTRODUCTION
The integrity of a security system relies not only in the performance of the control panel, keypads, motion detectors and other accessories, but in the ability to communicate information effectively back and forth through the system's wiring. With this in mind Paradox Security Systems created the next evolution in control panel technology: DigiplexNE.
Since data is
constantly transmitted through the 4-wire combus, any attempt to tamper with or disable any module or the wiring is immediately recognized and causes an alarm to be reported whether the system is armed or not.
DigiplexNE also offers the additional benefit of an innovative built-in access control system. Manage, control and monitor the traffic of up to 999 users through 32 secured areas by defining the days and times they are allowed access. By integrating access control and security, DigiplexNE provides the best of both worlds in a feature-rich and user-friendly system.
Beyond offering high security, the combus makes installing and programming effortless by eliminating the need for home run wiring, jumpers and EOL resistors. Connect the modules in any order anywhere on the combus and assign the zones as desired. Since programming a large security system through a keypad can be time consuming and tedious, installers can use the WinLoad software to complete all the programming remotely, including setting a motion detector's sensitivity. Even users can modify their security system through the comfort of their own computer with NEware, a simple, intuitive interface designed to add employees, set schedules, assign access rights, view the status of the system and all its modules and more.
CTR-21 APPROVAL The DigiplexNE control panel (DGP-NE96) meets the European Union Common Technical Requirement CTR-21. The CTR-21 requirement is an electrical standard that defines the analogue interface for all two-wire telecommunications equipment (i.e. DECT, PABXs, etc.) intended for connection to the Public Switched Telephone Network. This allows the DigiplexNE control panel to be used in as many as 19 countries, such as Belgium, Germany, Greece, Portugal, Sweden and Switzerland. DigiplexNE control panels with the CTR-21 approval are available as an option only.
1.1 FEATURES
Digital combus:
• Provides constant power, supervision and two-way communication between the control panel and all its modules
• Supports up to 127 modules
• Connect modules up to 3000ft (914m) from the panel
• Sabotage-proof technology without additional wiring
96 addressable zones8 partitions998 user codes, 1 System Master code and 1 installer codeBuilt-in access control 2048 stored events1 telephone line and optional secondary telephone lineRemote diagnostics and pager messagingFalse alarm prevention features32 independent keyswitch zones (does not use any of the 96 zones)8 on-board hardwired input terminals 3 on-board fully programma ble outputs (PGMs):
• 1 normally open, high-current transistor output (100mA)
• 2 normally open or normally closed 5A programmable relay outputs
• Up to 32 more PGM inputs through the Keyswitch’s PGM Input feature
PGM1 can be set as a two-wire smoke detector inputEvent reporting:
• a separate dialing sequence for each partition
• 4 Monitoring Station Telephone Numbers
• SIA, Contact ID, Ademco Contact ID Edition 2000, Pager Format and many more communicator formats
1.2 SPECIFICATIONS
CONTROL PANEL (NON-UL SYSTEMS)
AC Power: 16Vac, 20/40VA, 50-60Hz Battery: 12Vdc, 4Ah minimum Auxiliary Power: 12Vdc 600mA typical, 700mA maximum,
fuseless shutdown at 1.1A Bell Output: 1A, fuseless shutdown @ 3A PGM Output: PGM1 (100mA), PGM2 and PGM3 (5A relay) Event Buffer: 2048 events All control panel outputs are rated to operate between 10.8Vdc and
12.1Vdc
CONTROL PANEL (UL COMPLIANT SYSTEMS)
AC Power: 16Vac, 40VA, 60Hz Battery: 12Vdc, 4Ah minimum Auxiliary Power: 11.4 to 12.5Vdc, 200mA maximum, fuseless
shutdown at 1.1A Bell Output: 11.4 to 12.5Vdc, 1A maximum, fuseless
shutdown @ 3A PGM Output: PGM1 (100mA), PGM2 and PGM3 (5A relay) Event Buffer: 2048 events All control panel outputs are rated to operate between 11.4Vdc and
12.5Vdc
1.3 KEYPAD SPECIFICATIONS
Power input: 9-16 Vdc Typ. current consumption:60mA (DGP2-641)
45mA (DGP2-648) PGM current limit: 50 mA Number of inputs: 1 Power indication: Yellow LED on Locate indication:
Green and yellow LEDs flash simultaneously Combus fault indication: Red and yellow LEDs flash alternately Tamper Switch: Yes (also used to deactivate locate) LCD: Super Twisted Nematic display (STN), wide
viewing angle, 2 lines of 16 characters,
adjustable scrolling speed, backlight and
contrast
Specifications may change without prior notice.
UL Note: The DGP-NE96 control panel has only been tested with the LCD Keypad (DGP2-641)
General Note
When programming with the Grafica keypad (DNE-K07), the steps may differ. If not indicated, please refer to Grafica’s On-line Manual, which can be downloaded for free from our Web site at www.paradox.ca.
DIGIPLEXNE CONTROL PANEL 5
2 INSTALLATION
2.1 RECOMMENDED INSTALLATION PROCEDURE
This procedure is recommended to facilitate installation by verifying the wiring at different stages instead of only at the end. Step 1: Install the control panel. Step 2: Connect a portion of the system’s modules, including a keypad, to
the combus.
Step 3: Connect the battery and then connect the AC power. Only the Clock
Loss trouble should appear. Step 4: Disconnect AC power and the battery. Step 5:Continue the installation by following steps 2, 3 and 4. Step 6:Once the installation is complete, enter section [4000] to verify if all
the modules’ serial numbers appear (see section 11.19 on page
34). If modules were removed from the combus, enter [4005] to
remove them from the panel’s memory (see section 11.18 on page
34).
Step 7:Connect an LCD Keypad at various points farthest from the control
panel and use the keypad’s built-in Voltmeter to verify the combus’s
voltage (refer to the Digiplex/DigiplexNE LCD Keypad Reference &
Installation Manual).
2.2 LOCATION & MOUNTING
Before mounting the cabinet, push the five white nylon mounting studs into the back of the cabinet. Pull all cables into the cabinet and prepare them for connection before mounting the circuit board into the back of the cabinet. Select an installation site that is not easily accessible to intruders and leave at least 2" around the panel box to permit adequate ventilation and heat dissipation. The installation site should be dry and close to an AC source, ground connection and telephone line connection.
2.3 EARTH GROUND
Connect the zone and dialer ground terminals from the control panel to the enclosure and cold water pipe or grounding rod as per lo cal electrical codes.
For maximum lightning protection, use separate earth grounds for the zone and dialer grounds (see Figure 2-3 on page 6).
2.4 AC POWER
Use a 16.5Vac (50/60Hz) transformer with a minimum 20VA rating to provide sufficient AC power. For increased power use a transformer with a 40VA rating. For UL Listed systems, use model #BE156240CAA. For CSA listed systems, use model #BE116240AAA. Do not use any switch­controlled outlets to power the transformer. Connect the transformer as shown in Figure 2-3 on page 6.
Do not connect the transformer or the backup battery until all wiring is completed.
PLEASE NOTE: When powering up the DGP-NE96 control panel (V1.02 or higher), the panel will begin a module scan to verify if all the modules connected to the control panel are operational. The scanning process will take between 30 and 120 seconds to complete depending on the number of modules connected to the control panel. The module scan is complete when the keypad begins to show the partition status. Only after the module scan is complete will the control panel be fully operational.
2.5 BACKUP BATTERY
To provide power during power loss, connect a 12Vdc 4Ah rechargeable acid/lead or gel cell backup battery (YUASA model #NP7-12 recommended) as shown in Figure 2-3 on page 6. Connect the backup battery after applying AC power. When installing, verify proper polarity, as reversed connections will blow the battery fuse. For details on how to set the Battery Charge Current to either 350mA or 700mA, see section 11.5.
2.5.1 Battery Test
The control panel conducts a dynamic battery test under load every 64 seconds. If the battery is disconnected, if its capacity is too low or if the battery voltage drops to 10.5 volts or less when there is no AC, the “Battery Trouble” message will appear in the Trouble Display. At 8.5 volts, the panel shuts down and all outputs close.
2.6 AUXILIARY POWER TERMINALS
The auxiliary power supply can power the motion detectors, keypads and other accessories in the security system. A fuseless circuit protects the auxiliary output against current overload and automatically shuts down if the current exceeds 1.1A. Auxiliary power will resume once the overload condition has restored. For details on available output power, please refer to Figure 2-3 on page 6. To calculate power consumption, see Calculating Power Requirements on page 7.
2.7 BELL/SIREN OUTPUT
The
BELL+ and BELL- terminals power bells and/or other warning devices
that require a steady voltage output during an alarm. The bell output supplies 12Vdc upon alarm and can support one 30-watt or two 20-watt sirens. The bell output uses a fuseless circuit and will automatically shut down if the current exceeds 3A. If the load on the
BELL terminals returns to
normal (3A), the control panel will re-instate power to the
BELL terminals.
When connecting sirens, please verify correct polarity as shown in Figure 2-3. PGM2 and PGM3 are relays rated at 5A each and can be used to power bells and/or other warning devices by programming them as a bell/ siren outputs (see section 10 on page 31).
When the bell output is not used, the “Bell Absent” message appears in the Trouble Display. To avoid this, connect a 1k
resistor across the bell output. UL Note: The keypads must be programmed to beep with all troubles
2.8 PROGRAMMABLE OUTPUTS
The control panel comes standard with PGM1 to PGM3. When a specific event or condition occurs in the system, a PGM can be programmed to reset smoke detectors, activate strobe lights, open/close garage doors and much more. For details on how to program the PGMs, refer to section 10.
PGM1 is 100mA (max.) normally open output. PGM2 and PGM3 are 5A relay outputs that can be normally open or normally closed. If the current draw on PGM1 is to exceed the current output, we recommend using a relay as shown in Figure 2-1. PGM1 can be programmed as a 2-wire smoke detector input (see section
2.17.1 on page 10 and section 10.6 on page 31).
2.9 KEYSWITCH CONNECTIONS (NOT VERIFIED BY UL)
Connect the keyswitches to the keypad, control panel, or Zone Expansion Module's hardwired input terminals as shown in Figure 2-2. Once a keyswitch is connected, it must be assigned a keyswitch zone and its parameters must be defined as described in Keyswitch Programming on page 17.
2.10 ACCESS CONTROL CONNECTIONS
For all access control explanations and connection drawings, refer to Access Control: System Features on page 38.
Figure 2-1: PGM & Relay
Figure 2-2: Keyswitch
6 REFERENCE & INSTALLATION MANUAL
Figure 2-3: DigiplexNE Control Panel Wiring Diagram
This equipment should be installed in accordance with Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72, (National Fire Protection Association, Batterymarch Park, Quincy, MA 02269). Printed information describing proper installation, operation, testing, maintenance, evacuation planning, and repair service is to be provided with this equipment.
When installing the combus wires in a noisy environment, or when connecting the combus across separate buildings, you must use a shielded cable. Refer to section 2.16.1 on page 10.
PLEASE NOTE: When powering up the DGP-NE96 control panel (V1.02 or higher), the panel will begin a module scan to verify if all the mod ule s connected to the panel are operational. The scanning process will take between 30 and 120 seconds to complete depending on the numb er of modules connected to the control panel. The module scan is complete when the LCD keypad begins to show the partition status. Only after the module scan is complete will the control panel be fully operational.
PLEASE NOTE: It is strongly recommended that you test your system on a weekly basis, and have your system checked by a qualified technician a minimum of every 3 years.
Please see “UL and ULC Warnings” on page 62 for applicable UL/ ULC warnings and information.
WARNING: This equipment must be installed and maintained by qualified service personnel only.
DIGIPLEXNE CONTROL PANEL 7
2.11 CALCULATING POWER REQUIREMENTS
STEP 1: Using Table 1, calculate the total number of power units (PU) required by each device, module, and accessory in the system. Please take into
account devices connected to the control panel’s PGM outputs. Since the
BELL output has its own power supply, do not include the sirens
connected to it in the calculation.
STEP 2:
If Grand Total is less than 700PU, go to step 3. If the value is greater, an external power supply is required (see Figure 2-5 on page 8) to provide the additional power needed. Proceed with step 3 and refer to the example in Figure 2-4 on page 8.
STEP 3: Due to the degradation of a power signal over long distances, EACH length or run of wire in the system can support only a specific number of
power units (PU). Using Table 2, determine how many power units each length of wire can support. Please note that the total number of power units (PU) can never surpass 700PU.
If multiple runs of wire are being used, the total distance of all the runs combined cannot exceed 3000ft. (1000m). For example, if ten runs of wire each measuring 1000ft. (305m) were con nected, the total distance would b e 10,000ft. (3048m) and therefore exceeds the system’s capacity.
Table 1: Power Unit Consumption Table
Description QTY. PU used by each Total PU
LCD Keypad (DGP2-641):
_______
X 60PU =
__________ PU
Access Control Module (DGP2-ACM1P):
_______
X 165PU =
__________ PU
Addressable Digital Motion Detectors (DGP2-50/60/70):
_______
X 16PU =
__________ PU
Addressable Door Contact (DGP2-ZC1)
_______
X 14PU =
__________ PU
1-Zone Hardwire Expansion Module (DGP2-ZX1)
_______
X 15PU =
__________ PU
4-Zone Hardwire Expansion Modules (APR3-ZX4)
_______
X 20PU =
__________ PU
8-Zone Hardwire Module (APR3-ZX8)
_______
X 40PU =
__________ PU
Omnia 433MHz Wireless Receiver Module (OMN-RCV3):
_______
X 50PU =
__________ PU
1-PGM Output Expansion Module (APR3-PGM1):
_______
X 50PU =
__________ PU
4-PGM Output Module (APR3-PGM4):
_______
X 150PU =
__________ PU
Printer Module (APR3-PRT1)
_______
X 40PU =
__________ PU
InTouch Voice-Assisted Arm/Disarm Module (APR3-ADM2)
_______
X 70PU =
__________ PU
Maximum available power units = 700PU GRAND TOTAL __________ PU
Table 2: Power Unit (PU) Limitations For Each Run of Wire
Gauge: 18AWG, Surface: 0.823mm
2
Gauge: 22AWG, Surface: 0.326mm
2
Gauge: 24AWG, Surface: 0.205mm
2
Length of each run of wire
Available Power Units (PU)
Length of each run of wire
Available Power Units (PU)
Length of each run of wire
Available Power Units (PU)
100ft. (30m) 700 100ft. (30m) 700 100ft. (30m) 700 200ft. (61m) 700 200ft. (61m) 682 200ft. (61m) 429 300ft. (91m) 700 300ft. (91m) 454 300ft. (91m) 286 400ft. (122m) 700 400ft. (122m) 341 400ft. (122m) 214 500ft. (152m) 690 500ft. (152m) 273 500ft. (152m) 171 600ft. (183m) 575 600ft. (183m) 227 600ft. (183m) 143 700ft. (213m) 493 700ft. (213m) 195 800ft. (244m) 431 800ft. (244m) 170 900ft. (274m) 383 900ft. (274m) 151 1000ft. (305m) 345 1000ft. (305m) 136 1500ft. (457m) 230 2000ft. (610m) 172 2500ft. (762m) 138 3000ft. (914m) 115
8 REFERENCE & INSTALLATION MANUAL
Figure 2-4: Sample Power Requirement Calculations
An LCD Keypad (80PU) can be added to the 100ft. or 300ft. wire in Figure 2-4, but adding an LCD Keypad to the 1000ft. wire would exceed the wire’s limits and cause devices to function at decreased capacity.
Figure 2-5: External Power Supply Connections
Do not use the same transformer for the cont rol panel and the external power supplies. Do not install modules more than 3000ft (914m) from the control panel.
2.12 KEYPAD ZONE CONNECTIONS
Each keypad has one hardwired input terminal allowing you to connect a detector or door contact directly to the keypad. For example, a door contact located at the entry point of an establishment can be wired directly to the input terminal of the entry point keypad instead of back to the control panel.
Even with the ATZ feature enabled in the control panel, only one device can be connected to the keypad’s hardwired input terminal. Tamper is not recognized on keypad zones. The keypad zone follows the control panel’s EOL definition.
A device connected to the keypad’s input terminal must be assigned to a zone in the control panel and the zone’s parameters must be defined (see Zone Programming on page 13). The keypad communicates the status of the zone to the control panel via the combus. The detection device is connected as shown in Figure 2-3 on page 6.
2.13 ADDRESSABLE ZONE CONNECTIONS
The control panel includes eight hardwired input terminals for use with traditional hardwired (non-combus) door contacts, smoke detectors and/or motion detectors.
The control panel also supports several hardwire zone expansion modules. Devices connected to hardwired input terminals must be assigned to a zone and the zone's parameters must be defined (see Zone Programming on page 13). Figure 2-6 shows single zone (ATZ disabled) hardwire input terminal connections recognized by the DigiplexNE system. For UL listed installations, use EOL resistor part #2011002000.
As indicated in Table 2 on page 7, this run of wire can support 700PU. Total PU on this run of wire: (A) 40PU + (B) 40PU = 80PU<700PU = OK
As indicated in Table 2 on page 7, this run of wire can support 454PU. Total PU on this run of wire: (D) 60PU + (E) 16PU + (F) 60PU + (G) 60PU = 196PU<454PU = OK
As indicated in Table 2 on page 7, this run of wire can support 136PU. Total PU on this run of wire: (A) 40PU + (C) 16PU = 56PU<136PU = OK
DIGIPLEXNE CONTROL PANEL 9
Figure 2-6: Single Zone Input Connections
2.14 DOUBLE ZONE CONNECTIONS
Enabling the ATZ feature (see section 4.2) allows you to install two detection devices per input terminal. Connect the devices as shown in Figure 2-7. Devices connected to input terminals must be assigned to a zone and the zone's parameters must be defined (see Zone Programming on page 13). For UL listed Burglary System installations only, use EOL resistor part #2011002000.
Figure 2-7: Double Zone Connections
2.15 CONNECTING THE DGP2-ZX4
The 4-Zone Expansion Plug-in Device* (DGP2-ZX4*) provides four additional hardwired input terminals (8 zones with ATZ enabled). It connects directly to the control panel through its on-board
EXPANSION
connector as shown in Figure 2-3: on page 6. Connect detection devices to the DGP2-ZX4's terminals in the same way that they are connected to the control panel as shown in Figure 2-6 or Figure 2-7 on page 9. Devices connected to hardwired input terminals must be assigned to a zone and the zone's parameters must be defined (Zone Programming on page 13). For the 4-Zone Expansion Module (APR3-ZX4), refer to the DigiplexNE Modules Programming Guide.
* Do not use with UL Listed systems.
Enable ATZ (see section 4. 2 on page 14) and connect as follows (extra input cannot be used)
10 REFERENCE & INSTALLATION MANUAL
2.16 COMBUS CONNECTIONS
Modules can connect anywhere on the 4-wire combus, which can support up to 127 modules. Connect in a star and/or daisy chain configuration as shown in Figure 2-3 on page 6. The final device on the combus should not be more than 3000ft (914m) from the control panel. To assign a detection device to a zone in the control panel, see “Zone Programming” on page 13.
Before connecting a module to the combus, remove AC and battery power from the control panel.
2.16.1 Connecting the Combus in Noisy Environments
When installing the combus wires in proximity to high electrical interferences such as neon lights, motors, high-voltage wiring, transformers, or if connecting the combus across separate buildings, you must use shielded cables. Connect the shielded cable as detailed below:
Within the Same Building: Strip the outer jacket at one end of the shielded cable to expose the shield and connect the shield to the control panel ground (not the dialer ground), while leaving the shield at the other end of the cable open (floating).
Across Separate Buildings: Strip the outer jacket at one end of the shielded cable to expose the shield. In the same building that houses the control panel, connect the exposed shield to a cold water pipe or any other earth ground available, while leaving the shield at the other end of the cable open (floating). The same configuration applies for any subsequent building.
2.17 FIRE CIRCUITS
Connect the smoke detectors using any of the following methods. Assign the smoke detectors connected to the control panel or zone expansion input terminals to a zone and define the zone's parameters as a Fire Zone (see section 4 on page 13).
2.17.1 Smoke Detector Installation (2-Wire)*
PGM1 can be defined as a 2-wire smoke detector input (see section
10.6). Connect the 2-wire smoke detectors as shown in Figure 2-8 using a 1k
EOL resistor. If a line
short occurs or the smoke detector activates, whether the system is armed or disarmed, the control panel will generate an alarm. If the line is open, the “Zone Fault” trouble indication appears in the Trouble Display and the report code is sent to the Monitoring Station, if programmed.
*
UL Note: Not to be used with UL Listed systems.
2.17.2 ESL CleanMe® Installation
The DigiplexNE control panel supports ESL smoke detectors that have the CleanMe
®
feature. Connect ESL smoke detectors like the standard smoke detectors shown in Figure 2-8. Avoid connecting more than 20 ESL smoke detectors. When an ESL smoke detector sends a CleanMe signal, the control panel will generate a Zone Fault trouble and, if programmed, will transmit the Fire Loop report code to the Monitoring Station. The trouble will be cleared if there is no CleanMe signal for 255 seconds. If an alarm occurs, the trouble will be cleared until it is detected again.
2.17.3 Smoke Detector Installation (4-Wire)
Recommended: System Sensor model 2112/24D smoke detectors. Connect the 4-wire smoke detectors and a relay as shown in Figure 2-9. To comply with UL955, install the 4-wire smoke detectors with 18 gauge wire. If power is interrupted, the relay causes the control panel to transmit the Fire Loop Trouble report programmed in section [2906].
To reset (unlatch), connect the smoke detector’s negative (-) to a PGM. Then program the PGM with the “Smoke Detector Power Reset” activation event (see section 10.1 on page 31; Event Group #067, start # 004, end # 004) to interrupt power to the smoke detector for four seconds when the [
CLEAR] and
[
ENTER] keys are pressed and held for two
seconds.
If ATZ is enabled (see see section 4.2 on page 14), do not use the extra input (doubled zone). For example, in th is example input 13 cannot be used.
2.18 TELEPHONE LINE CONNECTIONS
Depending on the installation, the telephone lines can be connected directly to the control panel or through a CA38A or RJ31 as shown in Figure 2-10. The secondary telephone line terminals (optional) can be used as a backup telephone line. If the Event Call Direction process fails and the control panel is unable to communicate with the Monitoring Station through the main line, the control panel will switch to the second line and repeat the Event Call Direction process (see section 8.8 on page 28).
UL Note: Installer must verify line seizure after every installation
Figure 2-10: Telephone Line Connection Examples
Figure 2-8:
2-Wire Detectors
Note: It is recommended that the smoke detectors be connected in a daisy chain configuration.
Figure 2-9: 4-Wire Detectors
Note: It is recommended that the smoke detectors be connected in a daisy chain configuration.
DIGIPLEXNE CONTROL PANEL 11
For TBR-21 compliance, please note the following:
1) The DGP-NE96 can be connected to the telephone network via an RJ­11 connector.
2) The Maximum Dialing Attempts cannot exceed 15 attempts (page 28).
2.19 BUILT-IN RTC
The DigiplexNE incorporates an RTC directly on the PC board. The RTC will save the DigiplexNE’s internal clock when both the AC and battery power have been lost. After power is lost and then restored, the DigiplexNE will verify with and then retrieve the time from the RTC. The control panel will verify and compare its time with the time stored in the RTC every hour. If the times are different, the DigiplexNE will reset its internal clock to the time saved in the RTC. The RTC uses a 3V lithium battery (CR2032) with a battery life of 11 years. Change the battery as shown below:
Figure 2-11: Changing the RTC’s Battery
Reprogram the control panel’s clock after changing the battery. WARNING! Danger of explosion exists if the lithium battery is
incorrectly replaced. Replace only with the same or equivalent type recommended by the manufacturer. Dispose of used batteries according to the manufacturer’s instructions.
12 REFERENCE & INSTALLATION MANUAL
3 PROGRAMMING METHODS
DigiplexNE can be programmed using the following methods:
3.1 WINLOAD UPLOADING/DOWNLOADING SOFTWARE*
We highly recommend programming the control panel with WinLoad as it greatly simplifies the process and reduces potential data errors. Refer to Winload Software on page 41 for details.
* UL Note: Not verified by UL
3.2 PARADOX MEMORY KEY (NOT TO BE USED WITH UL LISTED SYSTEMS)
The Paradox Memory Key can copy the programmed contents of one control panel into as many others as needed. Downloading is completed in less than 5 seconds.
Copy to Memory Key
1) Place the Memory Key on the control panel’s connector labeled
MEM KEY. Make sure that the write
protect jumper is on.
2) Enter section: [4020] to copy the control panel’s contents except sections [0001] to [0096] and [0501] to [0532] to the key.
[4021] to copy the control panel’s contents including sections [0001] to [0096] and [0501] to [0532] to the key.
3) When the keypad emits a Confirmation Beep, remove the Memory Key. Remove the jumper to prevent accidentally overwriting the Memory Key’s contents.
Download to Control Panel
1) Place the Memory Key on the control panel’s connector labeled
MEM KEY.
2) Enter section:
[4010] to download the Memory Key’s contents except sections [0001] to [0096] and [0501] to
[0532] to the control panel.
[4011] to download the contents of the Memory Key including sections [0001] to [0096] and [0501] to
[0532] to the control panel.
3) When the keypad emits a Confirmation B eep, remo ve the Mem ory Ke y.
Figure 3-1: Using the Memory Key
3.3 MODULE BROADCAST
Keypads and other modules can also be programmed easily by using Module Broadcast (see section 11.15 on page 33). Once a module is programmed, its sections can be sent to other similar modules through the combus.
3.4 PROGRAMMING THROUGH A KEYPAD
Use the Programming Guide to record how the sections were programmed. To enter programming mode:
For LCD Keypads: The control panel will save the data and automatically advance to the next section or press the [
ENTER] key to save the data and
advance to the next section. Press the [
CLEAR] key to revert to the
preceding step or to erase the current data entry. For Grafica Keypads: After entering the required data, press Grafica’s
center action key (Save) to save the data and advance to the next section. Press the right action key (Exit) to revert to the preceding step or press the left action key (Clear) to erase the current data.
3.4.1 Feature Select Programming
Most of the options are programmed using the Feature Select Method.
For LCD Keypads:
Each number from 1 to 8 corresponds to a specific feature or option. Set these options by turning the number corresponding to the feature ON or OFF. The option is considered ON when the number appears within the brackets on the LCD keypad. Turn options ON and OFF by pressing the corresponding keys on the keypad. Press the keys as many times as needed to select the desired options and then press
[
ENTER
]
to save.
For Grafica Keypads: Select or clear the check boxes pertaining to the options or features that you wish to enable or disable. You can also set the options by pressing the corresponding keys on the keypad. The feature is considered ON when its check box is selected. To save the settings, press the Grafica’s center action key (Save).
3.4.2 Decimal Programming
Certain sections may require the entry of a 3-digit decimal value from 000 to 255.
3.4.3 Hexadecimal Programming
Certain sections may require the entry of one or more Hexadecimal values from 0 to F. Press:
For LCD Keypads: [0] to [9] = values 0 to 9 respectively [
STAY] key = A [DISARM] key = D
[
FORCE] key = B [BYP] key = E
[
ARM] key = C [MEM] key = F
For Grafica Keypads: [0] to [9] = values 0 to 9 respectively [*] = A to F (press the key until the desired letter appears)
3.5 MODULE PROGRAMMING MODE
All modules are programmed through any keypad in the system. To do so, enter Module Programming Mode:
The control panel will redirect all programming to the selected module. To exit the Module Programming Mode, press the [
CLEAR] key on LCD
keypads, or the right action key (Exit) on Grafica keypads, as many times as needed to return to the desired screen. The module's serial number can be located on the module's PC board.
1) Press and hold the [0] key
2) Key in the [
INSTALLER CODE] (Default is 000000)
3) Key in the 4-digit [
SECTION]
4) Key in required [
DATA]. Refer to the Programming Guide or to the
corresponding sections in this manual.
1) Press and hold the [0] key
2) Key in the [
INSTALLER CODE] (Default is 000000)
3) Key in section [4003]
4) Key in 8-digit [
SERIAL NUMBER] of the module
5) Key in 3-digit [
SECTION] and required [DATA]. Refer to the Module
Programming Guide for details.
DIGIPLEXNE CONTROL PANEL 13
4 ZONE PROGRAMMING
All detection devices connected to the control panel, keypads and zone expansion modules must be assigned to a zone and that zone must be defined as described in this section.
Figure 4-1: Zone Programming
4.1 ZONE NUMBERING
S
ECTIONS [0001] TO [0096]
The Zone Numbering feature is used to individually assign each detection device to any zone in the DigiplexNE system (see Figure 4-1). The Zone Parameters define the type of zone, the zone's partition assignment and how the control panel will react when an alarm occurs on that zone (see section 4.3 to section 4.5).
• To assign an addressable PIR or door contact to the combus, program the module’s serial number into the section corresponding to the desired zone (i.e. program zone 34 in section [0034]).
• To assign a detection device connected to a module or control panel's hardwired input terminal, program the module's or control panel's serial number and the input number where the device is connected into the section corresponding to the desired zone. See the Module Programming Guide for details of its input numbers (input numbers not required for keypad zones).
If PGM1 is defined as a smoke detector input (see section
10.6), the control panel will recognize it as input # 255.
Figure 4-2: Zone Numbering
Press & hold the
[0]
key
Zone Definition
First Digit
Zone Partition
Assignment
Second Digit
Zone Options
Feature Select
Enter the 8-digit
[
SERIAL NUMBER
]
of the
addressable detection device
or module that has a hardwire
device connected to it.
Enter the module's 3-digit
[
INPUT NUMBER
]
where the
hardwire device is connected.
NOTE:
For addressable PIRs, door
contacts and keypads, no input # is
required
Key in the
[
INSTALLER CODE
]
Zone Definitions
0- Disabled (Default)
8- 24Hr Gas 1- Entry Delay 1 9- 24Hr Heat 2- Entry Delay 2 A- 24Hr Water 3- Follow B- 24Hr Freeze 4- Instant C- Delayed 24Hr Fire 5- 24Hr Buzzer D- Standard 24Hr Fire 6- 24Hr Burglary E- Stay Delay 1 7- 24Hr Hold-up F- Stay Delay 2
Zone Partition Assignment
1- Zone Assigned to Partition 1 (Default)
2- Zone Assigned to Partition 2 3- Zone Assigned to Partition 3 4- Zone Assigned to Partition 4 5- Zone Assigned to Partition 5 6- Zone Assigned to Partition 6 7- Zone Assigned to Partition 7 8- Zone Assigned to Partition 8
Zone Options
[1] Auto Zone Shutdown
[2] Bypass Zone (Default)
[3] Stay Zone [4] Force Zone [5] [6] Zone Alarm Type off off Audible Alarm (steady) off on Audible Alarm (pulsed) on off Silent Alarm on on Generates only a report [7] Intellizone [8] Delay before transmission
Press
[
ENTER
]
Key in 4-digit
[
SECTION
]
Select
one only
Zone Parameters
Sections
[0101]
to
[0196]
represent
zones 1 to 96 respectively
Select
one only
Zone Numbering
Sections
[0001]
to
[0096]
represent
zones 1 to 96 respectively
Select one
or more
Input 2
Hardwired
Device B
Control Panel
SN#:020000A2
APR3-ZX8 Module
SN#: 34000041
Input 5
Detector A
SN#: 21000033
C
OMMUNICATION NETWORK
Input Terminals
1 2 3 4 5 6 7 8
Detector A: Hardwired Device A: Hardwired Device B: Hardwired Device C:
Zone#
1 = 2 = 3 = 4 =
Section#
[0001] [0002] [0003] [0004]
Serial#
21000033 1A000252 020000A2 34000041
Input#
N/A N/A 002 005
Keypad
SN#: 1A000252
Keypad Zone
Hardwired
Device C
Hardwired
Device A
Input Terminals
1 2 3 4 5 6 7 8
14 REFERENCE & INSTALLATION MANUAL
4.1.1 Clearing a Zone’s Numbering
For LCD Keypads:
1) Enter a section number between [0001] to [0096].
2) Press [0] and then [
ENTER] to save and exit.
For Grafica Keypads:
1) Enter a section number between [0001] to [0096].
2) Press [0] to clear the serial number
3) Use Grafica’s scroll keys, highlight the input number and then press [0] to clear the data.
4) Press Grafica’s center action key (Save) to save and exit.
4.2 ZONE DOUBLING (ATZ)
SECTION [3033]: OPTION [8]
(Default = disabled) The ATZ feature is a software oriented feature that enables two detection devices to be installed per hardwired input terminal (section 2.15 on page 9 and see section 2.14 on page 9). Each detection device has its own zone, displays its zone status on the keypad and sends its own alarm codes. Fire Zones cannot be doubled.
4.3 ZONE DEFINITIONS
The 16 zone definitions from Figure 4-1 on page 13 are described below. When an alarm occurs, the control panel can send a report, activate the bell output and display the alarm in the Alarm Memory.
4.3.1 Zone Disabled
SECTIONS [0101] TO [0196]: FIRST DIGIT = 0
Disables the corresponding zone. Zones are disabled by default.
4.3.2 Entry Delays 1 and 2
SECTIONS [0101] TO [0196]: FIRST DIGIT = 1 AND 2
(Default Entry Delay 1= 030, Entry Delay 2 = 060) When an armed zone defined as an Entry Delay opens, the control panel will not generate an alarm until the Entry Delay Timer elapses. A zone defined as Entry Delay 1 follows the Entry Delay 1 Timer of its assigned partition. Likewise, a zone defined as Entry Delay 2 follows the Entry Delay 2 Timer of its assigned partition.
For example, if zone 1 is assigned to Partition 5 and is defined as Entry Delay 1, the timer follows the amount programmed in [3511].
Each partition includes two Entry Delay Timers. To program an Entry Delay Timer, key in the desired 3-digit delay value (001 to 255 seconds) into the corresponding section.
Entry Delay zones are commonly used at the entry/exit points (i.e. front/ back door or garage). Using different Entry Delays is useful when one entry point requires a longer delay than another.
These are the same timers used for Stay Delay zones (see section
4.3.14).
4.3.3 Follow Zones
SECTIONS [0101] TO [0196]: FIRST DIGIT = 3
If an armed Follow zone opens, the control panel generates an alarm. If an armed Entry Delay zone (see section 4.3.2) opens before the Follo w zone, the control panel waits until the end of the Entry Delay before generating an alarm. If more than one Entry Delay zone opens before the Follow zone, the control panel waits until the end of the first Entry Delay before generating an alarm. This feature is commonly used when a motion detector is protecting the area occupied by the entry point keypad. This will prevent the motion detector from causing an alarm when a user enters through the entry point to disarm the system.
4.3.4 Instant Zones
SECTIONS [0101] TO [0196]: FIRST DIGIT = 4
When an armed Instant zone opens, the control panel immediately generates an alarm. Instant zones are commonly used for windows, patio doors, skylights and other perimeter type zones.
4.3.5 24Hr Buzzer Zones
SECTIONS [0101] TO [0196]: FIRST DIGIT = 5
Whenever a 24Hr Buzzer zone opens, whether the zone is armed or disarmed, the control panel activates the keypad buzzer to indicate that the zone was breached. The control panel will report the alarm, but will not enable the bell/siren output. Enter any valid access code on the keypad to stop the buzzer.
The keypads must be assigned to the same partition as the 24Hr Buzzer zone or the buzzer will not activate. UL Note: Not to be used for perimeter protection.
4.3.6 24Hr Burglary Zones
SECTIONS [0101] TO [0196]: FIRST DIGIT = 6
When a 24Hr Burglary zone opens, whether the system is armed or disarmed, the control panel will immediately generate a burglary alarm.
4.3.7 24Hr Hold-up Zones
SECTIONS [0101] TO [0196]: FIRST DIGIT = 7
When a 24Hr Hold-up zone opens, whether it is armed or disarmed, the control panel will immediately generate an alarm. The SIA FSK reporting format includes specific codes to identify the alarm as a Hold-up Alarm.
4.3.8 24Hr Gas Zones*
SECTIONS [0101] TO [0196]: FIRST DIGIT = 8
When a 24Hr Gas zone opens, whether it is armed or disarmed, the control panel will immediately generate an alarm. The SIA FSK reporting format includes specific codes to identify the alarm as a Gas Alarm.
4.3.9 24Hr Heat Zones**
SECTIONS [0101] TO [0196]: FIRST DIGIT = 9
When a 24Hr Heat zone opens, whether it is armed or disarmed, the control panel will immediately generate an alarm. The SIA FSK reporting format includes specific codes to identify the alarm as a Heat Alarm.
** UL Note: UL Listed compatible devices shall be used for UL systems. For UL Listed systems, this type of zone shall be programmed as a pulsing Fire alarm.
Input Doubled Zone Input
Input 01 Input 13 (ATZ of Input 01) Input 02 Input 14 (ATZ of Input 02) Input 03 Input 15 (ATZ of Input 03) Input 04 Input 16 (ATZ of Input 04) Input 05 Input 17 (ATZ of Input 05) Input 06 Input 18 (ATZ of Input 06) Input 07 Input 19 (ATZ of Input 07) Input 08 Input 20 (ATZ of Input 08) Input 09 (DGP2-ZX4 Input 01) Input 21 (ATZ of Input 09) Input 10 (DGP2-ZX4 Input 02) Input 22 (ATZ of Input 10) Input 11 (DGP2-ZX4 Input 03) Input 23 (ATZ of Input 11) Input 12 (DGP2-ZX4 Input 04) Input 24 (ATZ of Input 12)
Partition 1
Entry Delay 1 Timer: [3111] Entry Delay 2 Timer: [3112]
Partition 5
Entry Delay 1 Timer: [3511] Entry Delay 2 Timer: [3512]
Partition 2
Entry Delay 1 Timer: [3211] Entry Delay 2 Timer: [3212]
Partition 6
Entry Delay 1 Timer: [3611] Entry Delay 2 Timer: [3612]
Partition 3
Entry Delay 1 Timer: [3311] Entry Delay 2 Timer: [3312]
Partition 7
Entry Delay 1 Timer: [3711] Entry Delay 2 Timer: [3712]
Partition 4
Entry Delay 1 Timer: [3411] Entry Delay 2 Timer: [3412]
Partition 8
Entry Delay 1 Timer: [3811] Entry Delay 2 Timer: [3812]
DIGIPLEXNE CONTROL PANEL 15
4.3.10 24Hr Water Zones*
SECTIONS [0101] TO [0196]: FIRST DIGIT = A
When a 24Hr Water zone opens, whether it is armed or disarmed, the control panel will immediately generate an alarm. The SIA FSK reporting format includes specific codes to identify the alarm as a Water Alarm.
4.3.11 24Hr Freeze Zones*
SECTIONS [0101] TO [0196]: FIRST DIGIT = B
When a 24Hr Freeze zone opens, whether it is armed or disarmed, the control panel will immediately generate an alarm. The SIA FSK reporting format includes specific codes to identify the alarm as a Freeze Alarm.
* UL Note: UL Listed compatible devices shall be used for UL systems. For UL Listed systems, this type of zone shall be programmed as a silent auxiliary alarm.
4.3.12 Delayed 24Hr Fire Zone (Not to be used with UL Listed systems)
SECTIONS [0101] TO [0196]: FIRST DIGIT = C
The Delayed 24Hr Fire Zone definition from Figure 4-3: on page 15 is commonly used in residential homes where a smoke detector often generates false alarms (i.e. cigarette smoke, burning bread, etc.). A zone programmed as Fire becomes normally open (will not function as normally closed) and requires an EOL resistor.
The keypads must be assigned to the same partition as the Delayed 24Hr Fire zone for the buzzer to activate.
Figure 4-3: Delayed 24Hr Fire Zone
4.3.13 Standard 24Hr Fire Zone
SECTIONS [0101] TO [0196]: FIRST DIGIT = D
A zone programmed as Fire becomes normally open (will not function as normally closed) and requires an EOL resistor. When a Standard 24Hr Fire Zone triggers, the control panel can:
• send a Zone Alarm report code (see section 8.2.1 on page 25).
• send a Fire Loop Trouble Report (see section 8.2.11 on page 26) if a tamper/wiring fault occurs on a Fire Zone. A “Zone Fault Trouble” will also appear in the keypad's Trouble Display.
• generate a Fire alarm, which is always audible, regardless of other settings. Fire alarms generate an intermittent signal (see Figure 4-4).
Figure 4-4: Bell/Siren Output During Fire Alarm
4.3.14 Stay Delay Zone
SECTIONS [0101] TO [0196]: FIRST DIGIT = E AND F
When a Stay Delay zone is armed using the Regular or Force arming methods, the control panel processes the zone as an Instant zone (see section 4.3.4). When a Stay Delay zone is armed using the Stay or Instant arming methods and the zone is triggered, the control panel will not generate an alarm until the programmed Stay Delay elapses. A zone defined as Stay Delay 1 follows the Entry Delay 1 Timer of its assigned partition. Likewise, a zone defined as Stay Delay 2 follows the Entry Delay 2 Timer of its assigned partition. To program the Entry Delay Timers, refer to Entry Delays 1 and 2 on page 14.
For example, if zone 1 in Partition 5 is defined as Stay Delay 1, the timer will follow the amount programmed in [3511].
4.4 ZONE PARTITION ASSIGNMENT
S
ECTIONS [0101] TO [0196]: SECOND DIGIT = 1 TO 8
A control panel can be divided into eight completely independent systems (see section 11.9 on page 32). Assign each zone to one partition (see Figure 4-1 on page 13).
4.5 ZONE OPTIONS
The zone options from Figure 4-1 on page 13 are described below.
4.5.1 Auto Zone Shutdown
SECTIONS [0101] TO [0196]: OPTION [1]
(Default = 000) When option [1] is disabled, the control panel generates an alarm when an armed zone is breached even if the same zone opens repeatedly during the same alarm, which may cause several reportings and further activation of the bell output. When option [1] is enabled, the control panel will stop regenerating alarms on the zone during the same armed period once the Auto Zone Shutdown Limit is reached. The Auto Zone Shutdown Limit resets every time the system is armed. To program the Auto Zone Shutdown Limit, key in the desired 3-digit counter (000 to 255) into section corresponding to the desired partition (000 = disabled):
4.5.2 Bypass Zones
SECTIONS [0101] TO [0196]: OPTION [2]
Only zones with option [2] enabled can be Manually Bypassed (see section
15.7). Fire Zones cannot be bypassed. Default = enabled.
Delayed Fire Zone
Triggered
Activate bell/siren output & delay
report transmission for 30 seconds.
Yes
Yes
Any key on
keypad pressed
within 30
seconds?
Bell/siren silenced. Delay report
transmission an additional 90 sec.
Problem
corrected?
Latch alarm and transmit report code as described
in the section "Standard
24Hr. Fire Zone".
END
Alarm Disabled
No
Has a 2nd
Delayed Fire
Zone opened in
30 sec.?
No
Yes
Yes
No
Has the zone closed within
30 seconds?
Yes
No
Partition 1: [3114] Partition 5: [3514] Partition 2: [3214] Partition 6: [3614] Partition 3: [3314] Partition 7: [3714] Partition 4: [3414] Partition 8: [3814]
16 REFERENCE & INSTALLATION MANUAL
4.5.3 Stay Zones
SECTIONS [0101] TO [0196]: OPTION [3]
Only zones with option [3] enabled will be bypassed when the partition is Stay Armed (see section 15.2) or Instant A rmed (see section 15.3). All other zones will remain activated. Fire Zones cannot be set as Stay Zones.
4.5.4 Force Zones (Not to be used with UL Listed systems)
SECTIONS [0101] TO [0196]: OPTION [4]
Only zones with option [4] enabled can be bypassed when the partition is Force armed (see section 15.4). Fire Zones cannot be Force Zones.
4.5.5 Alarm Types
SECTIONS [0101] TO [0196]: OPTIONS [5] & [6]
4.5.6 Intellizone*
SECTIONS [0101] TO [0196]: OPTION [7]
(Default = 010) If an alarm condition occurs on a zone with option [7] enabled, the control panel triggers the Intellizone Delay and seeks confirmation of the alarm situation before generating an alarm. Fire Zones cannot be set as Intellizones. An alarm will only be generated if one of the following conditions occurs during the Intellizone Delay:
1) An alarm occurs on another zone defined as Intellizone.
2) The zone in alarm restores and reoccurs.
3) The zone stays in alarm for the entire Intellizone Delay.
Key in the desired 3-digit delay value (010 to 255 seconds) into the section corresponding to the desired partition (000 = 10 seconds):
* UL Note: For UL Listed systems, the detection pattern of both zones shall be installed so that each zone has the capability of protecting the area alone.
4.5.7 Delay Before Alarm Transmission
SECTIONS [0101] TO [0196]: OPTION [8]
(Default = 000) When an alarm condition occurs on a zone with option [8] enabled, the control panel activates the bell output, but will not report the alarm to the Monitoring Station until the end of the Alarm Transmission Delay. During this period, disarming the system cancels any report originating from this zone. T o program the Alarm Transmission Delay, key in the desired value (000 to 255 seconds, 000 = instant) into section [3055]. This feature is commonly used with Entry Delay zones to reduce false alarms created by new users who may not disarm the system in time.
4.6 INPUT SPEED
(001 to 255 X 30msec, default: 600ms) The Input Speed defines how quickly the control panel responds to an open zone detected on any hardwired input terminal (does not apply to addressable motion detectors and door contacts). All other zone definitions and options do not come into effect until the Input Speed elapses. The control panel will not display and/or respond to an open zone until the Input Speed elapses to prevent glitches from causing an alarm or unnecessary reporting.
For example, if an armed zone with an Input Speed of 600ms opens and closes in less than 600ms, the control panel will not respond (i.e. no reporting, no alarm and no display on the keypad).
Set the Input Speed (001 to 255 X 30ms, default = 600msec.):
Set the Input Speeds for the optional 4-Zone Hardwire Module, DGP2-ZX4:
4.7 EOL ON HARDWIRE ZONES
S
ECTION [3033]: OPTION [7]
(Default = disabled) If detection devices connected to hardwired input terminals use 1k
end of line resistors, enable option [7] in section [3033].
For details on using EOL resistors, refer to Addressable Zone Connections on page 8 and Double Zone Connections on page 9.
4.8 KEYPAD NUMBERING
S
ECTIONS [2801] TO [2832]
Keypad Numbering is only used to identify the keypad in the event buffer. When Keypad Numbering is not used, the event buffer will then display any events pertaining to any keypad as Keypad 00. When Keypad Numbering is used, each keypad is identified by a specific number. The keypad is assigned to a Keypad Number from 1 to 32 through the keypad's serial number in sections [2801] to [2832]. Enter the 8-digit serial keypad serial number in the desired section.
Option Feature Description
[5] [6]
OFF OFF
Steady Alarm
sends the report code and activates the bell output
ON OFF
Pulsed Alarm
sends the report code and pulses the bell output (see Figure 4-4 on page 15)
OFF ON
Silent Alarm
sends the report code, but the bell output is not activated. Partition must be disarmed.
ON ON
Report Only
sends the report code. Disarming is not required. Fire Zones cannot be Report Only.
Partition 1: [3110] Partition 3: [3310] Partition 5: [3510] Partition 7: [3710] Partition 2: [3210] Partition 4: [3410] Partition 6: [3610] Partition 8: [3810]
Section Input Section [0961] Input 01 [0973] Input 13 (ATZ of Input 01) [0962] Input 02 [0974] Input 14 (ATZ of Input 02) [0963] Input 03 [0975] Input 15 (ATZ of Input 03) [0964] Input 04 [0976] Input 16 (ATZ of Input 04) [0965] Input 05 [0977] Input 17 (ATZ of Input 05) [0966] Input 06 [0978] Input 18 (ATZ of Input 06) [0967] Input 07 [0979] Input 19 (ATZ of Input 07) [0968] Input 08 [0980] Input 20 (ATZ of Input 08)
Section Input [0969] Input 09 (DGP2-ZX4 Input 01) [0970] Input 10 (DGP2-ZX4 Input 02) [0971] Input 11 (DGP2-ZX4 Input 03) [0972] Input 12 (DGP2-ZX4 Input 04)
[0981] Input 21 (ATZ of DGP2-ZX4 Input 01) [0982] Input 22 (ATZ of DGP2-ZX4 Input 02) [0983] Input 23 (ATZ of DGP2-ZX4 Input 03) [0984] Input 24 (ATZ of DGP2-ZX4 Input 04)
DIGIPLEXNE CONTROL PANEL 17
5 KEYS WITCH PROGRAMMING
The DigiplexNE control panel can support up to 32 keyswitch zones in addition to the 96 standard zones. A keyswitch allows a user to ar m or disarm a system by pressing a key or by toggling a keyswitch. A keyswitch can also be used to generate a Utility Key event which can then be used to activate or deactivate the control panel’s PGM outputs. The keyswitches are connected to the hardwired input terminals of either the control panel, zone expansion modules or the keypad. For installation instructions, see section 2.9 on page 5. Keyswitches must be programmed as described in this section (see Figure 5-
1). UL Note: Keyswitches are not to be used in UL Listed systems.
Figure 5-1: Keyswitch Programming
5.1 KEYSWITCH NUMBERING
S
ECTIONS [0501] TO [0532]
Keyswitch Numbering allows you to assign any hardwired input in the system to any of the 32 keyswitch zones in the control panel. It identifies where the keyswitch is connected and which keyswitch zone is assigned to the keyswitch (see Figure 5-2).
Figure 5-2: Example of Keyswitch Numbering
5.2 KEYSWITCH DEFINITIONS
Keyswitch Definitions determine how the control panel reacts when a keyswitch is activated.
5.2.1 Keyswitch Disabled
SECTIONS [0601] TO [0632]: FIRST DIGIT = 0
Disables keyswitch input.
5.2.2 Momentary Keyswitch
SECTIONS [0601] TO [0632]: FIRST DIGIT = 1
T o arm a partition using the Momentary Keyswitch, turn on the keyswitch for approximately three seconds then turn it off. Repeating this sequence will disarm the system. The selected Keyswitch Option (see section 5.4) determines the type of arming.
5.2.3 Maintained Keyswitch
SECTIONS [0601] TO [0632]: FIRST DIGIT = 2
To arm a partition using the Maintained Keyswitch, turn the switch from the
ON to the OFF position. To disarm a partition set the keyswitch in the ON
position. The selected Keyswitch Option (see section 5.4) determines the type of arming. If the keyswitch’s Arm Only option is enabled, the control panel will not perform any action when the switch is in the on position.
Press & hold the
[0] key
Enter your
[
INSTALLER CODE]
Enter 4-digit
[
SECTION]
Keyswitch Numbering
Sections [0501] to [0532] represent
keyswitches 1 to 32 respectively
Keyswitch Parameters
Sections [0601] to [0632] represent
keyswitches 1 to 32 respectively
Enter the module’s 8-digit
[
SERIAL NUMBER] where the
keyswitch is installed
Enter the 3-digit [
INPUT
NUMBER] where the
keyswitch is connected
Keyswitch Definition
First Digit
Keyswitch Partition
Assignment
Second Digit
Keyswitch Options
Feature Select
Press [
ENTER]
Keyswitch Definitions
[0] Disabled (default) [1] Momentary Keyswitch [2] Maintained Keyswitch [3] Generates a Utility Key Event on Open [4] Generates a Utility Key Event on Open & Close
Keyswitch Partition Assignment
[0] Not assigned to partition(s) (default) [1] Assigned to partition 1 [2] Assigned to partition 2 [3] Assigned to partition 3 [4] Assigned to partition 4 [5] Assigned to partition 5 [6] Assigned to partition 6 [7] Assigned to partition 7 [8] Assigned to partition 8
Keyswitch Options
Default = All OFF [1] to [3] = Future Use [4] Stay/Instant Disarm [5] Arm Only [6] Stay Arming* [7] Force Arming* [8] Instant Arming*
* Select one only; if all are OFF, defaults to regular
arming.
Select one
only
Select one
only
Set
options
Control Panel
SN#: 020000A2
Keyswitch B
Keyswitch C
Keyswitch Zone # Section Serial# Input# Keyswitch A: 1 = [0501] 020000A2 001 Keyswitch B: 2 = [0502] 34000041 002 Keyswitch C: 3 = [0503] 34000041 006
Input 2
Input 6
Keyswitch A
Input 1
Input Terminals
1 2 3 4 5 6 7 8
C
OMMUNICATION NETWORK
Zone Expansion Module
SN#: 34000041
Input Terminals
1 2 3 4 5 6 7 8
18 REFERENCE & INSTALLATION MANUAL
5.2.4 Generates a Utility Key Event on Open
SECTIONS [0601] TO [0632]: FIRST DIGIT = 3
When option [3] is enabled, a Utility Key Event will be generated whenever the keyswitch input is opened. This option can be used to activate or deactivate one or more of DigiplexNE’s PGM outputs. When a keyswitch is defined with the Generate a Utility Key Event on Open option, the Keyswitch Partition Assignment and Keyswitch Options are disabled. To program a Keyswitch to generate a Utility Key Event:
1) Program the Activation Event of a PGM output with the Utility Key Event corresponding to the desired keyswitch (see PGM Programming Table in the Programming Guide: Event Group 048).
2) Enable option [3] in the section corresponding to the desired keyswitch.
If the Utility Key events from 1 to 8 are chosen as Activation Events, the PGM will activate whether the keyswitch input opens or when the keys on the keypad are used. Utility Key events from 9 to 32 are only generated when keyswitch inputs from 9 to 32 with this option enabled are opened.
5.2.5 Generates a Utility Key Event on Open and Close
SECTIONS [0601] TO [0632]: FIRST DIGIT = 4
When option [4] is enabled, a Utility Key Event will be generated whenever the keyswitch input is opened and closed. As a result, the Utility Key Events increase from 32 to 64 events when option [4] is enabled; one event for each state (open and closed). See Table 3 on page 18. This option can be used to activate or deactivate one or more of DigiplexNE’s PGM outputs. When a keyswitch is defined with the Generate a Utility Key Event on Open and Close option, the Keyswitch Partition Assignment and Keyswitch Options are disabled. To program a Keyswitch to generate a Utility Key Event:
1) Program the Activation Event of a PGM output with the Utility Key Event corresponding to the desired keyswitch (see PGM Programming Table in the Programming Guide: Event Group 048).
2) Enable option [4] in the section corresponding to the desired keyswitch.
If the Utility Key events from 1 to 8 are chosen as Activation Events, the PGM will activate whether the keyswitch input opens or when the keys on the keypad are used. Utility Key events from 9 to 32 are only generated when keyswitch inputs from 9 to 32 with this option enabled are opened.
5.3 KEYSWITCH PARTITION ASSIGNMENT
S
ECTIONS [0601] TO [0632]: SECOND DIGIT = 1 TO 8
The control panel provides the option of partitioning the security system into eight completely independent systems. Therefore, each keyswitch must be assigned to one partition as shown in Figure 5-1 on page 17. For details on Partitioning, see section 11.9 on page 32.
5.4 KEYSWITCH OPTIONS
Each keyswitch zone can be programmed with one or more of the options below as shown in Figure 5-1 on page 17.
5.4.1 Stay/Instant Disarm Option (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [4]
When option [4] is enabled, the keyswitch can only disarm assigned Stay or Instant Armed partitions. The Arm Only Option (see section 5.4.2) must be disabled for this feature to function. When option [4] is disabled, the keyswitch can disarm partitions armed using any arming method.
5.4.2 Arm Only (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [5]
When option [5] is enabled, the keyswitch can arm assigned partitions, but cannot disarm any partitions. The type of arming is determined by the other Keyswitch Options selected.
5.4.3 Regular Arming (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [6] TO [8]
When options [6] to [8] are disabled, the keyswitch arming option will default to Regular Arming (see section 15.1).
5.4.4 Stay Arming (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [6]
Activating the keyswitch will bypass any zones defined as Stay Zones (see section 4.5.3) in the selected partition. All other zones will remain activated. For more information on Stay Arming, refer to section 15.2.
5.4.5 Force Arming (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [7]
Activating the keyswitch will arm the selected partition bypassing any open zones defined as Force Zones (see section 4.5.4) at the time of arming. For more information on Force Arming, refer to section 15.4.
5.4.6 Instant Arming (Keyswitch)
SECTIONS [0601] TO [0632]: OPTION [8]
This option is identical to Stay Arming except that all armed zones will become Instant Zones (see section 4.3.4). For more information on Instant Arming, refer to section 15.3.
Only one of the arming options (Stay, Force, Instant and Regular) can be selected.
*KS = Keyswitch
Table 3: Utility Key Event Activation
Utility Key
Event
Activation Method
Keypad (Keys)
Keyswitch
Def. = [3]
Keyswitch
Def. = [4]
LCD Grafica
1 [1] & [2] [1] & [2] KS* Input 1 opens KS* Input 1 opens 2 [4] & [5] [4] & [5] KS* Input 2 opens KS* Input 1 closes 3 [7] & [8] [7] & [8] KS* Input 3 opens KS* Input 2 opens 4[CLEAR] & [0] [*] & [0] KS* Input 4 opens KS* Input 2 closes 5 [2] & [3] [2] & [3] KS* Input 5 opens KS* Input 3 opens 6 [5] & [6] [5] & [6] KS* Input 6 opens KS* Input 3 closes 7 [8] & [9] [8] & [9] KS* Input 7 opens KS* Input 4 opens 8[0] & [ENTER][0] & [#]KS* Input 8 opens KS* Input 4 closes
L N/A N/A LL 31 N/A N/A KS* Input 31 opens KS* Input 16 opens 32 N/A N/A KS* Input 32 opens KS* Input 16 closes
L N/A N/A N/A L 63 N/A N/A N/A KS* Input 32 opens 64 N/A N/A N/A KS* Input 32 closes
DIGIPLEXNE CONTROL PANEL 19
6 ARMING & DISARMING OPTIONS
6.1 ARMING FOLLOWS PARTITION
(Default = disabled) A partition can be set to follow the arming and disarming status of one or more partitions. If a partition is set to follow more than one partition, the partition will arm when all the selected partitions are armed. However, the partition will disarm as soon as one of the selected partitions is disarmed.
For example, if options [2] and [3] are ON in section [3121], Partition 1 will automatically arm whenever partitions 2 and 3 are armed. Partition 1 will disarm when either partition 2 or partition 3 is disarmed.
6.2 RESTRICT ARMING ON SUPERVISION LOSS
S
ECTION [3034]: OPTION [4]
(Default = disabled) When option [4] is enabled, the control panel can restrict arming if it receives a supervision loss signal from the Omnia 433MHz Wireless System OMN-RCV3 (see section 7.3). Partitions will not arm until all supervision loss trouble conditions are corrected.
6.3 RESTRICT ARMING ON TAMPER
SECTION [3034]: OPTION [8]
(Default = disabled) When option [8] is enabled, the control panel prevents arming if it detects a tamper on a zone or module (see section 7.5). Partitions will not arm until the Installer Code is entered and tamper trouble conditions are corrected.
6.4 RESTRICT ARMING ON AC FAILURE
S
ECTION [3035]: OPTION [1]
(Default = disabled) When option [1] is enabled, the control panel can prevent arming if it detects a loss of AC power. Partitions will not arm until power is restored.
6.5 RESTRICT ARMING ON BATTERY FAILURE
S
ECTION [3035]: OPTION [2]
(Default = disabled) When option [2] is enabled, the control panel prevents arming if it detects a battery loss or if the battery voltage is less than 10.5V. The control panel will not arm a partition until all battery trouble conditions are corrected.
6.6 RESTRICT ARMING ON BELL OR AUXILIARY FAILURE
S
ECTION [3035]: OPTION [3]
(Default = disabled) When option [3] is enabled, the control panel can prevent arming if it detects that:
• the bell or siren is disconnected
• the Bell Output has exceeded its current limits
• the Auxiliary Outputs have exceeded their current limits The control panel will not arm any partition until all bell or auxiliary trouble conditions are corrected.
6.7 RESTRICT ARMING ON TLM FAILURE
S
ECTION [3035]: OPTION [4]
(Default = disabled) When option [4] is enabled, the control panel can prevent arming if it is unable to access the telephone line. The control panel will not arm any partition until all TLM trouble conditions are corrected.
6.8 RESTRICT ARMING ON MODULE TROUBLES
S
ECTION [3035]: OPTION [5]
(Default = disabled) When option [5] is enabled, the control panel will monitor the same Restrict Arming options selected for the control panel (battery, tamper, supervision, AC, bell, auxiliary and/or TLM failures) for the modules connected to the combus. The control panel will prevent arming if the control panel detects the equivalent trouble condition occurring on a module.
For example, if options [1], [2] and [5] are ON in section [3035], the control panel prevents arming if it detects an AC or battery failure on the control panel or on a module connected to the combus.
6.9 TIMED AUTO-ARMING
(Default = disabled) When this option is enabled, the control panel arms the selected partition every day at the time set by the Auto-Arm Timer (see section 6.9.1). A 60-second Exit Delay triggers before the partition arms, but Auto-Arming can be cancelled by entering a valid access code. The Auto-Arming Option sets the arming method (see section 6.11). If zones are open when a partition is Auto-Armed, the control panel arms the partition and considers all open zones as temporarily bypassed (except 24hr. zones).
When the partition Auto-Arms, the control panel transmits the Auto-Arming report code programmed in section [3910]. Whether the partition was successfully armed or not, the control panel will always transmit the Late to Close report code programmed in section [3912]. Enable option [1] in the desired section:
Partition 1: [3121]
Partition 1 arms & disarms with: Option [1] = N/A Option [2] = Partition 2 Option [3] = Partition 3 Option [4] = Partition 4 Option [5] = Partition 5 Option [6] = Partition 6 Option [7] = Partition 7 Option [8] = Partition 8
Partition 5: [3521]
Partition 5 arms & disarms with: Option [1] = Partition 1 Option [2] = Partition 2 Option [3] = Partition 3 Option [4] = Partition 4 Option [5] = N/A Option [6] = Partition 6 Option [7] = Partition 7 Option [8] = Partition 8
Partition 2: [3221]
Partition 2 arms & disarms with: Option [1] = Partition 1 Option [2] = N/A Option [3] = Partition 3 Option [4] = Partition 4 Option [5] = Partition 5 Option [6] = Partition 6 Option [7] = Partition 7 Option [8] = Partition 8
Partition 6: [3621]
Partition 6 arms & disarms with: Option [1] = Partition 1 Option [2] = Partition 2 Option [3] = Partition 3 Option [4] = Partition 4 Option [5] = Partition 5 Option [6] = N/A Option [7] = Partition 7 Option [8] = Partition 8
Partition 3: [3321]
Partition 3 arms & disarms with: Option [1] = Partition 1 Option [2] = Partition 2 Option [3] = N/A Option [4] = Partition 4 Option [5] = Partition 5 Option [6] = Partition 6 Option [7] = Partition 7 Option [8] = Partition 8
Partition 7: [3721]
Partition 7 arms & disarms with: Option [1] = Partition 1 Option [2] = Partition 2 Option [3] = Partition 3 Option [4] = Partition 4 Option [5] = Partition 5 Option [6] = Partition 6 Option [7] = N/A Option [8] = Partition 8
Partition 4: [3421]
Partition 4 arms & disarms with: Option [1] = Partition 1 Option [2] = Partition 2 Option [3] = Partition 3 Option [4] = N/A Option [5] = Partition 5 Option [6] = Partition 6 Option [7] = Partition 7 Option [8] = Partition 8
Partition 8: [3821]
Partition 8 arms & disarms with: Option [1] = Partition 1 Option [2] = Partition 2 Option [3] = Partition 3 Option [4] = Partition 4 Option [5] = Partition 5 Option [6] = Partition 6 Option [7] = Partition 7 Option [8] = N/A
Partition 1: [3122] Partition 3: [3322] Partition 5: [3522] Partition 7: [3722] Partition 2: [3222] Partition 4: [3422] Partition 6: [3622] Partition 8: [3822]
Loading...
+ 47 hidden pages