Digicom ED-20 PPP User Manual

PPP Router
INSTALLATION MANUAL
6609-2221
ED-20 PPP
©
Westermo Teleindustri AB • 2003 • REV.A
PPP ROUTER
Serial Interface
Galvanic Isolation
Transient
Protection
Balanced
Transmission
CE
Approved
Rurstraße 4 D-41564 Kaarst 1
Telefon (02131) 6 69 08-0 Telefax (02131) 66 71 48
Internet: www.digicomm.de e-mail: info@digicomm.de
2 6609-2221
Contents
1. Safety .................................................................................................................................................................................. 3
2. Approvals ....................................................................................................................................................................... 3
2.1 Declaration of Conformity ....................................................................................................................... 4
3. Introduction ............................................................................................................................................................... 5
4. Specification ........................................................................................................................................................ 6–7
5. Maintenance .............................................................................................................................................................. 8
6. Installation .......................................................................................................................................................... 8–13
6.1 Mounting/Removal .......................................................................................................................................... 8
6.2 Connections ................................................................................................................................................ 9–10
6.3 LED Indicators ................................................................................................................................................ 11
6.4 DIP Switch Settings .................................................................................................................................... 12
6.4.1 MAC address ........................................................................................................................................ 13
6.5 Installation of ED-Tool for ED-20 .................................................................................................... 13
7. Functional description .................................................................................................................... 14–15
7.1 Application mode ......................................................................................................................................... 14
7.1.1 About PPP .............................................................................................................................................. 14
7.1.2 Network interfaces .......................................................................................................................... 14
7.1.2.1 Ethernet connection ........................................................................................................... 14
7.1.2.2 PPP connection ....................................................................................................................... 15
7.1.2.3 Brouter function ..................................................................................................................... 15
7.1.2.4 Firewall function ..................................................................................................................... 15
7.2 Configuration mode .................................................................................................................................. 15
8. Configuration .............................................................................................................................................. 16–29
8.1 Configuration by ED-Tool for ED-20 ............................................................................................. 16
8.1.1 ED-Tool for ED-20 commands ................................................................................................ 17
8.1.1.1 General commands ............................................................................................................. 17
8.1.1.2 Serial Interface – Channel 1 specific commands .......................................... 17
8.1.1.3 Modem Settings ............................................................................................................ 18–19
8.1.1.4 Network Settings .................................................................................................................. 20
8.1.1.5 Brouter Settings ..................................................................................................................... 21
8.1.1.6 Firewall Settings ..................................................................................................................... 22
8.2 Configurable parameters .............................................................................................................. 23–29
8.2.1 Serial interface .................................................................................................................................... 23
8.2.2 Modem settings ........................................................................................................................ 23–27
8.2.3 Network Settings .................................................................................................................... 27–28
8.2.4 Brouter settings ................................................................................................................................. 29
8.2.4 Firewall Settings ................................................................................................................................ 29
9. Application examples ....................................................................................................................... 30–31
36609-2221
1. Safety
General:
Before using this unit, read this manual completely and gather all information on the unit. Make sure that you understand it fully. Check that your application does not exceed the safe operating specifications for this unit.
Before installation, maintenance or modification work:
Prevent damage to internal electronics from electrostatic discharges (ESD) by discharging your body to a grounding point (e.g. use of wrist strap).
Prevent access to hazardous voltages by disconnecting the unit from AC/DC mains supply and all other electrical connections.
Installation:
This unit should only be installed by qualified personnel. This unit should only be installed in a “restricted access area”, for example
a lockable cabinet where access is restricted to service personnel only. This unit is intended for permanent connection to the AC/DC mains supply. The power supply wiring must be sufficiently fused, and if necessary it must be
possible to disconnect manually from the AC/DC mains supply. Ensure compliance to national installation regulations.
Unit with the rated voltage exceeding 42.4 V peak or 60 VDC, is defined as class I equipment with a protective earthing conductor terminal.
Unit with the rated voltage up to 42.4 V peak or 60 VDC, is defined as class III equipment and shall be separated from hazardous voltage by double or reinforced insulation.
This unit uses convection cooling.To avoid obstructing the air flow around the unit, follow the spacing recommendations (see under chapter Installation).
2. Approvals
Conformity with the Directive 89/339/EEC (Electromagnetic compatibility) has been assessed by application of standards EN 61000-6-2 (industrial immunity) and EN 61000-6-4 (industrial emission).
!
!
!
4 6609-2221
2.1 Declaration of Conformity
Westermo Teleindustri AB
Declaration of conformity
Org.nr/ Säte/
Postadress/Postal address Tel. Telefax Postgiro Bankgiro Corp. identity number Registered office
S-640 40 Stora Sundby 016 - 42 80 00 016 – 42 80 01 52 72 79-4 5671-5550 556361-2604 Eskilstuna
Sweden Int +46 16 42 80 00 Int +46 16 42 80 01
The Westermo Teleindustri AB company declares that the listed products conforms to the Council Directive 89/336/EEC, related to Electro Magnetic Compability.
Type of equipment:
Industrial Ethernet adapter
Model:
ED-10LV 3609-0001 ED-10LV TCP 3609-0010 ED-10LV Custom 3609-0020 ED-20LV 3609-1001
Standards:
EMC Immunity: EN 50082-1:1997
EN 50082-2:1995 EN 61000-6-2:1999
EMC Emission: EN 50081-1:1992
EN 50081-2:1993
Technical Manager April 2002
56609-2221
3. Introduction
The ED-20 is an industrialised DIN Rail mounted, serial to Ethernet Router.The device will allow access to a remote Ethernet network via a Westermo communication product. The device is easily set-up using the ED-Tool for ED-20 configuration program via TELNET or serial connection.
Standard PPP dial-up networking tools can be used from Microsoft Windows 9x, ME, NT, 2000 or XP, Or another ED-20 to connect to the device.Any other platform supporting the PPP protocol could equally be used.
Passwords are provided to increase the remote site security. Once connected to the remote network all TCP/IP, FTP,TELNET and UDP protocol types can be used. Connection to the ED-20 is via 10Base-T on the Ethernet and RS-232 on the serial side. The serial port supports speeds up to 115 k/bit.
Total galvanic isolation ensures that the data communication will not be effected by ground loops or transfer electrical noise between communications ports.The high EMC specification, like all other Westermo production ensures reliability of operation in the harshest of site conditions.
TD-32B
TCP/IP
Ethernet
ED-20
PSTN
TD-33
ED-20
PPP
ROUTER
Serial Interfa
ce
6 6609-2221
4. Specification
Network Interface 10BASE-T. IEEE std 802.3, 2000 Edition.
Data rate 10 Mbit/s, half duplex. Mechanical RJ-45 Modular Jack (ISO/IEC 8877:1992),
Unshielded or shielded (UTP/STP).
Serial Interface 1 (CH 1) RS-232 Data rate 300–115 200 bit/s Full, half duplex or simplex. Data format 8 Data Bits, No Parity Bit,1 Stop Bit Control signals RTS, CTS, DSR, DCD, DTR Mechanical 9-pin female D-sub, DCE.
Serial Interface 2 (CH 2) RS-232 Data rate 19 200 bit/s Data format 8 Data Bits, No Parity Bit, 1 Stop Bit Control signals – Mechanical 9-pin female D-sub, DCE.
Power Interface
Rated voltage 10–60 VDC polarity independent. / 12–30 VAC Rated current 350 mA, max @ 10VDC input. Rated frequency 48–62 Hz Mechanical Screw Terminal. 0,2–2,5 mm
2
, 24-12 AWG
Isolation Functional and safety Power Interface to all other Interfaces* 4.2 kV DC,3 kV RMS @50–60 Hz. EN 60950:2000 Network Interface 2.1 kV DC, 1.5 kV RMS @ 50–60 Hz.Applied for 60 sec to serial interface as specified in 5.3.2 of EN 60950:2000.
76609-2221
Transient Protection
Power Interface ±4 kV, EN 61 000-4-5:1995 Class 4 Network Interface ±2 kV, EN 61 000-4-5:1995 Class 3 Serial Interface ±0.5 kV, EN 61 000-4-5:1995 Class 1
Application Serial/Network conversion Throughput (maximum) 115 kbit/s (1.44 MB data) Network protocols TCP, IP,ARP, ICMP,Telnet
Configuration Remotely over network or locally at serial interface.
Windows based PC-programme.
Indicators (LED) TD, RD, CTS, RTS, PWR,TD, RD, CONFIG, NET
Climatic environment
Temperature, operating 5–50°C Relative humidity, operating 5–95% REL non condensing Dimension (WxHxD) 55 x 100 x 128 mm Weight 0.35 kg Mounting 35 mm DIN-rail Approvals CE
* Power to network interface,1.5 kV RMS @50–60 Hz functional isolation.
8 6609-2221
5. Maintenance
No maintenance is required, as long as the unit is used as intended within the specified conditions.
6. Installation
6.1 Mounting /Removal
Before mounting or removing the unit:
Prevent damage to internal electronics from electrostatic discharges (ESD) by discharging your body to a grounding point (e.g. use of wrist strap).
Prevent access to hazardous voltages by disconnecting the unit from AC/DC mains supply and all other electrical connections.
Mounting
This unit should be mounted on 35 mm DIN-rail which is horizontally mounted on a wall or cabinet backplate.
This unit uses convection cooling. To avoid obstructing the air flow around the unit, use the following spacing rules. Minimum spacing 25 mm (1.0 inch) above/below and 10 mm (0.4 inches) left/right the unit.
Snap on mounting, see figure.
Removal
Press down the black support at the back of the unit using a screwdriver, see figure.
Min
10 mm
!
CLICK!
96609-2221
6.2 Connections
ED-20
PPP ROUTER
Serial Interface
Power
Cannel 1: RS-232 connection
Cannel 2: RS-232 connection
Ethernet 10Base-T connection
8 7
6
5 4
3 2 1
Ethernet 10Base-T Connection (RJ-45 connector), straight function MDI (no crossover)
Contact Signal Name Direction** Description
1 TD+ Out Transmitted Data 2TD Out Transmitted Data 3 RD+ In Received Data 4NC 5NC 6RD In Received Data 7NC 8NC
** Direction relative ED-20 NC Not connected
CAT 5 cable is recomended. Unshielded (UTP) or shielded (STP) cables might be used.
10 6609-2221
Pin Signal Name*
Direction** Description
Number Description V.24 RS-232C
1 DCD 109 CF Out Data Carrier Detect 2 RD 104 BB Out Received Data 3 TD 103 BA In Transmitted Data 4 DTR 108.2 CD In Data Terminal Ready 5 SG 102 AB In/Out Signal Ground 6 DSR 107 CC Out Data Set Ready 7 RTS 105 CA In Request to Send 8 CTS 106 CB Out Clear to Send 9 RI 125 CE Ring Indicator, NC
CH1: RS-232 Connections, DCE
* Functionality might differ from standard ** Direction relative ED-20 NC Not connected
Pin Signal Name*
Direction** Description
Number Description V.24 RS-232C
1 DCD 109 CF Data Carrier Detect, NC 2 RD 104 BB Out Received Data 3 TD 103 BA In Transmitted Data 4 DTR 108.2 CD Data Terminal Ready, NC 5 SG 102 AB In/Out Signal Ground 6 DSR 107 CC Data Set Ready, NC 7 RTS 105 CA In Request to Send, NU 8 CTS 106 CB Out Clear to Send, NU 9 RI 125 CE Ring Indicator, NC
CH2: RS-232 Connections, DCE
* Functionality might differ from standard ** Direction relative ED-20 NC Not connected NU Not used
5
4
3
2
1
9
8
7
6
5
4
3
2
1
9
8
7
6
116609-2221
6.3 LED Indicators
From left to right.
CH1:TD Transmitted Data (incoming serial data):
LED off RS-232 TD =1, Mark (<–3V). LED on RS-232 TD =0, Space (>3V).
CH1: RD Received Data (outgoing serial data):
LED off RS-232 RD =1, Mark (<–3V). LED on RS-232 RD =0, Space (>3V).
CH1: RTS Request To Send:
LED off RS-232 RTS =Off (<–3V). LED on RS-232 RTS =On (>3V).
CH1: CTS Clear To Send:
LED off RS-232 CTS =Off (<–3V). LED on RS-232 CTS =On (>3V).
PWR Power:
LED off No internal power, (external power not connected). LED on Power OK.
CH2:TD Transmitted Data (incoming serial data):
LED off RS-232 TD =1, Mark (<–3V). LED on RS-232 TD =0, Space (>3V).
CH2: RD Received Data (outgoing serial data):
LED off RS-232 RD =1, Mark (<–3V). LED on RS-232 RD =0, Space (>3V).
CONFIG ED-20 working mode:
LED on Configuration mode. LED off Application mode,
(or during start up of configuration mode).
NET Indication of network status:
LED off Link Test failed (no network). LED on Link Test passed. LED flashing Data on Network (traffic).
12 6609-2221
6.4 DIP Switch Settings
DIP-switches are accessible under the lid on top of the unit.
Warning! Prevent damage to internal electronics from electrostatic discharges
(ESD) by discharging your body to a grounding point (e.g. use of wrist strap), before the lid on top of the modem is removed.
Warning! Do not open connected equipment.
Prevent access to hazardous voltages by disconnecting the unit from AC/DC mains supply and all other electrical connections.
NOTE The change of DIP switch settings are valid only after a power on.
Factory settings
ON
12345678
S2
Channel 2
ON
12345678
S1
Channel 1
1 2
3 4
5
S1:1-8
Channel 1
S2:1-8
Channel 2
IC 2
The DIP Swiches is not used in this product, leave as it is.
!
!
136609-2221
6.4.1 MAC address
The MAC address of the unit can be found on the product label “00 30 56 F” + last 5 digits on IC2 see figure in section 6.4 Switch settings on page 12. Example: Label on IC2 SC12 RTOS 0092C2 this will give the unit MAC address “00 30 56 F0 92 C2
The MAC address can also be find out with the DOS command “ARP –a”. (Perform the PING command with the ED-10 local IP address before the ARP command.)
6.5 Installation of ED-Tool for ED-20
System Requirements:
To install and run the ED-Tool for ED-20 program following requirements are needed.
Minimum:
386, 486 or Pentium Processor-based personal computer
Microsoft Windows 95/98/Me, NT 3.51/4.0, 2000 or XP Or compatible OS.
16 MB of RAM for Windows 95/98/Me systems
24 MB of RAM for Windows NT systems
32 MB of RAM for Windows 2000/XP systems
CD-ROM drive
8 MB of space on hard drive
Serial and/or ethernet network connections
Internet Explorer 5.0 or higher
Recommended:
Pentium processor-based personal computer
32 MB of RAM
Installation:
To install ED-Tool for ED-20
Insert the ED-Tool for ED-20 CD-ROM into the CD-ROM drive.
Locate the Setup.exe file on the ED-Tool CD-ROM.
Start the Setup.exe and follow the instructions.
14 6609-2221
7. Functional description
The ED-20 can be in either configuration mode or in application mode. Normally the ED-20 is in application mode, where the serial-to-network data transfer is enabled and all configuration settings are readable.
Change of configuration parameters are done in ED-20 configuration mode. Configurable parameters are listed in chapter 6.3.
7.1 Application mode
In application mode the ED-20 transfers data between the serial interface (CH1) and the network interface (10BaseT).At the network interface data is transferred using the TCP/IP protocol suit.At the serial interface data is transferred using PPP.
7.1.1 About PPP
PPP (the Point to Point Protocol) is a mechanism for creating and running TCP/IP over a serial link – a direct serial connection or a link made using one of following: Westermo analogue PSTN-, Leased-line-, ISDN-, GSM-, Radio-, Fibre- or Short-haul modem. Other computers can connect via the ED-20 and communicate over the PPP link using FTP,Telnet,Web, etc. in the same manner as with an Ethernet TCP/IP link. One major difference between a PPP and an Ethernet connection is of course the speed.A standard Ethernet connection operates at 10 Mbs maximum theoretical throughput, whereas an analogue modem operates at speeds up to 56 kbps.
PPP is strictly a peer to peer protocol; there is no difference between the machine that dials in and the machine that is dialed into. However, it is still useful to think in terms of servers and clients.When you dial into a site to establish a PPP connection, you are a considered the client.The machine to which you connect is considered the server.
Authentication is provided with the protocols PAP and CHAP.
7.1.2 Network interfaces
ED-20 has two network interfaces, Ethernet and PPP, so the unit can forward IP-packets between these interfaces.
7.1.2.1 Ethernet connection
This interface is a part of the local network and the ‘Local IP Address* and ‘Subnet Mask’ must be set to the right ‘Network ID’
* The IP address must be compliant to the attached network.
Ask the network administrator when in doubt.
156609-2221
7.1.2.2 PPP connection
The PPP connection can be established over PSTN, Leased Line or private lines. ED-20 can act as a PPP Server, PPP Client or both.These functions is set on the ‘Modem settings tab in ED-Tool for ED-20. See application example on page 30.
Connections can be established in several ways depending on the application:
Standard PPP dial-up networking tool.
•‘Connect’ command on CH2: or via TELNET
Using the ‘Brouter function.
7.1.2.3 Brouter function
The Brouter function will establish a dial-up connection when valid outbound IP address (Defined on the tab ‘Brouter Settings’ in ED-Tool for Ed-20) is sent to the ED-20. See application example on page 31.
The connection will be open until one of following is true:
There is no traffic during and the ‘Idle Time parameter is set to a value greater than zero. e.g. Idle Time is set to 600s and there is no traffic sent to the ED-20 for more than 10 minutes.
•‘Close command on CH2: or via TELNET
Note! It may be wise to use the Firewall function while the Brouter function being used to reduce the traffic over the PPP link.
7.1.2.4 Firewall function
The Firewall function can be set-up to allow or block certain IP Addresses through the ED-20. See application example on page 31.
7.2 Configuration mode
Local or remote configuration is managed by ED-Tool for ED-20. ED-Tool for ED-20 is a Windows based set-up programme which provides easy configuration. Configuration is possible locally by using serial connection and remote using network (telnet) connection. Configuration mode will be entered automatically by ED-Tool for ED-20. Config LED will lit when ED-20 is in configuration mode. (The unit is not in configuration mode until the ‘Write config’ button been pushed.) The unit will be in configuration mode until a reboot is made.
First time configure: ED-20 is shipped with IP-address 169.254.100.100. Please make sure that 169.254.100.100 is compliant to your network, before ED-20 is connected. Otherwise use serial interface to locally set a valid IP address compliant with the network in use and not chosen arbitrarily, ask your network administrator when in doubt.
16 6609-2221
8. Configuration
Before read, write or reboot can be made, Select type of connection:
Network
Serial com port must be selected from menu ‘Tools – Serial COM Port’
8.1 Configuration by ED-Tool for ED-20
This section describes the configuration of the ED-20 with the software ED-Tool for ED-20.
Program Start:
To start ED-Tool for ED-20
Locate ED-Tool under Program on the Start-Menu.
Click on the ED-Tool for ED-20 icon
When the ED-Tool for ED-20 has been successful opened the user is presented with an empty configuration screen.The user can now get an existing configuration by reading the configuration from an ED-20, create a new file from default values or by opening a stored configuration file.
After all the parameters are set the user can write the configuration to the ED-20.
Typical configuration procedures:
Read configuration from an ED-20
Change some parameters
Write configuration to the ED-20
Reboot
Done
or
Read configuration from a file
(Change some parameters)
Write configuration to the ED-20
Reboot
Done
or
Set parameters
Write configuration to ED-20
Reboot
Done
or
Set parameters
Save configuration to a file
Done
176609-2221
8.1.1 ED-Tool for ED-20 commands
This section describes the ED-Tool for ED-20 commands. The commands are described by there use. Details about allowed values and default values is described is section 6.2.
8.1.1.1 General commands
1 Selects type of connection, Serial or over the Network.
If ‘Serial’ is selected, use the “Tools menu – Serial COM port to select which of COM1:, COM2:, COM3:, or COM4: your serial cable is connected to.
2 Read Config Reads configuration from the ED-20. 3 Write Config Writes configuration to the ED-20.
Note! ED-20 must be rebooted before any new configuration
is activated.
4 Reboot Reboots the ED-20.
8.1.1.2 Serial Interface – Channel 1 specific commands
5 Data Rate Selects Data Rate for serial communication, ED-20 Modem. 6 Flow Control Selects if flow control is used or not.
Note! All interconnecting wires are required between the ED-20
and the attached modem.
1
2
3
4
5
6
57600
RTS/CTS
18 6609-2221
PSTN
1 2 3 4 5 6 7
8.1.1.3 Modem Settings
General 1 Modem Select Type of connection, PSTN or LL.
Connection Use PSTN for dial-up connections, e.g. Phone modem, GSM
modem or ISDN adapter.
Use LL for fixed connections, e.g. LeasedLine-, Radio-, Fibre­or any Short-haul- modem.
2 Dial IN/OUT Select if the ED-20 shall act as a PPP Server, PPP Client or both.
When the unit is set to be a server, it will answer incoming calls.
3 Connect at Select if the ED-20 shall initiate a connection at power on
PWR On with the Modem Connect (Dial Out) command.
4 DCD Control* Select if the ED-20 shall disconnect the PPP link at modem DCD
loss. Note! All interconnecting wires are required between the ED-20
and the attached modem.
5 Escape Set the modem escape sequence wich switches the modem into
Sequence command mode. Not used for Leased Line mode. Usually ‘+++’.
6 Escape Delay Set the delay time in seconds after the escape sequence before
any other command.
7 Idle Time Set the idle time in seconds, after which the PPP server closes the
connection if no data being sent.
DIAL IN/OUT
NO
NO
+++
2
600
AT&F&DOSO
OK
3
1
ATDS=0
CONNECT
60 0
1
ATH
OK
3
1
RING
ATA
196609-2221
AT&F&DOSO
OK
3
1
ATH
OK
3
ATDS=0
CONNECT
60 0
1
RING
ATA
1
1 2 3
4 5 6 7 8
16 17 18
19 20 21
22
Modem Init
8 Command Set the modem init string, max string length:25 characters. 9 Answer Set the expected answer from the modem on the command
string. Note! Modem result codes must be enabled.
10 Timeout Set the timeout in seconds for how long the ED-20 shall wait
for the answer string.
11 Retries Set the number of retries before the modem init fails.
Modem Hangup
12 Command Set the modem hangup string, max string length:25 characters. 13 Answer Set the expected answer from the modem on the command
string. Note! Modem result codes must be enabled.
14 Timeout Set the timeout in seconds for how long the ED-20 shall wait for
the answer string.
15 Retries Set the number of retries before the modem hangup fails.
Modem Connect (Dial Out)
16 Command Set the modem connect string, max string length:25 characters. 17 Answer Set the expected answer from the modem on the command.
string. Note! Modem result codes must be enabled.
18 Timeout Set the timeout in seconds for how long the ED-20 shall wait for
the answer string.
19 Retries Set the number of retries before the modem connect fails.
Modem Connect (Dial In)
20 Command Set the modem connect string, max string length:25 characters. 21 Answer Set the expected answer from the modem on the command. 22 Timeout Set the timeout in seconds for how long the ED-20 shall wait for
the answer string.
Modem AT-Commands
Refer to the user guide or installation manual to the attached modem.
20 6609-2221
NONE
1 2
3 4
5 6
7 8
8.1.1.4 Network Settings
Login
1 Authentication Select if authentication shall be used or not. 2 Username Set the login username.
This is also used for Telnet sessions (Network configuration).
3 Password Set the login password
This is also used for Telnet sessions (Network configuration).
PPP Network Interface*
4 Local IP Set the Server IP address. 5 Remote Address Set the Client IP address. 6 Subnet Mask Set the Subnet mask.
Ethernet Interface*
7 Local IP Address Set the Local IP address i.e. the address of the ED-20. 8 Subnet Mask Set the Subnet mask.
* The IP address must be compliant to the attached network.
Ask the network administrator when in doubt.
ed20
****
169.254.200.100
169.254.200.101
255.255.255. 0
169.254.100.100
255.255.255. 0
216609-2221
1 2
3 4
5 6
8.1.1.5 Brouter Settings
Brouter Mode
1 Off / On Disables or enables the Brouter mode.
See 8.2.4
Brouter Settings
2 IP Address Set the target IP address that shall initiate a connection. 3 Connect Set the Connect message that shall be sent to the attached
Message modem. E.g.ATDnnnnnn
4 Add >> Adds the values IP Address and Connect message to the
brouter entry list
5 Remove Remove marked entry from entry list. 6 Brouter Entry List
Displays the Brouter entrys: IP Address, Connect message. Up to 32 entrys can be added.
To Add an entry: Fill in the field IP Address and the field Connect message, Press add.
To Edit an entry: Double click the entry that shall be edited, Edit the values in the fields
to the left, Press add.
To Remove an entry: Click the entry that shall be removed, Press remove.
. . .
22 6609-2221
. . .
1 2
3 4
5
8.1.1.6 Firewall Settings
Firewall Mode
1 Off / Pass / Block Disables or enables the Firewall mode and selects if the firewall
shall work in Block or Pass mode. See 8.2.5
Firewall Settings
2 IP Address Set the source and destination IP addresses that shall be allowed
to pass through the ED-20, or set the source or destination IP addresses that shall be blocked from passing through the ED-20.
3 Add>> Adds the values IP Address and Connect message to the
Firewall entry list.
4 Remove Remove marked entry from entry list. 5 Firewall Entry List.
Displays the Firewall entrys: IP Address. Up to 32 entrys can be added.
236609-2221
8.2 Configurable parameters
8.2.1 Serial interface
Communication
Data Rate
The data rate can be set from 1 200 bit/s to 115.2 kbit/s.
Allowed values:
1 200, 2 400, 4 800, 7 200, 9 600, 14 400, 16 000, 19 200, 38 400, 56 000, 57 600 and 115 200 bit/s.
Default: 57 600 bit/s.
Flow Control
Flow control can be chosen between none or RTS/CTS. If the RTS/CTS being used then the cable must have all interconnecting wires between the ED-20 and the modem connected and the modem shall have the flow control enabled.
Allowed values: None, RTS/CTS Default: RTS/CTS.
8.2.2 Modem settings
General
The general settings is used to set the fundamental modes of the ED-20.
Modem Connection
Type of modem connection can be selected between PSTN (Public Switched Telephone Network) and LL (Leased Line). PSTN shall be used for dial-up/dial-in connections with PSTN, ISDN or GSM modem. LL shall be used in fixed connections, e.g. short-haul-, fibre-, LL-, or Radio-modem. In LL mode the unit will not use any modem AT-commands, Modem escape sequence, AT-commands and the Brouter function will be disabled.The modem will be handled as a transparent connection.
Allowed values: LL, PSTN Default: PSTN.
24 6609-2221
Dial IN/OUT
Select the operating mode of the ED-20.
-Dial IN, The unit will act as an PPP Server and only accept incoming calls. Modem Connect (Dial OUT) and the Brouter function will be disabled.
-Dial IN/OUT, The unit will act both as an PPP Server and an PPP Client. When an incoming call is detected then the PPP Client is disabled. –Dial OUT, The unit will act as an PPP Client and not accept incoming calls. Modem Connect (Dial IN) and the function Connect at PWR on will be disabled.
Allowed values: Dial IN, Dial IN/OUT, Dial OUT Default: Dial IN/OUT
Connect at PWR on
Selects if the ED-20 shall establish a connection at Power on or not. In PSTN mode the ED-20 will dial up using the command string defined in Modem Connect (Dial OUT) and when the modem link is ready, Establish the PPP link. In LL Mode the ED-20 will establish the PPP link. This function is disabled in Dial IN mode.
Allowed values: NO,YES Default: NO
DCD Control
When the signal DCD is lost the ED-20 will close the PPP link and when PSTN mode is selected the AT commands for Modem hangup and Modem init will be sent to the modem. This function requires a special cable.
Allowed values: NO,YES Default: NO
TD-XX
With 9-pos. female
DCE connection
9-pos. female 9-pos. female 25-pos. female 9-pos. female
ED-20
With 9-pos. female
DCE connection
22 33 88 77 44 55 11
33 22 77 88 66 55 44
TD-XX
With 25-pos. female
DCE connection
ED-20
With 9-pos. female
DCE connection
33 22 55 44
20
20
77 88
33 22 77 88 66 55 44
256609-2221
Escape Sequence
When communication is established with another modem it is still possible to reach the command mode by sending an escape sequence to the modem. Note! Refer to the user guide or installation manual to the attached modem.
Default: +++
Escape Delay
Define the delay time in seconds after the escape sequence been sent until the next AT-command will be sent.
Allowed values, 1 to 9999
If this value is set to zero, the unit will do nothing but wait!
Default: 2 (seconds)
Idle Time
If no data is being sent over the PPP link the ED-20 will close the connection. Define the time in seconds.
Allowed values, 0, 1 to 9999 Default: 0 (function disabled)
Modem AT-Commands
Commands used in PSTN mode for controlling the behaviour of the attached modem.
Note! Refer to the user guide or installation manual to the attached modem. Modem Init
Command
Init string that will be sent to the modem.
Default:AT&F&D0S0=0&K3+MS=V34;&W
Answer
Expected answer from the modem on the sent command.
Default: OK
Timeout
Define the time in seconds between the sent command and the expected answer before the command have failed.
Allowed values: 0 to 9999 Default: 3
Retries
Define the number of retries in case if a failed command.
Allowed values: 0 to 9999 Default: 1
26 6609-2221
Modem Hangup
Command
Hangup string that will be sent to the modem.
Default:ATH
Answer
Expected answer from the modem on the sent command.
Default: OK
Timeout
Define the time in seconds between the sent command and the expected answer before the command have failed.
Allowed values: 0 to 9999 Default: 3
Retries
Define the number of retries in case if a failed command.
Allowed values: 0 to 9999 Default: 1
Modem Connect (Dial Out)
Command
Dial out string that will be sent to the modem. Default:ATDS=0 (dials the stored number in location 0, stored with AT&Z command)
Answer
Expected answer from the modem on the sent command.
Default: CONNECT
Timeout
Define the time in seconds between the sent command and the expected answer before the command have failed.
Allowed values: 0 to 9999 Default: 60
Retries
Define the number of retries in case if a failed command.
Allowed values: 0 to 9999 Default: 1
Modem Connect (Dial In)
Command
Dial in string that will be sent from the modem on an incoming call.
Default: RING
276609-2221
Answer
Command that will answer the incoming call.
Default:ATA
Timeout
Define the time in seconds, For how long time the ED-20 will accept incoming calls from power-up. Normally not used, leave as is.
Allowed values: 0-9999 Default: 0
8.2.3 Network Settings
Login
The login username and password is used on the dial-in connection and when the ED-20 is configured with ED-Tool for ED-20 over a network connection.
Authentication
Select if authentication shall be used over the PPP link or not. Authentication can be used with either the PAP (Password Authentication Protocol) or CHAP protocols (Challenge Handshake Authentication Protocol) If a invalid Username or password is entered the ED-20 will disconnect the PPP link and cause the modem to disconnect.
Allowed values: NONE, PAP, CHAP Default: NONE
Username
Allowed string length: 1 – 19 characters. Allowed characters:‘0’ to ‘9’,‘a’ to ‘z’ lower case. Default: ed20
Password
Allowed string length: 1 – 19 characters. Allowed characters:‘0’ to ‘9’,‘a’ to ‘z’ lower case. Default: ed20
28 6609-2221
PPP Network Interface
These values is used when the ED-20 is in Server mode. The server will provide the IP addresses for the PPP link.
Note! When connecting to a private remote network via the ED-20 using Windows net-
work connection wizard,Always Obtain an IP address automatically
Local IP*
When the ED-20 is in server mode, this will be the Servers IP address on the PPP link Note! The Network ID must be different than the Network ID on the remote network
and the Network ID locally.
Allowed values: Should be in decimal dotted notation in one off the following ranges:
1.0.0.0 126.0.0.0
128.1.0.0 191.255.0.0
192.0.1.0 223.255.255.0 Default: 169.254.200.100
Remote address*
When the ED-20 is in server mode, this will be the Clients IP address on the PPP link Allowed values: Should be in decimal dotted notation And have the same Network ID
as Local IP and different then Local IP
Default: 169.254.200.101
Subnet Mask*
Set a valid subnet mask in decimal dotted notation.
Default: 255.255.255.0
Ethernet Interface
Local IP Address*
This is the address of the router and this address shall be used as default gateway in the units that will use the ED-20 as a gateway.
Set the local IP address in the rage of the Network ID. Note! The Network ID must be different than the Network ID on the PPP link
and the Network ID on the other network.
Allowed values: Should be in decimal dotted notation in one off the following ranges:
1.0.0.0 126.0.0.0
128.1.0.0 191.255.0.0
192.0.1.0 223.255.255.0 Default: 169.254.100.100
Subnet Mask*
Set a valid subnet mask in decimal dotted notation.
Default: 255.255.255.0
* The IP address must be compliant to the attached network.
Ask the network administrator when in doubt.
296609-2221
8.2.4 Brouter settings
The brouter function will initiate outgoing connections. This function is only available in PSTN + Dial Out mode (Refer to section 8.2.2 – General – Modem settings and Dial IN/OUT.) When a IP packet sent to the ED-20 have a IP Address that match a IP Address in the entry list, the ED-20 will send the connect message to the attached modem.This will result in an connection to another location and establishment of a PPP link. Note! Since the ED-20 and the attached modems need some time to establish a modem
connection and a PPP link,The IP packets sent before the PPP link is ready may be lost depending of the application used.
Brouter Mode
Enable or disable the brouter function with the radio buttons. Note! The brouter function can only be enabled when the ED-20 is allowed to act as a
PPP client. (Refer to section 8.2.2 – General – Dial IN/OUT.)
Default: Off
Brouter Settings
IP Address
Allowed values: Should be in decimal dotted notation and in another Network ID than the Local IP Address of the ED-20.
(Refer to section 8.2.3 – Ethernet Interface – Local IP Address)
Connect Message
This message will establish the modem connection. Allowed values: Is decided by the attached modem.
Note! Refer to the user guide or installation manual to the attached modem.
8.2.5 Firewall settings
The firewall function will allow the network administrator to control the network access and limit the traffic on the PPP link. Its possible to accomplish this in two modes.
- Pass,Will only allow traffic where the source and destination IP address is present in the entry list.
- Block,Will block traffic where either source or destination is present in the entry list.
See application exampes on page 31.
Firewall Mode
Disables or enables the Firewall mode with the radio buttons. And selects if the firewall shall work in Block or Pass mode.
Default: Off
Firewall Settings
IP Address
Allowed values: Should be in decimal dotted notation and in another Network ID than the Local IP Address of the ED-20. (Refer to section 8.2.3 – Ethernet Interface – Local IP Address)
30 6609-2221
9. Application examples
Example of application with IP address settings.
Remote connection – LAN (Dial In)
LAN – LAN (Leased Line)
LAN – LAN (PSTN, GSM)
169.254.200.100
169.254.200.101
255.255.255. 0
169.254.100.100
255.255.255. 0
DIAL IN
PSTN
NO
NO
PSTN
LAN
PLC
PLC
ED-20
TD-33
Remote connection
TD-33
ED-20
PPP ROUTER Serial Inter
face
IP: 169.254.100.101 GW: 169.254.100.100
IP: 169.254.100.102 GW: 169.254.100.100
169.254.200.100
169.254.200.101
255.255.255. 0
179.254.100.100
255.255.255. 0
169.254.200.100
169.254.200.101
255.255.255. 0
169.254.100.100
255.255.255. 0
+++
DIAL IN/OUT
L.L
NO
NO
2
600
+++
DIAL IN/OUT
L.L
NO
NO
2
600
LAN
LAN
PLC
PLC
PLC
PLC
ED-20
TD-34
Leased Line
ED-20
PPP ROUTER Serial Inter
face
ED-20
ED-20
PPP ROUTER Serial Inter
face
TD-34
IP: 179.254.100.101 GW: 179.254.100.100
IP: 179.254.100.102 GW: 179.254.100.100
IP: 169.254.100.101 GW: 169.254.100.100
IP: 169.254.100.102 GW: 169.254.100.100
PLC
LAN
PLC
ED-20
PPP ROUTER Serial Inter
face
PSTN
DIAL IN/OUT
NO
NO
+++
2
600
ED-20
TD-33/V.90
GD-01
PSTN
9
8
7
6
5
4
3
2
1
ID-90/V.90
ED-20
PPP
ROUTER
Serial Inter
face
ED-20
PSTN
DIAL IN/OUT
NO
NO
+++
2
600
LAN
PLC
PLC
316609-2221
LAN – LAN (PSTN, Brouter, Firewall)
IP: 179.254.100.101 GW: 179.254.100.100
PLC
IP: 179.254.100.102 GW: 179.254.100.100
PLC
LAN
169.254.200.100
169.254.200.101
255.255.255. 0
169.254.100.101
ATDnnnnnn
179.254.100.100
255.255.255. 0
ED-20
PPP ROUTER Serial Inter
face
ED-20
169.254.100.101 ATDnnnnnn
TD-34
PSTN
IP: 169.254.100.101 GW: 169.254.100.100
PLC
IP: 169.254.100.102 GW: 169.254.100.100
TD-34
169.254.200.100
169.254.200.101
255.255.255. 0
169.254.100.100
255.255.255. 0
ED-20
PPP
ROUTER
Serial Interface
ED-20
LAN
. . .
179.254.100.101
PLC
T03-0376 6609-2221 03.06 Mälartryck AB, Eskilstuna, Sweden
Rurstraße 4 D-
Telefon (02131) 6 69 08-0 Telefax (02131) 66 71 48
Internet: www.digicomm.de e-mail: info@digicomm.de
Loading...