A. SYSTEM OVERVIEW ......................................................................................................................................... 1
B. SWITCH OVERVIEW ......................................................................................................................................... 1
ON OFF ............................................................................................................................................................................... 2
MIN AVG MAX SCAN ................................................................................................................................................. 2
SE T ....................................................................................................................................................................................... 2
BACK ................................................................................................................................................................................... 3
SYSTEM INSTALLATION ......................................................................................................... 5
A. CONSOLE MOUNTING ..................................................................................................................................... 5
B. CONSOLE HARNESS INSTALLATION ....................................................................................................... 6
C. IMPLEMENT HARNESS/MODULE/SENSORS .......................................................................................... 9
A. SETUP CONSTANTS ............................................................................................................................................ 1 9
1 . Population Hi Limit ....................................................................................................................................................... 2 0
2 . Population Lo Limit ....................................................................................................................................................... 2 0
9 . Number of Seed Modules ............................................................................................................................................. 2 5
10. Number of Seed Sensors Per Module ....................................................................................................................... 2 5
12. Total Number Of Rows Configured ......................................................................................................................... 2 7
13. Number of Fan Speed Sensors .................................................................................................................................... 2 7
14. Fan Speed Sensor Constant .......................................................................................................................................... 2 8
15. Fan Speed Sensor Hi Limit .......................................................................................................................................... 2 8
16. Fan Speed Sensor Lo Limit .......................................................................................................................................... 2 9
17. Number of Shaft Speed Sensors .................................................................................................................................. 2 9
19. Shaft Speed Sensor Hi Limit ....................................................................................................................................... 3 0
20. Shaft Speed Sensor Lo Limit ....................................................................................................................................... 3 1
21. Number of Hopper Level Sensors .............................................................................................................................. 3 1
22. Number of Pressure Sensors ........................................................................................................................................ 3 2
23. Pressure Sensor Hi Limit .............................................................................................................................................. 3 2
24. Pressure Sensor Lo Limit.............................................................................................................................................. 3 3
26. Population Filter.............................................................................................................................................................. 3 4
27. Population Scaling Factor............................................................................................................................................. 3 4
1 . Boot Version Number ................................................................................................................................................... 3 6
2 . Flash Version Number .................................................................................................................................................. 3 7
A. OPERATE MODE .............................................................................................................................................. 3 9
B. RUN HOURS ....................................................................................................................................................... 3 9
C. POPULATION ...................................................................................................................................................... 40
1 . Population SCAN ........................................................................................................................................................ 4 1
2 . Population MIN AVG MAX ................................................................................................................................... 4 1
3 . Population SELECT ROW ....................................................................................................................................... 4 2
4 . Population Hi Limit Warning .................................................................................................................................. 5 2
5 . Population Lo Limit Warning ................................................................................................................................. 5 3
6 . Fan Speed Hi Limit Warning ................................................................................................................................... 5 3
7 . Fan Speed Lo Limit Warning................................................................................................................................... 5 4
8 . Shaft Speed Hi Limit Warning ................................................................................................................................54
9 . Shaft Speed Lo Limit Warning ................................................................................................................................55
10. Pressure Hi Limit Warning....................................................................................................................................... 5 5
11. Pressure Lo Limit Warning ...................................................................................................................................... 5 6
12. Hopper Lo Warning .................................................................................................................................................... 5 6
13. Battery Voltage Warning .......................................................................................................................................... 5 7
SELF TEST ERROR CODES .................................................................................................... 59
A. MONITOR DEAD .............................................................................................................................................. 61
B. BATTERY SYMBOL APPEARS ON DISPLAY ........................................................................................ 61
C. ERROR CODE E00 ........................................................................................................................................... 62
D. ERROR CODE E01 ........................................................................................................................................... 62
E. ERROR CODE E10 ........................................................................................................................................... 6 2
F. ERROR CODE E11 ........................................................................................................................................... 63
G. ERROR CODE E20 ........................................................................................................................................... 63
H. ERROR CODE E21 ........................................................................................................................................... 64
I.ERROR CODE E30 X ...................................................................................................................................... 64
J.ERROR CODE E31 X ......................................................................................................................................65
K. ERROR CODE E40 ........................................................................................................................................... 65
L. ERROR CODE E41 ........................................................................................................................................... 6 6
M. ERROR CODE E50 ........................................................................................................................................... 66
N. ERROR CODE E51 ........................................................................................................................................... 66
O. ERROR CODE E70 ........................................................................................................................................... 67
P. ERROR CODE E71 ........................................................................................................................................... 6 7
SETUP RECORD SHEET ........................................................................................................................................... 69
OPERATOR'S MANUAL
INTRODUCTION
A. SYSTEM
OVERVIEW
The Seed Manager® SE System offers
features such as the ability to monitor up
to ninety six (96) seed or material flow
compatible with DICKEY-john Standard
and Hi-Rate seed sensors and Recon
Flow sensors. The monitor will store all
implement configuration data in nonvolatile memory, retaining information even
when disconnected from the tractor
battery. Figure 1 shows the Seed
Manager® SE console.
Figure 1
B. SWITCH
OVERVIEW
The switches are used to control system
power, select the mode of operation, and
enter implement configuration constants.
To help distinguish between switch
names and display messages in the text
of this manual, switch names are always
shown in italicized print. An overview of
the switches follows:
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
Seed Manager® SE Console
1 2 3 . . .
l l l l
SELECT
SET
1 2 3 ...
1 2 3 4 5
®
START
STOP
RESET
INTRODUCTION/ 1
OPERATOR'S MANUAL
ON OFF
Pressing this switch applies power to the
monitor. Upon power up, the monitor
performs internal diagnostic checks,
illuminates all segments of the LCD,
sounds the alarm, and determines what
sensors are connected to the system.
Depressing the ON OFF switch for at
least one (1) second causes the system to
power down.
ALARM
Momentarily pressing this switch silences
the alarm and acknowledges the alarm
condition. Additionally, holding the
switch pressed for more than one (1)
second allows the volume level of the
alarm to be adjusted. As the switch is
held pressed, the alarm sounds continu-
ously and the volume level slowly
decreases to a minimum, then increases
to a maximum. Releasing the switch
establishes the desired volume level.
MIN AVG MAX SCAN
This switch is pressed to toggle between
the MIN AVG MAX and SCAN options
for Population and Spacing.
1 2 3 . . .
SELECT ROW
Pressing this switch while in Population
or Spacing functions freezes the display
on the current row data. Successive
depressions then cause stepping from
one row to the next. In the Setup Mode,
this switch allows stepping through the
rows while entering Row Status.
SELECT
SELECT
This switch is used to change constants in
the Setup Mode as explained in the
Setup Mode chapter. To move the
selected digit to the next digit, press the
SELECT switch.
2/ INTRODUCTION
SETUP
This switch is pressed for one (1) second
to enter the Setup Mode and to step
from one Setup constant to the next as
detailed in the Setup Mode Chapter.
SET
SET
This switch is used to change constants in
the Setup Mode as explained in the
Setup Mode chapter. To increase the
selected digit by one press the SET
switch. SET can also toggle a selection
between ON and OFF for example.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
START
STOP
RESET
START STOP RESET
This switch is used in multiple modes for
multiple purposes. Some examples are
as follow: It is used in the Operate
Mode Seed Count and Distance
Accumulator functions to start or stop
the accumulations. It is also used in
Setup Mode Distance Calibration,
Automatic Configuration, and Sensor
Self Test functions to start or stop the
test. Other functions include: Clearing
the Run Hours, Area Accumulators,
Seed Count, Distance Accumulator, and
simply clearing digits when editing Setup
constant values.
l l l l
OPERATE 1
This switch is used to select Population,
Spacing, or Ground Speed Mode.
Pressing the switch repeatedly, will
change to the next mode.
OPERATE 2
This switch is used to select Fan Speed,
Shaft Speed, or Pressure Mode (if
available on system). Pressing the switch
repeatedly, will change to the next mode.
1 2 3 ...
1 2 3 4 5
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
BACK
This switch is used in multiple modes for
multiple purposes. Some examples are
as follow: It is used in the Operate
Mode Population and Spacing functions
to step to the previous row display. It is
also used in Setup Mode to return to the
previous Setup Mode screen.
OPERATE 3
This switch is used to select Area, Seed
Count, or Distance Accumulator Mode.
Pressing the switch repeatedly, will
change to the next mode.
INTRODUCTION/ 3
OPERATOR'S MANUAL
4/ INTRODUCTION
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
SYSTEM INSTALLATION
A. CONSOLE
MOUNTING
The console should be mounted inside
the tractor cab in a location accessible to
the operator but does not obstruct the
driving view.
Refer to Figure 2 for a typical console
mounting using the U-bracket and
hardware. Install as follows:
STEP 1
Verify the rear side of the selected
mounting surface is free of wiring or
other obstructions and is accessible for
inserting and tightening the mounting
bolts.
STEP 2
Use the U-shaped mounting bracket as a
template to mark the two outside holes of
the bracket on the selected location and
drill two 9/32 inch ( 7 mm ) holes. An
alternate mounting method, which allows
the console to swivel, requires drilling the
center bracket hole only.
STEP 3
Attach the mounting bracket to the
mounting surface using the ¼ - 20 x ½
inch bolts, lockwashers, flatwashers, and
nuts.
STEP 4
Secure the console to the mounting
bracket using the two knob screws.
Insert the two rubber washers between
the bracket and console.
STEP 5
Tilt console so that the J1 connector on
the rear of the console is accessible.
Temporarily tighten the two knob screws.
Warning:
The console must not obstruct the view or
interfere with the operation of the tractor.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
Figure 2
Display Console Mounting
U-Bracket
1/4
-20 Nuts
and Lockwasher
U-Bracket
Knob
Screw
Console
Rubber
Washer
Knob
Screw
1/4-20 x 3/4 Inch
Hex Bolts &
Flat washers
Rubber
Washer
(Preferred Mounting
U-Bracket
Position)
INSTALLATION/ 5
OPERATOR'S MANUAL
B. CONSOLE
HARNESS
INSTALLATION
The J1 connector on the back of the
console connects all input and output
signals to the Seed Manager® SE
console.
The primary tractor harness is shown in
Figure 3. This harness contains connectors for a ground speed sensor (digital),
a ground speed sensor (reluctance),
system power, and P1 and P2 Bus
connectors. A secondary module
harness is used to connect to P1 and/or
P2.
For systems that contain a J2 connector, a
separate accessory harness will contain a
RS-232 connector for PC/GPS applica-
tions.
The following procedures describe
installing the primary (J1) harness from
the rear of the console to the tractor
hitch:
STEP 1
Route the primary harness from J1 on
the console rear to the rear of the
tractor, near the hitch. Route it on the
Figure 3
Primary Tractor Harness
46682-0132
Mates with Reluctance
Ground Speed Sensor
6/ INSTALLATION
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
side of the tractor opposite the alternator
and spark plugs. Locate the harness to
prevent being pinched, cut, or stepped
on and secure it with wire ties.
STEP 2
Install or connect an existing ground
speed sensor. The ground speed sensor
may be one of three types radar,
reluctance, or Hall Effect. A radar
sensor or reluctance sensor connects
directly to the designated connector on
the primary harness. A Hall Effect
sensor may require an adapter harness
to connect to the primary harness.
Sensor mounting instructions accompany
the sensor. Select the mounting location
and install as the instructions describe.
STEP 3
Follow instructions to install Module and
Sensor Harnessing in Implement
Harness section.
STEP 4
The power connections are made last to
avoid accidental shorts during harness
installation.
The Seed Manager® SE System
operates on 12 volts DC only. The
battery connections on the primary
harness consist of two wires, each
terminated with a ring terminal.
Before making the battery connections,
determine the tractor battery arrange-
ment from Figures 4, 5, and 6, found on
page 8. After the 12 volt source is
known, connect the black wire directly to
the negative (-) terminal of the battery.
The red wire (containing the fuse link)
connects directly to the positive (+)
battery terminal. Make sure the connections are clean and tight. Do not route
these wires in close proximity to the
existing battery cables. Secure the battery
wires with wire ties.
If your tractor battery arrangement
differs from those shown in Figures 4, 5,
and 6, or if in any doubt exists about
how to connect to the battery, use a
voltmeter first. Verify 11 to 14 volts
across the battery connection points. On
Tractors using two batteries, be sure to
make connections to the grounded
battery.
Note: Due to the power requirements for the Seed Manager® SE
system, the battery connections must
be made directly to the tractor
battery.
WARNING:
Before welding on the frame or chassis, be
certain to disconnect battery leads.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
INSTALLATION/ 7
OPERATOR'S MANUAL
r
e
Figure 4
12 Volt Battery Source Connections
Vehicl
Ground
12V
Vehicle
Ground
Figure 5
24 Volt Battery Source Connections
Red
Black
Power
Cable
6V
6V
Black
Red
Powe
Cable
8/ INSTALLATION
Figure 6
Negative or Positive Sources Connections
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
C. IMPLEMENT
HARNESS /
MODULES /
SENSORS
The Seed Manager® SE system uses any
combination of three basic module types,
each with their own specific harness
configurations. There are 12 Row
Material Flow Modules, 16 Row Material
Flow Modules, and Shaft Speed
Modules. A single Bus cable connects to
each module, then serially (daisy chains)
connects to following modules. The
primary harness divides into two halves
at the implement hitch (P1 and P2). The
following requirements must be ob-
served when connecting modules to the
bus:
1. A maximum of six Material Flow
Modules can be connected to the bus.
3. No more than three Material Flow
Modules can be connected to P1 or P2.
4. Any combination of 12 Row or 16 Row
Material Flow Modules may be used.
The order in which the Material Flow
Modules are connected and their
position on the toolbar or implement is
important to note. The Material Flow
Modules are identified by the console as
b1, b2, . . . bn (where n is the total
number of Material Flow Modules
connected). The order in which the
console identifies the modules depends
upon how they are connected to the bus.
The following figures show example
system configurations and how the
Console identifies the modules connect-
ed for each configuration. Note order of
the modules in relation to how they
connect to the bus.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
2. Only one Shaft Speed Module may be
connected to the bus. The Shaft Speed
Module may be connected anywhere on
the bus that is convenient. It can be
connected to either P1 or P2.
INSTALLATION/ 9
OPERATOR'S MANUAL
In this four module setup, two modules are connected to P1 and two to P2.
Figure 6A
Four module setup
P1
InOutInOutInOutInOut
P2
b1b2b3b4
In this three module setup, all modules are connected to P1.
Figure 6B
Three module setup
P1
InOutInOut
b1b2
InOut
b3
In this three module setup, one module is connected to P1 and two are connected to
P2.
Figure 6C
Three module setup
P1
P2
InOutInOut
InOut
10/ INSTALLATION
b1
b2
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
b3
OPERATOR'S MANUAL
In this two module configuration, one module is connected to both P1 and P2.
Figure 6D
Two module setup
P1
InOut
b1
P2
InOut
b2
In this five module configuration, three modules are connected to P1 and two are
connected to P2.
Figure 6E
Five module setup
P1
InOut
InOutInOut
P2
InOutInOut
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
b1b2b3b4b5
As the previous examples show, b1 is always identified as the LAST module connected
to P1. The remaining modules on P1 are number sequentially, along with any
modules connected to P2.
INSTALLATION/ 11
OPERATOR'S MANUAL
When connecting sensors to the Material Flow Modules, the following requirement
must be observed:
1. All seed sensors installed on a Material Flow Module must be connected sequential-
ly starting with Row 1 as shown below.
Figure 6F
Correct Install
CORRECT
RS-485 INRS-485 OUT
Row1Row2Row
3
Row
Row
4
9
Row6Row7Row8Row
5
Row
10
Row
11
Row
12
In the event that not all row inputs on a module will be used, the unused row inputs
must be last as shown in the following eight row module setup:
Figure 6G
Correct Install
CORRECT
RS-485 INRS-485 OUT
Row1Row2Row
3
Row
4
Row
Row6Row7Row8Row
5
Row
Row
9
10
Row
11
12
12/ INSTALLATION
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
There can be no skips in the row inputs on a Material Flow Module. The following
shows the previous eight row module setup incorrectly:
Figure 6H
Incorrect Install
INCORRECT
RS-485 INRS-485 OUT
Row1Row2Row
3
Row
Row
4
9
Row6Row7Row8Row
5
Row
10
Row
11
Row
12
Follow the same examples on all Material Flow Modules used in the system. When
correctly connected, row 1 sensor should be connected to the Row 1 input on b1. The
monitor will then number the sensors from 1 to n starting on b1, then b2, and so on.
Hopper level sensors can be connected to 12 Row Material Flow Modules. Hopper
sensors can be connected to either of the hopper inputs on a Material Flow Module.
The monitor will identify the number of hopper sensors connected to each Material
Flow Module and will number them from 1 to n starting with any sensors connected to
b1. If no sensors are connected to b1, the number starts from b2 and so on.. In the
event that two hopper sensors are connected to a given module, the sensor connected
to input 1 is numbered before the sensor connected to input 2. The following shows
an example configuration with hopper sensors connected and how they would be
identified by the console.
Figure 6I
P1
Hop 1Hop 2
P2
Hop 3Hop 4
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
InOutInOutInOutInOut
b1b2b3b4
INSTALLATION/ 13
OPERATOR'S MANUAL
When hopper level sensors are connected to a Shaft Speed Module, they are num-
bered relative to the position of the Shaft Speed Module on the bus. If the Shaft
Speed Module is connected to the RS-485 Out of b1, the numbering of the hopper
sensors starts with this module, then continues with any hopper sensors connected to
b1, b2, etc. If the Shaft Speed Module is connected between Material Flow Modules,
any hopper sensors connected are numbered in the order in which they are detected
as shown below.
Figure 6J
P2
P1
Hop 1 Hop 2Hop 3
InOutInOutIn OutIn Out
Hop 4
b1
SHAFT
b2b3
Shaft, fan, and pressure sensors can only be connected to the Shaft Speed Module.
These sensors are identified by the monitor according to what input they are connected
to regardless of the position of the Shaft Speed Module on the bus.
Figure 6K shows a complete example system setup and how each connected sensor
would be identified.
Installation Steps
STEP 1
Mount each of the modules to the toolbar or implement from in a location that will
minimize vibration and will allow for easy access to harness hookup.
STEP 2
Lay out each module harness along the frame of the implement to each of the seed
rows (or appropriate sensors). Secure the harness to the toolbar.
STEP 3
Install and/or connect each of the seed sensors (or appropriate sensor). Sensor
mounting instructions accompany the sensor. Select the mounting location and install
as described in the instructions.
14/ INSTALLATION
STEP 4
Connect each module together with a bus harness. Finally, connect the Tractor
Harness P1 and P2 connectors to the bus harness. Coil and secure existing cables
with wire ties to avoid pinching or damage to the harness.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 6K
R11 R12 R13 R14 R15 R16 R17 R18 R19 R20 R21 R22
Hop
4
Fan
1
Shaft
1
Shaft
2
Press
1
Press
2
Row
1
Row
2
Row
3
Row
4
Row
5
Row
6
Row
7
Row
8
Row
9
Row
10
Row
11
Row
12
RS-485 INRS-485 OUT
RS-485 INRS-485 OUT
Shaft
R1 R2 R3 R4 R5 R6 R7 R8 R9 R10
R23 R24 R25 R26 R27 R28 R29 R30 R31 R32
Row
1
Row
2
Row
3
Row
4
Row
5
Row
6
Row
7
Row
8
Row
9
Row
10
Row
11
Row
12
Hop
1
b1
RS-485 INRS-485 OUT
b2
P1
P2
Row
1
Row
2
Row
3
Row
4
Row
5
Row
6
Row
7
Row
8
Row
9
Row
10
Row
11
Row
12
RS-485 IN
RS-485 OUT
3
Hop
2
b3
Hop
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
INSTALLATION/ 15
OPERATOR'S MANUAL
Figure 6L
12 Row Harness
Figure 6M
16 Row Harness
16/ INSTALLATION
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 6N
Shaft Speed Module Harness
Figure 6O
RS-485 Extension Harness
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
INSTALLATION/ 17
OPERATOR'S MANUAL
18/ INSTALLATION
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
SETUP MODE
A. SETUP
CONSTANTS
The Setup Mode is used to enter the
implement configuration constants,
which are listed in Figure 7, in the order
of their presentation. Depressing the
Setup switch for one (1) second, places
the console in the Setup Mode, which is
identified by the SETUP message on the
display. Additional messages uniquely
identify the constant displayed.
Each constant has a fixed number of
digits. Leading zeroes are displayed.
When it is desired to change the value of
a constant, use the SELECT, SET, and
START STOP RESET switches as
follows:
Pressing START STOP RESET zeroes
the digit. Each depression of the
SELECT switch makes the next digit to
the right the selected digit.
When the desired value is entered (or
there is no change from the original
value), press the Setup switch to store the
value and advance to the next constant
on the list. To return to the previous
constant on the list, press the BACK
switch. If a value is entered which
exceeds the minimum or maximum
shown for that constant in Figure 7, the
alarm sounds for one (1) second, the
value of the exceeded limit appears on
the screen, and the advance to the next
constant is aborted.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
Initially, the left most digit flashes on and
off indicating it is the selected digit.
Each depression of the SET switch
increases the selected digit by one count.
After reaching the maximum value of
nine (9), the digit rolls over to zero (0).
CAUTION: To allow rapid recovery
from an entry error, it is important to
record all values of constants on the
SETUP RECORD sheet on the last page
of this manual, immediately after console
entry.
SETUP/ 19
OPERATOR'S MANUAL
Figure 8
POPULATION HI LIMIT Display
To exit the Setup Mode, press any of the
three Operate switches. Exiting automat-
ically stores the last constant changed.
The first parameter displayed after
entering the Setup Mode is the Population Hi Limit. Definitions and consider-
ations when entering values for each
constant are as follows:
1. Population Hi Limit
When the population on any row
exceeds the value entered for this
constant, in thousands of seeds per acre
Figure 9
POPULATION LO LIMIT Display
(hectare), the alarm sounds, as indicated
under the heading ALARMS, POPULATION HI LIMIT WARNING.
Figure 8 shows the display for a limit of
176,000 seeds/acre.
2. Population Lo Limit
When the population on any row falls
below the value entered for this constant,
in thousands of seeds per acre (hectare),
the alarm sounds, as indicated under the
heading ALARMS, POPULATION
LO LIMIT WARNING. Figure 9
shows the display for a limit of 144,500
seeds/acre.
20/ SETUP
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 10
ROW WIDTH Display
3. Row Width
This is the distance in inches (centime-
ters) between rows, with a resolution of
0.1. Figure 10 shows a Row Width of
38.0 inches.
Figure 11
IMPLement WIDTH Display
4. Implement Width
This is the seeding width of the imple-
ment in inches (centimeters) with a
resolution of 0.1. It is automatically
calculated when either the Number of
Modules, Number of Rows per Module,
or the Row Width is changed and can be
edited for special applications such as
skip row seeding. Figure 11 shows an
Implement Width of 720.0 inches.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
SETUP/ 21
OPERATOR'S MANUAL
Figure 12
Ground Speed Sensor Type Display
5. Ground Speed Source
Pressing the Set switch causes the lower
right display to toggle between d1, r1,
or d2. If a digital (radar or Hall Effect)
type ground speed sensor is used, and is
connected directly to the Seed Manager®
Console, press the SET switch until d1
appears. If a digital (radar or Hall Effect)
type ground speed sensor is used, and is
connected to a Shaft Speed Module, press
the SET switch until d2 appears. If a
reluctance type ground speed sensor is
used press the SET switch until r1
appears. Figure 12 shows a configuration
for a digital 1 ground speed source.
Figure 13
Distance Calibration Display
6. Distance Calibration
The Distance Calibration constant is the
number of pulses generated by the
ground speed sensor while traveling a
distance of 400 feet (122 meters). Figure
13 shows the display with the SETUP,
SPEED, and COUNT messages and the
default value of 6096, which is the
nominal pulse count for the radar
ground speed sensor. A smaller
number, typically 3100, results with a
reluctance ground speed sensor.
22/ SETUP
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
To perform the Distance Calibration:
STEP 1
Carefully measure a 400 foot (122 meter)
course, plainly marking the start and finish
points.
STEP 2
With the tractor moving between 2 and 5
MPH (3.2 and 8 Km/h), press the START
STOP RESET switch when the tractor is
exactly even with the start marker. The
display showing the Distance Calibration
constant zeroes, then counts the ground
speed pulses.
STEP 3
When the tractor is even with the finish
marker, press the START STOP RESET
switch.
STEP 4
To ensure best accuracy, perform this
procedure at least three (3) times. Record
the count each time, then enter the average
as the Distance Calibration constant, using
the SELECT and SET switches.
7. Automatic Configuration
To begin the Automatic Configuration,
press the START STOP RESET switch.
The TEST message flashes while the
Automatic Configuration is running.
Configuration is complete when the TEST
message disappears. The Automatic
Configuration will automatically detect how
many Seed Modules are connected to the
system, how many Seed Sensors are
connected to each Module, how many
Hopper Sensors are connected in the
system, and how many Pressure Sensors
are connected in the system. Note: Fan
Speed Sensors and Shaft Speed Sensors
are not automatically configured and will
need to be setup manually by the user.
When Automatic Configuration is run, the
number of seed modules, number of seed
sensors, number of hopper sensors, and
number of pressure sensors is configured
to be whatever the results of Automatic
Configuration detects in the system. Verify
the detected configuration by reviewing the
setup constants for the number of seed
modules, number of seed sensors,
number of hopper sensors, and number
of pressure sensors before beginning
operation of the implement. Figure 14
shows the Automatic Configuration
screen.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
Figure 14
Automatic Configuration Display
SETUP/ 23
OPERATOR'S MANUAL
8. Split Row Configuration
For users that utilize split, twin, or skip
row type seeding implements, this feature
will allow easy configuration for setting
up the correct row pattern that is used.
Reference Figure 15 for a listing of all of
the row patterns that can be applied to
selected, all of the rows are automatically
turned ON or OFF according to the
pattern. The user can still edit individual
rows in the Row Configuration Screen,
but it can only be done after a pattern is
selected. Figure 16 shows a row pattern
of 01 being selected.
the system. When a row pattern is
Figure 15
Split Row
ConfigurationDescription/Example
00All Rows On
01Every other Row Off, with first Row On (OXOXOX)
02Every other Row Off with first Row Off (XOXOXO)
03Every Third Row On (OXXOXXOXX)
04Every Third Row On (XXOXXOXXO)
05Every Third Row On (XOXXOXXOXX)
06Every Third Row Off (OOXOOXOOX)
07Every Third Row Off (OXOOXOOXOO)
08Every Third Row Off (XOOXOOXOO)
09Every Fourth Row On (OXXXOXXXOXXX)
10Every Fourth Row On (XXXOXXXOXXXO)
11Every Fourth Row On (XXOXXXOXXXOXXX)
12Every Fourth Row On (XOXXXOXXXOXXX)
13Twin Rows (OOXXOOXXOOXX)
14Twin Rows (OXXOOXXOOXXOO)
15Twin Rows (XXOOXXOOXXOO)
16Twin Rows (XOOXXOOXXOOXX)
17Every Fourth Row Off (OOOXOOOXOOOX)
18Every Fourth Row Off (OOXOOOXOOOXOOO)
19Every Fourth Row Off (OXOOOXOOOXOOO)
20Every Fourth Row Off (XOOOXOOOXOOO)
24/ SETUP
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 16
Pattern Select Display
9. Number of Seed Modules
This is the actual number of Seed
Modules that are connected to the
system. Note: This does not include the
Shaft Speed Module if one is available
on the system. This parameter will be
checked as part of the Sensor/Module
Self-Test, and Error codes will be
generated if this value does not match the
actual number of Seed Modules. Figure
17 shows a configuration for six (6)
modules.
Figure 17
Seed Modules Display
10. Number of Seed Sensors Per
Module
For each Seed Module that is configured
on the previous Setup Screen, there will
be a Number of Seed Sensors Per
Module screen. This is the actual number
of Seed Sensors that are connected to the
particular Module. The Modules are
Numbered from the far left of the
implement (end of P1) to the far right of
the implement (end of P2). This parame-
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
SETUP/ 25
OPERATOR'S MANUAL
Figure 18
Sensors Per Module Display
ter will be checked as part of the Sensor/
Module Self-Test and Error codes will be
generated if this value does not match the
actual number of Seed Sensors. Figure 18
shows twelve (12) seed sensors configured
on Module 3.
11. Row Status
This parameter allows placing individual
seed sensors in ON or OFF staus. For
those situations where it is necessary to
turn off certain rows on the implement,
OFF status turns off the related sensors
so alarms do not occur.
Figure 19
Row Status Display
The display initially shows the messages
SETUP, ROW, 1, and the status of row
1. Figure 19 shows row 7 status set to
OFF. Press the SET switch to toggle
between ON and OFF the sensors.
Press the SELECT ROW switch to
advance to the next row. When the
status of all rows is correctly entered,
press SETUP to advance to the next
Setup constant.
26/ SETUP
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 20
Rows Configured Display
12. Total Number Of Rows
Configured
This parameter is used to calculate
Implement Width and is used in
checking the number of seed sensors
detected upon system power up. This
value is displayed for confirmation only
and can only be altered by changing the
Number of Seed Modules or Number
of Seed Sensors Per Module parame-
ters. Figure 20 shows the display for
sixteen (16) rows.
Figure 21
Fan Speed Sensor Display
13. Number of Fan Speed Sensors
This is the actual number of Fan Speed
Sensors that are connected to a Shaft
Speed Module on the system. For each
Fan Speed Sensor that is configured
here there will be an operate screen
generated. Fan Speed Sensors are not
Self-Tested and will not generate any
error codes except for operational error
codes for Hi and Lo Limit warnings.
Figure 21 shows a configuration of two
(2) Fan Speed Sensors.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
SETUP/ 27
OPERATOR'S MANUAL
Figure 22
Fan Speed Constant Display
14. Fan Speed Sensor Constant
The Fan Speed Constant is the number
of pulses the Fan Speed Sensor gener-
ates in one revolution of the monitored
fan. This is typically the number of teeth
(sense points) on the fan. The Fan
Speed Constant can be entered as a
decimal with 0.01 resolution. Entering a
value of zero (000.00) disables the Fan
Speed function. The Fan Speed Sensor
Constant is accessible only if the
Number of Fan Speed Sensors has a
value other than 0. Figure 22 shows the
display with a Fan Speed Constant of
34.00 pulses per revolution.
Figure 23
Hi Limit Fan Speed Display
15. Fan Speed Sensor Hi Limit
This constant is the highest Fan Speed
(RPM) allowed before sounding a
warning alarm. The Hi and Lo warning
limits are accessible only if the Number
of Fan Speed Sensors has a value other
than 0. The warning is enabled or
disabled by selecting the ON or OFF
message. Use the SELECT switch to
advance one step to the right of the right
most digit, then press the SET switch to
toggle between ON and OFF. Figure 23
shows a Hi limit of 500 RPM with the
warning enabled.
28/ SETUP
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 24
Lo Limit Fan Speed Display
16. Fan Speed Sensor Lo Limit
This constant is the lowest Fan Speed
(RPM) allowed before sounding a
warning alarm. The Hi and Lo warning
limits are accessible only if the Number
of Fan Speed Sensors has a value other
than 0. The warning is enabled or
disabled by selecting the ON or OFF
message. Use the SELECT switch to
advance one step to the right of the right
most digit, then press the SET switch to
toggle between ON and OFF. Figure 24
shows a Lo limit of 25 RPM with the
warning disabled.
Figure 25
Shaft Speed Sensor Display
17. Number of Shaft Speed
Sensors
This is the actual number of Shaft Speed
Sensors that are connected to a Shaft
Speed Module on the system. For each
Shaft Speed Sensor that is configured
here, there will be an operate screen
generated. Shaft Speed Sensors are not
Self-Tested and will not generate any
error codes except for operational error
codes for Hi and Lo Limit warnings.
Figure 25 shows a configuration of three
(3) Shaft Speed Sensors.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
SETUP/ 29
OPERATOR'S MANUAL
Figure 26
Shaft Speed Constant Display
18. Shaft Speed Sensor Constant
The Shaft Speed Constant is the number
of pulses the Shaft Speed Sensor
generates in one revolution of the
monitored shaft. This is typically the
number of teeth (sense points) on the
gear attached to the monitored shaft.
The Shaft Speed Constant can be
entered as a decimal with 0.01 resolution.
Entering a value of zero (000.00) disables
the Shaft Speed function. The Shaft
Speed Sensor Constant is accessible only
if the Number of Shaft Speed Sensors
has a value other than 0. Figure 26
shows the display with a Shaft Speed
Constant of 26.00 pulses per revolution.
Figure 27
Hi Limit Shaft Speed Display
19. Shaft Speed Sensor Hi Limit
This constant is the highest Shaft Speed
(RPM) allowed before sounding a
warning alarm. The Hi and Lo warning
limits are accessible only if the Number
of Shaft Speed Sensors has a value other
than 0. The warning is enabled or
disabled by selecting the ON or OFF
message. Use the SELECT switch to
advance one step to the right of the right
most digit, then press the SET switch to
toggle between ON and OFF. Figure 27
shows a Hi limit of 65 RPM with the
warning enabled.
30/ SETUP
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 28
Lo Limit Shaft Speed Display
20. Shaft Speed Sensor Lo Limit
This constant is the lowest Shaft Speed
(RPM) allowed before sounding a
warning alarm. The Hi and Lo warning
limits are accessible only if the Number
of Shaft Speed Sensors has a value other
than 0. The warning is enabled or
disabled by selecting the ON or OFF
message. Use the SELECT switch to
advance one step to the right of the right
most digit, then press the SET switch to
toggle between ON and OFF. Figure 28
shows a Lo limit of 12 RPM with the
warning disabled.
Figure 29
Hopper Level Display
21. Number of Hopper Level
Sensors
This is the actual number of Hopper
Level Sensors that are connected to all
modules in the system. This parameter
will be checked as part of the Sensor/
Module Self-Test and Error codes will
be generated if this value does not match
the actual number of Hopper Level
Sensors. Figure 29 shows a configura-
tion of five (5) Hopper Sensors.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
SETUP/ 31
OPERATOR'S MANUAL
Figure 30
Pressure Sensor Display
22. Number of Pressure Sensors
This is the actual number of Pressure
Sensors that are connected to a Shaft
Speed Module on the system. This
parameter will be checked as part of the
Sensor/Module Self-Test, and Error
codes will be generated if this value does
not match the actual number of Pressure
Sensors. Figure 30 shows a configuration of one (1) Pressure Sensor.
23. Pressure Sensor Hi Limit
The Pressure Sensor Hi Limit Warning
is entered in oz/in2 (kPa). The Hi and
Lo warning limits are accessible only if
Figure 31
Hi Limit Pressure Display
the Number of Pressure Sensors has a
value other than 0. Setting the Pressure
Sensor Hi Limit will cause the audible
alarm to sound when the pressure
exceeds the value that has been entered.
Use the SET and SELECT switches to
adjust the Pressure Sensor Hi Limit
value. The Pressure Sensor Hi Limit
can be enabled or disabled by selecting
the ON or OFF symbol after the
rightmost digit. Pressing the SET switch
will toggle the status of the warning
between ON and OFF. Figure 31 shows
a Pressure Sensor Hi Limit of 18.0 with
the warning enabled.
32/ SETUP
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 32
Lo Limit Pressure Display
24. Pressure Sensor Lo Limit
The Pressure Sensor Lo Limit Warning
is entered in oz/in2 (kPa). The Hi and
Lo warning limits are accessible only if
the Number of Pressure Sensors has a
value other than 0. Setting the Pressure
Sensor Lo Limit will cause the audible
alarm to sound when the pressure falls
below the value that has been entered.
Use the SET and SELECT switches to
adjust the Pressure Sensor Lo Limit
value. The Pressure Sensor Lo Limit
can be enabled or disabled by selecting
the ON or OFF symbol after the
rightmost digit. Pressing the SET switch
Figure 33
Blockage Configuration
Blockage
ModeDescription
will toggle the status of the warning
between ON and OFF. Figure 32 shows
a Pressure Sensor Lo Limit of 3.8 with
the warning disabled.
25. Blockage Mode Configuration
This configuration will select one of
three different modes according to the
Table in Figure 33. If Mode 0 or Mode
1 is selected, the Operate screens will
cycle through the Population Rows only.
If Mode 2 is selected, The Population
and Spacing Operate screens will show a
series of 5 dashes to represent no data.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
0All Rows are configured for displaying Population
1First Row of each Module is configured for displaying
Population – All other rows are configured for
Blockage Only .
2All Rows are configured for Blockage Only
SETUP/ 33
OPERATOR'S MANUAL
Figure 34
Blockage Mode Display
In all modes Row failures will be
displayed according to the details in the
ALARMS section of this document.
Figure 34 shows a Blockage Mode
Configuration of 0.
26. Population Filter
In certain applications, the Seed
Manager® SE, due to its rapid update
rate, might exhibit fluctuations in
population and spacing that are undesir-
able to the operator. The population
filtering option applies an averaging filter
to the population and spacing calcula-
Figure 35
Population Filter
tions. The filter values range from 0 to
99, with 0 having no filtering effect, and
99 being the maximum filtering value.
Use the SET and SELECT switches to
adjust the filtering value. Figure 35
shows a Population Filter of 15.
27. Population Scaling Factor
The population scaling factor allows the
operator to make fine adjustments in the
readout of population and spacing on a
percentage basis. This value is adjust-
able from 1% to 999% with the factory
default being 100%. Use the SET and
34/ SETUP
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 36
Population Scaling Display
SELECT switches to adjust to the
desired population scaling factor. Figure
36 shows a Population Scaling of 105%.
28. Sensor/Module Self-Test
Start the test by pressing the START
STOP RESET switch. The TEST
message flashes while the test is executing
(Note: This is the same test that is
performed automatically during console
power up). When the test is complete
the display will show either PASSED
(and scroll through all available seed
Figure 37
Sensor Self-Test Display
rows), or show FAILED and display the
appropriate error code(s). If multiple
errors exist, the E in the error code will
be flashing. To view the next error code,
press the Alarm switch. For a full
description of all the error codes and
their meanings, see the ERROR CODES
chapter. Figure 37 shows the Sensor/
Module Self Test Screen.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
SETUP/ 35
OPERATOR'S MANUAL
Figure 38
Units Selection Display
29. English/Metric Units
The user selects the system of units with
this constant. The SET switch is used to
toggle between English and Metric units.
Figure 38 shows the display when Metric
units are selected. The METRIC
message is absent when English units are
selected.
CUSTOMER SETUP
CONSTANTS
The Customer Setup Constants are
entered by holding the SETUP switch
depressed, while powering on the
console and continuing to hold it
depressed until the Display Test begins.
A flashing SETUP message indicates the
console is in the Customer Setup
Constants. Press the SETUP switch to
advance to the next Customer Setup
Constant. To exit the Customer Setup
Constants, power off the console. The
different Customer Setup Constants are
listed as follows:
1. Boot Version Number
DICKEY-johns Service Department
may request the customer to observe and
record the four (4) different 4-digit
numbers (to identify the boot memory
software version) in the unlikely event
field problems occur.
The first 4-digit number shows on the
upper numeric display at the same time a
b1 identifier appears on the lower
numeric display. Record this number,
then press and release the SELECT
switch to step to the b2, b3, and bc
numbers, recording each 4-digit number
along with its identifier. To return to
b1 again press the SELECT switch.
Press SETUP to advance to the next
constant. Figure 39 shows 0197 for
b1, the first Boot Version Number.
36/ SETUP
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 39
Boot Number
2. Flash Version Number
DICKEY-johns Service Department
may request the customer to observe and
record the four (4) different 4-digit
numbers (to identify the flash memory
software version) in the unlikely event
field problems occur.
The first 4-digit number shows on the
upper numeric display at the same time a
F1 identifier appears on the lower
Figure 40
Flash Version Number
numeric display. Record this number,
then press and release the SELECT
switch to step to the F2, F3, and Fc
numbers, recording each 4-digit number
along with its identifier. To return to
F1 again press the SELECT switch.
Press SETUP to advance to the next
constant. Figure 40 shows 12bE for
Fc, the first Boot Version Number.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
SETUP/ 37
OPERATOR'S MANUAL
38/ SETUP
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
OPERATE MODE
A. OPERATE MODE
Performance of the following Operate
Mode functions assumes the console has
been properly installed and setup as
detailed in the INSTALLATION and
SETUP MODE chapters respectively.
Figure 41 lists all Operate Mode
functions and shows which are available
in the Speed Area Mode (defined later
in this chapter). Notice, this list includes
all the function names on the three (3)
Operate Mode switches, plus the Run
Hours function, which is performed
automatically.
Figure 41
Operate Mode Function Name Available in Speed Area Mode
B. RUN HOURS
This is defined as the total number of
accumulated hours, in 0.1 hour increments, the console has been powered.
Run Hours are not accumulated during
an ALL ROWS FAILED condition or if
a lift switch is installed and the implement
is in the up position. The Run Hours
total is displayed for five (5) seconds
immediately following the power up
sequence. The SETUP switch or any of
the three Operate Mode switches can be
pressed during the display of the Run
Hours to advance immediately to the
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
Run HoursYes
PopulationNo
Seed SpacingNo
Ground SpeedYes
Fan SpeedY es
Shaft SpeedY es
PressureYes
Area AccumulatorY es
Seed CountNo
Distance AccumulatorY es
OPERATE/ 39
OPERATOR'S MANUAL
Figure 42
Run Hours Display
desired function. Otherwise the
Population function is automatically
selected. To zero the accumulated Run
Hours, press the START STOP
RESET switch for one (1) second while
Run Hours are displayed. Figure 42
shows Run Hours of 47.5.
C. POPULATION
This is the amount of seeds, in thou-
sands of seeds per acre (hectare), sown
in a given row based, upon the most
recent sampling of the seeding rate for
that row. The Population function is
selected automatically upon power up or
by pressing the OPERATE 1 switch until
the POPULATION message appears
on the display. Only the seed rows that
have their row status set to ON will be
displayed in the Population function. If
the Blockage Mode is set to All Rows
Blockage, the upper numeric display will
show a series of five (5) dashes and no
population values will be available. The
Population display has several different
modes based upon the Setup configuration and the scan mode that is selected.
A short description of each mode is
described as follows.
40/ OPERATE
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 43
Population SCAN Display
1. Population Scan
This mode will display the population of
each valid row for two (2) seconds, then
advances to the next row. After the last
row population is displayed, the average
seeding population (for all valid popula-
tion rows) is displayed, identified by the
AVG message. Population Scan mode is
selected automatically upon powerup or
can be selected by pressing the MIN
AVG MAX SCAN switch until the
SCAN message is displayed while in
Population function. Figure 43 shows a
population of 158,400 seeds/acre on row
nine (9) while in Population Scan.
Figure 44
Population MIN-AVG-MAX Display
2. Population Min Avg Max
This mode will display the seeding row
with the minimum population, the
average seeding population, and the
seeding row with the maximum popula-
tion in cyclic fashion, dwelling on each
for three (3) seconds. This option is
selected by pressing the MIN AVG
MAX SCAN switch while in the Popula-
tion function. Figure 44 shows a
minimum population of 152,300 seeds/
acre on row five (5).
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATE/ 41
OPERATOR'S MANUAL
Figure 45
Population SELECT ROW Display
3. Population Select Row
Depressing the SELECT ROW switch
while in either Population Scan or
Population Min Avg Max freezes the
population display on the current row or
the implement average. Pressing the
SELECT ROW switch again, causes the
display to advance to the next valid
population row. Pressing the BACK
switch, will cause the display to return to
the previous valid population row.
Figure 45 shows a population of 157,400
seeds/acre on row twelve (12) while in
Population Select Row.
Figure 46
Seed spacing average Display
4. Seed Spacing
This is the calculated average spacing
between seeds in the furrow, in inches
(centimeters). The resolution is in 0.1
inches (centimeters). This function is
selected by pressing the OPERATE 1
switch until the SPACING message
appears on the display. The Seed
Spacing display has several different
modes based upon the Setup configura-
tion and the scan mode that is selected.
They are the same modes as in the
Population function. Figure 46 shows an
implement average seed spacing of 2.3
inches between seeds.
42/ OPERATE
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 47
Ground Speed Display
5. Ground Speed
This is the ground speed in MPH (Km/
h), with 0.1 resolution, as measured by
the ground speed sensor. This function
is selected by pressing the OPERATE 1
switch until the SPEED message appears
on the display. The ground speed
sensor can be either radar, Hall Effect,
or reluctance type. Figure 47 shows a
ground speed of 5.6 MPH.
Figure 48
Fan Speed Display
6. Fan Speed
This is the rotational speed of any Fan
the user wishes to monitor. A Hall
Effect type sensor senses points on a fan
to a resolution of 0.1 RPM. This
function is selected by pressing the
OPERATE 2 switch until F1 or F2 is
displayed in the lower numerical display.
Figure 48 shows a fan speed of 275.8
RPM.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATE/ 43
OPERATOR'S MANUAL
Figure 49
Shaft Speed Display
7. Shaft Speed
This is the rotational speed of any shaft
the user wishes to monitor. A Hall
Effect type sensor senses a multi-toothed
gear mounted on the shaft, to a resolu-
tion of 0.1 RPM. Typically, a shaft
driving the seeding mechanism is
monitored. This function is selected by
pressing the OPERATE 2 switch until
S1, S2, or S3 is displayed in the
lower numerical display. Figure 49
shows a shaft speed of 53.0 RPM.
Figure 50
Pressure Display
8. Pressure
This is the pressure in oz/in2 (kPa), as
measured by a pressure sensor, to a
resolution of 0.1 oz/in2 (kPa). This
function is selected by pressing the
OPERATE 2 switch until P1 or P2 is
displayed in the lower numerical display.
Figure 50 shows a pressure of 12.3 oz/
in2 .
44/ OPERATE
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 51
Area Accumulator 1 Display
9. Area Accumulator
Area Accumulator 1 and 2 are intended
to be used as field area accumulators,
displaying acres with 0.1 resolution
(hectares with 0.01 resolution). Area
Accumulator 3 is intended to be used as
a total area accumulator with the same
resolution as Area Accumulator 1 and 2.
The area calculations are based on the
Implement Width and distance traveled.
Area does not accumulate during an
ALL ROWS FAILED condition, i. e.,
when the implement is raised. This
function is selected by pressing the
OPERATE 3 switch until the AREA
message appears and a 1, 2, or 3 is
shown in the lower right corner of the
display. Area Accumulator 1 and 2 is
reset by pressing the START STOP
RESET switch for at least one (1)
second. Area Accumulator 3 is reset by
pressing the START STOP RESET
switch for at least three (3) seconds.
When a total of 9999.9 acres (999.99
hectares) is exceeded, the decimal point
shifts to the right one place. When a
total area of 99999 acres (hectares) is
exceeded, it will roll over to zero (0).
Figure 51 shows Area Accumulator 1
with 1674.3 acres.
10. Seed Count
This function is used to count the
number of seeds passing through each
seed sensor. This function is selected by
pressing the OPERATE 3 switch until
the COUNT message appears.
Press the START STOP RESET switch
to start the measurement, then press it
again to stop. The ON and OFF messages on the display indicate the Seed Count
function status. To zero the accumulated
seed count on the selected row, press
and hold the START STOP RESET
switch until a beep occurs (approximately
one (1) second). To zero the seed count
for all rows, press and hold the START
STOP RESET switch for at least three
(3) seconds. When a total of 99999
counts are exceeded, the count rolls over
to zero (0). Depress the SELECT ROW
switch to advance the display to the next
row. Depress the BACK switch to
return to the previous row.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATE/ 45
OPERATOR'S MANUAL
Figure 52
Seed Count Display
46/ OPERATE
Any other Operate Mode function can
be selected while Seed Count is running
without affecting the actual seed counts.
Figure 52 shows a stopped seed counter
with 1693 seeds counted on row fourteen
(14).
11. Distance Accumulator
This function is used to measure distances
in feet (meters), with 0.1 resolution. It can
only be used after the Distance Calibra-
tion Constant has been accurately
established (See the SETUP MODE
chapter for details). This function is
selected by pressing the OPERATE 3
switch until the DISTANCE and ACC
messages appear on the display.
Press the START STOP RESET switch
to start the measurement, then press it
again to stop. The ON and OFF messag-
es on the display indicate the Distance
Accumulator function status. To zero
the distance accumulator, press and hold
the START STOP RESET switch until a
beep occurs (approximately one (1)
second). When a total of 9999.9 feet
(meters) are exceeded the accumulator
rolls over to zero (0).
Any other Operate Mode function can
be selected while Distance Accumulator
is running without affecting the actual
distance accumulation. Figure 53 shows
a running distance accumulator with
783.6 feet measured.
12. Speed Area Mode
The Speed Area Mode is used to monitor
non-seeding operations like cultivating.
Only the Speed, Fan Speed, Shaft Speed,
Pressure, Area, and Distance Accumulator functions are available in this mode.
Figure 41 shows this function availability
in chart form. The console display for
these functions is identical in the Speed
Area and Operate Modes.
Enter the Speed Area Mode as follows:
A lift switch (Implement status switch) must
be connected to a Shaft Speed Module
that is connected to the system. No seed
sensors can be connected at this time.
Power down, then power up the console
(wait a minimum of 10 seconds before
re-powering the system).
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 53
Distance Accumulator Display
The alarm will sound momentarily and a
E00 (No seed sensors connected) error
code will be displayed. Press the
OPERATE 2 or OPERATE 3 switch,
depending on which Speed Area Mode
function is desired.
To accumulate area in the Speed Area
Mode, the lift switch must indicate the
implement is down. Run Hours
accumulate only when the implement is
down. The Distance Accumulator
function is independent of the lift switch
status.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATE/ 47
OPERATOR'S MANUAL
48/ OPERATE
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
ALARMS
Priority levels are assigned to the Seed
Manager® SE alarms as shown in Figure
54, with level one (1) being the highest. If
two alarm conditions are detected at the
same time, only the higher priority alarm
is displayed. If they are the same level,
both are displayed simultaneously.
NOTE: A Row Failure Alarm will
acknowledge the audible alarm only and
will not clear the display. To clear a Row
Failure Alarm the condition must be
fixed, or the row must be turned OFF in
SETUP MODE.
Unless indicated below, when an alarm
condition occurs, the console exits the
current Operate Mode function to
display the alarm. It returns to that
Operate Mode function only after the
alarm condition ceases or the ALARM
switch has been pressed to acknowledge
the alarm condition (except for a Row
Failure Alarm).
A warning alarm is accompanied by a
beeping sound which lasting for a fixed
period or time, which is relative to its
priority level. The higher the priority, the
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
ALARM/ 49
OPERATOR'S MANUAL
longer the alarm is sounded. Unless
otherwise indicated, a failure alarm
sounds continuously (not beeping) until
Figure 54
Alarm Levels
the failure condition ceases or is
acknowledged by pressing the ALARM
switch.
Alarms Chart
Alarm Mode Priority Level
All Rows Failed1
Row Failed2
Distance Sensor Failed3
Population Hi Limit Warning4
50/ ALARM
Population Lo Limit Warning4
Fan Speed Hi Limit Warning5
Fan Speed Lo Limit Warning5
Shaft Speed Hi Limit Warning6
Shaft Speed Lo Limit Warning6
Pressure Hi Limit Warning7
Pressure Lo Limit Warning7
Hopper Lo Warning8
Battery Voltage W arning9
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
1. All Rows Failed
This occurs at the end of each row when
the implement is lifted from the ground.
The alarm sounds continuously for
three (3) seconds, the ROWS and
FAILED messages appear, and the row
numbers are displayed sequentially. After
the alarm silences, the console reverts to
the previous Operate Mode function.
2. Rows Failed
This occurs when two (2) seeds per
second or less are detected. The alarm
sounds continuously and the row
number of the failed sensor appears
with the messages ROW and FAILED.
If multiple rows fail, the numbers of the
failed rows are sequentially displayed at
the rate of one per second. This alarm
can be acknowledged by pressing the
ALARM switch. This will silence the
audible alarm, but the display will remain
until the condition ceases, or the user
enters the SETUP MODE Row Status
and turns the faulty rows to the OFF
status. After the audible alarm is
acknowledged, the only functions that are
available are in the SETUP MODE
(reference the SETUP MODE chapter
for more information).
3. Distance Sensor Failed
If seed flow is detected without a signal
from the ground speed sensor and the
monitor is not in Seed Count function
for a duration of thirty (30) seconds, the
alarm sounds continuously for five (5)
seconds and the console automatically
enters a mode to manually enter a ground
speed value. A manual (simulated)
ground speed value, in MPH (Km/h),
appears on the display along with the
SETUP, SPEED, and FAILED messages.
To continue in the Operate Mode
without a functioning ground speed
sensor, the operator must first enter a
suitable manual ground speed value
using the SELECT and SET switches.
Figure 55 shows the above mentioned
Setup display with a manual ground
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
Figure 55
Distance Sensor FAILED Display
SETUP
SPEED
FAILED
ALARM/ 51
OPERATOR'S MANUAL
Figure 56
POPULATION HI LIMIT Warning Display
52/ ALARM
POPULATION
ROW
speed of 5.3 MPH entered. The
operator next presses the desired
Operate Mode switch to return to
seeding.
CAUTION: It is important to maintain
ground speed close to the manually
entered value to ensure accurate
monitoring.
The console will continue to use this
manual ground speed until the console is
next powered off, or the ground speed
sensor signal begins to function again.
The operator may continue seeding
without repairing or replacing a damaged
ground speed sensor or cable. However,
the same alarm display will reappear
each time power is applied to the
console, with the manual ground speed
value last entered being retained. Again,
operation can continue by pressing the
switch for the desired Operate Mode.
When the ground speed sensor has
been properly repaired or replaced,
normal operation will automatically
resume without having to deactivate the
HI
LIMIT
manual ground speed. However, it is
very important to remember to immediately repeat the SETUP MODE
Distance Calibration before resuming
operation if a different ground speed
sensor has been installed. Otherwise,
the previously determined Distance
Calibration Constant will be used,
possibly resulting in ground speed
measurement errors which may not be
readily detected. Only, repairs to ground
speed sensor cables, do not require
recalibration.
4. Population Hi Limit Warning
This occurs when any row population
exceeds the value entered for Population
Hi Limit in the SETUP MODE. The
alarm beeps for four (4) seconds and the
row number and actual population, in
thousands of seeds per acre (hectare),
are displayed. If multiple rows exceed
the limit, the row numbers are displayed
sequentially, along with their respective
populations. Figure 56 shows a Population Hi Limit Warning on row four (4)
with a row population of 34,600 seeds
per acre.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 57
POPULATION LO LIMIT Warning Display
POPULATIONLO LIMIT
ROW
5. Population Lo Limit Warning
This occurs when any row population
falls below the value entered for
Population Lo Limit in the SETUP
MODE. The alarm beeps for four (4)
seconds and the row number and actual
population, in thousands of seeds per
acre (hectare), are displayed. If multiple
rows fall below the limit, the row
numbers are displayed sequentially,
along with their respective populations.
Figure 57 shows a Population Lo Limit
Warning on row thirteen (13) with a row
population of 23,100 seeds per acre.
Figure 58
FAN SPEED HI LIMIT Warning Display
6. Fan Speed Hi Limit Warning
This occurs when any fan speed exceeds
the value entered for Fan Speed Hi
Limit in the SETUP MODE. The alarm
beeps for three (3) seconds and the fan
speed sensor number and actual fan
speed, in RPM, are displayed. If
multiple fan speed sensors exceed the
limit, the fan speed sensor numbers are
displayed sequentially, along with their
respective fan speeds. Figure 58 shows a
Fan Speed Hi Limit Warning on fan
speed sensor one (1) with a fan speed of
2,387 RPM.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
ALARM/ 53
OPERATOR'S MANUAL
Figure 59
FAN SPEED LO LIMIT Warning Display
7. Fan Speed Lo Limit Warning
This occurs when any fan speed falls
below the value entered for Fan Speed
Lo Limit in the SETUP MODE. The
alarm beeps for three (3) seconds and
the fan speed sensor number and actual
fan speed, in RPM, are displayed. If
multiple fan speed sensors fall below the
limit, the fan speed sensor numbers are
displayed sequentially, along with their
respective fan speeds. Figure 59 shows a
Fan Speed Lo Limit Warning on fan
speed sensor two (2) with a fan speed of
167 RPM.
Figure 60
SHAFT SPEED HI LIMIT Warning Display
8. Shaft Speed Hi Limit Warning
This occurs when any shaft speed
exceeds the value entered for Shaft
Speed Hi Limit in the SETUP MODE.
The alarm beeps for three (3) seconds
and the shaft speed sensor number and
actual shaft speed, in RPM, are dis-
played. If multiple shaft speed sensors
exceed the limit, the shaft speed sensor
numbers are displayed sequentially,
along with their respective shaft speeds.
Figure 60 shows a Shaft Speed Hi Limit
Warning on shaft speed sensor one (1)
with a shaft speed of 1,592 RPM.
54/ ALARM
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 61
SHAFT SPEED LO LIMIT Warning Display
9. Shaft Speed Lo Limit Warning
This occurs when any shaft speed falls
below the value entered for Shaft Speed
Lo Limit in the SETUP MODE. The
alarm beeps for three (3) seconds and
the shaft speed sensor number and
actual shaft speed, in RPM, are dis-
played. If multiple shaft speed sensors
fall below the limit, the shaft speed
sensor numbers are displayed sequen-
tially, along with their respective shaft
speeds. Figure 61 shows a Shaft Speed
Lo Limit Warning on shaft speed sensor
three (3) with a shaft speed of 427 RPM.
Figure 62
PRESSURE HI LIMIT Warning Display
10. Pressure Hi Limit Warning
This occurs when any pressure input
exceeds the value entered for Pressure
Hi Limit in the SETUP MODE. The
alarm beeps for three (3) seconds and
the pressure sensor number and actual
pressure, in oz/in2 (kPa), are displayed.
If multiple pressure sensors exceed the
limit, the pressure sensor numbers are
displayed sequentially, along with their
respective pressures. Figure 62 shows a
Pressure Hi Limit Warning on pressure
sensor one (1) with a pressure of 18.2
oz/in2 .
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
ALARM/ 55
OPERATOR'S MANUAL
Figure 63
PRESSURE LO LIMIT Warning Display
11. Pressure Lo Limit Warning
This occurs when any pressure input
falls below the value entered for
Pressure Lo Limit in the SETUP
MODE. The alarm beeps for three (3)
seconds and the pressure sensor
number and actual pressure, in oz/in
2
(kPa), are displayed. If multiple
pressure sensors fall below the limit, the
pressure sensor numbers are displayed
sequentially, along with their respective
pressures. Figure 63 shows a Pressure
Lo Limit Warning on pressure sensor
two (2) with a pressure of 2.7 oz/in2 .
Figure 64
HOPPER LO Warning Display
12. Hopper Lo Warning
This occurs when any hopper input
signals a low material level. The alarm
sounds continuously and the hopper
sensor number is displayed along with
the HOPPER and LO messages. If
multiple hopper sensors signal a low
material level, the hopper sensor
numbers are displayed sequentially.
Figure 64 shows a Hopper Lo Warning
on hopper two (2).
56/ ALARM
HOPPER
LO
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Figure 65
BATTERY VOLTAGE Warning Display
13. Battery Voltage Warning
To ensure accurate operation of the
sensors and modules, the voltage to the
console must be at least eleven (11) volts.
When the tractor battery voltage falls
below this level, regardless of the
Operate Mode function, the alarm
beeps for three (3) seconds and the
battery symbol appears. The battery
symbol remains on the display until the
low battery condition ceases. The
warning beeps reoccur each time the
monitor is powered on. Figure 65 shows
the battery symbol in the Operate Mode
Speed function with a ground speed of
3.7 MPH.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
ALARM/ 57
OPERATOR'S MANUAL
58/ ALARM
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
SELF TEST ERROR CODES
The Seed Manager® SE Console
performs a Self Test upon power up
and when commanded by the user in
SETUP MODE. At the end of the Self
Test the console will either show
PASSED and cycle through all of the
seed rows, or the console will display the
Figure 66
Self-Test Error Codes
Error CodeDescription
E00No Modules Connected
E01Too Many Modules Connected on P1 or P2
E10T oo Few Seed Modules Connected
E11T oo Many Seed Modules Connected
E20T oo Few Shaft Modules Connected
appropriate error codes that were
detected. Figure 66 shows a complete list
of all error codes that can be displayed.
See the TROUBLESHOOTING
chapter for additional details and
recommended recovery procedures.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
E21T oo Many Shaft Modules Connected
E30 XToo Few Seed Sensors Connected to Module X
E31 XT oo Many Seed Sensors Connected to Module X
E40Too Few Hopper Sensors Connected
E41Too Many Hopper Sensors Connected
E50Too Few Pressur e Sensors Connected
E51Too Many Pressur e Sensors Connected
E70Module 8v Power Supply Too Low
E71Module 8v Power Supply Too High
E98Internal LCD Driver Failure
E99Internal Bus Failure
ERROR CODES/ 59
OPERATOR'S MANUAL
60/ ERROR CODES
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
TROUBLESHOOTING
MONITOR DEAD
Probable Cause
Corrective Action
1. Blown console fuse
2. Poor battery connections
3. Cut or broken battery cable
4. Low battery voltage
5. Defective Console
1. Check console fuse. If blown, replace with a seven one-half (7.5) Amp, type
AGC fuse. If it blows again, contact DICKEY-john Technical Support to replace
console. See inside, back cover of this manual for phone number.
2. Clean and tighten battery connections
3. Repair by splicing, soldering, and individually heatshrinking each
wire. Use only Rosin Core Solder.
4. Verify battery voltage is at least twelve (12) volts. If not, recharge or replace
battery.
5. Contact DICKEY-john Technical Support. See inside, back cover of this manual
for phone number.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
BATTERY SYMBOL APPEARS ON DISPLAY
Probable Cause
1. Low battery voltage
2. Intermittent harness short to ground
3. Poor battery connections
Corrective Action
1. Recharge or replace battery
2. Locate short and repair by splicing, soldering, and sealing the wire
3. Clean and tighten battery connections
TROUBLESHOOTING/ 61
OPERATOR'S MANUAL
ERROR CODE E00
No Modules have been detected by the Console.
Probable Cause
Corrective Action
1. Implement Harness not connected to Tractor Harness
2. Implement Harness not connected to First Module (on P1 or P2 line)
3. Harnessing cut and/or pinched
4. Defective Console or Defective Module
1. Check tractor harness and implement harness connections
2. Check connection at P1 and bus harness to the first module. Reapply power to
the console. If E00 occurs again, the tractor harness, module, or console is
defective.
3. Locate the fault and repair wires by splicing, soldering, and sealing wires.
4. Contact DICKEY-john Technical Support. See inside, back cover of this manual
for phone number.
ERROR CODE E01
Too Many Modules are connected to either P1 line or P2 line.
Probable Cause
More than Four modules are connected to either P1 or P2 Bus lines on
Implement Harness.
Corrective Action
Distribute modules evenly between P1 and P2 bus lines
ERROR CODE E10
Too Few Seed Modules are Connected.
Probable Cause
1. Number of Seed Modules Configuration is incorrect.
2. Implement Harness not connected to all Seed Modules
3. Harnessing cut and/or pinched
4. Defective Module
62/ TROUBLESHOOTING
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
Corrective Action
ERROR CODE E11
Too Many Seed Modules are Connected
1. Check the Number of Seed Modules Configuration in SETUP MODE with the
actual number of modules connected.
2. Check harness connection after the module number associated with number in
lower display.
3. Locate the fault and repair wires by splicing, soldering, and sealing wires.
4. Exchange module after the module number associated with number in lower
display and reapply power to the console. If the same exact error code and lower
digit number is displayed then the module number associated with the lower
display is defective. If the lower digit changes then the module that was replaced
was defective.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
Probable Cause
Number of Seed Modules Configuration is incorrect
Corrective Action
Check the Number of Seed Modules Configuration in SETUP MODE with the
actual number of modules connected
ERROR CODE E20
Too Few Shaft Modules are connected to the System.
Probable Cause
1. Number of Fan, Shaft, or Pressure Sensors Configuration is incorrect.
2. Ground Speed input Source is set incorrectly to d2.
3. Implement Harness not connected to Shaft Speed Module
4. Harnessing cut and/or pinched
5. Defective Module
Corrective Action
1. Check the Number of Fan, Shaft, and Pressure Sensor Configuration in SETUP
MODE with the actual number of sensors connected
2. Check the Ground Speed Sensor Configuration in SETUP MODE with the
actual ground speed sensor connected
3. Check harness connection before and after the Shaft Speed Module.
4. Locate the fault and repair wires by splicing, soldering, and sealing wires.
5. Contact DICKEY-john Technical Support. See inside, back cover of this manual
for phone number.
TROUBLESHOOTING/ 63
OPERATOR'S MANUAL
ERROR CODE E21
Too Many Shaft Modules are connected to the System
Probable Cause
Corrective Action
Disconnect any additional Modules that are connected. Disconnect one module at a
time to determine which module is incorrect.
ERROR CODE E30 X
Too Few Seed Sensors are connected to Module X (X is the number of the module,
and Modules are numbered from the far Left side of the implement to the far Right
side of the implement).
System Contains incorrect parts (multiple Shaft Modules)
Probable Cause
1. Failed Seed Sensors
2. Number of Seed Sensors for Module X Configuration is Incorrect.
3. Seed Sensors not connected sequentially
4. Implement Harness is not connected to all Seed Sensors.
5. Harnessing cut and/or pinched
Corrective Action
1. Contact DICKEY-john Technical Support for a replacement sensor. See inside,
back cover of this manual for phone number.
2. Check the Number of Seed Sensors for Module X Configuration in SETUP
MODE with the actual number of Seed Sensors connected.
3. Seed Sensors on each module must be connected from the lowest to highest row
inputs without skipping rows.
4. Check harness connection to sensor number that corresponds with the number
in the lower display.
5. Locate the fault and repair wires by splicing, soldering, and sealing wires.
64/ TROUBLESHOOTING
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
ERROR CODE E31 X
Too Many Seed Sensors are connected to Module X (X is the number of the module,
and Modules are numbered from the far Left side of the implement to the far Right
side of the implement).
Probable Cause
Corrective Action
1. Number of Seed Sensors for Module X Configuration is Incorrect.
2. Implement Harness is connecting the Wrong Seed Sensors to Module X.
1. Check the Number of Seed Sensors for Module X Configuration in SETUP
MODE with the actual number of Seed Sensors connected.
2. Check harness connection to sensor number that corresponds with the number
in the lower display.
ERROR CODE E40
Too Few Hopper Sensors are connected to the system
Probable Cause
1. Number of Hopper Sensors Configuration is incorrect.
2. Hopper Sensors are Failed
3. Implement Harness is not Connected to all Hopper Sensors
4. Harnessing cut and/or pinched
Corrective Action
1. Check the Number of Hopper Sensors Configuration in SETUP MODE with
the actual number of Hopper Sensors connected.
2. Contact DICKEY-john Technical Support for a replacement sensor. See inside,
back cover of this manual for phone number.
3. Check harness connection to sensor number that corresponds with the number
in the lower display.
4. Locate the fault and repair wires by splicing, soldering, and sealing wires.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
TROUBLESHOOTING/ 65
OPERATOR'S MANUAL
ERROR CODE E41
Too Many Hopper Sensors are connected to the system.
Probable Cause
Corrective Action
ERROR CODE E50
Too Few Pressure Sensors are connected to the system.
Probable Cause
Corrective Action
Number of Hopper Sensors Configuration is incorrect
Check the Number of Hopper Sensors Configuration in SETUP MODE with the
actual number of Hopper Sensors connected.
1. Number of Pressure Sensors Configuration is incorrect
2. Pressure Sensors are failed
3. Implement Harness is not connected to all Pressure sensors
4. Harnessing cut and/or pinched
1. Check the Number of Pressure Sensors Configuration in SETUP MODE with
the actual number of Pressure Sensors connected.
2. Contact DICKEY-john Technical Support for a replacement sensor. See inside,
back cover of this manual for phone number.
3. Check harness connection to sensor number that corresponds with the number
in the lower display.
4. Locate the fault and repair wires by splicing, soldering, and sealing wires.
66/ TROUBLESHOOTING
ERROR CODE E51
Too Many Pressure Sensors are connected to the system
Probable Cause
Number of Pressure Sensors configuration is incorrect.
Corrective Action
Check the Number of Pressure Sensors Configuration in SETUP MODE with the
actual number of Pressure Sensors connected.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
OPERATOR'S MANUAL
ERROR CODE E70
Module Supply Voltage is too Low (Shorted to 5v or to Ground)
Probable Cause
Corrective Action
ERROR CODE E71
Module Supply Voltage is too High (Shorted to 12v)
1. Harnessing cut and/or pinched
2. Module is defective
1. Locate the fault and repair wires by splicing, soldering, and sealing wires.
2. Contact DICKEY-john Technical Support for a replacement module. See inside,
back cover of this manual for phone number.
Probable Cause
1. Harnessing cut and/or pinched
2. Module is defective
Corrective Action
1. Locate the fault and repair wires by splicing, soldering, and sealing wires.
2. Contact DICKEY-john Technical Support for a replacement module. See inside,
back cover of this manual for phone number.
ERROR CODE E98 E99
Internal Console Error Contact DICKEY-john Technical Support for further
assistance. See inside, back cover of this manual for phone number.
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
TROUBLESHOOTING/ 67
OPERATOR'S MANUAL
CONNECTOR PIN OUTS
Console
Modules
MATERIAL
FLOW
MODULE
12 ROW
Non RS-232 Version
J1
FUNCTIONPIN #
PROGRAM OUT 1aa
PROGRAM OUT 2bb
RS-485 AA
RS-485 BB
+12VDC SW OUT-MODULE1
GND-MODULE2
+12VDC SW OUT-AUXV
GND- AUXW
AUX SENSOR SIGNALff
+V BATTERY3
GND BATTERY4
Seed Manager® SE NON-RS-232
RS-232 Version
J1J2
FUNCTIONPIN #FUNCTIONPIN #
PROGRAM OUT 1aaTxD11
PROGRAM OUT 2bbRxD12
RS-485 AADT R13
RS-485 BBDSR14
+12VDC SW OUT-MODULE1GND15
GND-MODULE2
+12VDC SW OUT-AUXV
GND- AUXW
AUX SENSOR SIGNALff
+V BATTERY3
GND BATTERY4
Seed Manager® SE RS-232
Gray ConnectorBlack Connector
PINSCHEMATIC LABELFUNCTION
1SENSOR_1Sensor 1 signal
2SENSOR_2Sensor 2 signal
3SENSOR_3Sensor 3 signal
4SENSOR_4Sensor 4 signal
5SENSOR_5Sensor 5 signal
6SENSOR_6Sensor 6 signal
7SENSOR_7Sensor 7 signal
8SENSOR_8Sensor 8 signal
9SENSOR_9Sensor 9 signal
10SENSOR_10Sensor 10 signal
11SENSOR_11Sensor 11 signal
12SENSOR_12Sensor 12 signal
PIN (B)SCHEMATIC LABELFUNCTION
1PROGRAM LINE INProgram line in
2PROGRAM LINE OUTProgram line out
3RS485-ARS-485 A in/out
4RS485-BRS-485 B in/out
5AUX_1Hopper Level 1
6AUX_2Hopper Level 2
7AUX_3Not Used
8AUX_4Not Used
9+8VSensor 8VDC out
10RTNSensor ground
1110-16VDC INModule 12VDC in
12RTNModule ground
Gray ConnectorBlack Connector
MATERIAL
FLOW
MODULE
16 ROW
PINSCHEMATIC LABELFUNCTION
1SENSOR_1Sensor 1 signal
2SENSOR_2Sensor 2 signal
3SENSOR_3Sensor 3 signal
4SENSOR_4Sensor 4 signal
5SENSOR_5Sensor 5 signal
6SENSOR_6Sensor 6 signal
7SENSOR_7Sensor 7 signal
8SENSOR_8Sensor 8 signal
9SENSOR_9Sensor 9 signal
10SENSOR_10Sensor 10 signal
11SENSOR_11Sensor 11 signal
12SENSOR_12Sensor 12 signal
1PROGRAM LINE INProgram line in
2PROGRAM LINE OUTProgram line out
3RS485-ARS-485 A in/out
4RS485-BRS-485 B in/out
5AUX_1Sensor 13 signal
6AUX_2Sensor 14 signal
7AUX_3Sensor 15 signal
8AUX_4Sensor 16 signal
9+8VSensor 8VDC out
10RTNSensor ground
1110-16VDC INModule 12VDC in
12RTNModule ground
PINSCHEMATIC LABELFUNCTION
1PROGRAM LINE INProgram line in
2PROGRAM LINE OUTProgram line out
3RS485-ARS-485 A
4RS485-BRS-485 B
5AUX_1Fan Speed 1
6AUX_2Fan Speed 2
7AUX_3Not Used
8AUX_4Not Used
9+8VSensor 8VDC out
10RTNSensor ground
1110-16VDC INModule 12VDC in
12RTNModule ground
Dj SEED MANAGER® SE PLANTER MONITOR
BENCHMARK Series® 11001-1218-200112 Rev A
Setup Record Sheet
Parameter Name
Population Hi Limit
Population Lo Limit
Row Width
Implement Width
Ground Speed Source
Distance Calibration
Split Row Configuration
Number Of Seed Modules
Number Of Seed Sensors Module 1
Number Of Seed Sensors Module 2
Number Of Seed Sensors Module 3
Number Of Seed Sensors Module 4
Number Of Seed Sensors Module 5
Number Of Seed Sensors Module 6
Row Status
Total Number Of Rows Configured
Number Of Fan Speed Sensors
Fan Speed Sensor 1 Constant
Fan Speed Sensor 1 Hi Limit
Fan Speed Sensor 1 Lo Limit
Fan Speed Sensor 2 Constant
Fan Speed Sensor 2 Hi Limit
Fan Speed Sensor 2 Lo Limit
Number Of Shaft Speed Sensors
Shaft Speed Sensor 1 Constant
Shaft Speed Sensor 1 Hi Limit
Shaft Speed Sensor 1 Lo Limit
Shaft Speed Sensor 2 Constant
Shaft Speed Sensor 2 Hi Limit
Shaft Speed Sensor 2 Lo Limit
Shaft Speed Sensor 3 Constant
Shaft Speed Sensor 3 Hi Limit
Shaft Speed Sensor 3 Lo Limit
Number Of Hopper Sensors
Number Of Pressure Sensors
Pressure Sensor 1 Hi Limit
Pressure Sensor 1 Lo Limit
Pressure Sensor 2 Hi Limit
Pressure Sensor 2 Lo Limit
Blockage Mode Configuration
Population Filter
Population Scaling
69
Setup Record Sheet
Parameter Name
Population Hi Limit
Population Lo Limit
Row Width
Implement Width
Ground Speed Source
Distance Calibration
Split Row Configuration
Number Of Seed Modules
Number Of Seed Sensors Module 1
Number Of Seed Sensors Module 2
Number Of Seed Sensors Module 3
Number Of Seed Sensors Module 4
Number Of Seed Sensors Module 5
Number Of Seed Sensors Module 6
Row Status
Total Number Of Rows Configured
Number Of Fan Speed Sensors
Fan Speed Sensor 1 Constant
Fan Speed Sensor 1 Hi Limit
Fan Speed Sensor 1 Lo Limit
Fan Speed Sensor 2 Constant
Fan Speed Sensor 2 Hi Limit
Fan Speed Sensor 2 Lo Limit
Number Of Shaft Speed Sensors
Shaft Speed Sensor 1 Constant
Shaft Speed Sensor 1 Hi Limit
Shaft Speed Sensor 1 Lo Limit
Shaft Speed Sensor 2 Constant
Shaft Speed Sensor 2 Hi Limit
Shaft Speed Sensor 2 Lo Limit
Shaft Speed Sensor 3 Constant
Shaft Speed Sensor 3 Hi Limit
Shaft Speed Sensor 3 Lo Limit
Number Of Hopper Sensors
Number Of Pressure Sensors
Pressure Sensor 1 Hi Limit
Pressure Sensor 1 Lo Limit
Pressure Sensor 2 Hi Limit
Pressure Sensor 2 Lo Limit
Blockage Mode Configuration
Population Filter
Population Scaling
70
11001-1218-200201
DICKEY-john® WARRANTY
DICKEY-john warrants to the original purchaser for use that, if any part of the product
proves to be defective in material or workmanship within one year from date of original instal-
lation, and is returned to DICKEY-john within 30 days after such defect is discovered, DICKEY-
john will (at our option) either replace or repair said part. This warranty does not apply to
damage resulting from misuse, neglect, accident or improper installation or maintenance. Said
part will not be considered defective if it substantially fulfills the performance specifications.
THE FOREGOING WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WAR-
RANTIES OF MERCHANTABILITY, FITNESS FOR PURPOSE AND OF ANY OTHER
TYPE, WHETHER EXPRESS OR IMPLIED. DICKEY-john neither assumes nor autho-
rizes anyone to assume for it any other obligation or liability in connection with said part and
will not be liable for consequential damages. Purchaser accepts these terms and warranty
limitations unless the product is returned within fifteen days for full refund of purchase price. In
no case shall DICKEY-john be liable for any incidental, special, consequential, or similar
damages.
For DICKEY-john Service Department,
call 1-800-637-3302 in either the U.S.A. or Canada