Devatec ELMC 5, ElectroVap MC Series, ELMC 20, ELMC 30, ELMC 40 User Manual

...
Page 1
Steam humidifier
Humidificateur vapeur
ELMC tech. rev.6.1 20-02-2008
Page 2
ElectroVap MC
Contents
Safety information 2
Declaration of conformity 3
INSTALLATION
Unit mounting 5 Water connection 6 Dimensions 7 Steam outlet 8 Condensate draining 9 Ventilation units 10 Steam distribution pipes 11 Steam pipes positioning 12 Calculation of evaporation distance 13
Optional temperature control system 14
ELECTRICAL INSTALLATION
Outlet wiring diagram 16 Steam capacity 17 Electrical features 18
Electrical and control connections 19-21
Wiring the remote information system 22
Master-slave system 23-24
ELMC wiring diagrams 25-31 Final inspection 32-33
SOFTWARE ASSISTANT
Front panel identification 34 ELMC commissioning 35 Menu user information 36-37
Menu humidifier condition 38
Menu changing parameter system 39-40 Faults messages 41
MAINTENANCE
Maintenance of the cylinder 42
Cylinder maintenance guide 43
Maintenance of the valves 44
Maintenance sheet 45
Drilling templates 46-48
1
1
Page 3
ElectroVap MC
Safety information
Important
This section should be read carefully to ensure the safe and correct installation of your humidifier.
GENERAL
This manual contains all details necessary for the planning and installation of the ElectroVap MC humidifier. In addition commissioning and maintenance details are included. The manual is intended for use by engineers and properly trained technical personnel. Maintenance, servicing or repair work must only be carried out by suitable skilled and qualified personnel, the customer must be responsible for ensuring their suitability. Any risks or hazards, especially when working from ladders or towers should be identified by a skilled and Health and Safety representative and effective control measure put in place. No liability will attach to the Distributor if any damage, injury or accident is attributable to inattentive, inappropriate, negligent or incorrect operation of the machinery whether or not caused deliberately. Always isolate all electrical and water supplied before commencing any maintenance. Every effort has been made to ensure details contained in this manual are correct, however, in view of the wide range of conditions experienced in air handling systems, the information provided should only be used as a guide. Please contact your Agent if any doubt.
CORRECT USE
ElectroVap MC humidifiers are ONLY intended for use with air handling systems or direct air humidification. ANY OTHER APPLICATION IS NOT CONSIDERED USE FOR THE INTENDED PURPOSE. THE MANUFACTURER CANNOT BE MADE LIABLE FOR ANY DAMAGE RESULTING FROM INCORRECT USE.
WATER
ElectroVap MC humidifiers are designed to be used with mains, demineralized R/O or softened water. On no account attempt to introduce any other fluid or chemical into the system. Water supply should not exceed 6.0 bar and installation should comply with local regulations.
ELECTRICITY
All work concerned with electrical installation MUST only be performed by skilled and qualified technical personnel (eg electrician or technicians with appropriate training). The customer MUST be responsible for ensuring their suitability. It is the duty of the installer to ensure that suitable sized cables and MCB protection is provided. Please observe the local regulations concerning the provision of electrical installations.
WARRANTY
Failure to specify and fit original parts and accessories will invalidate your warranty.
NOTE
Our policy is one of continuous research and development. We therefore reserve the right to amend without notice the specifications given in this document.
2
Page 4
ElectroVap MC
Declaration of conformity
DIRECTIVE APPLIED
ELECTROMAGNETIC Compatibility Directive 89/336/EEC
Machinery Directive 98/37/EC Amending Directive 89/392/EEC
Low Voltage Directive 73/23/EEC
Standard(s) to which EN50081-1: 1992, EN50082-1: 1992
Conformity Is declared: EN349: 1993 EN60204-1: 1993, EN292
Parts 1&2: 1991
Manufacturer’s Name and Address
DEVATEC Rue Saint Eloi
76550 Ambrumesnil - FRANCE
Authorised Representative
Type of equipment
ELECTROVAP MC
Model Name (s) & Series:
ELMC
Year of Manufacture
2001
We the undersigned, hereby declare that the equipment
specified above conforms to the above Directive(s) and Standard(s).
Signature :
Nom : MAZIRE Michel F
Fonction : President
Date : 20.09.2001
3
3
Page 5
LCD DISPLAY
ALPHANUMERICAL
ELECTRICAL DIN RAIL
QUARTER TURN
DOOR FASTENER
TAG
IDENTITICATION
POWER LAMP
INLET VALVE
COMPONENTS
CLEANABLE CYLINDER
OUTLET VALVE
Photos non-contractuelles
Page 6
ElectroVap MC
Unit wall installation
Unit mounting
Unpack the ELMC humidifier and check for any damage.
Damage to packing and/or unit must be reported by registered letter to carrier within 3 working days.
Provide free space all around the unit : 1 m. to 1.20 m. (3 to 3 ft.) from the floor to the bottom of the humidifier,
1.25 m. (4 ft.) ahead and 0.60 m. (2 ft.) on the right hand side for allowing easy access for maintenance.
Mark the mounting holes.
Drill the holes.
Insert screws or bolts appropriate for support.
Screw the screws allowing about 10 mm (3/8 in.) for hanging the cabinet.
Hang the cabinet. Level the cabinet with a spirit level and tighten up all the screws.
Please refer to the following pages for the water and
electrical connections.
5
5
Page 7
Water connection
Flexible hose supplied
ElectroVap MC
Installation
A fresh mains cold water service should be used to supply the unit. The water supply must also satisfy the following requirements.
• Water quality: 30 to 1000 µ/cm
• Water Pressure: 1-6 bar
• Water Temp: less than 40°C The water supply connection is under bottom of the unit. All the ELMC are delivered with a water inlet hose (500mm long) with a female 3/4” connection to the cold water supply.
A check valve should be located on the mains and cold water service connection to the unit.
The inlet valve base has a basket filter see (page n°44 part n° 3).
Softener
The water level must be between (a) and (b) for the maximum cylinder capacity.
D.I. water
a
The Humidifier ELMC can run with 3 different water qualities:
TAP WATER
The water TH should be between 0 and 40° French grade for a conductivity between 1000 and 350 µ/s.
For the maintenance frequency of the cylinder see the maintenance curve. The ELMC incorporates a time counter (hours, steam KG...) and shows maintenance messages when appropriate.
SOFTENED WATER
The ElectroVap MC humidifier may be used with softened water : 0°<TH< 2°. IMPORTANT: Softeners must be programmed correctly. Failure to programme the softener correctly may lead to excessive salt concentration in the steam cylinder. For assistance contact the Softener Manufacturer. The use of duplex softeners is recommended.
Reverse Osmosis and
b
Demineralised Water
The ElectroVap MC humidifier may be used with Reverse Osmosis or Demineralised water. The minimum water quality is 30 µ/s. On start-up with new steam cylinder a tea spoon of bicarbonate of soda must be added.
The water supply must be made without any additional chemicals (chlorine, disinfectant, ozone). Also some water qualities may generate foam causing disturbances with the correct control of the humidifier. Please refer to Devatec technical services for further assistance.
6
6
Page 8
ElectroVap MC
DIMENSIONS
A
1
C
B
a
E
LMC 15-20-30
Dimension Steam Steam Weight Weight
mm outlet drain empty kg full kg
A 545 1 135 a 135 22 37
B675
C270
D 465
E 505
F40
G110
H 525
I20
E
LMC 5-8-10
Dimensions Steam Steam Weight Weight
mm outlet drain empty kg full kg
A 470 1 115 a 115 15 23
B540
C215
D 425
E 425
F20
G110
H 380
I20
ø
6
ø
6
Unit mounting
F
D
E
G
H
1 2
a b
E
LMC 90
Dimension Steam Steam Weight Weight
mm outlet drain empty kg full kg
A 1070 1 14 0 a 140 45 90
B 675 2 275 b 275
C 270 3 275 c 275
D 990
E 1030
F40
G110
H 525
I20
E
LMC 40-50-60
Dimension Steam Steam Weight Weight
mm outlet drain empty kg full kg
A 840 1 140 a 140 30 60
B 675 2 300 b 300
C270
D760
E 795
F40
G110
H 525
I20
1 2 3
I
7
a b c
66
Photos non-contractuelles
Page 9
g = 25
ElectroVap MC
g = 25 ou 40
g = 3 x 40
Steam output
Installation
Use steam hose from our supply only.
This steam hose is able to withstand 100°C.
The humidifier should be located within 3m of the steam distribution pipes if hose is to be used. If the humidifier is located higher than 3m from the steam distribution pipe/s, insulated copper tube should be used. The maximum recommendable length for steam pipe, including elbows, is 6m.
IMPORTANT: 1 elbow = 1 m equivalent length of steam pipe. There should be NO HORIZONTAL RUNS of steam hose or pipework. All steam pipework must fall either back toward the unit or toward the steam distribution pipe at an angle of 15°C to prevent condensation being trapped.
a - Vertical rise at least 500mm before the bend b - The steam hose should be rigidly supported c - Steam hose (radius of bend superior to 300 mm) d - Duct work e - Obstacle f - A condensate separator is needed at this point to drain condensate . Steam hose connection g – Steam hose : make a radius of bend of diameter 200mm with the condensate hose (siphon) h – Condensate hose i – Humidifier height
g = 2 x 25
Radius of bend
ø 25 mm = 250 mm (minimal) ø 40 mm = 400 mm (minimal)
Number of steam outlet
ELMC 5-8-10-15 = 1 x ø 25 mm ELMC 20-30 = 1 x ø 40 mm ELMC 40-50-60 = 2 x ø 40 mm ELMC 90 = 3 x ø 40 mm
Permissible duct pressure (P) for a correct working :
- P inferior to 150 mm water column
For pressures between 150 and 300 mm water column,
our optional filling cup platform mus
t be used.
8
8
Page 10
X = 100 mm
Y = 130 mm
ElectroVap MC
Condensate outlet
Installation
The following drawings show the water draining connections that should be made.
Connection to the unit by a hose draining diam25
ELMC 5-30: 1 m hose with 3 hose clamps ELMC 40-60: 1m+1.20m hose with 6 hose clamps. ELMC 90: 1m+1.20m+1.80m hose with 9 hose
clamps
X = 100 mm
Y = 375 mm
X = 150 mm
Y = 550 mm
Please follow the recommendations hereafter. Drain hose internal, diam mini
- ELMC 5/8/10/15/20/30 ø 25mm
- ELMC 40/50/60 ø 25 mm
- ELMC 90 ø 25 mm
The drain operates under gravity only. Ensure drain pipework has a pitch of at least 15°C to allow the unit to drain efficiently.
The Devatec recommended steam hoses should be used for connecting the humidifier to the drain network. Regular replacement is recommended.
The temperature of the water discharged from the humidifier is between 60°C and 100°C. Ensure the pipe work used is capable of withstanding such temperatures.
The discharge hose must be free from any obstacle.
It is recommended that each steam cylinder has its own drain pipe and tundish arrangements. This will permit fast and easy identification of a fault within a cylinder.
The discharged water should be offset from the underside of the unit as shown. This will prevent any steam and/or condensation from getting into the cabinet.
9
9
Page 11
ElectroVap MC
Room ventilation unit
Installation
0,50 m
3 m
0,70 m
1,20 m
B
A
C
Two ventilation units permit the use of the ELMC in direct space applications where there is no ductwork.
The ventilation units may be top or remote mounted. In remote mounting applications, the distance between the ventilation unit and an opposite wall should be no less than 3 m. Where the output of an individual cylinder exceeds the the capacity of a single ventilation unit, two units should be used equally distant from the ELMC humidifier (X). (X1=X2).
T = is suitable tee, available from supplier (see option list). Connection of room ventilation units to the humidifier is via terminal blocks 3 and 4 on the DIN rail (230V, 2 cores+ground).
E
F
Egout
X1
X2
15°
B
Egout
T
Model
CVMC 1 390 195 165 330 35
CV 2 520 260 350 360 35
Model Weight Db Max steam M3/H Compatible
CVMC 1 4,6 35 10 150 ELMC 5/8/10
CV 2 12 38 20 300 ELMC 15/20
ABCE F
mm
mm KG KG/ST/H with model
Photos non-contractuelles
10
Page 12
See drill template
ElectroVap MC
Steam distribution pipe
Installation
Steam from the cylinder enters the duct via a steam distribution pipe. In order to obtain optimum performance of the humidifier, it is recommended that these instructions are adhered to as far as possible.
steam distribution pipe selection
This table shows the number and the diameter of the pipe(s) per unit.
ELMC model 5-8-10-15 20-30 40-50-60 90
Number of
pipes
Diam. Stea m
condensate
1123
25
8
40
8
40
8
40
8
Short steam pipe B110
For the ductwork of widths less than 300 mm, shorter distributor, ref. B110 is available in either diameter. Where multi-cylinder units are used, it is recommended that the steam distribution pipes of differing lenghts are used, Positioned them as indicated below.
L = length 290 - 590 - 790 - 1000 - 1250 - 1500 mm.
S = hole for support, if necessary ø 5 mm. K = cut-out for insertion into the duct (see
template).
R = 4 holes ø 5 mm. H1 = 140 mm mini H2 = H1 + 140 mm mini H3 = H2 + 140 mm mini H4 = 300 mm mini
11
11
Page 13
ElectroVap MC
Steam pipe positioning
Installation
Positioning the recommended template profile for cut-out in DUCT/AHU (at the end of the brochure)
A minimum distance of 300mm between the center of the steam distribution pipe and the top of the duct should be allowed. Where the distribution pipe is installed at an angle of between 30°C and 45°C, this may be reducted to 150mm.
d: Minimum distance between the steam distribution pipe and any obstacle in the duct (filter, bend, constriction. etc) should as far as possible, be no less than 2000 mm.
In the case where a steam pipe is installed after a bend, it should be positioned in the main air flow.
In vertical ducts where air flow is upward or downwards, the steam distribution pipe should be mounted at an angle of 15°C from vertical.
12
Page 14
0
0
ElectroVap MC
Calculation of the evaporation distance
Installation
In order to determine the evaporation distance, the enclosed calculation table can be used with :
RH1 = relative humidity of the air before humidification
Before or after ventilation area
After expansion or before constriction
Vapor trail = 0.5 D
Before control sensor allow
3 – 5D for evaporation
RH2 = Relative humidity of the air after humidfication in %
RH Max = maximum difference between RH1 & RH2
HOW TO USE THE CALCULATION TABLE
Determine the difference between the relative humidity after the humidification (RH2) and the relative humidity (RH1) before humidification. The intersection between the deducted maximum RH value and RH2 gives the evaporation distance in meters (or in inches).
The tables show the D distance (in meter/inches) that should be between the steam pipe and the first obstacle (s.a. pipe positioning drawings on the lelft hand side).
If the require distance cannot be obtained on site, it is possible to install two pipes in parallel to have a better steam distribution.
NOTA : the evaporation distance shown in the
enclosed tables are for temperature between 10°C (50°F) and 25°C (77°F) and for an air velocity of 2.5 m/s (8.20 ft/s).
If accurate values cannot be reached, a distance of 2 m. (78 ft) should be considered as a minimum distance between pipes & obstruction.
Before / after filter depending on filter type
VAPOR TRAIL IN METER / RH MAX=RH2-RH1 in %
4
13
13
----
---
--
--
-
-
APOR TRAIL IN INCHES / RH MAX=RH2-RH1 in %
11.8 15.7 19.7 23.6 27.5 31.5
4
15.7 19.7 23.6 27.5 31.5 35.4 39.4
50
15.7 19.7 23.6 27.5 35.4 39.4 43.3 47.2
60
19.7 23.6 27.5 35.4 39.4 47.2 51.2 59
19.7 27.5 35.4 39.4 47.2 55.1 63 70.8 77.7
80
23.6 31.5 39.4 47.2 55.1 63 70.8 77.7 90.5
85
27.5 39.4 47.2 55.1 67 77.7 90.5 98.4
90
39.4 55.1 67 77.7 98.4
95
114.2
----
---
126
137.8 153.4 169.3
--
--
-
-
110.2 118.1
Page 15
ElectroVap MC
Optional temperature control sys
tem
INSTALLATION
For sanitation : this system holds the water in the cylinder at a temperature of 65°C
(150°F) to prevent bacteria or mold from forming in the cylinder if there is no humidity
demand.
For fast boiling : when there is a demand for humidity, the water boils more quickly than
with cold water. This produces a faster response to the humidistat and more accurate
control.
For freeze protection : can prevent freeze-up if the humidifier is subject to cold
environments. (Additional protection required for the water feed and drain lines). The
optional temperature control system overrides the automatic pre-set draining time where
the cylinder(s) is (are) drained after x hours of stop.
Note : the humidifier temperature must be switched on for this system to operate.
Set supplied in parts : T° sensor, X4 connector, stainless steel tube x Ø40mm or Ø25mm (according to ELMC model) & clamps.
300mm
The electrical wiring of the temperature sensor is made on terminals n° 15 & 16 of the X4 connector of the main board ref : 500100/03.
For boards with reference inferior to 1_22963 (programm : V2-11-), a 5,11 K.ohm resistance should be put between terminal 15 & 17 of the X4 connector.
X4
17
16
15
14
Page 16
ElectroVap MC
Electrical installation
15
x All works concerned with the electrical installation must be carried out by
skilled and qualified personnel (eg electrician with appropriate training). The customer is responsible for ensuring their suitability. Please observe local regulations concerning the provision of electrical installations.
x After about 50 hours of operation, all the screws of the power terminals must
be retightened.
x Take care : the ELMC electronic components are very sensitive to electrostatic
shocks. Appropriate steps must be taken before any operation.
14
Page 17
ElectroVap MC
p
Connection of the unit and its options
Electrical installation
Connection for ventilation units
(terminal block 3-4).
Connection to mains.
Connection to ground
Connection to on/off hygrostat
(safety & room ventilation unit)
(Terminal block 1-2).
This allows the selection of the suitable regulation. Configure dip switch S1 as follows :
Devatec sensor 0-10 V 0-10 V/2-10 V regulator
0-5 V sensor 1-5 V sensor
4-20 mA sensor 0-20 / 4-20 mA regul.
Ɣ
ƔƔ Ɣ
ƔƔ
ƔƔ
ƔƔ
ƔƔ
Red lamp of High water level
0-20 V regulator 4-20 v regulator
Terminal block X5 : connect the control signal wires here (pins 19 & 20)
! Mind the
olarities
Ɣ
ƔƔƔ
1 2 3 4
All works concerned with electrical installation must be carried
out by a skilled and qualified personnel.
16
Page 18
ElectroVap MC
Steam capacity
Electrical installation
The 2 tables under indicate the nominal value of the steam capacity in steam Kg per hour, the electrical power and the intensity according to the different power supplies.
2 x 230 V 3 x 230 V 3 x 400 V 3 x 415 V 3 x 440 V
Model Capacity Power Current Current Current Current Current ELMC Kg/V/H Kw Amps Amps Amps Amps Amps
5 5 3.76 16.3 9.6 5.5 5.3 5
8 8 6.02 15.3 8.8 8.5 8 10 10 7.52 32.7 19.1 11 10.6 10 15 15 11.3 28.7 16.5 15.9 15 20 20 15 38.2 22 21.2 20 30 30 22.6 2 x 28.7 33 31.8 30 40 40 30.1 2 x 38.2 2 x 22 2 x 21.2 2 x 20 50 50 37.6 3 x 31.9 2 x 27.5 2 x 26.5 2 x 25 60 60 45.1 3 x 38.2 2 x 33 2 x 31.8 2 x 30
90 90 67.7 3 x 33 3 x 31.8 3 x 30
3 x 460 V 3 x 575 V 3 x 600 V 3 x 690 V
Model Capacity Power Current Current Current Current ELMC Kg/V/H Kw Amps Amps Amps Amps
5 5 3.76 4.8 3.8 3.7 3.2
8 8 6.02 7.6 6.1 5.9 5.1 10 10 7.52 9.6 7.6 7.3 6.4 15 15 11.3 14.3 11.5 11 9.6 20 20 15 19.1 15.3 14.7 12.7 30 30 22.6 28.7 22.9 22 19.1 40 40 30.1 2 x 19.1 2 x 15.3 2 x 14.7 2 x 12.7 50 50 37.6 2 x 23.9 2 x 19.1 2 x 18.3 2 x 16 60 60 45.1 2 x 28.7 2 x 22.9 2 x 22 2 x 19.1 90 90 67.7 3 x 28.7 3 x 22.9 3 x 22 3 x 19.1
This table enables to determine the steam quantity produced by the ELMC according to the intensity measured.
Current
Amps Kg/V/H Kg/V/H Kg/V/H Kg/V/H Kg/V/H Kg/V/H Kg/V/H Kg/V/H Kg/V/H
2
5 10 12 15 20 25 27 30 32 37 40
2x230 V 3x230 V 3x400 V 3x415 V 3x440 V 3x460 V 3x575 V 3x600 V 3x690 V
0.61 1.05 1,82 1,89 2,00 2,09 2,62 2,73 3,14
1.53 2.62 4,55 4,72 5,00 5,23 6,54 6,82 7,85
3.06 5.23 9,10 9,44 10,01 10,46 13,08 13,65 15,69
3.67 6.28 10,92 11,33 12,01 12,55 15,69 16,37 18,83
4.59 7.85 13,65 14,16 15,01 15,69 19,62 20,47 23,54
6.12 10.46 18,19 18,88 20,01 20,92 26,15 27,29 31,39
7.65 13.08 22,74 23,60 25,02 26,15 32,69 34,11 39,23
8.26 14.12 24,56 25,48 27,02 28,25 35,31 36,84 42,37
9.18 15.69 27,29 28,32 30,02 31,39 39,23 40,94 47,08
9.79 16.74 29,11 30,20 32,02 33,48 41,85 43,67 50,22
11.32 19.35 33,66 34,92 37,03 38,71 48,39 50,49 58,06
12.24 20.92 36,39 37,75 40,03 41,85 52,31 54,58 62,77
17
Page 19
ElectroVap MC
Wiring Characteristics
Electrical installation
The below table indicates the electrical supply of the ElectroVap MC units. In all cases, the control circuit must be in single phase 230V.
2 x 230 V
50/60 Hz
3 x 230 V
50/60 Hz
3 x 400 V
50/60 Hz
3 x 415 V
50/60 Hz
3 x 440 V
50/60 Hz
External
ELMC model
circuit in A
the control
protection of
Wire control
External
section mm²
circuit
the power
protection of
Kw
Power maxi in
power maxi in
5 2 2.5 4.3 17.6
8 2 2.5 6.7
10 2 2.5 8.2 34.8
15 2 2.5 12.2
20 2 2.5 16.1
30 2 2.5 24
40 2 2.5 32
See drawing p 18
50 2 2.5 39.9
60 2 2.5 47.8
90 2 2.5
71.6
A
3 x 460 V
50 / 60 Hz
A
power maxi in
10,5 6,2 6 5,7
16,5 9,7 9,3 8,8
20,5 12 11,6 10,9
30,6 17,8 17,1 16,2
40,7 23,5 22,7 21,4
2 x 30,4 35,1 33,6 32
2 x 40,5 2 x 23,4 2 x 22,7 2 x 21,3
3 x 33,6 2 x 29,1 2 x 28,1 2 x 26,5
3 x 40,5 2 x 35,1 2 x 33,6 2 x 32
3 x 575 V
50 / 60 Hz
A
power maxi in
3 x 35,1 3 x 33,6 3 x 32
3 x 600 V
50 / 60 Hz
A
power maxi in
A
power maxi in
3 x 690 V
50 / 60 Hz
External
ELMC model
protection of
the control in A
mm²
Section of the
control cable in
External
protection of the
power circuit in A
P maxi
5 2 2.5 4.3
8 2 2.5 6.7
10 2 2.5 8.2
15 2 2.5 12.2
20 2 2.5 16.1
30 2 2.5 24
40 2 2.5 32
See drawing p 18
50 2 2.5 39.9
60 2 2.5 47.8
90 2 2.5
71.6
in Kw
in A
Maximum courant
5,4 4,4 4,3 3,8
8,4 6,8 6,6 5,8
10,5 8,4 8,1 7,1
15,5 12,5 12 10,5
20,5 16,5 15,8 13,8
30,6 24,6 23,5 20,5
2 x 20,4 2 x 16,3 2 x 15,7 2 x 13,6
2 x 25,4 2 x 20,4 2 x 19,5 2 x 17
2 x 30,6 2 x 24,6 2 x 23,5 2 x 20,5
3 x 30,6 3 x 24,6 3 x 23,5 3 x 20,5
Courant maxi in A
Courant maxi in A
Courant maxi in A
18
Page 20
Electrovap MC
Electrical connections
Electrical Installation
19
All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
18
Page 21
ElectroVap MC
Electrical Connection
When neutralis not available
Electrical installation
19
All works concerned with electrical installation must be carried
out by a skilled and qualified personnel.
20
Page 22
ElectroVap MC
Electrical connections
Electrical Installation
Terminal blocs on
the Din rail
Connection onto the board
Connection onto the board
Connection onto the board
21
All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
Page 23
ElectroVap MC
Wiring cables for remote Information system
Electrical installation
21
All works concerned with electrical installation must be carried
out by a skilled and qualified personnel.
22
Page 24
ElectroVap MC
The ELMC steam humidifiers can be run as a master and slave system. You have to connect the regulator signal on (Connector x5 terminals 18-19-20) and servo control (terminals 1-2) to a master unit ( ex: the closer to the regulation system ) and to send back this wiring on the other units (slaves).
IMPORTANT:
All the units must have the remote circuit board built-in.
WITH A REGULATION 0 – 10 V
With a 0-10V signal, the number of the units is limited by the regulator power only.
High level safety
-
Régulator
0 – 10 V
+
All the units must be to set in 0 – 10 V regulation signal ( dip-switch S1 and software 0 – 10 V)
The output signal must be connected on all units to connector x5 (terminals 19 and 20) on the main board.
1
2
O 18 O 19 O 20
O 36 O 37
Ref 100501/05
1
2
O 18 O 19 O 20
X5
X5
X22
master
Dip-switch S1 0 – 10V
S1
1 2 3 4
Regulator selection
REGULT 0 – 10 V
SLAVE 1
Dip-switch S1 0 – 10V
S1
1 2 3 4
on
on
Terminal block 1-2 of the master unit must be connected and terminals 36­37of connector x22 to terminal 1-2 of the slave unit and so on. Should a unit fail, all the units are stopped.
23
O 36 O 37
Ref 100501/05
To terminals 1 and 2 of the following slave unit ( 0 – 10 V commissioning )
X22
Regulator selection
REGULT 0 – 10 V
Page 25
ElectroVap MC
With a regulation 0– 20 V
The wiring diagram is the same as that of a 0 – 10 V regulation.
Only dip-switch S1 ( 0 – 20 V ) should be set on and the software ( code 2.3.4 ) "CHOICE REGULATION " adjusted for "REGULT 0 – 20 V"
WITH A REGULATION 4 – 20 mA
With a signal 4 – 20 mA, only one slave unit can be run because the power regulator is not powerful enough to supply all links
The master unit must be commissioned in 4 – 20 mA and the slave 0 – 10 V to save energy.
High safety limit
-
Asservissement
REGULATOR
4 – 20 mA
+
-
Ref 100501/05
O 18 O 19 O 20
O 36 O 37
1
2
X5
X22
1
2
Dip-switch S1 4 – 20mA
S1
1 2 3 4
Regulator selection
REGULT 4 – 20 mA
SLAVE 1
Dip-switch S1 0 – 10 V
MASTER
on
The output signal from the regulator must be connected to all unit on terminalq 19 and 20 of connector x5 ( + in 20 & – in 19 )
Terminal block 1-2 of the master unit must be connected and terminals 36-37of connector x22 to terminal 1-2 of the slave unit and so on. Should a unit fail, all the units are stopped.
O 18 O 19 O 20
X5
Ref 100501/05
S1
1 2 3 4
1 2 3 4
Regulator selection
REGULT 2 – 10 V
on
24
Page 26
ElectroVap MC
ELMC 5-2 wiring diagram
Electrical Installation
25
Application date : 06-11-06 From unit S/N : 100120
Through the door
Through the divider
Through unit depth
All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
24
Page 27
ElectroVap MC
ELMC 5-3 wiring diagram
Electrical Installation
All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
24
26
Page 28
ElectroVap MC
E
LMC 8-10-15-20 WIRING DIAGRAMS
Electrical Installation
27
All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
24
Page 29
ElectroVap MC
ELMC 30 wiring diagram
Electrical Installation
All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
24
28
Page 30
ElectroVap MC
ELMC 40 wiring diagram
Electrical Installation
29
All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
24
Page 31
ElectroVap MC
ELMC 50-60 wiring diagram
Electrical Installation
All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
24
30
Page 32
ElectroVap MC
ELMC 90 wiring diagram
Electrical Installation
31
All works concerned with electrical installation must be carried out by a skilled and qualified personnel.
24
Page 33
Electrovap MC
Final inspection prior to commissioning
Installation
General
1. Visualy inspect the entire installation for loose or unconnected cables and for any disconnected pipework.
2. Check the steam cylinders are located correctly in the drain valve.
3. Check electrode cable connections on the top of the steam cylinder/s.
4. Inspect all pipework including internal hoses in the humidifier for any disconnection or leaks.
5. Before making the final connection to the humidifier, flush the water pipework to waste to remove any dirt, debris, or flux.
Electrical supply
1. Check all power supply cables including neutral and ground are correctly secured in appropriate terminals.
2. Check operation of local isolators.
Controls
1. Check that the control options have been wired correctly and secured in appropriate terminals.
2. Check that the correct dip switchs setting have been made for the control signal being used. Note: If no safety control interlocks have been fitted to terminals 1&2, a link will be required to enable commissioning.
3. Check the polarity of the control signal.
Water Supply
1. Inspect and check operation of isolating valve and non-return valve on water supply to the humidifier.
2. Measure and keep a record of water pressure to the humidifier.
3. Measure and keep record of the feed water quality to the humidifier. This should include: a) Conductivity (micro Siemens/cm) b) Hardness (mg/L)
Drain
1. Inspect the drain installation to ensure the following : a) each steam cylinder drains into its own individual tundish. b) the tundish/s and drain pipework are of the correct size. c) the tundish/s is/are offset and not located directly under the
unit.
26
32
Page 34
Electrovap MC
Final inspection continued
Installation
Steam Distribution Hose/Pipe
1. Inspect the steam distribution pipe and ensure there are no horizontal runs.
2. If flexible steam hose is used check the overall length is less than 3m.
3. If copper pipe is used check the effective length is less than 6m..
4. Check the steam distribution hose/pipe is the correct size.
5. Inspect the flexible steam hose fittings and ensure they are
secured and they will prevent the hose from sagging..
6.Check copper pipe is insulated.
7. Check there is at least 500mm of straight steam hose on the
outlet of the humifier.
8. Check hose clips have been fitted and secured.
Steam Distribution Pipe
1. Check the location of steam distribution pipes have been positioned in accordance with the dimensions shown in the installation section.
2. Check that steam distribution pipes have been positioned in accordance with the dimensions pipes over 290mm long have been supported adequately.
Condensate Hose
1. Visually inspect the condensate hose to ensure the following: a) The condensate hose is secured firmly to the condensate outlet on the steam distribution pipes.
b) There is a trap in the condensate hose. c) There is a fall of 45° away from the steam distribution pipe. d) The condensate hose ends to waste waters.
FAN DISTRIBUTION UNIT
1. Check the correct clearances have been observed around the unit.
2. Check the correct electrical connection has been made inside the humidifier electrical connection.
33
27
Page 35
ElectroVap MC
Front panel identification
Software assistant
Alpha digital display
Changing program
Scrolling program
Scrolling program
Manual draining
Steam production light
ON/OFF Switch
Power light
Identification tag
30
34
Page 36
ElectroVap MC
ELMC commissioning
Software assistant
Checking and Switching on
1 - After completion of the installation inspection,
switch on the water supply to the unit.
2 - Switch on the main power supply.
3 - The power lamp must be illuminated.
4 - Switch on the main power supply I/0 on I.
The display will default to show the rate of steam produced.
The ELMC unit offers 3 main menus:
.
USER INFORMATION
The User Information menu (Humidifier Status) provides information on the operation status of the unit. No parameter can be changed from within this menu.
35
HUMIDIFIER CONDITION
(Humidifier Configuration) menu provides information only regarding the unit set up. No parameters can be changed from within this menu.
CHANGING PARAMETER
The changing parameter System menu allows all operating parameters to be adjusted. An access code is required to gain entry (2 3 4).
34
Page 37
ElectroVap MC
V
A
V
Menu user information
Software assistant
Roll up or down the menu in pushing on keys
This shows the ELMC model
This shows the Amps consumption
If external proportional regulation
If regulation : ON/OFF 2 steps 3 steps 4 steps
ACTUAL CONTROL SIGNAL Y : XX
Signal of the regulation in case with an external regulation
, press the select button
MENU HUMIDIFIER STATUS
STEAM HUMIDIFIER ELMC XX 3X400
STEAM PRODUCED
ACTUAL CURRENT
If proportional regulation incorpored + sensor
Alpha digital status
SET POINT : % RH MEASURE : %
Indicates the Rh from the sensor in case of incorporated proportional + Devatec sensor
to change menu.
This indicates the nominal steam production of the ELMC
This shows the steam demand in the installation from 20 to 100 %.
NO
YES NO
Display indication
In the menu : changement parameter system, if the selection option is yes or no T°C will be at 65°C.
Display indication
WATER TEMP. KEPT
STEAM DEMAND %
YES
In the menu : changement parameter, if yes or no has been selected (draining if long stop).
OR
TEMP. SENSOR
°
MISSING
DRAINING AFTER XXX HR STOP
36
Page 38
ElectroVap MC
g
/V
Menu user information
Software assistant
Roll up or down the menu in pushing on keys , press the select button to change menu.
This indicates the steam production between the two maintenance periods
These indicate the number of kg produced between two maintenance
This shows the power consumed by the ELMC in KW
PRODUCT BEFORE
1
CLEAN KG
NEXT SERVICE DUE
2
H
HOUR METER
3
H
STEAM METER
4
KG
MINERAL CONCENTRATION
ELECTRICAL POWER
KW
This indicates the steam production time before maintenance – it allows to plan the cleaning intervention
These indicate the time running period between two maintenance periods
This indicates that the water is normally concentrated or bein
concentrated
37
1-2
3-4
Back to the first menu page
The counting up (Hr or Kg/St). To 0, the display indicates “Maintenance: drain valve + Cylinder”. The reset of the counting up is made by pushing on the drain buttom.
The time counter and steam can be reseted in pushing on drain buttom following up to push on the changing program push buttom.
Page 39
ElectroVap MC
g
V
Menu humidifier status
Software assistant
Scroll the menu up or down by pushing on
This Indicates all possible control modes that can be used: ON/OFF, 2-3-4 steps, proportional : (0-10V, 0-20V, 0-20mA, 1-5V, 2-10V, 4-20mA, Sensor (Devatec, 0-10V, 0-5V, 4-20ma), slave regulation.
keys, press the select button to change menu
HUMIDIFIER CONFIGURATION
CONTROL SIGNAL IN 0/10
TOTAL STEAM PROD. KG
TOTAL STEAM PRODUCED HR
TOTAL HOURS RUN XX H
Total steam production since the commissionin
Diposable cylinder Tap water (EV), soft water (EA), DI water (ED), cleanable cylinder, tap water (EV), soft water (EA), DI water (ED)
This indicates the maximum electrical power needed for the ELMC.
WATER QUALITY :
CYLINDER USED :
POWER SUPPLY (V)
MAXIMUM POWER
INSTALL KW
Back to the first menu page
Water used: tap water (EV) Soft water (EA), partial DI water, DI water (ED), supplying the unit.
Indicate the voltage selected for the power circuit.
32
38
Page 40
ElectroVap MC
y
Menu configuration changing
Software assistant
Scroll the menu up or down by pushing on keys
With the humidifier switched on, press the key until the Change System Parameters menu is displayed. Press thekey and the first digit will flash. Using the and key enter the first digit of the access code and press to confirm, The next digit will start to flash. Repeat for a second and third digit of the access code. Access Code = 234
If proportional control
incorporated + senso
, press the select button
Menu : CHANGING UNIT CONFIGURATION
DIAL ACCESS CODE
XXX
Enter your access code
CONTROL SIGNAL IN
STEAM CAPACITY LIMIT
If ON/OFF, stepped or external
r
proportional control is used.
Unit supplied in ON/OFF control – An upgrading kit to proportional control is also available.
This allows to restrict the steam production capacit
ADJUST SET POINT
ADJUST PROP BAND
This allows to set the time estimated before cylinder maintenance.
Alpha digital status
%
MAINTENANCE FREQUENCY
KG/S
MAINTENANCE INTERVAL
FOAM /SCALE CONTROL
This allows to set the quality of steam estimated before maintenance of the cylinder
This enables to set the time of a small drain at each time the unit takes water
39
35
Page 41
ElectroVap MC
X
Menu configurations changing
Software assistant
Scroll the menu up or down by pushing on keys, press the select button to change menu.
This selects how unit responds to the variations in control signal - if evaporation is selected water is boiled off in response to a decrease in the control signal. This is best used on units supplied with water of low conductivity. If draining is selected the water in the cylinder is drained as the control signal decreases. This might be used with water of hight TDS or where close control is required.
This enables to give a number to the ELMC when drived by an automate or GTC.
POWER OFF IF DRAINING YES
ADJUSTMENT STEAM BY : EVAPORATION DRAINING
CYLINDER SELECT CONFIGURATION
IDENTIFICATION OF ELMC
SPEED DATA
9600 b/s
SETTING TEMP °C WATER 65°C X/
This allows to switch the contactor off when draining, avoiding current leakage.
Factory setting : Evaporation Options : Evaporation draining
This selects the suitable cylinder (disposable / cleanable for tap water, soft or DI.)
This is the speed of the computer when RS422 or 485 is used. Protocol jbus or Mod bus.
The unit will drain if there is no demand for humidity after the selected time, Factory setting : Yes Option : Yes/No
This allows the time for the above to be selected, Factory setting : 72 hr Options : 12-168 hr in 12 hr intervals
Indication on the alpha digital display
DRAIN AFTER SHUNT DOWN
YES NO
Indication on the alpha digital
display
DRAIN AFTER
HR
Back to the first menu page
36
40
Page 42
ElectroVap MC
ElectroVap MC
ElectroVap MC
Electrical features
Electrical features
Electrical features
Software assistant
P ALERTS TROUBLE CAUSES / ACTIONS OPTION
P0 ALERT
P1 ALERT
P2 ALERT
P3 ALERT
P4 ALERT
P5 ALERT
A power phase is missing
Unit on steam demand
and contactor still on
Idle demand and
contactor still off
Inlet valve constantly
open
Cylinder is not filling
correctly
Cylinder not draining
correctly
Check power supply, fuses
or power circuit breaker
(general power switchboard)
F1 fuse (2A) or contactor
coil failure.
CHANGE FUSE OR
CONTACTOR
CHANGE CONTACTOR Standard
Check correct water inlet
pressure (1 to 6 bar).
CHANGE INLET VALVE
Water supply failure or low
water pressure. Drain valve
failure.
CHANGE INLET VALVE –
CLEAN DRAIN VALVE
Blockage at the drain valve.
Drain valve coil failure.
CLEAN or CHANGE DRAIN
VALVE – REPLACE COIL-
CHANGE or CLEAN
CYLINDER
Power phase
detection device is
required
Standard
Standard
Standard
Standard
P6 ALERT
35
41
Water leakage in cylinder
part
Cylinder leaking at the
gasket.
CHANGE GASKET or
CYLINDER
Water leakage
detection device is
required
Page 43
ElectroVap MC
Cylinder maintenance
Maintenance
The ElectroVap ELMC is delivered with disposable cylinder(s) in standard which can be replaced by cleanable ones, however, without any modification, according to the choice of the user. Drain the steam cylinder using the manual drain key. When the cylinder is fully drained switch off the unit and isolate the power. The
steam cylinder may be very hot. Allow it to cool down before removing.
Remove front panel from the humidifier to access the cylinder compartment. Disconnect the steam hose from the top of the steam cylinder. Remove power and high water level electrodes from top of the steam cylinder.
Lift the cylinder upwards until it is clear of the drain valve. Ensure that the gasket remains in the drain valves. The disposable cylinder will be merely replaced by new ones.
Cleanable cylinder:
Mark the edge of the cylinder halves so the can be matched up when reassembled.
Note: The constant heating and cooling of the cylinder may cause distortion. Consequently the cylinder halves must be assembled in the same relative position. Remove nuts and bolts around the centre of the cylinder. Open up cylinder. It is important that the strainer in the bottom half of the cylinder is also cleaned.
Clean the electrodes by scraping off the mineral deposits. Alternatively, this can be done using weak descaling solution. Rinse the electrodes and the body of the cylinder. IT IS IMPORTANT TO AVOID DISTORTION THE CYLINDER IN ATTEMPTING TO REMOVE ANY MINERAL DEPOSITS FROM IT. Relocate the strainer in the cylinder base. Replace the cylinder gasket on the rim of the bottom half of the cylinder and then locate the upper half of the cylinder on the gasket, TAKING CARE THAT THE MARKS ARE ALIGNED. Refit the nuts and bolts. Clean the O-ring on the drain valve and if necessary, change it. (every 2-3 cylinder cleanings). Locate the steam outlet of the cylinder in the retaining clip.Position the base of the cylinder over the drain valve and push downwards. Reconnect the power cables.
General:
The humidifier requires regular maintenance to ensure efficient operation and to prevent breakdown. The exact maintenance frequency is variable and will depend on water quality, hours run and level of demand for humidification. New installations should be inspected / serviced every 2 to 4 weeks. This may be too frequent, but it will enable a suitable maintenance routine to be established.
Routine inspection:
The following is a guide to work that should be undertaken in a routine inspection.
1 - Inspect water and steam installation for leaks and damage. 2 - Inspect electrical installation for any loose cables and or damages.
Components. 3 - Inspect the steam cylinder for scale deposits. If the scale in the cylinder is half way up the stainer in the lower half of the cylinder it should be replaced / cleaned (see changing steam cylinder). 4 - Inspect the inlet valve. The drain valve may become blocked with scale from the steam cylinder. This will cause water to continually run to drain.
36
42
Page 44
ElectroVap MC
Maintenance guide of the cleanable
cylinder for tap or hard water
X= humidifier steam output in kg/h
Maintenance
Working hours
¾ The water tightness is indicated in French grade, the said value is the water hydrotimetric
content (TH).
¾ The water quality is to be mentioned on your request so that to fit the most appropriate steam
cylinder for the best working of the humidifier.
Lenght of the genuine stainless steel electrodes :
Model ELMC 5 ELMC 8-10 ELMC 10 single ph ELMC 15 to 90
Length (mm) 135 110 270 250
During cylinder maintenance, it is recommended to measure the length of the electrodes. The latter should be replaced when the length is shorter than 1/3 or 1/2 of the original length (s.a. above table).
36
43
Page 45
ElectroVap MC
e
m
e
t
e
m
e
Valves maintenance
Maintenance
Drain valv
To be made at each cylinder maintenance
aintenanc
Drain the steam cylinder fully and remove it from the humidifier. Isolate power and water supply before attempting to carry out any maintenance.
• Remove the cap from, the end of the solenoid valve 1
• Remove the coil from the valve stem 2
• Unscrew and remove the valve steam from the valve body 3
• Clean the valve stem with fresh water 3
• Clean the valve seat and the piston (taking care not to loose the spring 7
• Remove the O ring and drain valve collar from the top of the valve body 4
Note
Grease the O ring with high temperature silicone grease before replacing. Remove the filling cup hose from the valve body. Remove the two screws that secure the valve body to the drain cup 5. Remove the drain valve body from the drain cup and rinse with clear water ensuring any scale deposits are removed. Pay particular attention to the piston seat 6. Assemble in reverse order.
Inle
To be made every six months
valv
aintenanc
Drain the steam cylinder fully and remove it from the humidifier
Isolate power and water supply before attempting to carry out any maintenance.
• Remove the water inlet hose from the valve. 1 Remove the solenoid coil in pushing and turning 2
•Remove the basket filter from the base of the valve with a pair of long nose pliers. 3
•Wash the basket filter under clean water to remove any dirt and debris. 3 Change the O ring if necessary 4
•Assembly in reverse order.
Note
Do not forget to fit the washer when attaching the water inlet hose.
37
44
Page 46
ElectroVap MC
Follow up and maintenance file
Model : ELMC
MAINTENANCE WORKS EFFECTED
Model : ELMC
INTERVENTION
DATE
Maintenance
NEXT
INTERVENTION
45
38
Page 47
ElectroVap MC
Drilling template
46
Page 48
ElectroVap MC
Drilling template
47
Page 49
ElectroVap MC
Drilling template
48
Page 50
devatec
CS
76550 Ambrumesnil - France
Export division: tel. +33 (0)2 35 83 06 44
or +33(0)2 35 83 03 86
fax. +33(0)2 35 85 36 72 - export@devatec.com
ELMC tech Rev.6.1 - 20-02-08 edition
devatec reserves the right to change specifications or design of the equipments described in this brochure without prior notice.