DEV 5071 Documentation

Page 1
Customer Documentation
DEV 5071
High Power DC Supply
DEV Systemtechnik GmbH
Grüner Weg 4A
61169 Friedberg
Tel: +49 6031 6975 100
Fax: +49 6031 6975 114
support@dev-systemtechnik.com
www.dev-systemtechnik.com
Revision: 2017-12-19
DEV 91-0073-C
Page 2
Customer Documentation DEV 5071
TABLE OF CONTENTS
1 REVISION HISTORY ------------------------------------------------------------------------------- 5 2 INTRODUCTION ------------------------------------------------------------------------------------ 5
2.1 Warranty ----------------------------------------------------------------------------------------------- 6
2.2 Limitation of Warranty ------------------------------------------------------------------------------ 6
3 PRODUCT DESCRIPTION ----------------------------------------------------------------------- 7
3.1 Features and Options ------------------------------------------------------------------------------- 7
3.1.1 Communication Features -------------------------------------------------------------------------- 7
3.1.2 Other Options ----------------------------------------------------------------------------------------- 7
3.2 Modules Description -------------------------------------------------------------------------------- 8
3.2.1 Power Supply Module ------------------------------------------------------------------------------- 8
3.2.2 CPU Module ------------------------------------------------------------------------------------------- 9
3.3 Product Drawings ---------------------------------------------------------------------------------- 10
4 INSTALLATION INSTRUCTIONS------------------------------------------------------------- 11
4.1 Scope of Delivery ---------------------------------------------------------------------------------- 11
4.2 Installation of the Product ------------------------------------------------------------------------ 11
4.2.1 Mechanical Integration of the Product -------------------------------------------------------- 11
4.2.1.1 Installation of the Grounding Fixture ---------------------------------------------------------- 11
4.2.1.2 Integration of the Chassis in a 19" Rack ----------------------------------------------------- 12
4.2.2 Grounding, Data Cables, and Power Connection ------------------------------------------ 12
4.2.3 Installation and Exchange of Power Supply Modules ------------------------------------- 14
4.2.4 Reboot of the Device and Restore of the Factory Default Settings -------------------- 15
4.3 Device Factory Settings -------------------------------------------------------------------------- 16
4.3.1 Factory Settings for the Power Supply and Limits Information -------------------------- 16
4.3.2 Factory Default Network Settings -------------------------------------------------------------- 17
4.3.3 Factory Default SNMP Settings ---------------------------------------------------------------- 17
4.4 Communication Interface Configuration ------------------------------------------------------ 18
4.4.1 Serial Interface ------------------------------------------------------------------------------------- 18
4.4.2 Ethernet Interface ---------------------------------------------------------------------------------- 18
4.4.2.1 Ethernet Connection ------------------------------------------------------------------------------ 18
4.4.2.2 Network Setup via the Serial Interface -------------------------------------------------------- 18
4.4.2.2.1 Start and Termination of the Configuration Program -------------------------------------- 19
4.4.2.2.2 1 set IP address ----------------------------------------------------------------------------------- 20
4.4.2.2.3 2 set netmask -------------------------------------------------------------------------------------- 21
4.4.2.2.4 3 set gateway -------------------------------------------------------------------------------------- 21
4.5 Maintenance Of the Product -------------------------------------------------------------------- 21
5 OPERATION OF THE PRODUCT ------------------------------------------------------------ 22
5.1 Modes of Operation ------------------------------------------------------------------------------- 22
5.1.1 Local Mode ------------------------------------------------------------------------------------------ 22
5.1.2 Remote Mode --------------------------------------------------------------------------------------- 22
5.2 Initialization of the Device ------------------------------------------------------------------------ 22
5.3 Operation at the Device -------------------------------------------------------------------------- 22
5.4 Operation via Web Interface -------------------------------------------------------------------- 23
5.4.1 Start of the Web Interface -------------------------------- --------------------------------------- 23
5.4.2 The Main Window and Common Features of the Main Tabs --------------------------- 25
2 Copyright DEV Systemtechnik GmbH 2007-2017
Page 3
Customer Documentation DEV 5071
5.4.3 Status Tab ------------------------------------------------------------------------------------------- 26
5.4.3.1 Error Log Window --------------------------------------------------------------------------------- 27
5.4.4 Control Tab ------------------------------------------------------------------------------------------ 29
5.4.4.1 Power Supply Module ----------------------------------------------------------------------------- 30
5.4.4.2 Power Supply Output ----------------------------------------------------------------------------- 31
5.4.5 Setup Tab -------------------------------------------------------------------------------------------- 32
5.4.5.1 Password and Language ------------------------------------------------------------------------- 33
5.4.5.2 User Setup ------------------------------------------------------------------------------------------ 33
5.4.5.3 IP Configuration ------------------------------------------------------------------------------------ 35
5.4.5.4 SNMP Configuration ------------------------------------------------------------------------------ 36
5.4.5.5 Restore Factory Defaults ------------------------------------------------------------------------- 37
5.4.5.6 Software Service ----------------------------------------------------------------------------------- 38
5.4.6 Info Tab ---------------------------------------------------------------------------------------------- 39
5.5 Control via Remote Interface: SNMP --------------------------------------------------------- 40
5.5.1 SNMP Overview ------------------------------------------------------------------------------------ 40
5.5.2 DEV Private Enterprise Number, Device Index Number --------------------------------- 40
5.5.3 The DEV 5071 MIB Tree ------------------------------------------------------------------------- 41
5.5.4 MIB Objects ----------------------------------------------------------------------------------------- 41
5.5.4.1 .instrument ------------------------------------------------------------------------------------------- 42
5.5.4.1.1 .instrument.controllerMac ------------------------------------------------------------------------ 42
5.5.4.1.2 .instrument.firmwareRevision ------------------------------------------------------------------- 42
5.5.4.1.3 .instrument.instrumentType --------------------------------------------------------------------- 42
5.5.4.2 .application ------------------------------------------------------------------------------------------ 43
5.5.4.2.1 .application.controlMode ------------------------------------------------------------------------- 43
5.5.4.2.2 .application.outputVoltage ----------------------------------------------------------------------- 44
5.5.4.2.3 .application.outputCurrent ----------------------------------------------------------------------- 44
5.5.4.2.4 .application.numberOfChannels ---------------------------------------------------------------- 44
5.5.4.2.5 .application.channelTable ------------------------------------------------------------------------ 44
5.5.4.2.5.1 .application.channelTable.channelEntry.channelIndex ----------------------------------- 44
5.5.4.2.5.2 .application.channelTable.channelEntry.channelOn --------------------------------------- 44
5.5.4.2.5.3 .application.channelTable.channelEntry.channelACInputStatus------------------------ 45
5.5.4.2.5.4 .application.channelTable.channelEntry.channelTempWarning ------------------------ 45
5.5.4.2.5.5 .application.channelTable.channelEntry.channelFanStatus ----------------------------- 45
5.5.4.2.5.6 .application.channelTable.channelEntry.channelOutVoltageSet ----------------------- 45
5.5.4.2.5.7 .application.channelTable.channelEntry.channelOutVoltage ---------------------------- 45
5.5.4.2.5.8 .application.channelTable.channelEntry.channelOutCurrentSet ----------------------- 46
5.5.4.2.5.9 .application.channelTable.channelEntry.channelOutCurrent ---------------------------- 46
5.5.4.3 .surveillance ----------------------------------------------------------------------------------------- 47
5.5.4.3.1 .surveillance.trapEnableMask ------------------------------------------------------------------- 47
5.5.4.3.2 .surveillance.errorEnableMask ----------------------------------------------------------------- 48
5.5.4.3.3 .surveillance.numberOfErrors ------------------------------------------------------------------- 49
5.5.4.3.4 .surveillance.errorTable -------------------------------------------------------------------------- 49
5.5.4.3.4.1 .surveillance.errorTable.errorEntry.errorIndex ---------------------------------------------- 49
5.5.4.3.4.2 .surveillance.errorTable.errorEntry.errorNr -------------------------------------------------- 49
5.5.4.3.4.3 .surveillance.errorTable.errorEntry.errorCount --------------------------------------------- 49
5.5.4.3.4.4 .surveillance.errorTable.errorEntry.errorDateTime ---------------------------------------- 49
5.5.4.3.4.5 .surveillance.errorTable.errorEntry.errorPending ------------------------------------------ 50
5.5.4.3.4.6 .surveillance.errorTable.errorEntry.errorAcknowledge ------------------------------------ 50
5.5.4.4 .SNMPv1 TRAPs ----------------------------------------------------------------------------------- 51
5.5.4.4.1 trapAlarmText --------------------------------------------------------------------------------------- 51
5.5.4.4.2 trapAlarm -------------------------------------------------------------------------------------------- 51
5.5.4.4.3 trapModeChange ---------------------------------------------------------------------------------- 51
Copyright DEV Systemtechnik GmbH 2007-2017 3
Page 4
Customer Documentation DEV 5071
6 ERROR INDICATION----------------------------------------------------------------------------- 52
6.1 Software Error Indication ------------------------------------------------------------------------- 52
6.1.1 Power Supply Errors -------------------------------- ---------------------------------------------- 52
6.1.2 Fan Errors ------------------------------------------------------------------------------------------- 52
6.1.3 Other Errors ----------------------------------------------------------------------------------------- 52
7 CONNECTORS ------------------------------------------------------------------------------------ 53 8 TECHNICAL DATA -------------------------------- ----------------------------------------------- 54 9 OPTIONS -------------------------------------------------------------------------------------------- 54 10 SPARE PARTS ------------------------------------------------------------------------------------ 54 11 CONFORMANCE DECLARATIONS --------------------------------------------------------- 54
11.1 Certificate of Conformance ---------------------------------------------------------------------- 54
11.2 EU Declaration of Conformity ------------------------------------------------------------------- 57
12 GLOSSARY ----------------------------------------------------------------------------------------- 58 13 TABLE OF TIME ZONES ----------------------------------------------------------------------- 59 14 NOTES ----------------------------------------------------------------------------------------------- 67
APPENDIX A DATA SHEET DEV 5071
4 Copyright DEV Systemtechnik GmbH 2007-2017
Page 5
Customer Documentation DEV 5071
Revision (Date)
Author
Short Description
19-DEC-2007
WP
Initial version
20-DEC-2007
WP
Corrections and supplementations
10-JAN-2008
WP
Corrections and supplementations: output voltage set point and reboot the instrument
23-JAN-2008
WP
Corrections and supplementations
12-JUN-2008
WP
Complete rework of the document to new format and due to change to new power supply modules
03-SEP-2008
WP
Corrections and supplementations
A (24-NOV-2009)
WP
Added Option 21 and Option 22
B (19-DEC-2013)
WP
Complete rework
C (19-DEC-2017)
WP
Minor changes

1 REVISION HISTORY

2 INTRODUCTION

Thank you for purchasing a DEV 5071 High Power DC Supply. This customer documentation is intended to familiarize you with the installation and operation of the device.
The DEV 5071 chassis for professional use can be equipped with one to four power supply modules, thus realizing a reliable, powerful and usually redundant source for DC loads working on -48V DC. Of course, redundancy is provided only, if the DEV 5071 is equipped with more than one power supply module.
DEV Systemtechnik GmbH declares that this equipment meets all relevant standards and rules. The unit carries a CE mark.
Please read all instructions before installation or usage of the product!
Copyright DEV Systemtechnik GmbH 2007-2017 5
Page 6
Customer Documentation DEV 5071

2.1 WARRANTY

The product has a warranty against defects in material and workmanship for a period of two years from the date of shipment. During the warranty period DEV Systemtechnik will, at its option, either repair or replace the product if it turns out to be defective.
For warranty service or repair, the product must be returned to DEV Systemtechnik. The customer has to pay shipping charges to DEV Systemtechnik and DEV Systemtechnik will pay shipping charges to return the product to the customer. However, the customer is obliged to pay all duties, all taxes, and all other additional costs arising from the shipment of the product.
DEV Systemtechnik warrants that the software and firmware designated by DEV Systemtechnik for use with the product will execute its programming instructions if installed properly. DEV Systemtechnik does not warrant that the operation of the product, software, or firmware will be uninterrupted or error-free.

2.2 LIMITATION OF WARRANTY

The preceding warranty does not apply to defects resulting from:
improper site preparation or site maintenance; improper or inadequate interfacing of the product; unauthorized modification or misuse of the product; the application of software supplied by the customer; improper or inadequate maintenance of the product; operation beyond the environmental conditions specified for the product.
Warning:
Disconnect the unit from any external power line before opening of the housing. In any case, the unit is to be opened by especially trained people, only.
6 Copyright DEV Systemtechnik GmbH 2007-2017
Page 7
Customer Documentation DEV 5071

3 PRODUCT DESCRIPTION

DEV Systemtechnik has developed with the DEV 5071 a compact 1 RU chassis, holding one to four power supply modules. Each of the 48 V DC power supply modules is capable to deliver 2000 W. Thus, the product provides up to 8000 W at the two sets of robust galvanically isolated DC output terminals if fully populated with four power supply modules.

3.1 FEATURES AND OPTIONS

3.1.1 Communication Features

In addition to the LEDs at the power supply modules (please refer to chapter
3.2.1), the DEV 5071 provides a Web Interface and SNMP support for the surveillance and the control of the product:
A single license for the Web Interface (chapter 5.4) is included in the delivery of the device. The Web Interface provides features for checking the health status of the device and for changing specific parameters.
The implementation of SNMP (Simple Network Management Protocol) via the Ethernet interface is intended for the remote surveillance and control of the device (chapter 5.5).

3.1.2 Other Options

By default, the product is delivered with 3 power supply modules. With applied Option 21, the maximum number of power supply modules (i.e. four power supply modules) is installed. It is also possible to equip the DEV 5071 with less than three power supply modules: By ordering the product with 2 * (1 *) Option 23, the device is equipped with 1 (2) power supply module(s). The installation of power supply modules starts in slot 1; if less than four power supply modules are installed, the unused slots are covered with a blind plate. Note, that the AC power plugs of unused slots are not to be connected!
Copyright DEV Systemtechnik GmbH 2007-2017 7
Page 8
Customer Documentation DEV 5071
3 4 5 6
1 2

3.2 MODULES DESCRIPTION

This paragraph points out the functionality of the power supply modules and the CPU module.

3.2.1 Power Supply Module

The product can be equipped with 1…4 power supply modules to deliver the
required power. It is recommended to install an additional power supply module for the required power in order to provide redundancy if one of the modules fails.
Power supply modules can be removed, installed, and/or exchanged even during the operation of the device. Upgrading the DEV 5071 via an additional power supply is possible as well; please refer to chapter 4.2.3.
Plastic handle (1) and metal lever (2):
These elements are necessary for the mechanical handling of a power supply module (chapter 4.2.3).
AC LED (3):
This green LED being lit indicates whether the AC connection of the corresponding power supply module is supplied with AC. If the LED is blinking, the input voltage is out of range.
DC LED (4):
This green LED being lit indicates that the power supply module is delivering DC to the output terminals of the device. If the LED is blinking, an overload situation is signalized.
Excess Temperature / Service LED (5):
This amber LED being lit indicates excess temperature of the power supply module. If the LED is blinking it indicates a service request, please contact DEV Systemtechnik.
Error LED (6):
This red LED indicates failures of the power supply module. Reasons can be a blown AC fuse in the unit, a defective fan, or a thermal shutdown.
Note: If one of the power supply modules is turned off via software control, the
DC LED of this power supply module is off, indicating that it is not delivering any output voltage.
8 Copyright DEV Systemtechnik GmbH 2007-2017
Page 9
Customer Documentation DEV 5071
4 5
6
Ethernet
RS 232
Reset
In idle state (all power supply modules are turned off via software control,
i.e. no power supply module is delivering any output voltage, but all AC connections being established) the AC LEDs of all installed power supply modules are turned on.

3.2.2 CPU Module

The CPU module is located at the rear side of the DEV 5071 and manages the surveillance and control functionality.
"Ethernet" connector (5):
This interface is used for the communication via Web Interface or via SNMP. Please refer to chapter 4.4.2 for the configuration of the interface.
"RS 232" connector (4):
The serial interface can be used for changing the network setup (chapter 4.4.2.2).
"Reset" button (6):
The reset push button of the CPU module can be used to reboot the device, by pressing and holding the reset button (e.g. by using a ballpoint pen) for approximately three seconds. For more information on this subject, please refer to chapter 4.2.4.
Copyright DEV Systemtechnik GmbH 2007-2017 9
Page 10
Customer Documentation DEV 5071
1 2 3
4
DEV 50 71
1
Slot for power supply module 1
2
Slot for power supply module 2
3
Slot for power supply module 3
CAUT ION
HAZA RDOU S ENER GY
BEHIN D COV ER
CAUT ION
HOT S URFA CE
123
4
CAUT ION
HAZA RDOU S ENER GY
BEHIN D COV ER
CAUT ION
HOT S URFA CE
1 9 108
7
32
4 5
6
Eth erne t
RS 232
Res et
1
DC output terminals (behind plastic cover)
2
AC plug for power supply module slot 4
3
AC plug for power supply module slot 3
4
"RS 232" connector, Sub-D 9 (f)
5
"Ethernet" connector, RJ-45
6
"Reset" button
7
AC plug for power supply module slot 2
8
AC plug for power supply module slot 1
9
DC output terminals (behind plastic cover)
10
Grounding bolt of grounding fixture DEV 65-0033 (here assembled on the right side)

3.3 PRODUCT DRAWINGS

Front View:
Rear View:
10 Copyright DEV Systemtechnik GmbH 2007-2017
Page 11
Customer Documentation DEV 5071
1.
2.
3. 3.

4 INSTALLATION INSTRUCTIONS

4.1 SCOPE OF DELIVERY

1 * DEV 5071 High power DC supply equipped with the number of power supply modules as ordered 1 * DEV 65-0033 Grounding fixture 8 * M6 nuts, AF 10 mm
(for the DC connections, please refer to chapter 4.2.2) 1 * Customer documentation (this document) 1…4 * AC power cords A
A
The product is generally delivered without power cords except for deliveries within
Germany and to Switzerland.

4.2 INSTALLATION OF THE PRODUCT

4.2.1 Mechanical Integration of the Product

4.2.1.1 Installation of the Grounding Fixture Before installing the DEV 5071 into a 19" rack, the DEV 65-0033 grounding
fixture being part of the delivery has to be assembled to the rear side of the chassis. It is the choice of the customer, how the bracket is to be installed:
on the left side or on the right side, and the grounding bolt facing towards the rack or towards the chassis
In the following figure, it was chosen the right side and the grounding bolt direction towards the rack.
For the assembly of the bracket first unscrew the two M2.5 x 4 mm screws on the fixture using a PH1 screwdriver. Align the bracket towards the chassis in a way as indicated by "1." Then shift the bracket to the right ("2."), so that the bracket resides in the two recesses of the chassis. Finally, screw on the bracket with the two M2.5 x 4 mm screws ("3.").
Copyright DEV Systemtechnik GmbH 2007-2017 11
Page 12
Customer Documentation DEV 5071
123
4
1b 9b 108
7
321a 9a
Eth erne t
RS 232
Res et
4 5
6
1a
DC output terminals V+
1b
DC output terminals V-
2
AC plug for power supply module slot 4
3
AC plug for power supply module slot 3
4
"RS 232" connector, Sub-D 9 (f)
5
"Ethernet" connector, RJ-45
6
"Reset" button
7
AC plug for power supply module slot 2
8
AC plug for power supply module slot 1
9a
DC output terminals V+
9b
DC output terminals V-
10
Grounding bolt of grounding fixture DEV 65-0033 (here assembled on the right side)
4.2.1.2 Integration of the Chassis in a 19" Rack For the integration in a 19" rack, the rack slots must be prepared with rails
for the chassis. After inserting the chassis in the rack, fix the chassis with four screws to the rack at its rack mount flanges.
Warning:
It is not permitted, to fix the chassis on the rack mount flanges, only. Sufficient airflow through the power supply must be ensured to achieve
best cooling results. Do not block or obstruct the airflow through the chassis at the front and at the rear side, e.g. by placing large components close to the rear side. It is recommended to provide 1 RU space in the rack above and below the chassis to ensure a good air circulation.

4.2.2 Grounding, Data Cables, and Power Connection

The chassis needs to be connected with the DEV 65-0033 grounding fixture to the 19" rack via a ground wire. The installation of the grounding fixture was already described in chapter 4.2.1.1. Take off the upper nut and the first washer of to the grounding bolt ((10) in the figure above). Then connect the grounding cable, which must have a ring tongue terminal matching for the M5 fastening bolt. The washer and the nut then have to be tightened again.
Establish the Ethernet connection by plugging an Ethernet cable from your network to the "Ethernet" port (5). If the network setup via the serial interface is required (please refer to chapter 4.4.2.2), a serial connection between a PC and the serial connector labeled "RS 232" (4) is to be established by using a 1:1 cable; the configuration of the serial interface is described in chapter 4.4.1.
12 Copyright DEV Systemtechnik GmbH 2007-2017
Page 13
Customer Documentation DEV 5071
Before connecting (the) power cords, the DC output connections are to be installed. There are provided two sets of DC output terminals (1a/1b, 9a/9b) located behind plastic covers. The click-on covers are easily to be opened, the left cover has the hinge at the bottom side, and the right cover has the hinge on the top side of the chassis, like shown in the figure above. The prepared DC cables are to be connected using the provided M6 nuts.
Note: The product can be used to supply +48 V DC by connecting the DC
cables in the fashion, that the positive cable(s) run(s) to the V+ DC output terminal(s) (1a, 9a). The negative (or ground) cable(s) is/are to be connected the V- DC output terminal(s) (1b, 9b). To obtain -48 V DC the polarity of the DC cables has to be inversed, i.e. the ground cable(s) to be connected to the V+ DC output terminal(s) and the positive cable(s) to be connected to the V- DC output terminal(s).
The grounding bolt is independent from the potential of the output
terminals and is connected to PE (Protective Earth) potential of the AC input connectors as well as to the GND potential of the data interface connectors.
For the connection to the M6 threaded studs of the output terminals,
double-hole lugs with 5/8" (15.875 mm) center distance and 90° cable taps are recommended, e.g. Burndy YA2CL-2TC14-90, capable of AWG 2 (i.e. 35 mm²) wires. As an alternative, a number of ring tongue terminals with an inner diameter of 6 mm and a maximum outer diameter of 14 mm can be used.
The number of cables and the diameters of the cables depend on the
current to be supplied and the length of the cables. Make sure, that an appropriate configuration with respect to number and to diameter of the cables is installed. For the sum of the cable cross section per polarity with an assumed maximum current of 120 A, a minimum of 35 mm² cross section is according to regulations!
After the application of the DC output wiring, the AC supply connections are to be established. The DEV 5071 can be equipped with one to four power supply modules. Depending on the number and the location of the installed power supply modules, the corresponding power cords are to be connected to (8, 7, 3, & 2).
Note: Due to the high power consumption of each power supply module, it is
highly recommended to use separately fused phases of the available electrical outlets.
Naturally, at least one power supply module has to be installed. The
installation location can be selected freely, though it is recommended to install the power supply modules in the order of slots (as shown in the front view figure of chapter 3.3). Make sure, that the corresponding AC power plugs are supplied with AC.
Copyright DEV Systemtechnik GmbH 2007-2017 13
Page 14
Customer Documentation DEV 5071
1 2
If the corresponding AC power plug is not connected (indicated via the
corresponding AC LED, please refer to chapter 3.2.1), a power supply module delivers no DC, but is capable to provide status information to the CPU module. Note, that this status information may be erroneous if less than one AC supply line per two power supply modules is active.
It is highly recommended to reboot the DEV 5071 after power-up
(chapter 4.2.4)!

4.2.3 Installation and Exchange of Power Supply Modules

The product is usually delivered with the number of ordered power supply modules that are already installed. Therefore, you may proceed in reading the next chapter. In case that a power supply module has to be exchanged, or that a DEV 5071 is to be upgraded with an additional power supply module, the following instructions are to be noticed:
Though the power supply modules are hot pluggable, it is recommended to power down the device for exchange operations for safety reasons and to avoid short circuits!
Removal of a power supply module: First, with the thumb of the left hand push the metal lever (1) of the power
supply module to the left. This releases the plastic handle (2) of the plastic cover, which now can be actuated with the index finger of the left hand. Pull gently and completely the plastic handle of the module; this releases the power supply module from the chassis. Then, pull out the power supply module completely using the plastic handle.
Installation of a power supply module: In the first step, release the plastic handle (2) of the exchange/new power
supply module by pushing the metal lever (1) to the left and then by pulling the plastic handle. Insert the power supply module into an unpopulated slot of the chassis and gently push in the module until experiencing a little resistance. Then, push gently the plastic handle of the module until the metal lever (1) locks the power supply module within the chassis. If applicable, power up the device and reboot (please refer to chapter 4.2.4)
14 Copyright DEV Systemtechnik GmbH 2007-2017
Page 15
Customer Documentation DEV 5071
the DEV 5071, then Finally, check the settings of the installed power supply module via the Web Interface. If there were changes on the default configuration of the power supply modules (chapter 4.3.1) and if a defective module is replaced by an exchange power supply module, the settings are transferred to the new module. Nevertheless, it is recommended to check the settings of the new power supply module directly after the exchange, to ensure, that the device behaves in the same fashion as before the substitution.

4.2.4 Reboot of the Device and Restore of the Factory Default Settings

During power-up or during a reboot, the CPU module performs a health check and scans the assemblies of the device e.g. to detect, whether a module is installed in a slot or not. If there is a module installed, the settings for this slot are transferred to the module. Usually it is not possible to apply AC to all installed power supply modules at power-up in parallel, or there are different latencies within the power supply modules. Additionally, it is possible that there were applied changes on the setup of the device, e.g. adding or swapping power supply modules. Therefore, it is highly recommended to reboot the device after power-up or after applying changes to the setup of the DEV 5071!
The reboot of the device can be performed in three different ways:
1. Reboot via the "Reset" push button of the CPU module; please refer to
chapter 3.2.2.
2. Reboot via the serial interface when terminating the configuration
program (chapter 4.4.2.2.1).
3. Reboot the device via Web Interface (chapter 5.4.5.6). Note:
It takes about 60 seconds after a reboot, that the device is completely
accessible again via serial interface, via Web Interface, and via SNMP.
If power supplies were turned off via software control before the reboot,
they will be turned on after the reboot!
If –for any reason neither a power cycle nor a reboot of the device
restores all functionality, a reset to factory defaults is to be considered. The factory default settings can be restored via Web Interface (chapter
5.4.5.5).
Copyright DEV Systemtechnik GmbH 2007-2017 15
Page 16
Customer Documentation DEV 5071
AC input voltage range (module output power)
DC output
voltage
per module or with 1 module
with
2 modules
with
3 modules
with
4 modules
Minimum current limits:
(independent)
(independent)
10.0 A
20.0 A
30.0 A
40.0 A
Maximum current limits:
200…240 V AC (2000 W)
44.2 V
45.2 A
90.5 A
135.7 A
181.0 A
200…240 V AC (2000 W)
58.0 V
34.5 A
69.0 A
103.4 A
137.9 A
100…120 V AC (1200 W)
44.2 V
27.1 A
54.3 A
81.4 A
108.6 A
100…120 V AC (1200 W)
58.0 V
20.7 A
41.4 A
62.1 A
82.8 A

4.3 DEVICE FACTORY SETTINGS

The product is delivered with the factory settings as described in the following. Please refer to chapter 5.4.5.5 to re-apply these settings.

4.3.1 Factory Settings for the Power Supply and Limits Information

There are available factory settings that apply to the (whole) DEV 5071 and factory settings that apply to the single power supply modules:
Output voltage: 48.0 V Output current limit (module): 41.0 A Output current limit (device): 20.0 A (per module)
The output voltage can be altered via Web Interface for the DEV 5071 (please refer to chapter 5.4.4.2) and via SNMP (chapter 5.5.4.2.5.6) for each installed power supply module. Note, that changing the output voltage of a single power supply module via SNMP affects implicitly the output voltage setting of the other installed power supply modules!
The output current limit for each power supply module can be changed via SNMP (chapter 5.5.4.2.5.8) and the output current limit of the DEV 5071 can be changed via Web Interface (chapter 5.4.4.2). The default setting for the output current limit of the device depends on the number of installed power supply modules. Note, that this limit is only used as a warning, if the total measured current exceeds the value, but does not physically affect the output current limits of the single power supply modules.
There are limits for each power supply module, which need to be considered: The output power depends on the AC input voltage. A module delivers up
to 1200 W if supplied with 100…120 V AC and is capable to deliver 2000 W if supplied with 200…240 V AC.
The output voltage of a power supply module (thus of the DEV 5071) can
be adjusted between 44.2 V and 58.0 V.
The output current limit of a power supply module can be adjusted
between 10.0 A and 45.2 A.
Note, that it is possible to alter output voltage and output current to values, which may exceed the capabilities of the power supply module and of the DEV 5071! Since the firmware does not always restrict the input set values, consider the conditions regarding AC input voltage, DC output voltage, and the number of installed power supplies! The following table may help if it is intended to alter the factory default values for the output current limit of a power supply module (via SNMP) and/or of the device (via Web Interface).
16 Copyright DEV Systemtechnik GmbH 2007-2017
Page 17
Customer Documentation DEV 5071
Note: Note, that after the exchange of a power supply module, the replacement
power supply module inherits the settings of the corresponding slot!

4.3.2 Factory Default Network Settings

The factory default network settings of the device are:
IP-Address: 192.168.0.11 Netmask: 255.255.255.0 Gateway: 192.168.0.99
For changing the network setup, please refer to chapters 4.4.2.2 & 5.4.5.3.

4.3.3 Factory Default SNMP Settings

The factory default SNMP settings of the device are:
Read Community: public Write Community: private Local/Remote changeable per SNMP:
Note, that if a Trap Destination IP Address is defined without the explicit assignment of a port, the standard SNMP trap port 162 is assigned implicitly.
For changing the SNMP setup, please refer to chapter 5.4.5.4. There are software factory defaults for some SNMP objects, please refer to
the corresponding chapters:
.application.controlMode chapter 5.5.4.2.1 .application.channelTable.channelEntry.channelOutVoltageSet
chapter 5.5.4.2.5.6
.application.channelTable.channelEntry.channelOutCurrentSet
chapter 5.5.4.2.5.8
.surveillance.trapEnableMask chapter 5.5.4.3.1 .surveillance.errorEnableMask chapter 5.5.4.3.2
Copyright DEV Systemtechnik GmbH 2007-2017 17
Page 18
Customer Documentation DEV 5071

4.4 COMMUNICATION INTERFACE CONFIGURATION

Two hardware interfaces are provided for the communication with the device: a serial interface and an Ethernet interface. The serial interface can be used for the basic network setup of the device. The Ethernet interface is used for the operation via Web Interface or for operation via SNMP.

4.4.1 Serial Interface

The Sub-D 9 pos female connector labeled "RS 232" for the standard serial interface is located at rear side of the chassis; for the pin assignment please refer to chapter 7.
The following parameters describe the serial interface configuration: Transmission rate: 38400
Data bits: 8 Parity check: none Start/Stop bit: 1 Handshake: none

4.4.2 Ethernet Interface

The RJ-45 connector labeled "Ethernet" for the standard 100Base-TX (IEEE 802.3, Clause 24) Ethernet interface is located at the rear side of the chassis; for the pin assignment please refer to chapter 7.
4.4.2.1 Ethernet Connection If the standalone device is to be connected to a PC only, the connection can
be established by a crossed Ethernet cable (or via a local hub/switch with straight Ethernet cables) and the network setup of the PC is to be altered, that it is in the same subnet as the device. So, if it is intended to use the factory default network settings, the IP address of the standalone PC should
be set to 192.168.0.xxx, with xxx ranging from 001…254, except 11 which is
the address of the device, e.g. set the IP address of the standalone PC to default gateway address 192.168.0.99. If the device is to be connected to the local network, make sure to change the network setup as required. Ask your system administrator for the details on network parameters which are to be used. The factory default network settings are subject of chapter 4.3.2.
There are two different methods to change the network setup of the device. First, the network setup can be changed via Web Interface (Setup Tab IP Configuration), please refer to chapter 5.4.5.3. The other method that can be performed is subject of the following chapter.
4.4.2.2 Network Setup via the Serial Interface To change a few elementary parameters of the network setup of the device
via the serial interface, establish a hardware connection between a PC serial port (e.g. COM1 or COM2) and the RS 232 interface of the device ("RS 232"
18 Copyright DEV Systemtechnik GmbH 2007-2017
Page 19
Customer Documentation DEV 5071
connector at the chassis) using a straight cable (please refer to chapter 7 for the pin assignment of the serial connector). On the PC, start a terminal connection application (e.g. MS Windows HyperTerminal).
Note: The interface settings of the terminal connection application have to
match the serial interface configuration settings (chapter 4.4.1); otherwise, it is not possible to enter the configuration program as described below.
The terminal application is to be configured, that the "Backspace" or "←"
key on the keyboard works properly in the application, and that it sends a
<CR> only (and not a <CR><LF>) when hitting the "Enter" or "" key on the
keyboard. When using MS Windows HyperTerminal, select the "Properties" entry from the "File" menu and click on the "Settings" tab. There, select "ANSI" from the Emulation drop down list and then click on the ASCII Setup… button to uncheck "Send line ends with line feeds" as shown in the following figure:
4.4.2.2.1 Start and Termination of the Configuration Program In this application, the serial interface is exclusively used for the
configuration program, i.e. if the terminal connection application is started (and connected) either the following text is displayed initially or after hitting the "Enter" or "" key on the keyboard:
(none) login:
With the following authentication the configuration program is started:
(none) login: config<CR> Password: devConfig<CR>
Note:
<CR> stands for hitting the "Enter" or "" key on the keyboard. All characters/commands to be entered are case sensitive.
Copyright DEV Systemtechnik GmbH 2007-2017 19
Page 20
Customer Documentation DEV 5071
After successful authentication, the configuration program of the device is launched. After start and after the finalization of most of the choices the program lists the choices, which can be performed with the program:
config ======
1 set IP address (192.168.0.225) 2 set netmask (255.255.0.0) 3 set gateway (192.168.0.99) q quit without saving x save configuration and exit
your choice >
Choices can be executed by typing the character in the first column of each line followed by a <CR>. The second column of each line provides a short description of the choice and the third column displays in parentheses the current setting of the corresponding choice. In the example above, the IP address and the netmask are different from the factory default network settings (please refer to chapter 4.3.2).
When using the "q" choice, the configuration program terminates and the login message is displayed again:
(none) login:
When using the "x" choice, the configuration program saves all changes made and reboots the device:
(...)
your choice > x<CR>
rebooting the device, please wait...
When rebooting, all processes are stopped and the reboot of the device is initialized. After a reboot, it takes a few moments before the serial interface is accessible again as described at the beginning of this chapter. In the following, the available choices are explained:
4.4.2.2.2 1 set IP address This choice is used to change the IP address of the device:
(...)
your choice > 1<CR> Current IP address is 192.168.0.225
Enter IP address ('NONE' to clear) >
To change the current IP address, type in a different valid address; to clear the address, type in "NONE<CR>"; and just entering <CR> maintains the current setting:
Enter IP address ('NONE' to clear) ><CR> unchanged
After that the choices list reappears.
20 Copyright DEV Systemtechnik GmbH 2007-2017
Page 21
Customer Documentation DEV 5071
4.4.2.2.3 2 set netmask This choice is used to change the netmask of the device:
(...)
your choice > 2<CR> Current netmask is 255.255.0.0
Enter netmask ('NONE' to clear) >
To change the current netmask, type in a different valid entry; to clear, it type in "NONE<CR>"; and just entering <CR> maintains the current setting:
Enter netmask ('NONE' to clear) ><CR> unchanged
After that the choices list reappears.
4.4.2.2.4 3 set gateway This choice is used to change the gateway address of the device:
(...)
your choice > 3<CR> Current gateway is 192.168.0.99
Enter gateway ('NONE' to clear) >
To change the current gateway address, type in a different valid address; to clear the address, type in "NONE<CR>"; and just entering <CR> maintains the current setting:
Enter gateway ('NONE' to clear) ><CR> unchanged
After that the choices list reappears.

4.5 MAINTENANCE OF THE PRODUCT

The product is maintenance-free. Cleaning of the surface of the chassis should be done carefully with a moistened lint-free cloth.
Copyright DEV Systemtechnik GmbH 2007-2017 21
Page 22
Customer Documentation DEV 5071

5 OPERATION OF THE PRODUCT

After going through the installation steps as described above, the device is ready to use. The DEV 5071 can be monitored locally; additionally there are the possibilities for the surveillance and for the control of the product via the Web Interface and/or via SNMP. Before the operation of the device via each of these possibilities is explained, the different device operation modes are described:

5.1 MODES OF OPERATION

Local Mode and Remote Mode define the manner how the device is controlled.
Note: Changing the operation mode can only be done via Web Interface
(please refer to chapter 5.4.2) and via SNMP (chapter 5.5.4.2.1), only.

5.1.1 Local Mode

In Local Mode the device executes commands (i.e. the change of settings), which are issued via the Web Interface. The communication to the SNMP remote interface is disabled for modifying the settings of the device, but open for surveillance and status queries.

5.1.2 Remote Mode

The Remote Mode is implemented for operation via SNMP. In Remote Mode, the status of the power supplies is still indicated via the LEDs at the device and via Web Interface, but the control functionality of the Web Interface is disabled.

5.2 INITIALIZATION OF THE DEVICE

The device performs a health check and a configuration check during power up or after a reboot e.g. via Web Interface. This takes about 60 seconds, there is no manual configuration necessary, all settings (including the operation mode of the device, except possible switched off power supply modules) after power-up or after a reboot are the same as before shut down.
However -as explained in chapter 4.2.4- it is highly recommended to reboot the device after power up!

5.3 OPERATION AT THE DEVICE

Beside the reset push button at the CPU module (please refer to chapter 3.2.2), there are no elements to be operated. The status of the power supply modules is indicated via LEDs, which were already presented in chapter 3.2.1.
22 Copyright DEV Systemtechnik GmbH 2007-2017
Page 23
Customer Documentation DEV 5071

5.4 OPERATION VIA WEB INTERFACE

The Web Interface is a user interface for operating the DEV 5071, i.e. the device is controlled via a computer and a Web Browser as the communication application. Several users (assumed the appropriate number of licenses) can access the device at a time. The first license is included in the delivery. It is possible to purchase additional license keys at any time, please contact DEV Systemtechnik.
Note: The screenshots shown in the following were made from the Web
Interface of a DEV 5071 equipped with three power supply modules. Other configurations deviate from the layout but not from the basic functionality of the Web Interface.

5.4.1 Start of the Web Interface

To start the Web Interface, open a web browser (recommended is Mozilla Firefox (version 3.5 or higher), but also Chrome, Opera, Safari, or Internet Explorer version 8 or 9 (recommended)) and type in the URL (IP address) of the device:
http://<IP-of-the-device>/
After a moment, the Start Screen of the Web Interface appears:
Copyright DEV Systemtechnik GmbH 2007-2017 23
Page 24
Customer Documentation DEV 5071
To log on the first time use the factory default account:
Username: ADMIN Password: ADMIN
After entering username and password, click on Login . Note:
Both, username and password are case sensitive! Note the header in the Start Screen:
The labels "SystemName" and "SystemLocation" are the SNMP variables 'System Name' and 'System Location'; both variables can be set within the SNMP setup (please refer to chapter 5.4.5.4).
If the Start Screen is not accessible, make sure that the computer
accessing the device is in the same subnet of the common network (chapter 4.4.2.1).
The Web Interface permits the definition of a number of users with
different permission (chapter 5.4.5.2) for accessing the Web Interface in parallel (in accordance to the number of installed licenses). An additional user, who tries to log in, receives a corresponding notification informing about the logged in user(s), e.g.:
DEV 5071
SystemName SystemLocation
It is recommended to add user(s) AND to change the password of the
factory default account. How this is to be done is subject of chapters
5.4.5.2 & 5.4.5.1.
The language of the screenshots shown here is English, as a second
language currently German is available, please refer to chapter 5.4.5.1.
24 Copyright DEV Systemtechnik GmbH 2007-2017
Page 25
Customer Documentation DEV 5071

5.4.2 The Main Window and Common Features of the Main Tabs

After successful authentication the main window of the Web Interface shows up with the Status Tab opened, which is the default view:
In the top of the window on the left side, the four tabs are located ("Status", "Control", "Setup", and "Info"). The active tab is highlighted; clicking on an inactive tab opens the corresponding tab instead.
In the top of the window on the right side, the currently logged in user (here: "ADMIN") and the permission of the user (here: "admin") are shown. Please refer to chapter 5.4.5.2 for more information on this subject.
As a common feature between the Status Tab and the Control Tab two buttons and two indicators are located at the bottom of the window in the middle indicating that the device is either in Remote Mode (as shown in the screenshot above), or in Local Mode (as shown in the screenshot of chapter
5.4.3). Changing the operation mode of the device via Web Interface is performed by clicking on the desired button, e.g. clicking in the situation above on the Local button, turns on the "Local" indicator, and turns off the "Remote" indicator. In the lower right corner of all main tabs, the Logout button is located. Clicking on this button returns the Web Interface to the Start Screen.
Note:
It is highly recommended to finish a Web Interface session by clicking on
the Logout button. This instantaneously releases the allocated license and enables other users to log in.
Copyright DEV Systemtechnik GmbH 2007-2017 25
Page 26
Customer Documentation DEV 5071
A timeout feature (60 seconds) is implemented within the Web Interface,
i.e. a session is automatically terminated (and the allocated license is released) if a user who is currently logged in closes the web browser.
It is possible to start a Web Interface session on another computer using
the same user account; naturally, this automatically terminates the session on the preceding computer.

5.4.3 Status Tab

The upper part of the Status Tab shows a simplified representation of the front side and of the rear side of the device. Thus, a quick overview is provided regarding the detected module configuration, and regarding the health status of the device. The round indicators are equivalent to the physical LEDs (green = ok, red = error, amber = service / excess tempera­ture, or gray = off; blinking LEDs on the power supply modules will be shown here as static, only) at the device, please refer to chapter 3.2.1 for details on the indicator information.
The internal status table in the middle of the Status Tab additionally shows for each power supply module the status of the AC supply, of the temperature, and of the fan status, plus the setup and the measurement results of the output voltage and the output current for each module. The background of some of these fields is green, if the values are detected as ok and it will be red, otherwise. The centered table below shows the setup and the measurement results of the output voltage and the output current of the DC output of the device.
26 Copyright DEV Systemtechnik GmbH 2007-2017
Page 27
Customer Documentation DEV 5071
Note:
The representation of the rear side of the device is mirrored in the Status
Tab (i.e. visible as when looking at the rear side of the DEV 5071), this means, that the AC connector of power supply module 4 is located on the left side and that the AC connector of power supply module 1 is located on the right side.
In addition, the voltages of DEV 5071 are shown as unsigned values, i.e.
not stating the polarity of the output voltage; please refer to chapter 4.2.2.
In the lower part of the window on the left side, the Active Events Window is located. This window shows appearing and pending errors with the corresponding error message and a date/time stamp. The "AC Line 3" error shown in the Active Events Window of the screenshot was triggered for demonstration purpose, just by pulling a primary power connector. To obtain more details on the errors detected by the device, please click on the Error Log button to open the Error Log Window:
5.4.3.1 Error Log Window The Error Log Window is to be opened with the Error Log button located in
the Status Tab below the Active Events Window.
The Error Log Window displays a table of the errors, which were detected by the device.
The different errors are listed in the table line-by-line, i.e. each error carries a Date/Time stamp (in the format: "DD.MM.YY hh:mm:ss", here "17.12.13 18:13:29") informing about the last occurrence of that error. The 2nd column is a
Copyright DEV Systemtechnik GmbH 2007-2017 27
Page 28
Customer Documentation DEV 5071
Counter reporting the number of occurrences of that error (here: "1"). The 3rd column denotes whether that error is Ack.nowledged ("X") or not (" ") (here: " ", i.e. <space>, meaning not acknowledged). The 4th column shows whether that error is Pend.ing ("X") or not (" ") (here: "X", i.e. pending). The 5th column informs about the error code No. in hexadecimal notation (here: "1103"); and the last column reports the corresponding Error Description (here: "AC Line 3"), please refer to chapter 6.1.1.
In addition to the Exit button in the lower right corner, which causes the return to the previous window, the Error Log Window comprises two buttons: the Acknowledge Entry button and the Delete Entry button:
With the Acknowledge Entry button one or more errors can be acknowledged. The acknowledgement of an error is intended to provide means to mask out a pending error of the Active Events Window in the Status Tab (chapter 5.4.3). If an acknowledged error occurs again, the counter in the table is increased and the acknowledgement is reset (i.e. the "X" disappears). An error can be acknowledged by highlighting (i.e. clicking on) the corresponding line and by operating the Acknowledge Entry button then.
The Delete Entry button is intended to remove acknowledged and not pending errors from the list. If a deleted error occurs again, there is a line added at the end of the table. An error entry can be deleted by highlighting the corresponding line and then by clicking on the Delete Entry button then.
Note:
It is possible to acknowledge and to delete more than one entry at a time
by highlighting more errors in the Error Log Window using the <Ctrl> or the
<Shift> key of the keyboard in combination with mouse click(s).
Users with "read" permission only have no rights to acknowledge or to
delete error entries (chapter 5.4.5.2)!
If an error is still pending or if an error is not acknowledged, it cannot be
deleted!
Again, error codes and error messages are subject of chapter 6.1.
28 Copyright DEV Systemtechnik GmbH 2007-2017
Page 29
Customer Documentation DEV 5071

5.4.4 Control Tab

The Control Tab provides means for switching (on or off) the installed power supply modules, and to change the settings of the output voltage and the current limit of the device. After opening the Control Tab, radio buttons are provided on the left side for the installed power supply modules (shown with the corresponding serial number) and for the device output status and settings. Clicking on one of the radio buttons initiates the available panel for the corresponding item to appear on the right side, see below. At the bottom of the Control Tab, five buttons are located. The functionality of the Remote button, the Local button, and the Logout button were already described in chapter 5.4.2. The Cancel button and the Save button are required for modifications in the available panels, see below. They are functional only if one of the radio buttons in the list on the left side of the Control Tab is activated. The Cancel button discards any intended but not yet saved editing and brings back the saved settings. The Save button saves the current editing, the finalization of it is indicated via a confirmation pop-up window.
Note:
The change of settings via the Web Interface can be performed only, if
the device is in Local Mode! In Remote Mode, the Save button is grayed out.
Copyright DEV Systemtechnik GmbH 2007-2017 29
Page 30
Customer Documentation DEV 5071
5.4.4.1 Power Supply Module
If a power supply is selected via a radio button on the left side of the Control Tab, the corresponding power supply module panel appears on the right side. It consists of two sections:
1) In the upper "Status" section, first the status indicators "AC OK",
"DC OK", "Service", and "Fault" are displayed. Then, the measured temperature of the power supply module is shown (in °C).
2) Within the "Setup" section the corresponding power supply module can
be turned on or off by selecting the appropriate radio button ("On" or "Off"). The change becomes effective after the Save button was operated (in Local Mode!). Note that after a reboot, a power supply module, which was turned off in that way, will be turned on again!
30 Copyright DEV Systemtechnik GmbH 2007-2017
Page 31
Customer Documentation DEV 5071
5.4.4.2 Power Supply Output
If "Power Supply Output" is selected via the radio button on the left side of the Control Tab, the power supply output panel appears on the right side. It consists of two sections:
1) In the "Status" section measured output voltage and the measured
output current of the device are shown.
2) In the "Setup" section, the output voltage of the device can be modified
and the maximum output current can be adjusted. The value for the maximum output current serves as a threshold for alarming purposes, only. I.e. the CPU module sums up the measured currents of the installed power supply modules and compares it against this value. If the sum exceeds the value, an alarm is triggered. Note that values above 100 A can be entered as integer value (e.g. "163" instead of "162.9"), only. Please refer to chapter 4.3.1 providing information on the meaning of the values and on the limits for adjusting the two values! Changes on the values become effective after the Save button was operated (in Local Mode!).
Copyright DEV Systemtechnik GmbH 2007-2017 31
Page 32
Customer Documentation DEV 5071

5.4.5 Setup Tab

The Setup Tab contains a number of buttons in order to branch out in the different setup functionalities described in the following.
32 Copyright DEV Systemtechnik GmbH 2007-2017
Page 33
Customer Documentation DEV 5071
5.4.5.1 Password and Language
The input fields of the Password and Language functionality enable the user who is currently logged in to change the password and to alter the personal language setting.
To change the password, enter the old password, the new password, and the confirmation of the new password and click on the button Change Password . A window pops up to confirm the action.
To change the language, choose the language from the drop down list "Language" and click on the button Change Language . A window pops up to confirm the action.
A click on the button Exit closes the functionality and initiates the return to the Setup Tab.
Note:
English and German are the languages supported by the current
firmware version.
5.4.5.2 User Setup The currently logged in user has to have "admin" permission to access the
User Setup functionality, where users can be added or deleted and the permission can be modified.
In the following screenshot, a user named TEST with "admin" permission is in the process to be restricted to "read/write" permission. After a click on the button Modify Permission (and after the confirmation via pop-up window),
Copyright DEV Systemtechnik GmbH 2007-2017 33
Page 34
Customer Documentation DEV 5071
this user will then have all rights but only access to the Password and Language functionality within the Setup Tab. A user with "read" permission additionally is not able to apply any changes within the other tabs of the Web Interface.
To add a new user, enter a name in the text field "User Name", select the appropriate permission category and click on the button Add New User . A confirmation window pops up and the user is added to the "User List" drop down list. To delete a user, select a user from the drop down list "User List" that it appears in the field "User Name". Click on the button Delete User . A confirmation window pops up and the user is deleted from the "User List".
A click on the button Exit closes the functionality and initiates the return to the Setup Tab.
Note:
As already mentioned, user names and passwords are case sensitive! When adding a new user, this user logs on the first time without any
password. It is recommended that the originator (or the new user) logs in as the new user (without a password) to set up a password by using the Password and Language functionality (please refer to chapter 5.4.5.1).
It is not possible to delete the ADMIN user but it is recommended to
change the default password!
34 Copyright DEV Systemtechnik GmbH 2007-2017
Page 35
Customer Documentation DEV 5071
5.4.5.3 IP Configuration
The currently logged in user has to have "admin" permission to access the IP Configuration functionality, where the network setup of the device can be modified.
If the device is intended to obtain the IP address, the netmask and the gateway from a DHCP server within the network, check the DHCP check box. Then, the values entered in the fields "Static IP Address", "Netmask", and "Gateway" will not be considered after a reboot of the device. If DHCP is not checked, at least the fields "Static IP Address" and "Netmask" have to contain valid entries.
"Gateway", "Nameserver 1", and "Nameserver 2" (if required) are to be specified by their IP addresses, the "Nameserver" entries are used for the resolution of the "Timeserver" fields, only.
The "Time Server" fields are used to specify one or two timeservers either via full-qualified domain name or via IP address.
To specify the time zone, an appropriate string is to be entered in the field "Time Zone". The list of valid entries is provided in chapter 13.
The three buttons at the bottom of the window are used for the handling of the data entered above. The Cancel button is used for discarding changes possibly applied. Save and Reboot (in Local Mode, only!) downloads the data to the CPU module to be stored there permanently and reboots the device. A click on the button Exit closes the functionality and initiates the return to the Setup Tab.
Copyright DEV Systemtechnik GmbH 2007-2017 35
Page 36
Customer Documentation DEV 5071
5.4.5.4 SNMP Configuration
The currently logged in user has to have "admin" permission to access the SNMP Configuration functionality, where the SNMP setup of the device can be modified.
Within the SNMP setup, the settings for the "System Name" and the "System Location" can be modified. An "Administrator" can be defined and the passwords for the "Read Community" and for the "Write Community" can be set.
The check box below these entries is used to enable the switching between Local Mode and Remote Mode via SNMP, please refer to chapter 5.5.4.2.1.
Additionally, up to four Trap Receiver IP Addresses can be defined via the IP address and the port in the format <ip-address>{:<port>}, e.g.
192.168.0.29:121. If <port> is not specified, the standard SNMP trap port 162 is assumed.
Finally, a click on the download icon initiates the download of the MIB of the device.
The three buttons at the bottom of the window are used for the handling of the data entered above. The Cancel button is used for discarding changes possibly applied. Save (in Local Mode, only!) downloads the data to the CPU module to be stored there permanently and reboots the device. A click on the button Exit closes the functionality and initiates the return to the Setup Tab.
36 Copyright DEV Systemtechnik GmbH 2007-2017
Page 37
Customer Documentation DEV 5071
Note:
The strings "System Name" and "System Location" are part of standard
SNMP functionality and are limited to 40 characters, each. The number of characters visible in the text fields is limited by the field size.
As mentioned, the strings "System Name" and "System Location" are
also displayed in the Start Screen of the Web Interface (chapter 5.4.1).
5.4.5.5 Restore Factory Defaults With a click on the button Restore Factory Defaults in the Setup Tab the
settings of the device are reset to the factory default values as described in chapter 4.3 including all changes on the Web Interface. If the button was operated (by a user with "admin" permission), a window pops up to confirm the action:
If the OK button was clicked, another window pops up as a reminder to reboot the device (the message "Prevent this page from creating additional dialogs" is browser specific and can be ignored or it can be (un-)checked):
For rebooting the device, please refer to the next chapter or to chapter 4.2.4.
Copyright DEV Systemtechnik GmbH 2007-2017 37
Page 38
Customer Documentation DEV 5071
5.4.5.6 Software Service
The currently logged in user has to have "admin" permission to access the Software Service functionality, where means are provided to update the firmware of the device and/or to reboot the device via Web Interface.
Precondition for updating the device firmware is a service package provided by DEV Systemtechnik! The input field permits the insertion of a filename including the path where the file resides. Alternatively, the Browse… , button can be used to locate the file. When the file is selected, click on the Upload button to activate the file transfer to the device. After the upload is finished, the installation is started, please observe the text output that appears in the text window.
If –for any reason– a reboot of the device is required, the Reboot Device button can be used to reboot the device even without updating the firmware. After operating Reboot Device a reboot is initiated, indicated via a pop up window:
Finally, a click on the button Exit closes the functionality and initiates the return to the Setup Tab.
38 Copyright DEV Systemtechnik GmbH 2007-2017
Page 39
Customer Documentation DEV 5071

5.4.6 Info Tab

The Info Tab provides information regarding configuration and setup of the device. This information is mainly intended for support purposes, part of this information may be requested when contacting DEV Systemtechnik.
In the left column, first the "Hardware Configuration" is described:
Device, here: DEV 5071 MAC Address, here: 00-05-51-04-90-0C Power supply module data (here three modules are installed):
- Type of power supply module, here: Tyco P2000AC54TEC109
- Serial number, here: 3KZ29005288, 3KZ29005344, & 3KZ29005420.
In the right column on the top, the "Software Configuration" is described:
Device Firmware version, here: 32-0060 H.01 Linux Kernel version, here: 2.6.25-M SNMP Software version, here: 3.1.13 the current IP Address of the device, here: 192.168.0.11 Web Interface Licenses, here: 1 SNMP Licenses, here: 1
A download icon is located on the bottom of the right column for downloading the electronic version of the user manual.
Finally, in the right column in the middle the manufacturer's name, country and hyperlink are listed.
Copyright DEV Systemtechnik GmbH 2007-2017 39
Page 40
Customer Documentation DEV 5071

5.5 CONTROL VIA REMOTE INTERFACE: SNMP

5.5.1 SNMP Overview

The "Simple Network Management Protocol" (SNMP) essentially is a request-reply protocol running over UDP (usually ports 161 and 162). SNMP is an asymmetric protocol, operating between two types of management units: managers and agents.
A manager is called "Network Management Station" (NMS). This is usually a computer, on which one or more management systems are running.
On small NMS, command line tools can be used. On larger NMS, normally third-party software, also called a "network management suite" collects the data and provides a graphical user interface.
An agent or SNMP-agent is software, which runs on a "Network Element" (NE). NEs in a SNMP environment are called "nodes". An agent collects and stores information from the system, translates the information in SNMP­compatible form, and makes this information available to the manager. The agents manage the "objects" of the node. Each of the objects has its own individual management "Object ID" (OID). In the system, the objects are the variables, which can be simple values or tables.
The information about the objects is stored in the "Management Information Base" (MIB).
Note: The iReasoning MIB Browser Personal Edition v6.11 (including Trap
Receiver) by iReasoning Inc. is recommended to test the communication with the device via SNMP.

5.5.2 DEV Private Enterprise Number, Device Index Number

The Private Enterprise Number of DEV Systemtechnik GmbH is 21035. The actual MIB content for the DEV 5071 starts with the object section
.dev5071, which has the Device Index Number 34. This concatenates to the (MIB-) string (i.e. the numerical OID: .1.3.6.1.4.1.21035.34):
iso.org.dod.internet.private.enterprises.dev-systemtechnik.dev-5071 1 . 3 . 6 . 1 . 4 . 1 . 21035 . 34
40 Copyright DEV Systemtechnik GmbH 2007-2017
Page 41
Customer Documentation DEV 5071

5.5.3 The DEV 5071 MIB Tree

The MIB is stored on the controller of the device and can be downloaded via the SNMP setup of the Web Interface (please refer to chapter 5.4.5.4) or directly from the device with a web browser via the link:
http://<IP-of-the-device>/dev-5071.mib
As shown above, the MIB is divided in four branches: .instrument (chapter
5.5.4.1), .application (chapter 5.5.4.2), .surveillance (chapter 5.5.4.3), and .SNMPv1 TRAPs (chapter 5.5.4.4). In the corresponding sub-chapter, the content of each branch is shown expanded and each object within a branch is described.

5.5.4 MIB Objects

In the following, the objects of the MIB tree are described. The complete object name of an MIB object results out of the concatenation of the MIB-String (please refer to chapter 5.5.2):
iso.org.dod.internet.private.enterprises.dev-systemtechnik.dev-5071
and of the corresponding MIB object. E.g., the object .instrument.controllerMac has the full textual OID ("" and ""
are symbolizing that the corresponding two lines are actually not separated):
iso.org.dod.internet.private.enterprise.dev-systemtechnik.dev-5071⌡ ⌠.instrument.controllerMac
Note:
Some of the objects are set to a factory default value (chapter 4.3.3). Some of the objects can be modified in Remote Mode only:
- .application.(…).channelOn (chapter 5.5.4.2.5.2),
- .application.(…).channelOutVoltageSet (chapter 5.5.4.2.5.6), and
- .application. (…).channelOutCurrentSet (chapter 5.5.4.2.5.8) And some objects can be modified in all modes of operation:
- .application.controlMode (chapter 5.5.4.2.1),
- .surveillance.trapEnableMask (chapter 5.5.4.3.1), and
- .surveillance.errorEnableMask (chapter 5.5.4.3.2)
Copyright DEV Systemtechnik GmbH 2007-2017 41
Page 42
Customer Documentation DEV 5071
5.5.4.1 .instrument
5.5.4.1.1 .instrument.controllerMac OID: .1.3.6.1.4.1.21035.34.1.1.0
Syntax: OCTET STRING (SIZE(18)) Access: read-only Description: The individual MAC address of the controller of the device
in hexadecimal characters, separated by dashes ("-").
Example: "00-05-51-04-90-0C"
5.5.4.1.2 .instrument.firmwareRevision OID: .1.3.6.1.4.1.21035.34.1.2.0
Syntax: OCTET STRING (SIZE(32)) Access: read-only Description: The firmware revision of the device Example: "H.01"
5.5.4.1.3 .instrument.instrumentType OID: .1.3.6.1.4.1.21035.34.1.3.0
Syntax: INTEGER Access: read-only Description: The type of device
For this device, always "2" is returned
42 Copyright DEV Systemtechnik GmbH 2007-2017
Page 43
Customer Documentation DEV 5071
5.5.4.2 .application
5.5.4.2.1 .application.controlMode OID: .1.3.6.1.4.1.21035.34.2.1.0
Syntax: INTEGER {local (1), remote (2)} Access: read-write OR read-only Description: The operation mode of the device (please refer to
chapter 5.1), possible values "1" Local Mode, i.e. local operation at the device or via Web Interface
"2" Remote Mode, i.e. remote operation via SNMP Note: Via the SNMP setup of the Web Interface (chapter 5.4.5.4), this object
can be set to read-write (default) or to read-only.
By default, this object is set to "2" (Remote Mode)
Copyright DEV Systemtechnik GmbH 2007-2017 43
Page 44
Customer Documentation DEV 5071
5.5.4.2.2 .application.outputVoltage OID: .1.3.6.1.4.1.21035.34.2.2.0
Syntax: INTEGER (0..60000) Access: read-only Description: The effective output voltage, i.e. the average calculated from
the measured voltages from all installed power supply modules in [mV].
Example: "48675", i.e. 48.675 V
5.5.4.2.3 .application.outputCurrent OID: .1.3.6.1.4.1.21035.34.2.3.0
Syntax: INTEGER (0..100000) Access: read-only Description: The calculated cumulative output current in [mA]
5.5.4.2.4 .application.numberOfChannels OID: .1.3.6.1.4.1.21035.34.2.4.0
Syntax: INTEGER (0..8) Access: read-only Description: The number of installed power supply modules.
Note: This value is used to determine the maximum index of the following table:
5.5.4.2.5 .application.channelTable The table describes the special features and settings of each of the power
supply modules.
5.5.4.2.5.1 .application.channelTable.channelEntry.channelIndex OID: .1.3.6.1.4.1.21035.34.2.5.1.1.x
Syntax: INTEGER (0..8) Access: read-only Description: A unique value for each table entry Its value ranges between
"1" and the number of entries (defined by the object .numberOfChannels, please refer chapter 5.5.4.2.4).
5.5.4.2.5.2 .application.channelTable.channelEntry.channelOn OID: .1.3.6.1.4.1.21035.34.2.5.1.2.x
Syntax: INTEGER {off (1), on (2), unplugged (3)} Access: read-write Description: The power supply operation state (on/off) can be read or set,
possible values: "1" the power supply module (is) off, "2" the power supply module (is) on, "3" the power supply module is unplugged.
44 Copyright DEV Systemtechnik GmbH 2007-2017
Page 45
Customer Documentation DEV 5071
5.5.4.2.5.3 .application.channelTable.channelEntry.channelACInputStatus OID: .1.3.6.1.4.1.21035.34.2.5.1.3.x
Syntax: INTEGER {ok (1), warning (2), error (3)} Access: read-only Description: The status of the corresponding AC line, possible values:
"1" ok, i.e. the AC line status is detected as being ok; "2" warning, i.e. the AC input is less than 102 V AC, i.e. causing limited output performance; "3" error, i.e. the AC line status is detected as being not ok.
5.5.4.2.5.4 .application.channelTable.channelEntry.channelTempWarning OID: .1.3.6.1.4.1.21035.34.2.5.1.4.x
Syntax: INTEGER {ok (1), warning (2), error (3)} Access: read-only Description: The temperature status of the module, possible values:
"1" ok, i.e. the temperature is detected as being ok; "2" warning, i.e. the temperature is high causing a warning; "3" error, i.e. the temperature exceeds 85 °C (185 °F).
5.5.4.2.5.5 .application.channelTable.channelEntry.channelFanStatus OID: .1.3.6.1.4.1.21035.34.2.5.1.5.x
Syntax: INTEGER {ok (1), error (3)} Access: read-only Description: The fan speed status of the module, possible values:
"1" ok, i.e. the fan speed is detected as being ok; "3" error, i.e. the fan speed is detected as being not ok.
5.5.4.2.5.6 .application.channelTable.channelEntry.channelOutVoltageSet OID: .1.3.6.1.4.1.21035.34.2.5.1.6.x
Syntax: INTEGER (0..60000) Access: read-write Description: The output voltage set point of the module in [mV].
Note: The output voltage of each power supply module can be set individually.
However, alterations on the value of a module will affect the setting of this value for all installed modules; i.e. because the modules are in parallel, it is pointless to adjust the modules to different values.
Note the default setting and the limits for adjusting this value; please
refer to chapter 4.3.1.
5.5.4.2.5.7 .application.channelTable.channelEntry.channelOutVoltage OID: .1.3.6.1.4.1.21035.34.2.5.1.7.x
Syntax: INTEGER (0..60000) Access: read-only Description: The measured output voltage of the module in [mV]
Copyright DEV Systemtechnik GmbH 2007-2017 45
Page 46
Customer Documentation DEV 5071
5.5.4.2.5.8 .application.channelTable.channelEntry.channelOutCurrentSet OID: .1.3.6.1.4.1.21035.34.2.5.1.8.x
Syntax: INTEGER (0..80000) Access: read-write Description: The output current set point of the module in [mA].
Note: The output current limit of each power supply module can be set
individually. However, it is recommended to keep the output current set point for all installed modules at the same value.
Note the default setting and the limits for adjusting this value; please
refer to chapter 4.3.1.
5.5.4.2.5.9 .application.channelTable.channelEntry.channelOutCurrent OID: .1.3.6.1.4.1.21035.34.2.5.1.9.x
Syntax: INTEGER (0..60000) Access: read-only Description: The measured output current of the module in [mA]
46 Copyright DEV Systemtechnik GmbH 2007-2017
Page 47
Customer Documentation DEV 5071
Hex:
0x80 (MSB)
0x40
0x20
0x10
0x08
0x04
0x02
0x01 (LSB)
Bit:
0 1 2 3 4 5 6
7
Trap:
unused4
unused3
unused2
unused1
trap modechange
trap error
trap errortext
trap coldstart
5.5.4.3 .surveillance
5.5.4.3.1 .surveillance.trapEnableMask OID: .1.3.6.1.4.1.21035.34.3.1.0
Syntax: BITS {unused4 (0), unused3 (1), unused2 (2), unused1 (3),
modechange (4), error (5), errortext (6), coldstart (7)} Access: read-write Description: The trap mask:
A trap is enabled if the corresponding bit is set. Note: The .trapEnableMask for the device is defined as follows:
I.e. only the lower nibble (bits 4…7) is supported, refer to chapter 5.5.4.4.
Note the differences for the Set-method of the .trapEnableMask
(BITS has the reverse order vs. hex addressing via OCTET STRING (e.g. writing of "0x0F" to enable all supported traps))!
By default, all traps are disabled, i.e. all bits are zero.
Copyright DEV Systemtechnik GmbH 2007-2017 47
Page 48
Customer Documentation DEV 5071
Bit:
15
14
13
12
11
10 9 8 7 6 5 4 3 2 1 0
Error Class:
future use
future use
future use
future use
Antenna Controller
Communication
Bias
Optical Card
Amplifier Card
Matrix Card
Output Card
Input Card
Switch Card
Fan
Power Supply
Internal Error
Class No. / Bit
Class
Chapter
0
Internal Error
6.1.3
1
Power Supply
6.1.1
2
Fan
6.1.2
3
Switch Card
(no reference)
4
Input Card
(no reference)
5
Output Card
(no reference)
6
Matrix Card
(no reference)
7
Amplifier Card
(no reference)
8
Optical Card
(no reference)
9
Bias
(no reference)
A (10)
Communication
(no reference)
B (11)
Antenna Controller
(no reference)
C (12)
future use
(no reference)
D (13)
future use
(no reference)
E (14)
future use
(no reference)
F (15)
future use
(no reference)
5.5.4.3.2 .surveillance.errorEnableMask OID: .1.3.6.1.4.1.21035.34.3.2.0
Syntax: INTEGER (0..65535) Access: read-write Description: The error enable mask:
All bits 1: all errors are enabled; errors are grouped into classes; each error class can be masked out with its
corresponding bit set to 0. Note: The .errorEnableMask for the device is defined as follows:
References:
If an error class is masked out, an appearing or disappearing error of this
class is not generating a trap and will not appear/disappear in the Active Events Window of the Web Interface. The error and its status (pending or not) is still stated in the .surveillance.errorTable and in the Error Log Window of the Web Interface, where it can be acknowledged and deleted (if it is not pending anymore).
By default, all errors are enabled, i.e. the .errorEnableMask is "65535".
48 Copyright DEV Systemtechnik GmbH 2007-2017
Page 49
Customer Documentation DEV 5071
5.5.4.3.3 .surveillance.numberOfErrors OID: .1.3.6.1.4.1.21035.34.3.3.0
Syntax: INTEGER (0..255) Access: read-only Description: The number of errors (in the following table)
Note: This value is used to determine the maximum index of the following table:
5.5.4.3.4 .surveillance.errorTable The .errorTable of the MIB can contain entries, which are classified by an
error number object. An error count object for the entry indicates the number of occurrences of the specific error and furthermore there are three objects for the entry which show when the last error of this kind did occur, whether the error is still pending and whether the error was acknowledged or not. If the object .surveillance.numberOfErrors (please refer to chapter 5.5.4.3.3) is "0", the .surveillance.errorTable is not available.
5.5.4.3.4.1 .surveillance.errorTable.errorEntry.errorIndex OID: .1.3.6.1.4.1.21035.34.3.4.1.1.x
Syntax: INTEGER (1..64) Access: read-only Description: A unique value for each table entry Its value ranges between
"1" and the number of entries (defined by .numberOfErrors, please refer to chapter 5.5.4.3.3).
5.5.4.3.4.2 .surveillance.errorTable.errorEntry.errorNr OID: .1.3.6.1.4.1.21035.34.3.4.1.2.x
Syntax: INTEGER Access: read-only Description: The error code (error identification number) Example: "4353" (for a "AC Line 1" error, please refer to chapter 6.1)
5.5.4.3.4.3 .surveillance.errorTable.errorEntry.errorCount OID: .1.3.6.1.4.1.21035.34.3.4.1.3.x
Syntax: INTEGER Access: read-only Description: The number of occurrences of this error
5.5.4.3.4.4 .surveillance.errorTable.errorEntry.errorDateTime OID: .1.3.6.1.4.1.21035.34.3.4.1.4.x
Syntax: INTEGER Access: read-only Description: The last occurrence of the error
(Unix time stamp, seconds since 01-Jan-1970 00:00:00 UTC)
Example: "1387477000" 19-Dec-2013 18:16:40 CET
Copyright DEV Systemtechnik GmbH 2007-2017 49
Page 50
Customer Documentation DEV 5071
5.5.4.3.4.5 .surveillance.errorTable.errorEntry.errorPending OID: .1.3.6.1.4.1.21035.34.3.4.1.5.x
Syntax: INTEGER {pending (1), gone (2)} Access: read-only Description: The last occurrence of the error is
"1" still pending, or "2" not pending anymore, i.e. gone
5.5.4.3.4.6 .surveillance.errorTable.errorEntry.errorAcknowledge OID: .1.3.6.1.4.1.21035.34.3.4.1.6.x
Syntax: INTEGER {not-acknowledged (1), acknowledged (2)} Access: read-only Description: The last occurrence of the error is
"1" not acknowledged, or "2" acknowledged
50 Copyright DEV Systemtechnik GmbH 2007-2017
Page 51
Customer Documentation DEV 5071
5.5.4.4 .SNMPv1 TRAPs
The current firmware version supports the SNMP standard trap 'Cold Start Trap', only. This MIB additionally supports 3 specific traps:
Note: As factory default, all traps are disabled. To enable specific traps, set the
corresponding bits in the .trapEnableMask (chapter 5.5.4.3.1).
Traps for specific error classes can be masked out by clearing the
corresponding bits in the .errorEnableMask (chapter 5.5.4.3.2).
5.5.4.4.1 trapAlarmText This trap (specific 3) is triggered if the device detects a new error. It delivers
the corresponding error description string (please refer to chapter 6.1). To enable the trap, bit 6 (enum: errortext) in the .trapEnableMask (chapter 5.5.4.3.1) is to be set.
5.5.4.4.2 trapAlarm This trap (specific 4) is triggered if the device detects a new error or if a
pending error disappears. The trap delivers the objects .errorNr (please refer to chapter 5.5.4.3.4.2) & .errorPending (chapter 5.5.4.3.4.5) for the corresponding entry in the .errorTable. To enable the trap, bit 5 (enum: error) in the .trapEnableMask (chapter 5.5.4.3.1) is to be set.
5.5.4.4.3 trapModeChange This trap (specific 5) is triggered if the device detects that an operation mode
change was performed. The trap delivers the object .application.controlMode (please refer to chapter 5.5.4.2.1). To enable the trap, bit 4 (enum: modechange) in the .trapEnableMask (chapter 5.5.4.3.1) is to be set.
Copyright DEV Systemtechnik GmbH 2007-2017 51
Page 52
Customer Documentation DEV 5071
Error
Code
Description
Decimal
Hexadecimal
04353…04356
0x1101…0x1104
AC Line [i] Error (i = {1…4})
04865…04868
0x1301…0x1304
Power Supply [i] Error (i = {1…4})
05121…05124
0x1401…0x1404
Temperature [i] Error (i = {1…4})
05889…05892
0x1701…0x1704
Error Output [i] Voltage (i = {1…4})
06913…06916
0x1B01…0x1B04
Current [i] Limit Exceeded (i = {1…4})
07169…07172
0x1C01…0x1C04
Commu Error PowerModule [i] (i = {1…4})
Error
Code
Description
Decimal
Hexadecimal
08449…08452
0x2101…0x2104
Fan [i] Error (i = {1…4})
Error
Code
Description
Decimal
Hexadecimal
00001...04095
0x0001... 0x0FFF
(various error messages, internal errors)

6 ERROR INDICATION

In this context, an alarm refers to the indication of an error. The indication of an error is realized via hardware, i.e. via red LEDs at the power supply modules; and additionally via software, i.e. via Web Interface, via an SNMP trap, or by polling the corresponding SNMP object(s). The hardware indication via LEDs on the device is subject of chapter 3.2.1. The indication via Web Interface is described in chapter 5.4.3; the indication via SNMP is explained in chapters 5.5.4.3.4 & 5.5.4.4. The software error indication (i.e. the error codes) is described in the following.

6.1 SOFTWARE ERROR INDICATION

The device is capable to detect several types of errors, which are reported to the Web Interface and to the M&C system. The M&C system has to poll the device for this events or it is informed via an alarm trap, assuming that the specific SNMP trap is enabled.

6.1.1 Power Supply Errors

1…4 power supply modules are installed, which are monitored. In case that an AC line error, a power supply error, a temperature error, an output voltage error, a current limit exceeded error, or that a communication error is detected, the corresponding alarm is generated.

6.1.2 Fan Errors

Each power supply module of the DEV 5071 has fans installed, which may fail.

6.1.3 Other Errors

For the sake of completeness, the other error codes, which might be reported by the device, are listed here. When experiencing one of these errors, please contact DEV Systemtechnik for assistance.
52 Copyright DEV Systemtechnik GmbH 2007-2017
Page 53
Customer Documentation DEV 5071
AC Power Plug
Pin
Functionality
Pin 1
L (Live/Phase)
Pin 2
PE (Protective Earth)
Pin 3
N (Neutral)
Serial Connector
RS 232
Pin
Functionality
Pin 1
do not use
Pin 2
Tx
Pin 3
Rx
Pin 4
do not use
Pin 5
GND
Pin 6
do not use
Pin 7
do not use
Pin 8
do not use
Pin 9
do not use
Ethernet Connector
Pin
Functionality
Pin 1
Tx+
Pin 2
Tx-
Pin 3
Rx+
Pin 4
not connected
Pin 5
not connected
Pin 6
Rx-
Pin 7
not connected
Pin 8
not connected
1
2
3
9
1
8
1

7 CONNECTORS

AC Power Plugs
Connector: IEC rubber connector (male) IEC 60320 C14 Connector screws: none
Serial Connector (at the CPU module)
Connector: Sub-D 9 (f) Connector screws: UNC 4-40
Note: "do not use" means that normally the pin should be left open.
It is usually not a problem to use a fully populated 1:1 Sub-D 9 (m)-(f) cable to establish a RS 232 connection between the device and a PC.
Ethernet Connector (at the CPU module) Connector: RJ-45
Connector assembly: none
Copyright DEV Systemtechnik GmbH 2007-2017 53
Page 54
Customer Documentation DEV 5071

8 TECHNICAL DATA

For the technical data, please refer to the data sheet in the appendix.

9 OPTIONS

For the options, please refer to the data sheet in the appendix.

10 SPARE PARTS

Power Supply Module; 100…240 V AC, 2000 W DEV 79-0177

11 CONFORMANCE DECLARATIONS

11.1 CERTIFICATE OF CONFORMANCE

Since DEV Systemtechnik develops and produces in Germany, the Certificate of Conformance for each product or product series is to be issued in German (as stated on the next page).
For the ease of comprehension, the harmonized standards, which were taken into consideration during development and production of the device, are listed here in English:
EN 50083-2:2006 Cabled Distribution Systems for Television and Sound Signals EN 60950-1:2002 Standard for Safety Information Technology Equipment EN 61000-3-2:2006 EMC Limits for Harmonic Current Emissions (Equipment Input Current ≤16 A per Phase) EN 61000-3-3:1995 EMC Limitation of Voltage Changes, Voltage + A1:2001 Fluctuations and Flicker in Public Low-Voltage Supply + A2:2005 Systems, for Equipment with rated Current ≤16 A per Phase and not Subject to Conditional Connection EN 61000-6-2:2005 EMC Generic Immunity Standard – Industrial Environment EN 61000-6-4:2007 EMC Generic Emission Standard – Industrial Environment EN 61293:1995 Marking of Electrical Equipment with Ratings Related to Electrical Supply – Safety Requirements
54 Copyright DEV Systemtechnik GmbH 2007-2017
Page 55
Customer Documentation DEV 5071
DEV Systemtechnik GmbH & Co. KG
Der Hersteller: DEV Systemtechnik GmbH & Co. KG Grüner Weg 4A 61169 Friedberg
erklärt hiermit in alleiniger Verantwortung, dass das nachfolgend bezeichnete Produkt in der von uns in Verkehr gebrachten Ausführung:
Bezeichnung des Produktes: High Power DC Supply; -48 V, 4*2000 W; 1 RU Produktnummer: DEV 5071 Baujahr: ab 2009
auf das sich diese Erklärung bezieht, mit den folgenden Normen übereinstimmt. Bei der Konzipierung und beim Bau des Gerätes wurden die folgenden harmonisierten Normen
berücksichtigt: EN 50083-2:2006 Kabelverteilsysteme für Ton- und Fernsehrundfunk-Signale
EN 60950-1:2002 Sicherheitsbestimmungen für Einrichtungen der Informationstechnik EN 61000-3-2:2006 EMV Grenzwerte für Oberschwingungsströme (Geräte-Eingangsstrom ≤16 A je Leiter) EN 61000-3-3:1995 Grenzwerte für Spannungsänderungen, -schwankungen + A1:2001 und Flicker in öffentlichen Niederspannungs-Versorgungsnetzen + A2:2005 für Geräte mit einem Bemessungsstrom ≤16 A je Leiter, die keiner Sonderanschlussbedingung unterliegen EN 61000-6-2:2005 EMV Fachgrundnorm Störfestigkeit Industriebereich EN 61000-6-4:2007 EMV Fachgrundnorm Störaussendung Industriebereich EN 61293:1995 Kennzeichnung elektrischer Betriebsmittel mit Bemessungsdaten für die Stromversorgung; Anforderung für die Sicherheit
DEV Systemtechnik GmbH & Co. KG _____________________________ Friedberg, 19.12.2013 Jörg Schmidt Geschäftsführer
Konformitätserklärung nach
EMV-Richtlinie (2004/108/EG)
Niederspannungsrichtlinie (73/23/EWG)
Copyright DEV Systemtechnik GmbH 2007-2017 55
Page 56
Customer Documentation DEV 5071
(This Page Intentionally Left Blank)
56 Copyright DEV Systemtechnik GmbH 2007-2017
Page 57
Customer Documentation DEV 5071
DEV 5071
High Power DC Supply; -48 V, 4*2000 W; 1 RU
Options:
21, 23, 79, and future options

11.2 EU DECLARATION OF CONFORMITY

As original manufacturer of Electrical & Electronic Equipment (EEE) DEV Systemtechnik GmbH & Co. KG
Grüner Weg 4A 61169 Friedberg GERMANY
declares under sole responsibility that the product
to which this declaration refers to, is in conformity with Directive 2011/65/EU of the European Parliament and of the Council of 8 June 2011 on the restriction of the use of certain hazardous substances in electrical and electronic equipment (RoHS).
Signed for and on behalf of DEV Systemtechnik GmbH & Co. KG Name: Jörg Schmidt Position: Managing Director Place and date of issue: Friedberg, 19-DEC-2013
Signature:
Copyright DEV Systemtechnik GmbH 2007-2017 57
Page 58
Customer Documentation DEV 5071
AC
Alternating Current
AF
(width) Across Flats
AWG
American Wire Gauge
CEST
Central European Summer Time
CET
Central European Time
CPU
Central Processing Unit
DC
Direct Current
DHCP
Dynamic Host Configuration Protocol: Protocol used by networked computers (clients) to obtain IP addresses and other parameters like netmask and gateway from a DHCP server.
IP
Internet Protocol
LED
Light Emitting Diode
M&C System
Management and Control System
MAC
Media Access Control (address) is the hardware address for the unique identification of a device within a network.
MIB
Management Information Base
NE
Network Element
NMS
Network Management System
OID
Object IDentifier
PC
Personal Computer
PE
Protective Earth
RU
Rack Unit: Units of vertical height. 1 RU = 1 ¾" = 44.45 mm Sometimes simply referred to as "U" (Unit).
SNMP
Simple Network Management Protocol
TCP
Transmission Control Protocol
TCP/IP
TCP/Internet Protocol
UDP
User Datagram Protocol
URL
Uniform Resource Locator

12 GLOSSARY

58 Copyright DEV Systemtechnik GmbH 2007-2017
Page 59
Customer Documentation DEV 5071
Country­code
Coordinates
Time Zone
Comments
AD
+4230+00131
Europe/Andorra
AE
+2518+05518
Asia/Dubai
AF
+3431+06912
Asia/Kabul
AG
+1703-06148
America/Antigua
AI
+1812-06304
America/Anguilla
AL
+4120+01950
Europe/Tirane
AM
+4011+04430
Asia/Yerevan
AO
-0848+01314
Africa/Luanda
AQ
-7750+16636
Antarctica/McMurdo
McMurdo, South Pole, Scott (New Zealand time)
AQ
-6734-06808
Antarctica/Rothera
Rothera Station, Adelaide Island
AQ
-6448-06406
Antarctica/Palmer
Palmer Station, Anvers Island
AQ
-6736+06253
Antarctica/Mawson
Mawson Station, Holme Bay
AQ
-6835+07758
Antarctica/Davis
Davis Station, Vestfold Hills
AQ
-6617+11031
Antarctica/Casey
Casey Station, Bailey Peninsula
AQ
-7824+10654
Antarctica/Vostok
Vostok Station, Lake Vostok
AQ
-6640+14001
Antarctica/DumontDUrville
Dumont-d'Urville Station, Terre Adelie
AQ
-690022+0393524
Antarctica/Syowa
Syowa Station, E Ongul I
AR
-3436-05827
America/Argentina/Buenos_Aires
Buenos Aires (BA, CF)
AR
-3124-06411
America/Argentina/Cordoba
most locations (CB, CC, CN, ER, FM, MN, SE, SF)
AR
-2447-06525
America/Argentina/Salta
(SA, LP, NQ, RN)
AR
-2411-06518
America/Argentina/Jujuy
Jujuy (JY)
AR
-2649-06513
America/Argentina/Tucuman
Tucuman (TM)
AR
-2828-06547
America/Argentina/Catamarca
Catamarca (CT), Chubut (CH)
AR
-2926-06651
America/Argentina/La_Rioja
La Rioja (LR)
AR
-3132-06831
America/Argentina/San_Juan
San Juan (SJ)
AR
-3253-06849
America/Argentina/Mendoza
Mendoza (MZ)
AR
-3319-06621
America/Argentina/San_Luis
San Luis (SL)
AR
-5138-06913
America/Argentina/Rio_Gallegos
Santa Cruz (SC)
AR
-5448-06818
America/Argentina/Ushuaia
Tierra del Fuego (TF)
AS
-1416-17042
Pacific/Pago_Pago
AT
+4813+01620
Europe/Vienna
AU
-3133+15905
Australia/Lord_Howe
Lord Howe Island
AU
-5430+15857
Antarctica/Macquarie
Macquarie Island
AU
-4253+14719
Australia/Hobart
Tasmania - most locations
AU
-3956+14352
Australia/Currie
Tasmania - King Island
AU
-3749+14458
Australia/Melbourne
Victoria
AU
-3352+15113
Australia/Sydney
New South Wales - most locations
AU
-3157+14127
Australia/Broken_Hill
New South Wales - Yancowinna
AU
-2728+15302
Australia/Brisbane
Queensland - most locations
AU
-2016+14900
Australia/Lindeman
Queensland - Holiday Islands
AU
-3455+13835
Australia/Adelaide
South Australia
AU
-1228+13050
Australia/Darwin
Northern Territory
AU
-3157+11551
Australia/Perth
Western Australia - most locations
AU
-3143+12852
Australia/Eucla
Western Australia - Eucla area
AW
+1230-06958
America/Aruba
AX
+6006+01957
Europe/Mariehamn
AZ
+4023+04951
Asia/Baku
BA
+4352+01825
Europe/Sarajevo
BB
+1306-05937
America/Barbados
BD
+2343+09025
Asia/Dhaka
BE
+5050+00420
Europe/Brussels
BF
+1222-00131
Africa/Ouagadougou
BG
+4241+02319
Europe/Sofia
BH
+2623+05035
Asia/Bahrain
BI
-0323+02922
Africa/Bujumbura
BJ
+0629+00237
Africa/Porto-Novo

13 TABLE OF TIME ZONES

(obtained from: http://www.ietf.org/timezones/data/zone.tab)
Copyright DEV Systemtechnik GmbH 2007-2017 59
Page 60
Customer Documentation DEV 5071
Country­code
Coordinates
Time Zone
Comments
BL
+1753-06251
America/St_Barthelemy
BM
+3217-06446
Atlantic/Bermuda
BN
+0456+11455
Asia/Brunei
BO
-1630-06809
America/La_Paz
BQ
+120903-0681636
America/Kralendijk
BR
-0351-03225
America/Noronha
Atlantic islands
BR
-0127-04829
America/Belem
Amapa, E Para
BR
-0343-03830
America/Fortaleza
NE Brazil (MA, PI, CE, RN, PB)
BR
-0803-03454
America/Recife
Pernambuco
BR
-0712-04812
America/Araguaina
Tocantins
BR
-0940-03543
America/Maceio
Alagoas, Sergipe
BR
-1259-03831
America/Bahia
Bahia
BR
-2332-04637
America/Sao_Paulo
S & SE Brazil (GO, DF, MG, ES, RJ, SP, PR, SC, RS)
BR
-2027-05437
America/Campo_Grande
Mato Grosso do Sul
BR
-1535-05605
America/Cuiaba
Mato Grosso
BR
-0226-05452
America/Santarem
W Para
BR
-0846-06354
America/Porto_Velho
Rondonia
BR
+0249-06040
America/Boa_Vista
Roraima
BR
-0308-06001
America/Manaus
E Amazonas
BR
-0640-06952
America/Eirunepe
W Amazonas
BR
-0958-06748
America/Rio_Branco
Acre
BS
+2505-07721
America/Nassau
BT
+2728+08939
Asia/Thimphu
BW
-2439+02555
Africa/Gaborone
BY
+5354+02734
Europe/Minsk
BZ
+1730-08812
America/Belize
CA
+4734-05243
America/St_Johns
Newfoundland Time, including SE Labrador
CA
+4439-06336
America/Halifax
Atlantic Time - Nova Scotia (most places), PEI
CA
+4612-05957
America/Glace_Bay
Atlantic Time - Nova Scotia - places that did not observe DST 1966-1971
CA
+4606-06447
America/Moncton
Atlantic Time - New Brunswick
CA
+5320-06025
America/Goose_Bay
Atlantic Time - Labrador - most locations
CA
+5125-05707
America/Blanc-Sablon
Atlantic Standard Time - Quebec ­Lower North Shore
CA
+4339-07923
America/Toronto
Eastern Time - Ontario & Quebec ­most locations
CA
+4901-08816
America/Nipigon
Eastern Time - Ontario & Quebec ­places that did not observe DST 1967-1973
CA
+4823-08915
America/Thunder_Bay
Eastern Time - Thunder Bay, Ontario
CA
+6344-06828
America/Iqaluit
Eastern Time - east Nunavut - most locations
CA
+6608-06544
America/Pangnirtung
Eastern Time - Pangnirtung, Nunavut
CA
+744144-0944945
America/Resolute
Central Standard Time - Resolute, Nunavut
CA
+484531-0913718
America/Atikokan
Eastern Standard Time - Atikokan, Ontario and Southampton I, Nunavut
CA
+624900-0920459
America/Rankin_Inlet
Central Time - central Nunavut
CA
+4953-09709
America/Winnipeg
Central Time - Manitoba & west Ontario
CA
+4843-09434
America/Rainy_River
Central Time - Rainy River & Fort Frances, Ontario
CA
+5024-10439
America/Regina
Central Standard Time ­Saskatchewan - most locations
CA
+5017-10750
America/Swift_Current
Central Standard Time ­Saskatchewan - midwest
CA
+5333-11328
America/Edmonton
Mountain Time - Alberta, east British Columbia & west Saskatchewan
CA
+690650-1050310
America/Cambridge_Bay
Mountain Time - west Nunavut
60 Copyright DEV Systemtechnik GmbH 2007-2017
Page 61
Customer Documentation DEV 5071
Country­code
Coordinates
Time Zone
Comments
CA
+6227-11421
America/Yellowknife
Mountain Time - central Northwest Territories
CA
+682059-1334300
America/Inuvik
Mountain Time - west Northwest Territories
CA
+4906-11631
America/Creston
Mountain Standard Time - Creston, British Columbia
CA
+5946-12014
America/Dawson_Creek
Mountain Standard Time - Dawson Creek & Fort Saint John, British Columbia
CA
+4916-12307
America/Vancouver
Pacific Time - west British Columbia
CA
+6043-13503
America/Whitehorse
Pacific Time - south Yukon
CA
+6404-13925
America/Dawson
Pacific Time - north Yukon
CC
-1210+09655
Indian/Cocos
CD
-0418+01518
Africa/Kinshasa
west Dem. Rep. of Congo
CD
-1140+02728
Africa/Lubumbashi
east Dem. Rep. of Congo
CF
+0422+01835
Africa/Bangui
CG
-0416+01517
Africa/Brazzaville
CH
+4723+00832
Europe/Zurich
CI
+0519-00402
Africa/Abidjan
CK
-2114-15946
Pacific/Rarotonga
CL
-3327-07040
America/Santiago
most locations
CL
-2709-10926
Pacific/Easter
Easter Island & Sala y Gomez
CM
+0403+00942
Africa/Douala
CN
+3114+12128
Asia/Shanghai
east China - Beijing, Guangdong, Shanghai, etc.
CN
+4545+12641
Asia/Harbin
Heilongjiang (except Mohe), Jilin
CN
+2934+10635
Asia/Chongqing
central China - Sichuan, Yunnan, Guangxi, Shaanxi, Guizhou, etc.
CN
+4348+08735
Asia/Urumqi
most of Tibet & Xinjiang
CN
+3929+07559
Asia/Kashgar
west Tibet & Xinjiang
CO
+0436-07405
America/Bogota
CR
+0956-08405
America/Costa_Rica
CU
+2308-08222
America/Havana
CV
+1455-02331
Atlantic/Cape_Verde
CW
+1211-06900
America/Curacao
CX
-1025+10543
Indian/Christmas
CY
+3510+03322
Asia/Nicosia
CZ
+5005+01426
Europe/Prague
DE
+5230+01322
Europe/Berlin
most locations
DE
+4742+00841
Europe/Busingen
Busingen
DJ
+1136+04309
Africa/Djibouti
DK
+5540+01235
Europe/Copenhagen
DM
+1518-06124
America/Dominica
DO
+1828-06954
America/Santo_Domingo
DZ
+3647+00303
Africa/Algiers
EC
-0210-07950
America/Guayaquil
mainland
EC
-0054-08936
Pacific/Galapagos
Galapagos Islands
EE
+5925+02445
Europe/Tallinn
EG
+3003+03115
Africa/Cairo
EH
+2709-01312
Africa/El_Aaiun
ER
+1520+03853
Africa/Asmara
ES
+4024-00341
Europe/Madrid
mainland
ES
+3553-00519
Africa/Ceuta
Ceuta & Melilla
ES
+2806-01524
Atlantic/Canary
Canary Islands
ET
+0902+03842
Africa/Addis_Ababa
FI
+6010+02458
Europe/Helsinki
FJ
-1808+17825
Pacific/Fiji
FK
-5142-05751
Atlantic/Stanley
FM
+0725+15147
Pacific/Chuuk
Chuuk (Truk) and Yap
FM
+0658+15813
Pacific/Pohnpei
Pohnpei (Ponape)
FM
+0519+16259
Pacific/Kosrae
Kosrae
FO
+6201-00646
Atlantic/Faroe
FR
+4852+00220
Europe/Paris
Copyright DEV Systemtechnik GmbH 2007-2017 61
Page 62
Customer Documentation DEV 5071
Country­code
Coordinates
Time Zone
Comments
GA
+0023+00927
Africa/Libreville
GB
+513030-0000731
Europe/London
GD
+1203-06145
America/Grenada
GE
+4143+04449
Asia/Tbilisi
GF
+0456-05220
America/Cayenne
GG
+4927-00232
Europe/Guernsey
GH
+0533-00013
Africa/Accra
GI
+3608-00521
Europe/Gibraltar
GL
+6411-05144
America/Godthab
most locations
GL
+7646-01840
America/Danmarkshavn
east coast, north of Scoresbysund
GL
+7029-02158
America/Scoresbysund
Scoresbysund / Ittoqqortoormiit
GL
+7634-06847
America/Thule
Thule / Pituffik
GM
+1328-01639
Africa/Banjul
GN
+0931-01343
Africa/Conakry
GP
+1614-06132
America/Guadeloupe
GQ
+0345+00847
Africa/Malabo
GR
+3758+02343
Europe/Athens
GS
-5416-03632
Atlantic/South_Georgia
GT
+1438-09031
America/Guatemala
GU
+1328+14445
Pacific/Guam
GW
+1151-01535
Africa/Bissau
GY
+0648-05810
America/Guyana
HK
+2217+11409
Asia/Hong_Kong
HN
+1406-08713
America/Tegucigalpa
HR
+4548+01558
Europe/Zagreb
HT
+1832-07220
America/Port-au-Prince
HU
+4730+01905
Europe/Budapest
ID
-0610+10648
Asia/Jakarta
Java & Sumatra
ID
-0002+10920
Asia/Pontianak
west & central Borneo
ID
-0507+11924
Asia/Makassar
east & south Borneo, Sulawesi (Celebes), Bali, Nusa Tengarra, west Timor
ID
-0232+14042
Asia/Jayapura
west New Guinea (Irian Jaya) & Malukus (Moluccas)
IE
+5320-00615
Europe/Dublin
IL
+314650+0351326
Asia/Jerusalem
IM
+5409-00428
Europe/Isle_of_Man
IN
+2232+08822
Asia/Kolkata
IO
-0720+07225
Indian/Chagos
IQ
+3321+04425
Asia/Baghdad
IR
+3540+05126
Asia/Tehran
IS
+6409-02151
Atlantic/Reykjavik
IT
+4154+01229
Europe/Rome
JE
+4912-00207
Europe/Jersey
JM
+175805-0764736
America/Jamaica
JO
+3157+03556
Asia/Amman
JP
+353916+1394441
Asia/Tokyo
KE
-0117+03649
Africa/Nairobi
KG
+4254+07436
Asia/Bishkek
KH
+1133+10455
Asia/Phnom_Penh
KI
+0125+17300
Pacific/Tarawa
Gilbert Islands
KI
-0308-17105
Pacific/Enderbury
Phoenix Islands
KI
+0152-15720
Pacific/Kiritimati
Line Islands
KM
-1141+04316
Indian/Comoro
KN
+1718-06243
America/St_Kitts
KP
+3901+12545
Asia/Pyongyang
KR
+3733+12658
Asia/Seoul
KW
+2920+04759
Asia/Kuwait
KY
+1918-08123
America/Cayman
KZ
+4315+07657
Asia/Almaty
most locations
KZ
+4448+06528
Asia/Qyzylorda
Qyzylorda (Kyzylorda, Kzyl-Orda)
KZ
+5017+05710
Asia/Aqtobe
Aqtobe (Aktobe)
62 Copyright DEV Systemtechnik GmbH 2007-2017
Page 63
Customer Documentation DEV 5071
Country­code
Coordinates
Time Zone
Comments
KZ
+4431+05016
Asia/Aqtau
Atyrau (Atirau, Gur'yev), Mangghystau (Mankistau)
KZ
+5113+05121
Asia/Oral
West Kazakhstan
LA
+1758+10236
Asia/Vientiane
LB
+3353+03530
Asia/Beirut
LC
+1401-06100
America/St_Lucia
LI
+4709+00931
Europe/Vaduz
LK
+0656+07951
Asia/Colombo
LR
+0618-01047
Africa/Monrovia
LS
-2928+02730
Africa/Maseru
LT
+5441+02519
Europe/Vilnius
LU
+4936+00609
Europe/Luxembourg
LV
+5657+02406
Europe/Riga
LY
+3254+01311
Africa/Tripoli
MA
+3339-00735
Africa/Casablanca
MC
+4342+00723
Europe/Monaco
MD
+4700+02850
Europe/Chisinau
ME
+4226+01916
Europe/Podgorica
MF
+1804-06305
America/Marigot
MG
-1855+04731
Indian/Antananarivo
MH
+0709+17112
Pacific/Majuro
most locations
MH
+0905+16720
Pacific/Kwajalein
Kwajalein
MK
+4159+02126
Europe/Skopje
ML
+1239-00800
Africa/Bamako
MM
+1647+09610
Asia/Rangoon
MN
+4755+10653
Asia/Ulaanbaatar
most locations
MN
+4801+09139
Asia/Hovd
Bayan-Olgiy, Govi-Altai, Hovd, Uvs, Zavkhan
MN
+4804+11430
Asia/Choibalsan
Dornod, Sukhbaatar
MO
+2214+11335
Asia/Macau
MP
+1512+14545
Pacific/Saipan
MQ
+1436-06105
America/Martinique
MR
+1806-01557
Africa/Nouakchott
MS
+1643-06213
America/Montserrat
MT
+3554+01431
Europe/Malta
MU
-2010+05730
Indian/Mauritius
MV
+0410+07330
Indian/Maldives
MW
-1547+03500
Africa/Blantyre
MX
+1924-09909
America/Mexico_City
Central Time - most locations
MX
+2105-08646
America/Cancun
Central Time - Quintana Roo
MX
+2058-08937
America/Merida
Central Time - Campeche, Yucatan
MX
+2540-10019
America/Monterrey
Mexican Central Time - Coahuila, Durango, Nuevo Leon, Tamaulipas away from US border
MX
+2550-09730
America/Matamoros
US Central Time - Coahuila, Durango, Nuevo Leon, Tamaulipas near US border
MX
+2313-10625
America/Mazatlan
Mountain Time - S Baja, Nayarit, Sinaloa
MX
+2838-10605
America/Chihuahua
Mexican Mountain Time - Chihuahua away from US border
MX
+2934-10425
America/Ojinaga
US Mountain Time - Chihuahua near US border
MX
+2904-11058
America/Hermosillo
Mountain Standard Time - Sonora
MX
+3232-11701
America/Tijuana
US Pacific Time - Baja California near US border
MX
+3018-11452
America/Santa_Isabel
Mexican Pacific Time - Baja California away from US border
MX
+2048-10515
America/Bahia_Banderas
Mexican Central Time - Bahia de Banderas
MY
+0310+10142
Asia/Kuala_Lumpur
peninsular Malaysia
MY
+0133+11020
Asia/Kuching
Sabah & Sarawak
MZ
-2558+03235
Africa/Maputo
Copyright DEV Systemtechnik GmbH 2007-2017 63
Page 64
Customer Documentation DEV 5071
Country­code
Coordinates
Time Zone
Comments
NA
-2234+01706
Africa/Windhoek
NC
-2216+16627
Pacific/Noumea
NE
+1331+00207
Africa/Niamey
NF
-2903+16758
Pacific/Norfolk
NG
+0627+00324
Africa/Lagos
NI
+1209-08617
America/Managua
NL
+5222+00454
Europe/Amsterdam
NO
+5955+01045
Europe/Oslo
NP
+2743+08519
Asia/Kathmandu
NR
-0031+16655
Pacific/Nauru
NU
-1901-16955
Pacific/Niue
NZ
-3652+17446
Pacific/Auckland
most locations
NZ
-4357-17633
Pacific/Chatham
Chatham Islands
OM
+2336+05835
Asia/Muscat
PA
+0858-07932
America/Panama
PE
-1203-07703
America/Lima
PF
-1732-14934
Pacific/Tahiti
Society Islands
PF
-0900-13930
Pacific/Marquesas
Marquesas Islands
PF
-2308-13457
Pacific/Gambier
Gambier Islands
PG
-0930+14710
Pacific/Port_Moresby
PH
+1435+12100
Asia/Manila
PK
+2452+06703
Asia/Karachi
PL
+5215+02100
Europe/Warsaw
PM
+4703-05620
America/Miquelon
PN
-2504-13005
Pacific/Pitcairn
PR
+182806-0660622
America/Puerto_Rico
PS
+3130+03428
Asia/Gaza
Gaza Strip
PS
+313200+0350542
Asia/Hebron
West Bank
PT
+3843-00908
Europe/Lisbon
mainland
PT
+3238-01654
Atlantic/Madeira
Madeira Islands
PT
+3744-02540
Atlantic/Azores
Azores
PW
+0720+13429
Pacific/Palau
PY
-2516-05740
America/Asuncion
QA
+2517+05132
Asia/Qatar
RE
-2052+05528
Indian/Reunion
RO
+4426+02606
Europe/Bucharest
RS
+4450+02030
Europe/Belgrade
RU
+5443+02030
Europe/Kaliningrad
Moscow-01 - Kaliningrad
RU
+5545+03735
Europe/Moscow
Moscow+00 - west Russia
RU
+4844+04425
Europe/Volgograd
Moscow+00 - Caspian Sea
RU
+5312+05009
Europe/Samara
Moscow+00 - Samara, Udmurtia
RU
+5651+06036
Asia/Yekaterinburg
Moscow+02 - Urals
RU
+5500+07324
Asia/Omsk
Moscow+03 - west Siberia
RU
+5502+08255
Asia/Novosibirsk
Moscow+03 - Novosibirsk
RU
+5345+08707
Asia/Novokuznetsk
Moscow+03 - Novokuznetsk
RU
+5601+09250
Asia/Krasnoyarsk
Moscow+04 - Yenisei River
RU
+5216+10420
Asia/Irkutsk
Moscow+05 - Lake Baikal
RU
+6200+12940
Asia/Yakutsk
Moscow+06 - Lena River
RU
+623923+1353314
Asia/Khandyga
Moscow+06 - Tomponsky, Ust­Maysky
RU
+4310+13156
Asia/Vladivostok
Moscow+07 - Amur River
RU
+4658+14242
Asia/Sakhalin
Moscow+07 - Sakhalin Island
RU
+643337+1431336
Asia/Ust-Nera
Moscow+07 - Oymyakonsky
RU
+5934+15048
Asia/Magadan
Moscow+08 - Magadan
RU
+5301+15839
Asia/Kamchatka
Moscow+08 - Kamchatka
RU
+6445+17729
Asia/Anadyr
Moscow+08 - Bering Sea
RW
-0157+03004
Africa/Kigali
SA
+2438+04643
Asia/Riyadh
SB
-0932+16012
Pacific/Guadalcanal
SC
-0440+05528
Indian/Mahe
SD
+1536+03232
Africa/Khartoum
SE
+5920+01803
Europe/Stockholm
SG
+0117+10351
Asia/Singapore
64 Copyright DEV Systemtechnik GmbH 2007-2017
Page 65
Customer Documentation DEV 5071
Country­code
Coordinates
Time Zone
Comments
SH
-1555-00542
Atlantic/St_Helena
SI
+4603+01431
Europe/Ljubljana
SJ
+7800+01600
Arctic/Longyearbyen
SK
+4809+01707
Europe/Bratislava
SL
+0830-01315
Africa/Freetown
SM
+4355+01228
Europe/San_Marino
SN
+1440-01726
Africa/Dakar
SO
+0204+04522
Africa/Mogadishu
SR
+0550-05510
America/Paramaribo
SS
+0451+03136
Africa/Juba
ST
+0020+00644
Africa/Sao_Tome
SV
+1342-08912
America/El_Salvador
SX
+180305-0630250
America/Lower_Princes
SY
+3330+03618
Asia/Damascus
SZ
-2618+03106
Africa/Mbabane
TC
+2128-07108
America/Grand_Turk
TD
+1207+01503
Africa/Ndjamena
TF
-492110+0701303
Indian/Kerguelen
TG
+0608+00113
Africa/Lome
TH
+1345+10031
Asia/Bangkok
TJ
+3835+06848
Asia/Dushanbe
TK
-0922-17114
Pacific/Fakaofo
TL
-0833+12535
Asia/Dili
TM
+3757+05823
Asia/Ashgabat
TN
+3648+01011
Africa/Tunis
TO
-2110-17510
Pacific/Tongatapu
TR
+4101+02858
Europe/Istanbul
TT
+1039-06131
America/Port_of_Spain
TV
-0831+17913
Pacific/Funafuti
TW
+2503+12130
Asia/Taipei
TZ
-0648+03917
Africa/Dar_es_Salaam
UA
+5026+03031
Europe/Kiev
most locations
UA
+4837+02218
Europe/Uzhgorod
Ruthenia
UA
+4750+03510
Europe/Zaporozhye
Zaporozh'ye, E Lugansk / Zaporizhia, E Luhansk
UA
+4457+03406
Europe/Simferopol
central Crimea
UG
+0019+03225
Africa/Kampala
UM
+1645-16931
Pacific/Johnston
Johnston Atoll
UM
+2813-17722
Pacific/Midway
Midway Islands
UM
+1917+16637
Pacific/Wake
Wake Island
US
+404251-0740023
America/New_York
Eastern Time
US
+421953-0830245
America/Detroit
Eastern Time - Michigan - most locations
US
+381515-0854534
America/Kentucky/Louisville
Eastern Time - Kentucky - Louisville area
US
+364947-0845057
America/Kentucky/Monticello
Eastern Time - Kentucky - Wayne County
US
+394606-0860929
America/Indiana/Indianapolis
Eastern Time - Indiana - most locations
US
+384038-0873143
America/Indiana/Vincennes
Eastern Time - Indiana - Daviess, Dubois, Knox & Martin Counties
US
+410305-0863611
America/Indiana/Winamac
Eastern Time - Indiana - Pulaski County
US
+382232-0862041
America/Indiana/Marengo
Eastern Time - Indiana - Crawford County
US
+382931-0871643
America/Indiana/Petersburg
Eastern Time - Indiana - Pike County
US
+384452-0850402
America/Indiana/Vevay
Eastern Time - Indiana - Switzerland County
US
+415100-0873900
America/Chicago
Central Time
US
+375711-0864541
America/Indiana/Tell_City
Central Time - Indiana - Perry County
US
+411745-0863730
America/Indiana/Knox
Central Time - Indiana - Starke County
Copyright DEV Systemtechnik GmbH 2007-2017 65
Page 66
Customer Documentation DEV 5071
Country­code
Coordinates
Time Zone
Comments
US
+450628-0873651
America/Menominee
Central Time - Michigan - Dickinson, Gogebic, Iron & Menominee Counties
US
+470659-1011757
America/North_Dakota/Center
Central Time - North Dakota - Oliver County
US
+465042-1012439
America/North_Dakota/New_Sale m
Central Time - North Dakota - Morton County (except Mandan area)
US
+471551-1014640
America/North_Dakota/Beulah
Central Time - North Dakota - Mercer County
US
+394421-1045903
America/Denver
Mountain Time
US
+433649-1161209
America/Boise
Mountain Time - south Idaho & east Oregon
US
+332654-1120424
America/Phoenix
Mountain Standard Time - Arizona (except Navajo)
US
+340308-1181434
America/Los_Angeles
Pacific Time
US
+611305-1495401
America/Anchorage
Alaska Time
US
+581807-1342511
America/Juneau
Alaska Time - Alaska panhandle
US
+571035-1351807
America/Sitka
Alaska Time - southeast Alaska panhandle
US
+593249-1394338
America/Yakutat
Alaska Time - Alaska panhandle neck
US
+643004-1652423
America/Nome
Alaska Time - west Alaska
US
+515248-1763929
America/Adak
Aleutian Islands
US
+550737-1313435
America/Metlakatla
Metlakatla Time - Annette Island
US
+211825-1575130
Pacific/Honolulu
Hawaii
UY
-3453-05611
America/Montevideo
UZ
+3940+06648
Asia/Samarkand
west Uzbekistan
UZ
+4120+06918
Asia/Tashkent
east Uzbekistan
VA
+415408+0122711
Europe/Vatican
VC
+1309-06114
America/St_Vincent
VE
+1030-06656
America/Caracas
VG
+1827-06437
America/Tortola
VI
+1821-06456
America/St_Thomas
VN
+1045+10640
Asia/Ho_Chi_Minh
VU
-1740+16825
Pacific/Efate
WF
-1318-17610
Pacific/Wallis
WS
-1350-17144
Pacific/Apia
YE
+1245+04512
Asia/Aden
YT
-1247+04514
Indian/Mayotte
ZA
-2615+02800
Africa/Johannesburg
ZM
-1525+02817
Africa/Lusaka
ZW
-1750+03103
Africa/Harare
66 Copyright DEV Systemtechnik GmbH 2007-2017
Page 67
Customer Documentation DEV 5071

14 NOTES

Copyright DEV Systemtechnik GmbH 2007-2017 67
Page 68
The Art of Engineering
Product:
DEV 5071
48 V, 4*2000 W Power Supply Chassis
Features:
Powerful DC Supply with up to 8000 W maximum Output Power 1…4 hot-pluggable 48 V, 2000 W Power Supply Modules Compact 19" 1 RU Chassis Galvanic Isolation of the Output Terminals Selectable Polarity of the Output Voltage SNMP Support DEV Web Interface
High Power DC Supply
Page 69
DEV 5071
2/2
The Art of Engineering
Contact
DEV Systemtechnik GmbH Grüner Weg 4A 61169 Friedberg GERMANY Phone: +49 6031 6975 100 Fax: +49 6031 6975 114 info@dev-systemtechnik.com www.dev-systemtechnik.com Rev. 17-Jul-2014
Technical Data
DEV 5071 48 V, 4*2000 W Power Supply Chassis
Remote Communication
Interface (Connector)
Ethernet (RJ-45)
Remote Control & Surveillance (Interface)
via Web Interface (Ethernet)
• via SNMP (Ethernet)
Redundant Power Supply
Power Supply Slots
4
Number of Power Supplies
3
Primary Voltage
100…240 V AC; each Module is supplied via a separate Line
Output Voltage
-48 V DC or +48 V DC selectable (by reversing the Connection to the Output Terminals)
Output Power per Module
1200 W @ Input 100…120 V AC nominal 2000 W @ Input 200…240 V AC nominal
Output Power (total max.)
6000 W (3 Power Supply Modules)
Power Consumption
<6450 VA (3 Power Supply Modules)
General Specifications
Size
19" (483 mm) Width, 1 RU (44 mm) Height, 475 mm Depth
Weight
~15 kg (equipped with 4 Power Supply Modules)
Environmental Conditions
ETS 300019 Part 1-3 Class 3.1
Option 21 Additional Power Supply Module
The device is delivered with four instead of three power supply modules.
Number of Power Supplies
4
Output Power (total max.)
8000 W (4 Power Supply Modules)
Power Consumption
<8600 VA (4 Power Supply Modules)
Option 23 Delete one Power Supply Module
Option 23 can be ordered one or two times, i.e. device is delivered with two or one instead of three power supply modules.
Number of Power Supplies
1 (2) (2 * (1 *) Option 23)
Output Power (total max.)
2000 W (4000 W) (1 (2) Power Supply Module(s))
Power Consumption
<2150 VA (<4300 VA) (1 (2) Power Supply Module(s))
Product
DEV 5071
48 V, 4*2000 W Power Supply Chassis
Options
Option 21
Additional Power Supply Module
Option 23
Delete one Power Supply Module
Option 79
Additional Web License 1 RU
Order Information
Loading...