Programming Manual
Pages
PC 2003 Amplifier
English
1 INTRODUCTION
2 PARAMETER SETTING
2.1 Calibrating the reference 4
2.2 Adjusting the tolerances 7
2
4
3 CONTROL FUNCTIONS 8
3.1 Masking a measurement 8
3.2 Transferring a measurement 9
3.3 Setting the machine shutdown parameter 11
3.4 Table of the programming modes 12
Page 1/14
PROPC2003EN – Index A
Page 3
Programming Manual
PC 2003 Amplifier
1. Introduction
Détector France congratulates and thanks you for having selected its PC2003 amplifier for your applications. After a brief presentation of the device’s capabilities, this guide describes all the menus and functions you will encounter during programming and use. For details about the sensor and its mechanical mounting, please refer to the Integration and mechanical adjustment manual.
Don’t hesitate to contact us for additional information or problems, a technician will answer your questions.
The PC2003 is designed to measure part length or diameters (depending on the sensor type chosen) using an LVDT linear probe. Three measurement modes are available: Peak , Peak Controlled or Realtime.
The Peak mode (default) can be described as follows:
1- During the passing of a part (spindle indexing), the sensor moves when it
comes in contact with the part.
2- The largest value (the sensor’s peak movement) is stored by the amplifier. 3- After the valid signal is sent by the machine at end of the cycle, the stored
value is compared to the reference value and the programmed tolerances.
4- The amplifier instantaneously triggers relays based on the results of its
comparison (good part, min. part, max. part or machine shutdown).
5- If the measured part is not within tolerance, the machine can be shutdown
using these relays. On the contrary, if the measured part is within tolerance, the amplifier is automatically reset and awaits the next cycle.
The Peak Controlled mode differs only from the Peak mode because there is another check (internal to the amplifier) to assure that the sensor is working correctly: The first stages (1 and 2) are the same until the valid signal. 3-When the valid signal is sent from the machine, the value stored in memory is compared to the reference and to the programmed tolerances, but there is also another check of the instantaneous position of the sensor (sensor value at the time of the valid signal). This control will be correct only if this instantaneous value is not within the defined tolerances at the moment of the valid signal. 4-The amplifier instantaneously sends the results to the machine (control of the stored value + control of the instantaneous value) 5-If the measured part is not within tolerance, the machine will be shutdown at the end of the cycle and will show a bad part on the screen. If the sensor does not come back to its initial position, so the instantaneous value at the moment of the valid signal is still within tolerance, the machine will stop at the end of the cycle and show defective sensor on the screen.
On the contrary if the 2 controls are Ok (peak measure within tolerance and instantaneous measure at the moment of the valid signal not within tolerance) the machine is not shutdown and the measurement is reset and will wait for the next cycle.
English
Page 2/14
PROPC2003EN – Index A
Page 4
Programming Manual
PC 2003 Amplifier
The Realtime mode can be described as follows:
1- The sensor, mounted at a station (like a drill tool), comes in contact with the
part (during the work) until it is at the machining end stop.
2- Then the valid pulse is sent by the machine; the instantaneous (current
position of sensor) value is directly compared to the reference and the tolerances.
3- The amplifier triggers the relays based on the result of its comparison (good
part, min. part, max. part or machine shutdown).
4- If the measured part is not within tolerance, the machine can be shutdown
using these relays. On the contrary, if the measured part is within tolerance, the measurement is reset and awaits the next valid signal.
Other functions are present in this amplifier, such as the masking of a measurement during a material feed operation, the transfer of a measurement, or the machine shutdown function.
The PC2003 is suitable for most multi-spindle/single spindle machine tools which are cam driven or numerically controlled. Thanks to the user friendliness of the menus, any user can rapidly plug in and use the amplifier and easily navigate within it. In addition, once adjusted, the amplifier can be locked to prevent any handling errors. All the menus and functions are detailed in the rest of this guide.
English
Page 3/14
PROPC2003EN – Index A
Page 5
Programming Manual
CHAN 2
channel) device.
PC 2003 Amplifier
2. PARAMETER SETTINGS
2.1 Calibrating the reference
Calibrating the reference allows the calibration of the sensor to a reference part on your machine. Calibration must be done only after the amplifier has been correctly wired and your machine correctly adjusted so that the dimension to be measured is a mean and stable dimension (without machine drift). By default, the sensor is delivered to you preloaded in the probe. However, if the internal sensor was disassembled from the probe for replacement or a cleaning, the sensor has to be preloaded and tare reset in the probe. This procedure is detailed below in subsection Adjusting sensor preloading in Integration and mechanical adjustment manual
CHAN 1 : +0.000mm
CHAN 2 : +0.000mm
V
appears only if you
have a PC2003B (dual
English
V
-> PART SETUP OPTIONS PARAMETERS DISPLAYS
V
V
TOLERANCES
-> REFERENCE STATISTICS
V
V
REFERENCE :
-> CHANNEL 1 CHANNEL 2
This page appears only
if you have a PC2003B
(dual channel) device.
Calibration on a single reference part. Is used the first time to adjust the part reading on the sensor.
REFERENCE ADJUST CHANNEL 1 :
-> MANUAL AUTOMATIC
V
Calibration on the average of a parts sample. Is used after the adjustment of the part reading on the sensor.
REFERENCE ADJUST CHANNEL 1 : MANUAL
-> AUTOMATIC
V
Page 4/14
PROPC2003EN – Index A
Page 6
Programming Manual
samples.
Start machine
real dimension
type.
zero dimension
nom dimension
Manua
l
reference
Automatic Re
f
erence
PC 2003 Amplifier
English
V V
REFERENCE ADJUST CHANNEL 1 IN MANUAL: SENSOR +0.386mm VALIDATE BY OK
This screen shows the instantaneous value of the sensor to adjust the sensor’s reading between 0.3 and 0.5mm.
V
REFERENCE ADJUST CHANNEL 1 IN AUTO:
VALIDATE BY OK
V
then
V
REFERENCE ADJUST CHANNEL 1 IN AUTO: START MACHINE CYCLE
REFERENCE ADJUST CHANNEL 1 IN AUTO:
V
REFERENCE ADJUST CHANNEL 1 IN AUTO:
V
MAX 0.341mm AVERAGE 0.336mm MIN 0.332 mm VALIDATE BY OK
V
V
REFERENCES CHANNEL 1
-> REAL DIMENSION ZERO DIMENSION NOM DIMENSION
V
REFERENCES CHANNEL 1 REAL DIMENSION
-> ZERO DIMENSION NOM DIMENSION
V
The
corresponds to the sensor
value which you adjusted in
the previous page:
+0.386mm remains
displayed
The
corresponds to the
difference with the real
dimension reset to zero:
+0.386mm becomes
0.000mm. A measured part of 0.390mm will be
displayed+0.004mm
2 SAMPLE(S)
1 SAMPLE(S)
OUT OF 2
2 SAMPLE(S)
OUT OF 2
Select the display
REFERENCES CHANNEL 1 REAL DIMENSION ZERO DIMENSION
-> NOM DIMENSION
V
The
allows replacing the real
dimension by a nominal
dimension on your
drawings. Example:
19.500mm. A measured part of 0.390mm will be
displayed as 19.504mm
Define the number of
Page 5/14
PROPC2003EN – Index A
Page 7
Programming Manual
PC 2003 Amplifier
V
TOLERANCES
-> REFERENCE STATISTICS
V
X2
V
TOLERANCES
-> REFERENCE STATISTICS
V
X2
CHAN 1 : +0.000mm
CHAN 2 : +0.000mm
V
REFERENCE ADJUST NOM DIMENSION +00.000mm VALIDATE BY OK
then
V
REFERENCE ADJUST NOM DIMENSION +19.500mm VALIDATE BY OK
V
V
TOLERANCES
-> REFERENCE STATISTICS
V
X2
English
Page 6/14
PROPC2003EN – Index A
Page 8
Programming Manual
CHAN 2
PC 2003 Amplifier
2.2 Adjusting the tolerances
The tolerances limits define the range of acceptable readings, beyond which the amplifier is going to react by triggering relays to their fault states. These tolerances are adjusted with respect to a reference, which must be set earlier.
CHAN 1 : +0.000mm
CHAN 2 : +0.000mm
V
V
-> PART SETUP OPTIONS PARAMETERS DISPLAYS
V
appears only if you
have a PC2003B (dual
channel) device.
English
V
then
-> TOLERANCES REFERENCE STATISTICS
V
-> TOLERANCES REFERENCE STATISTICS
V
This page appears only
if you have a PC2003B
(dual channel) device
V
TOLERANCES :
-> CHAN 1 CHAN 2
V V TOLERANCES CHAN1 + 0.050mm
- 0.050mm VALIDATE BY OK
X2
V
then
TOLERANCES CHAN1
-> CHANNEL 1 CHANNEL 2
This page appears only if you have a PC2003B
(dual channel) device
X3
Page 7/14
PROPC2003EN – Index A
Page 9
Programming Manual
CHAN 2
PC 2003 Amplifier
3. CONTROL FUNCTIONS
3.1 Masking a measurement
This function allows masking of a measurement during a material feed operation, isolating the fed part (short) without shutting down the machine. The masking of a measurement can be configured:
- Either inactive (no masking) ;
- Or at N closures of the VALID input (N between 1 and 25) after the MASKING
input is closed. For a masked measurement, the corresponding channel indicates VALUE MASKED in addition to the display of the measured value; the indicator
corresponding to the defect, if any, remains off and the outputs remain inactive.
CHAN 1 : +0.000mm
CHAN 2 : +0.000mm
V
appears only if
you have a PC2003B
(dual channel) device.
English
PART SETUP
-> OPTIONS PARAMETERS DISPLAYS
-> MEASURE MASKING ACTION DELAY MULTI-PART ACTION
V
CHAN 1 MASKING :
FOR 1 MEASUREMENTS
VALIDATE BY OK
V
V
V
This page appears only if
V
V
MEASURE MASKING
-> CHANNEL 1 CHANNEL 2
V
V
you have a PC2003B (dual channel) device
Define the number of measurements after which the measured value will be masked
Page 8/14
PROPC2003EN – Index A
Page 10
Programming Manual
CHAN 2
PC 2003 Amplifier
English
V
V
V
-> MEASURE MASKING ACTION DELAY MULTI-PART ACTION
V
V
MEASURE MASKING
-> CHANNEL 1 CHANNEL 2
V
X2
X3
Here is an example to get a better understanding of this function: Everything depends on the station which the machine feeds and where the sensor is positioned. For our example, let’s take a TORNOS AS14 (6 spindles) machine and place the sensor between spindles 5 and 6: The feeding takes place at station 6, and at the same time the feed information is sent to the amplifier. From then on, the electronic box is going to count down the number of measurements in order to mask the measurement of the fed part which will be short. Therefore, the 6th measurement after the masking pulse (feed information) has to be masked and so the amplifier has to be programmed FOR 6 MEASUREMENTS.
3.2 Transferring a measurement
Transferring a measurement’s processing consists of offsetting a relay’s fault state to the desired station. An immediate action after a part is detected outside tolerance is not always practical for its removal. Therefore, this function allows triggering the machine shutdown relay when the bad part is accessible, such as when it is located in the pickoff spindle. This function can be INACTIVE or ACTIVE after n measurements (1 to 25 maximum).
CHAN 1 : +0.000mm
CHAN 2 : +0.000mm
V
V
MEASURE
-> OPTIONS PARAMETERS DISPLAYS
V
you have a PC2003B
(dual channel) device.
appears only if
V
Page 9/14
PROPC2003EN – Index A
Page 11
Programming Manual
PC 2003 Amplifier
V
V
V
MEASURE MASKING
-> ACTION DELAY MULTI-PART ACTION
V
MEASURE MASKING
-> ACTION DELAY MULTI-PART ACTION
CHAN 1 DELAY SIGNAL
FOR 1 MEASUREMENTS
VALIDATE BY OK
X2
V
V
ACTION DELAY
-> CHANNEL 1 CHANNEL 2
V
V
V
Define the number of measurements corresponding to the offset after which the machine will be shutdown
V
ACTION DELAY
-> CHANNEL 1 CHANNEL 2
V
X3
This page appears only if
you have a PC2003B
(dual channel) device.
English
Page 10/14
PROPC2003EN – Index A
Page 12
Programming Manual
CHAN 2
machine
PC 2003 Amplifier
3.3 Setting the machine shutdown parameter
Setting the machine shutdown parameter is very useful if you don’t want to penalize productivity by shutting down the machine even though the measured bad parts are isolated from production by a recovery system controlled by the MIN and MAX contacts. The parameter to be adjusted is the number of consecutive measurements outside tolerances after which the machine will be shutdown. This parameter is adjusted by default to the minimum, that is, after 1 measurement outside tolerance. The maximum is 25 measurements.+
CHAN 1 : +0.000mm
CHAN 2 : +0.000mm
V
V
MEASURE
-> OPTIONS PARAMETERS DISPLAYS
V
appears only if
you have a PC2003B
(dual channel) device.
English
MEASURE MASKING ACTION DELAY
-> MULTI-PART ACTION
V
CHAN 1 TRIGGER RELAY
FOR 3 MEASUREMENTS
NOT WITHIN TOLERANCE
VALIDATE BY OK
V
V
MEASURE MASKING ACTION DELAY
-> MULTI-PART ACTION
V
X2
V
V
V
MULTI-PART ACTION :
-> CHANNEL 1 CHANNEL 2
V
V
V
This page appears only if
you have a PC2003B
(dual channel) device.
Define the number of consecutive measurements outside tolerance after which you want to shutdown the
V
MULTI-PART ACTION :
-> CHANNEL 1 CHANNEL 2
V
X3
Page 11/14
PROPC2003EN – Index A
Page 13
Programming Manual
PC 2003 Amplifier
3.4 Table of the programming modes
This table is a summary of all the menus and the adjustments present in the amplifier.
>MEASURE
OPTIONS PARAMETERS DISPLAYS
>TOLERANCES
REFERENCE STATISTICS
TOLERANCES
>REFERENCE
STATISTICS
TOLERANCES REFERENCE
>STATISTICS
MEASURE
>OPTIONS
PARAMETERS DISPLAYS
>MEASURE MASKING
ACTION DELAY MULTI-PART ACTION
MEASURE MASKING
>ACTION DELAY
MULTI-PART ACTION
MEASURE MASKING ACTION DELAY
>MULTI-PART ACTION
TOLERANCES :
> CHANNEL 1
> CHANNEL 2
REFERENCE :
> CHANNEL 1
> CHANNEL 2
STATISTICS CHOICE
> STANDARD
SAMPLING
STATISTICS CHOICE
STANDARD
>SAMPLING
MEASURE MASKING :
> CHANNEL 1
> CHANNEL 2
ACTION DELAY:
> CHANNEL 1
> CHANNEL 2
MULTI-PART ACTION :
> CHANNEL 1
> CHANNEL 2
Adjusting the tolerance in a range of ± 2mm
REFERENCE ADJUST: CHANNEL 1 OR 2
> MANUAL
AUTOMATIC
REFERENCE ADJUST : CHANNEL 1 OR 2
MANUAL
> AUTOMATIC
STANDARD : Display of the measurement statistics: number of measurement, number of measurement undersized, number of measurement oversized. Reset to zero with OK.
SAMPLING :
- Choice of the number parts samples (1 to 200)
- Measurement in automatic
- Calculation of the mean + min. value and max. value maxi.
INACTIVE disables the function. MEASUREMENT MASKING after 1 to 25 measurements.
Description of the function in subsection 3.1, pages 8
INACTIVE disables the function. Measurement Transfer after 1 to 25 measurements.
Description of the function in subsection 3.2, page 9
INACTIVE disables the function. Machine Shutdown after 1 to 25 measurements.
Description of the function in subsection 3.3, page 11
English
Calibrating the reference value on a part between
0.300 and 0.400mm
-Calibrating the reference value from 0.300 to 0.4000 mm in manual.
- Choice of number of samples (1 to 25).
- Measurement in automatic
- Calculation of the mean
Page 12/14
PROPC2003EN – Index A
Page 14
Programming Manual
PC 2003 Amplifier
MEASURE OPTIONS
>PARAMETERS
DISPLAYS
MEASURE OPTIONS
>PARAMETERS
DISPLAYS
>SENSOR PARAMETERS
ADDITIONNAL DATA PROGRAM SETTINGS ADMIN
SENSOR PARAMETERS
>ADDITIONNAL DATA
PROGRAM SETTINGS ADMIN
SENSOR PARAMETERS ADDITONNAL DATA
>PROGRAM SETTINGS
ADMIN
SENSOR PARAMETERS ADDITIONNAL DATA
>PROGRAM SETTINGS
ADMIN
English
>TARE
MEAS. ARM CORRECT. TOLERANCES MODE MEASUREMENT MODE
TARE
>MEAS.ARM CORRECT.
TOLERANCES MODE MEASUREMENT MODE
TARE MEAS.ARM CORRECT.
>TOLERANCES MODE
MEASUREMENT MODE
TARE MEAS.ARM CORRECT. TOLERANCES MODE
>MEASUREMENT MODE
TARE :
> CHANNEL 1
> CHANNEL 2
Adjustment of the tare of the sensor in the probe. (See Integration an
mechanical adjustment for gauge)
This parameter is used only for the length gauges L00A and L00B. It allows to correct the ratio of the measuring arm.
TOLERANCES MODE :
INTERVALS
VALIDATE BY OK
NUMBER OF SENSORS
ONE
VALIDATE BY OK
Allows to choose the display mode of tolerances : INTERVALS : Ex : +0.05 / -0.05 LIMITS : 5.95/6.05 Allow to select the number of sensor: ONE, TWO
INDEPENDENT, TWO COUPLED and HIRTH.
Then select the measurement mode:
PEAK, PEAK CONTROLLED or STABILIZED.
Extended data are released via 4 digits (release code), allowing additional data to be obtained at the output of the RS232 link exploited and analyzed by a specific software. speed of the serial link : 9.6 Kbauds parity of the serial link : NONE
>CONFIGURATION
GOOD MEASUREMENT MI/MA MEASUREMENT
Configuration of the logical outputs : INACTIVE 60S: As soon as you enter the programming mode, measurements are no longer taken. After 60 seconds without any manipulation of the keypad, the measurement mode is returned to and therefore measurements are again taken. INACTIVE INF: the same as for adjustment INACTIVE 60S; but without automatically return to measure mode. ACTIVE 60S: Your entry in the programming mode doesn’t stop measurements as in adjustment INACTIVE. After 60 seconds without any manipulation on the keypad, there is an automatic exit from the programming mode ACTIVE INF: the same as for adjustment ACTIVE 60S; but without automatically return to measure mode.
CONFIGURATION
>GOOD MEASUREMENT
MI/MA MEASUREMENT
Memorization of the output good measurement: STORED: When a part is good, the output relay “good” closes and stays closed until the next valid signal. The state of the output is stored. NOT STORED: When a part is good, the output relay “good” closes for 50ms minimum and then reopens. The state of the output is not stored.
(adjustment by default)
Page 13/14
PROPC2003EN – Index A
Page 15
Programming Manual
PC 2003 Amplifier
English
MEASURE OPTIONS
>PARAMETERS
DISPLAYS
SENSOR PARAMETERS SERIAL PORT
>PROGRAM SETTINGS
ADMIN
CONFIGURATION GOOD MEASUREMENT
>MI/MA MEASUREMENT
Memorization of the outputs min. and max.: STORED: When a part is bad min. or max., the outputs close (or open if Normally Closed) and stay close until the next valid signal. The state of the output is stored. (adjustment by default) NOT STORED: When a part is bad, the outputs min. or max. close 50ms minimum and reopen.
SENSOR PARAMETERS SERIAL PORT PROGRAM SETTINGS
>ADMIN
>LOCK
UNLOCK CODE CHANGE FACTORY VALUES
LOCK
>UNLOCK
CODE CHANGE FACTORY VALUES
LOCK UNLOCK
The state of the outputs is not stored.
This function allows locking all the adjustments (preload, reference, tolerances, etc) made, leaving only the display to the user. The original code is
0000. This function allows unlocking all the adjustments (preload, reference, tolerances, etc.).
Change the original code (0000) by the code you want.
>CODE CHANGE
FACTORY VALUES LOCK
UNLOCK CODE CHANGE
>FACTORY VALUES
PART SETUP OPTIONS PARAMETERS
>DISPLAYS
>BRIGHT./CONTRAST
LANGUAGE MEASUREMENT UNIT
BRIGHT./CONTRAST
>LANGUAGE
MEASUREMENT UNIT BRIGHT./CONTRAST
LANGUAGE
>MEASUREMENT UNIT
Adjust the brightness of the LCD screen. Minimum 0 and maximum 15. NB : After the factory values are returned to, the value will be 8
Adjust the contrast of the LCD screen. Minimum 0 and maximum 15. NB : After the factory values are returned to, the value will be 8
Select the language, Français, English, Italiano, Espagnol and Deutsch NB : After the factory values are returned to, the value will be French.
Select the measurement unit, Millimeter or Inch. NB : After the factory values are returned to, the value will be MILLIMETER In mm: 3 digits are displayed before the decimal point + 3 digits after the
Return to the box’s original parameter. Warning: This will force you to redo the preload, referencing and adjustment of the tolerances.
decimal point. Maximum 999.999mm In Inch: 2 digits are displayed before the decimal point + 4 digits after the decimal point. Maximum 21.4747in
: Screens appear only if you have a PC2003 DUAL CHANNEL device.
Page 14/14
PROPC2003EN – Index A
Page 16
www.detector
france.com