Detection Systems DS7436 Installation Instructions Manual

Installation Instructions
for the
DS7436 Multiplex Expansion Module
1.0 General Information
The DS7436 is a two-loop Multiplex Expansion Module for use with the DS7400(Xi) Series Control/Communicator. It connects directly to the DS7400(Xi) and provides a two-wire multiplex bus for the connection of up to 120 remote points. Each bus is isolated to so that failure in one bus will not cause failure in the other.
Current Draw: 130 mA-H Standby or Alarm.
Outputs: DC Bus A = 200 mA Mux Bus A = 75 mA DC Bus B = 200 mA Mux Bus B = 75 mA
2.0 Installation
Failure to follow the mounting instructions in this manual may result in damage to the DS7400(Xi) Control Panel.
The DS7436 and DS7400(Xi) contain static-
CAUTION
sensitive components and must be handled with care. Follow anti-static procedures when handling the modules.
NOTE: Loops A and B may be used for fire and intrusion
zones. Loop A is recommended for burglary. Loop B is recommended for fire. Only Loop A may be used to program the multiplex addresses. Disconnect Loop B units prior to programming units on Loop A.
4.0 Program Jumper
The DS7436 is shipped with the program jumper in the Disable position. To enable programming, move the jumper so that it shorts the middle and bottom pins.
After programming the multiplex points, the
PROGRAM [] DISABLE
[] ENABLE
jumper must be moved back to the Disable position.
NOTE: The DS7436 MUST have a jumper installed at all times.
DS7436
PROGRAM [] DISABLE
[] ENABLE
+
+
BUS APWR A
+
+
BUS BPWR B
Install the DS7436 board prior to installing the DS7400(Xi)
board in the control enclosure. If the DS7400(Xi) board is already installed in the control enclosure, remove the DS7400(Xi) board at this time.
Place the DS7400(Xi) board on a flat surface with the
component side of the board facing up.
Install the four plastic standoffs in the holes provided in the
DS7400(Xi) board. Avoid bending or flexing the DS7400(Xi) board when inserting the standoffs. Be sure the standoff tabs are aligned so that they do not touch any components on the module. Be sure that the stand-offs are firmly pressed into the board so that the “ears” can expand out. See drawings.
Install the DS7436 board onto the standoffs, noting that the
connector pins from the DS7400(Xi) are properly aligned to install into the connector on the DS7436. Avoid bending or flexing the boards while pressing them onto the standoffs.
The DS7400(Xi) control board may be installed in the control
panel enclosure at this time.
3.0 Wiring
Connect the multiplex loop to the DS7436 as shown. Up to 2000 feet (610 m) of #22 AWG (0.8 mm) or 5000 feet (1525 m) of #18 AWG (1.0 mm) wire may be used. Do NOT use shielded cable.
The Bus Power output is for connection of separately-powered multiplex devices such as the DS7432 8-Input Remote Module. If using separate powered detectors, they should be powered from the auxiliary power terminals of the DS7400(Xi). The DS7432 may also be powered from the auxiliary terminals.
Stand-off “Ears”
Printed Circuit Board (PCB)
Stand-off
Be sure that the Stand-off is pressed firmly
through the Printed Circuit Board, so that
the Stand-off ears can expand outward.
A/C Power Indication LED
1
2 3
A C
4
5
A
6
7
+
8
R
O P
B
T
I
G
O N
Y
9 10 1 12 13 14 15 16
R B G Y G B S R
Install DS7436 Here
Expansion Port
171819 20 21 22 23 24 25 26 27 28 29 30
PO1 PO21–LP+
(supervised)
Power Bus
+
+
Stand-Offs (4)
DS7400(Xi)
2– 3– 5– 6 – 7– 8–4–LP+ LP+ LP+
Detection Systems, Inc.
Copyright © 2001 Detection Systems, Inc
DS7436 Installation Instructions
(585) 223-4060 • (888) 289-0096 • Fax: (585) 223-9180 P/N: 36319C 12/01
130 Perinton Parkway, Fairport, New York, USA 14450-9199
Loading...