Detcon 1610A-FB User Manual

Page 1
detcon inc.
Gas Detection System
Operators Instruction Manual
Document #889, September 14, 1999, Revision 1.0
C
C
C
C
C
C
C
C
C
C
C
C
C
MODEL 10A
H2S MONITOR
HOUSTON, TEXAS
K
K
K
K
K
K
K
K
K
K
O
O
O
O
O
O
O
L
L
L
L
MODEL 10A
H2S MONITOR
HOUSTON, TEXAS
L
MODEL 10A
MODEL 10A
H2S MONITOR
H2S MONITOR
ppm
ppm
ppm
HIGH
HIGH
HIGH
LOW
LOW
LOW
FAULT
FAULT
FAULT
ALARM
ALARM
ALARM
RESET
RESET
RESET
detcon inc.
detcon inc.
detcon inc.
HOUSTON, TEXAS
HOUSTON, TEXAS
MODEL 10A
H2S MONITOR
ppm
ppm
HIGH
HIGH
LOW
LOW
FAULT
FAULT
ALARM
ALARM
RESET
RESET
detcon inc.
detcon inc.
HOUSTON, TEXAS
POWER
L
L
MODEL 10A
MODEL 10A
MODEL 10A
H2S MONITOR
H2S MONITOR
H2S MONITOR
ppm
ppm
HIGH
HIGH
LOW
LOW
FAULT
FAULT
ALARM
ALARM
RESET
RESET
detcon inc.
detcon inc.
detcon inc.
HOUSTON, TEXAS
HOUSTON, TEXAS
HOUSTON, TEXAS
AMBIENT AIR MONITOR
3AMP 10 AMP
O
L
ppm
HIGH LOW FAULT
ALARM RESET
MODEL 1610AFB
detcon inc.
HOUSTON, TEXAS
MODEL 10A
H2S MONITOR
HOUSTON, TEXAS
K
O
O
O
L
L
L
MODEL 10A
MODEL 10A
H2S MONITOR
H2S MONITOR
ppm
ppm
ppm
HIGH
HIGH
HIGH
LOW
LOW
LOW
FAULT
FAULT
FAULT
ALARM
ALARM
ALARM
RESET
RESET
RESET
detcon inc.
detcon inc.
detcon inc.
HOUSTON, TEXAS
HOUSTON, TEXAS
MODEL 10A
H2S MONITOR
HOUSTON, TEXAS
ALARM DISABLE
C
K
K
K
O
O
O
MODEL 10A
H2S MONITOR
HOUSTON, TEXAS
O
L
L
L
MODEL 10A
MODEL 10A
H2S MONITOR
H2S MONITOR
ppm
ppm
ppm
HIGH
HIGH
HIGH
LOW
LOW
LOW
FAULT
FAULT
FAULT
ALARM
ALARM
RESET
RESET
detcon inc.
detcon inc.
detcon inc.
HOUSTON, TEXAS
HOUSTON, TEXAS
L
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
C
C
K
K
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM
ALARM
RESET
RESET
detcon inc.
HOUSTON, TEXAS
❏ 1.0 INTRODUCTION
Detcon Model 1610AFB gas detection system consists of 3 major assemblies:
1. The NEMA 4 fiberglass control enclosure.
2. The single channel digital control modules.
3. The remote mount gas sensor assemblies. The NEMA 4 fiberglass control enclosure is detailed in section 1.0 of the manual, the control modules in section 2.0 and applicable sensor assemblies in section 3.0.
Page 2
❏ 1.1 DESCRIPTION
Detcon Model 1610A-FB control enclosure is a NEMA 4X molded fiberglass case with hinged, gasketed door and is designed for surface mounting in both indoor and outdoor locations. An unbreakable glass view window is mounted in the door. The NEMA 4X rating is by definition raintight and therefore suitable for outdoor location in electrically non-hazardous environments. The control enclosure houses the mainframe hardware compatible with Detcon Model Series 10A digital electronic controls. Model 1610A-FB system capacity is up to 10 channels consisting of remote mounted area sensors and single channel electronic controls (Detcon Model 10A). The system is powered by AC line power and/or 24 VDC unless otherwise specified at time of order. The control enclosure includes, as standard operating controls (DWG #886.27A); a power on/off
switch, an alarm disable switch and a line power fuse. Discreet output terminal strips located on the controller mother board are provided for sensor terminations, Form C dry contact alarm outputs, 4-20ma outputs for remote recording devices, AC power in, DC power in, remote reset as well as relay logic and power terminations for the multiple alarm relay circuit. Form C relay outputs may be discreet, zoned or common by gold plated jumper tabs located on the controller mother board. Form C dry contacts; common, normally open and normally closed, are provided for 3 alarms; High, Low and Fault. Contacts are rated at .6 amp @125 VAC / 2 amp @ 30 VDC. When used in conjunction with the multiple alarm relay circuit (part #5026), contacts are rated 8 amp @ 117 VAC / 5 amp @ 30 VDC.
❏ 1.2 MUTIPLE ALARM RELAY CIRCUIT
A multiple alarm relay circuit (DWG #377.01A) mounted on the controller mother board is provided with each Detcon Model 1610A-FB. Mounting provisions for an additional alarm circuit are also provided. The alarm circuit consists of 4 interposing relays (contacts are rated 8 amp @ 117 VAC / 5 amp @ 30 VDC) with 24VDC coils as standard. Other coil voltage ratings must be specified at time of order. The alarm circuit can be configured to output Form C dry contacts (common, normally open and normally closed), AC power or DC power. A 5 amp microfuse is provided for each relay and is configured in series with the common pole of its respective relay. This configuration is functional regardless of whether Form C dry contacts, AC power or DC power outputs are used. An In/Out termination is provided for applying AC or DC power into any one of the interposing relays. A gold plated jumper tab is used to apply the in/out power option to its corresponding relay, thus the 4 relays may be used in a combination of Form C dry contacts and VDC outputs or Form C contacts and VAC outputs. The terminations labled "Alarm Coil Power" located to the left of the alarm circuit are used only
for coil power. The "+" termination may be used to provide for various relay logic through the Form C dry contacts of each individual Model 10A channel located on the controller mother board directly above the alarm circuit card. The "-" termination should be wired into the common termination (shown by a common symbol) located on the left of the alarm circuit board. The terminations labled "Alarm Power" located to the far left of the unit are used for providing power to the In/Out termination on the alarm circuit card. As can be seen in the 1610A-FB schematic / wiring diagram (DWG #888.01A), the alarm power terminations for AC come directly from the AC input terminals located above on the controller mother board. The same is true of the DC power terminations. Note: DC power used to drive alarms must be obtained through a remote DC power source. The remote DC power source should be terminated to the terminals labled "DC IN" located on the controller mother board. The "DC IN" terminations function as both an alternative DC source used to power the 1610A-FB as well as provide power for DC alarms. The 1610A-FB power supply is not capable of providing power for alarm devices.
❏ 1.3 ALARM DISABLE
The alarm disable switch, located on the front panel, operates by removing DC common from the "Alarm Coil Power" terminals. Disabling of alarms
Detcon Model 1610A-FB Gas Detection System PG.2
does not inhibit any function of the Model 10A digital control module. The digital display, alarm LED's and on board alarm relays remain active.
Page 3
❏ 1.4 REMOTE RESET
A remote mounted normally open momentary switch may be used to reset all Model 10A controllers. The reset function is effective when the Model 10A's respective alarms have been
❏ 1.5 INSTALLATION
Step 1. Securely mount the 1610A-FB enclosure in accordance with detail drawing NO. 887.26A. Step 2. Connect 117 VAC input wiring to the lugless terminal strip (labled AC IN) on the controller mother board as detailed in drawing No.
886.27A. Line power current load is maximum 2 amps. (Note: a jumper selectable plug located on the power supply may be used to allow for 220 VAC input.) Step 3. Connect the 24 VDC standby battery to the lugless terminal strip (labled DC IN) on the controller mother board as detailed in drawing NO.
886.27A. The DC current load is a maximum 3 amps. Caution: Observe correct polarity when terminating all input / output field wiring. Failure to
programmed in the latching position and alarm conditions have passed. Each Model 10A controller has its own alarm reset switch which is discussed further in section 2.0.
do so may result in circuit damage on power up. Step 4. If applicable, connect a normally open momentary remote mounted switch to the lugless terminal strip (labeled RESET) located on the controller mother board as detailed in drawing NO.
886.27A. Step 4. Refer to installation and wiring detail of remote mount sensor assemblies as detailed in section 3.0. Terminate field wiring from sensors to Model 1610A-FB lugless terminal strips located on the controller mother board as shown in drawing NO. 886.27A. Note: Based on the application and use of relay contact outputs, complete all wiring terminations prior to application of power. Shut-in controls may be omitted until system test is complete.
❏ 1.6 START-UP
Upon completion of all field wiring: Depress the power switch on the controller assembly front panel. Note that each Model 10A controller digital display illuminates. Varying
❏ 1.7 POWER SUPPLY
The power supply on the 1610A-FB may be changed from 110 VAC to 220 VAC input if available power should warrant the change. The procedure does not necessarily require the removal of the power supply, however, if it is the first time it is done by a given operator or if the control enclosure is already wired in (making removal of the mainframe assembly from the weatherproof enlosure difficult) it is advisable that the power supply be removed. The actual procedure is as simple as moving the plug selectable wire from the 110V terminal to the 220V terminal located on the power supply printed circuit board. The wire is labled W1 on the power supply PCB and the terminals are labled 110V and 220v respectively.
readings may occur during sensor warm-up. A 10 second alarm delay will occur on power up. Refer to section 3.0 for additional sensor start-up detail.
(1) Remove the power supply (unless experienced in the procedure) according to the instructions listed below. (2) Remove the wire (W1) from the 110V terminal and plug it into the 220V terminal. The 1010A-FB is modularly designed so as to avoid unnecessary down time in the event of component failure. In the event of a power supply failure, the power supply may be removed without disconnecting field wiring. To remove and replace the power supply: (1) Remove the Model 10A control modules. (2) Remove the 4 screws from the front panel and expose the power supply. (3) Disconnect the 5 pin plug on the left of the power supply.
Detcon Model 1610A-FB Gas Detection System PG.3
Page 4
(4) Disconnect the 2 pin plug on the right of the power supply. (5) Remove the 3 screws from the bracket that holds the power supply to the controller mother board. (6) Lift the power supply out of the enclosure and remove the five wires from the two terminal strips located on the power supply.
❏ 1.8 WARRANTY
(7) Replace by reversing the above steps. Note: Be sure to re-connect the wires properly. Connect AC to the 3 pin terminal strip; Pin 3 = GROUND, Pin 2 = L1, Pin 1 = L2. Connect DC to the Stand up terminals (+ is red; - is black); Pin numbers are screened on the power supply PCB.
Detcon inc., as manufacturer, warrants under intended normal use each new Model 1610A-FB control enclosure to be free from defects in material and workmanship for a period of one year
from the date of shipment to the original purchaser. All warranties and service policies are FOB the Detcon Inc. facility located in the Woodlands, Texas.
❏ 1.9 SPARE PARTS
PART # DESCRIPTION 5026 Multiple alarm relay circuit 3622 250 watt, 24 vdc switcher power supply 0224 Gold plated jumper tab 2812 28 vdc lamp for power and disable switch 0295 5 amp micro fuse 0301 4 amp 3AG fuse 3218 Power switch 3218 Disable switch 2806 Green switch cap 2807 Red switch cap 3280 Fuse holder
Mailing address: P.O. Box 8067, The Woodlands, Texas 77387-8067 ❏ Phone: (281) 367-4100 ❏ Fax: (281) 292-2860
Shipping address: 3200 A-1 Research Forest Dr., The Woodlands, TX 77381
Page 5
MODEL 1610A-FB
GND
+DC
COM
GND
+
L1
L2
L1
L2
DC IN
RESET
AC IN
ALARM LOGIC
C
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
+
MANCNOCNONCCNONCC
SENSOR
FAULTHIGHLOW
+
4-20MA
K
ALARM
COIL
POWER
C
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
+DC
COM
POWER 4 AMP ALARM
HOUSTON TEXAS
C
C
C
ALARM RESET
C
K
K
O
O
L
L
MODEL 10A
MODEL 10A
H2S MONITOR
H2S MONITOR
ppm
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
detcon inc.
HOUSTON, TEXAS
K
K
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
K
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
detcon inc.
HOUSTON, TEXAS
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
INTERPOSING
RELAY CARD
HIGH LOW FAULT
C
ALARM RESET
detcon inc.
C
K
K
O
O
L
L
MODEL 10A
MODEL 10A
H2S MONITOR
H2S MONITOR
ppm
ppm
HIGH
HIGH
LOW
LOW
FAULT
FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
detcon inc.
HOUSTON, TEXAS
OPTIONAL
INTERPOSING
RELAY CARD
C
ALARM RESET
DISABLE
C
C
C
C
C
C
ALARM RESET
C
K
K
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
K
K
K
K
K
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
ALARM RESET
detcon inc.
HOUSTON, TEXAS
K
O
L
MODEL 10A
H2S MONITOR
ppm
HIGH LOW FAULT
detcon inc.
HOUSTON, TEXAS
detcon inc.
MATERIAL
TITLE
DRN BY
FINISH
1610AFB CONTROLLER TERMINALS
TED S.
SCALE
SHEET OF
APPROVED BY
STOCK #
DRAWING NUMBER
DATE
7-18-91
STATUS
886.27A
REV #
0
Page 6
10.25
887.26A
8-4-97
14
DRAWING NUMBER
TITLE
20.25
1610A-FB DIMENSIONS / MOUNTING DETAIL
REFERENCE
DATE
APPROVED BY
SCALE
SHEET OF
0
TED S.
DRN BY
REVISION
MOUNTING HOLE - .44 DIA.
23.07
21.81
detcon inc.
MATERIAL
Page 7
#4
IN / OUT
COM
N.C.
N.O.
#3
COM
N.C.
N.O.
#2
COM
N.C.
N.O.
#1
COM
N.C.
N.O.
39-6-89
REV #
377.01A
#4 #3 #2 #1
I/O JUMPERS
5 AMP MICRO FUSE
#4
#3
#2
#1
DRAWING NUMBER
TITLE
STATUS
DATE
STOCK #
APPROVED BY
SCALE
SHEET OF
TED S.
MULTIPLE ALARM RELAY CIRCUIT
DRN BY
FINISH
5026
detcon inc.
MATERIAL
32 1
TOP VIEW RELAY
NO NC C
45
COIL #4
COIL #3
COIL #2
COIL #1
COMMON
Page 8
16 GA.-BLK-9"
16 GA.-RED-9"
TO PS COM
TO PS +
TO PS GND
TO PS L2
TO PS L1
16 GA.-GRN
16 GA.-WHT
16 GA.-BLK
16 GA.-BLK
2 AMP
16 GA.-BLK
COMMON
+OUT
DISABLE
DC IN
RESET
AC IN
L1
+IN
+
L1
L2
GND
+DC
COM
L1
L2
GND
16 GA.-BLK
16 GA.-BLK
16 GA.-RED
16 GA.-RED
16 GA.-BLK
ALARM
COIL
POWER
+DC
COM
ALARM
POWER
SWITCH PCB
COMMON BUS
RESET BUS + POWER BUS
DISABLE
TYP. MODEL 10A CONTROLLER TERMINALS
+
MANCNOCNONCCNONCC
SENSOR
FAULTHIGHLOW
+
4-20MA
detcon inc.
MATERIAL
ALARM POWER
TITLE
DRN BY
FINISH
1610AFB WIRING DIAGRAM
SCALE
TED S.
SHEET OF
APPROVED BY
STOCK #
DRAWING NUMBER
DATE
7-18-91
STATUS
888.01A
REV #
0
Loading...