desmon GBF-3GN2/3, GBC-5G, GBF-5G, GBF-5P, GBC-7 Service Manual

...
Service Manual
Blast Chiller
Rev 07/04/2015
2
Blast chiller Service Manual
3
Rev 07/04/2015
Safety Precautions
THIS MANUAL HAS BEEN PREPARED FOR PERSONNEL QUALIFIED TO INSTALL, MAINTAIN AND REPAIR ELECTRICAL REFRIGERATION EQUIPMENT, WHO SHOULD PERFORM THE INITIAL FIELD STARTUP AND ADJUSTMENTS OF THE EQUIPMENT COVERED BY THIS MANUAL.
READ THIS MANUAL THOROUGHLY BEFORE OPERATING, INSTALLING, PERFORMING MAINTENANCE ON, OR REPAIRING THE EQUIPMENT.
WARNING Failure to follow all the instructions in this manual can cause
property damage, injury or death.
WARNING Improper installation, adjustment, alteration, service or maintenance
can cause property damage, injury or death.
WARNING Electrical connections should be performed only by a certified professional. Electrical and grounding connections must comply with the applicable portions of the National Electric Code and/or all local electric codes. Failure to comply with this procedure can cause property damage, injury or death.
WARNING Before connecting the unit to the electrical supply, verify that the electrical and grounding connections comply with the applicable portions of the National Electric Code and/or other local electrical codes. Failure to comply with this procedure can cause property damage, injury or death.
WARNING Before connecting the unit to the electrical supply, verify that the electrical connection agrees with the specifications on the data plate. Failure to comply with this procedure can cause property damage, injury or death.
WARNING Appliance must be connected to a grounded, metal, permanent wiring system. Or an equipment-grounding conductor must be run with the circuit conductors and connected to the equipment-grounding terminal or lead on the appliance. Failure to comply with this procedure can cause property damage, injury or death.
WARNING Appliances equipped with a flexible electric supply cord, are provided with a three-prong grounding plug. It is imperative that this plug be connected into a properly grounded three-prong receptacle. Failure to comply with this procedure can cause property damage, injury or death.
WARNING If the receptacle is not the proper grounding type, contact an electrician. Do not remove the grounding prong from the plug. Failure to comply with this procedure can cause property damage, injury or death.
WARNING Before performing any service that involves electrical connection or disconnection and/or exposure to electrical components, always perform the
Rev 07/04/2015
4
Blast chiller Service Manual
Electrical LOCKOUT/TAGOUT Procedure. Disconnect all circuits. Failure to comply with this procedure can cause property damage, injury or death.
WARNING Before removing any sheet metal panels, always perform the Electrical LOCKOUT/TAGOUT Procedure. Be sure all circuits are disconnected. Failure to comply with this procedure can cause property damage, injury or death.
WARNING Do not operate this equipment without properly placing and securing all covers and access panels. Failure to comply with this procedure can cause property damage, injury or death.
WARNING Do not use or store gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance. Failure to comply can cause property damage, injury or death.
WARNING In the event of a power failure, do not attempt to operate this appliance. Failure to comply can cause property damage, injury or death.
General Safety
WARNING Desmon accepts no responsibility for any situation resulting from work carried out in an unprofessional manner, or from the incorrect interpretation or application of regulations.
General Installation
WARNING Incorrect installation or any modifications made to the appliance may damage property or result in injury or death.
Electrical
WARNING Electrical connections or any work required on the electrical circuits inside the appliance must be performed by certified technicians in compliance with local, state, and federal regulations.
WARNING Make sure all facility electrical connections are in compliance with all local and federal electrical code regulations.
Inspection and Maintenance
WARNING Appliance maintenance must be carried out by only by suitably trained personnel.
WARNING Before any maintenance work is performed, the appliance must be disconnected from the electrical supply. Apply a lockout tag to the electrical supply connection.
WARNING All replacement parts that are not supplied by Desmon must be pre­approved before installation.
5
Rev 07/04/2015
Repair Work Safety
WARNING Repair work must only be performed by Desmon’s approved distributors or one of its authorized representatives. Desmon accepts no responsibility for any situation resulting from work performed by untrained and/or unauthorized technicians.
ELECTRICAL LOCKOUT/TAGOUT PROCEDURE
WARNING Before performing any service that involves electrical connection or disconnection and/or exposure to electrical components, always follow the Electrical LOCKOUT/TAGOUT Procedure. Disconnect all circuits. Failure to comply can cause property damage, injury or death.
The Electrical LOCKOUT/TAGOUT Procedure is used to protect personnel working on an electrical appliance. Before performing any maintenance or service that requires exposure to electrical components, follow these steps:
1. In electrical box, place appliance circuit breaker into OFF position.
2. Place a lock or other device on electrical box cover to prevent someone from placing circuit breaker ON.
3. Place a tag on electrical box cover to indicate that appliance has been disconnected for service and power should not be restored until tag is removed by maintenance personnel.
4. Disconnect appliance power cord from electrical outlet.
5. Place a tag on the cord to indicate that unit has been disconnected for service and power should not be restored until tag is removed by maintenance personnel.
Rev 07/04/2015
6
TABLE OF CONTENTS
Blast chiller Service Manual
1. BASIC SERVICE DIAGNOSTIC (STANDARD CONTROLLER) ............................................................ 9
1.1. ALARM/FAILURE LIST ....................................................................................... 10
1.2. FAILURE CODE DETAILS .................................................................................. 11
1.3. SERVICE MENU – CONFIGURATION PARAMETER ........................................ 11
1.3.1 Entering the configuration parameter ........................................................................................ 11
1.3.2 Parameter list (factory setting) ................................................................................................... 11
1.3.3 Temperature Probes Display ..................................................................................................... 28
2. BASIC SERVICE DIAGNOSTIC (TOUCH SCREEN CONTROLLER) .................................................. 33
2.1. ALARM/FAILURE LIST ....................................................................................... 34
2.2. FAILURE CODE DETAILS .................................................................................. 36
2.3. SERVICE MENU – CONFIGURATION PARAMETERS ...................................... 37
2.3.1 Entering the configuration parameter ........................................................................................ 37
2.3.2 Parameter list (factory settings) ................................................................................................... 1
2.3.3 Temperature Probes Display ....................................................................................................... 5
3. TROUBLESHOOTING ............................................................................................................................. 7
3.1. PROBES ............................................................................................................... 7
3.1.1. Checking the Probes ............................................................................................. 8
3.1.2. NTC (10kOhms@25°C/77°F) Diagram .................................................................. 9
3.1.3. NTC (10kOhms@25°C/77°F) Chart Table........................................................... 11
3.1.4. Pt1000 (1kOhms@0°C/32°F) Diagram ................................................................ 12
3.1.5. Pt1000 (1kOhms@0°C/32°F) Chart Table........................................................... 12
3.2. DOOR SWITCH ................................................................................................... 13
3.2.1 Checking the door switch ........................................................................................................... 13
3.3. PRESSURE SWITCH .......................................................................................... 14
3.3.1 Pressure Switch Working Principles – Alarm Connection ......................................................... 14
3.3.2 Pressure Switch Working Principles – Pump Down .................................................................. 15
3.3.3 Pressure Switch Factory Setting ................................................................................................ 15
3.4. DOOR FRAME HEATER ..................................................................................... 15
3.4.1 Heater cable features ................................................................................................................. 16
3.5. MAIN BOARD – STANDARD CONTROLLER ..................................................... 16
3.5.1 Checking Relay Outputs ............................................................................................................ 16
3.6. KEYPAD – STANDARD CONTROLLER ............................................................. 18
3.6.1 Keypad Troubleshooting ............................................................................................................ 18
3.7. MAIN BOARD – TOUCH SCREEN CONTROLLER ............................................ 18
3.7.1 Checking Relay Outputs ............................................................................................................ 19
3.8. DISPLAY – TOUCH SCREEN VERSION ............................................................ 22
3.8.1 Touch Screen Display Troubleshooting ..................................................................................... 22
3.9. REFRIGERANT PRESSURES CHECKS ............................................................ 23
4 SERVICE AND REPAIR ......................................................................................................................... 24
4.1 REMOVE THE FRONT PANEL ........................................................................... 24
4.1.1. Units from 5 to 18 shelves ................................................................................... 24
4.1.2 GBF-GN2/3 (smallest self-contained unit) ................................................................................. 25
4.1.3 Latest version of self-contained (5 to 18 pans) Effective June 2014 .............................. 26
4.2. REVERSING THE DOOR SWING (ONLY NON TOUCH SCREEN) ................... 27
4.3. ACCESSING THE CONDENSING UNIT ............................................................. 32
4.3.1 Unit from 5 to 18 shelves ........................................................................................................... 32
4.3.2 5 shelves units ........................................................................................................................... 37
7
Rev 07/04/2015
4.3.3 GBF-3GN2/3 (smallest self-contained unit) ............................................................................... 38
4.3.4 Remote units, units GBF20GN2/1, GBF40GN2/1,GBF20GN1/1 .............................................. 39
4.4. HOW TO ACCESS EVAPORATOR ASSEMBLY ................................................ 39
4.4.1 Evaporator Assembly Description .............................................................................................. 39
4.4.2 Accessing the Evaporator .......................................................................................................... 41
4.4.3 Replacing the Temperature Sensing Probes ............................................................................. 41
4.5. REPLACING THE EVAPORATOR FAN .............................................................. 44
4.6. REPLACING THE DOOR SWITCH ..................................................................... 44
4.6.1 GBF-3GN2/3 (smallest self-contained unit) ............................................................................... 44
4.6.2 Units from 5 up to 18 shelves ................................................................................................... 44
4.7 REPLACING THE PRESSURE SWITCH ............................................................ 45
4.8 REPLACING THE DOOR FRAME HEATER ....................................................... 46
4.9 REPLACING THE RELAY BOARD ..................................................................... 47
4.10 REPLACING THE KEYPAD ................................................................................ 48
5 VACUUM AND CHARGE PROCEDURE ............................................................................................... 49
5.1 VACUUM AND CHARGING INSTRUCTION ....................................................... 49
5.1.1 Self Contained Models ............................................................................................................... 49
5.1.2 Remote Models .......................................................................................................................... 50
5.1.3 Vacuum and Charging Recommendations ................................................................................ 50
6 SCHEMATICS ........................................................................................................................................ 51
6.1 SCHEME OF COMPONENTS ............................................................................. 51
6.2 AIRFLOW REQUIREMENTS .............................................................................. 52
6.2.1 Self Contained - Airflow Requirements ................................................................ 52
6.2.2 Remote - Airflow Requirements ........................................................................... 53
6.3 CONNECTION OF REMOTE CABINET TO “NON-DESMON” CONDENSING UNIT 55
6.3.1 Connection with existing refrigerant lines ............................................................ 55
6.3.2 Hook the electrical power to the unit .................................................................... 56
I. HOW TO READ THE MODEL NUMBER ............................................................................................... 58
II. DATA CHART TABLE ........................................................................................................................... 59
Rev 07/04/2015
8
Blast chiller Service Manual
1. Basic Service Diagnostic (Standard Controller)
The Controller will display alarms and failure codes that will assist in identifying the cause of a problem and direct attention to the components and circuits involved. In addition, a diagnostic service menu allows technicians to quickly check the temperature sensors, such as the needle probe, the chamber probe or the evaporator probe.
9
Rev 07/04/2015
1.1. ALARM/FAILURE LIST
CODE
CAUSE
CONSEQUENCE
Tab 1
Er0 ROOM PROBE FAILURE Does not allow unit to cycle. If running,
cycle will stop.
Er1 EVAPORATOR PROBE FAILURE During storage cycle, evaporator fans
do not run.
Er3 NEEDLE PROBE FAILURE Does not allow a needle probe set
temperature cycle to run. Unit will stop if running on needle probe set temperature cycle.
HP HIGH DISCHARGE PRESSURE (OR
LOW SUCTION PRESSURE)1
d-r DOOR IS OPEN FOR MORE THAN
P39
AH HIGHT ROOM TEMPERATURE None AL LOW ROOM TEMPERATURE None Err MOTHER BOARD-KEYBOARD
CONNECTION FAILURE 2
Res POWER FAILURE DURING
RUNNING OF CYCLE
1
The pressure switch in this model series provides a single output, open or closed. The circuit is normally open and will close when either the High or Low Pressure limits are reached. In effect, the failure code, HP, could mean either high discharge pressure as well as low suction pressure.
2
Additional troubleshooting at the Key Pad – Control Module connections:
No Ground connection – Display flashes and/or dims No Negative (-) connection – Display may work normally without failure code No Positive (+) connection – Failure Code Error is displayed No 12V connection – Display will not light up.
Unit will not operate in any cycle. If running, compressor, evaporator and condenser fans will stop. Compressor and condenser fan will stop. Evaporator fan will cycle according to P37
None Cycle will restart when power is
restored. Message will flash to indicate cycle has restarted.
Rev 07/04/2015
10
FAILURE CODE DETAILS
The HACCP feature provides the ability to get additional information such as
failure code, date of occurrence, min/max temperature (if applicable), and
To access previous failure codes, press and hold
the PROGRAM key for 5 seconds.
Use the UP and DOWN arrow keys to scroll
SERVICE MENU
configurat
The service menu can be accessed only during OFF mode.
for 5 seconds to enter the menu.
controller doesn’t need actually any password to
the up arrow key the parameter list can be accessed directly
the parameter by pressing Up/do
Change the value by up/down keys. Pr
ist
The following table shows parameter factory settings for both Blast
Selecting a freezing cycle on a GBC unit
(Cabinet at 0°C, needle probe end cycle temperature at 3°C)
Blast ch
through the previous failure codes. Press the
PARAMETER
will be shown as first
configure the parameters. By pressing
(first parameter is P0).
parameter by pressing
to save and go back to the list.
will run a normal chilling cycle
iller Service Manual
1.2.
duration of alarm condition.
PROGRAM key to exit.
1.3.
1.3.1 Entering the
Press the up/down keys
together
– CONFIGURATION
ion parameter
Label PA (password)
. The
1.3.2 Parameter l
and Shock Freezers (GBF).
NOTE:
wn keys. Select a
ess again time key
(factory setting)
the time key
chillers units (GBC)
Scroll
11
Rev 07/04/2015
GBF-3GN2/3 and all GBF Trolley Units (Cycle Off Defrost)
Parameter
Description
Factory Value
P0 unit of temperature measurement
1 0 = °F 1 = °C
P1 cabinet probe offset 0 P2 evaporator probe offset 0 P3 needle probe offset 0 P4 operational setpoint during the second hard chill step; also,
0 operational setpoint during normal chilling (with reference to the cabinet probe)
P5 operational setpoint during freezing (with reference to the
-40
cabinet probe)
P6 operational setpoint during the first hard chill step (with
-20
reference to the cabinet probe)
P7 operational setpoint during post-chill storage (with reference to
3 the cabinet probe)
P8 operational setpoint during post-freeze storage (with reference
-20
to the cabinet probe)
P9 P4, P5, P6, P7 and P8 differential 1 P10 set temperature chill end temperature (with reference to the
3 needle probe)
P11 set temperature freeze end temperature (with reference to the
-18
needle probe)
P12 temperature at which the hard chill switches from the first step
20 to the second (with reference to the needle probe)
P13 temperature above which it is not possible to start a set-
99 temperature operational cycle (with reference to the needle probe)
P14 needle probe and the cabinet temperature for verification of
P15 duration of the second test to check correct needle probe
P16 maximum set temperature chill duration; also timed chill
P17 maximum set temperature freeze duration; also timed freeze
P18 first hard timed chill step duration 45 P19 compressor delay from device power on (from restoration of
P20 minimum elapsed time period between two consecutive
P21 minimum compressor shut-down time 0
correct needle probe insertion 0 = the test will not be performed
insertion; see also P14
duration
duration
power)
compressor start-up operations
0
60
90
240
0
0
Rev 07/04/2015
12
Blast chiller Service Manual
Parameter
Description
Factory Value
P22 defrost type
0 = electric (defrost on relay) 1 = hot gas (defrost compressor and relay on) 2 = air (evaporator fan on)
P23 defrost end temperature (with reference to the evaporator
probe)
P24 maximum defrost duration 10 P25 defrost interval during storage; see also P26
0 = intermittent defrosting will never be activated (only the first will be activated)
P26 first defrost delay from start of storage; see also P25 1 P27 defrosting at start of chilling and freezing
1 = YES
P28 drip-drain duration 2 P29 resetting of compressor protections at start of defrosting (only
if P22 = 1) 1 = YES
P30 elapsed time between the defrost request and switching on the
compressor (only if P22 = 1 and providing that the compressor is off when the defrost is requested); see P31 (7) (8)also
2
8
6
0
0
30
P31 elapsed time between the defrost request and activation of the
solenoid valve (only if P22 = 1 and on condition that the compressor is off when defrosting is requested); see also P30
P32 temperature above which the evaporator fan is switched off
during storage (with reference to the evaporator probe)
P33 P32 differential 1 P34 evaporator fan activity during defrosting (only if P22 = 0 or 1)
0 = on 1 = off
P35 evaporator stop time after dripping 3 P36 temperature above which the evaporator fan is switched off
(with reference to the cabinet probe)
P37 effect caused by activation of microport input on evaporator
fan 0 = no effect 1 = the evaporator fan will be switched off
P38 microport input contact type
0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P39 micro port input alarm delay 0 P40 high pressure input contact type
0 = NA (input active with contact closed) 1 = NC (input active with contact open)
0
3
0
90
1
1
0
P41 high pressure input alarm delay 120
13
Rev 07/04/2015
Parameter
Description
Factory Value
P42 low pressure input contact type
0 0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P43 low pressure input alarm delay 0 P44 compressor thermal protection input contact type
0 0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P45 compressor thermal protection input alarm delay 0 P46 UV light on duration (duration of cabinet sterilisation) 5 P47 needle probe heating end temperature (with reference to the
45 needle probe)
P48 maximum duration of needle probe heating 15 P49 the temperature, below which the door elements are switched
5 on (with reference to the cabinet probe)
P50 P49 differential 2 P51 condenser fan activity in the absence of the condenser probe
1 (P61 = 0) 0 = in parallel with compressor 1 = on
P52 the temperature below which the condenser fan is switched off
20 in the presence of the condenser probe (P61 = 1) and on condition that the compressor is on (with reference to the condenser probe); see also P54
P53 P52 differential 5 P54 condenser fan switch off delay on switching off the compressor
30 in the presence of the condenser probe (P61 = 1); see also P52
P55 chill and freeze cycle completion buzzer duration 3 P56 maximum buzzer duration during an alarm state 15 P57 elapsed time between switching on the compressor and pump
10 down valve activation (pump down in power up); also elapsed time between deactivation of the pump down valve and switching off the compressor (pump down in power down)
P58 defrost parameter units of measurement
0 0 = P25 h, P24, P26, P28 and P35 min 1 = P25 min, P24, P26, P28 and P35 s
P59 reserved 0 P60 probe type
0 0 = NTC 1 = PTC
P61 condenser probe enabling
P62 the temperature above which the condenser temperature
P63 P62 differential 10
1 = YES
alarm is activated (with reference to the condenser probe)
Rev 07/04/2015
0
70
14
Blast chiller Service Manual
Parameter
Description
Factory Value
P64 temperature below which the minimum temperature alarm is
activated during post-chill storage, with relation to P7, i.e. "P7 + P64" (with reference to the cabinet probe) 0 = no alarm
P65 temperature above which the maximum temperature alarm is
activated during post-chill storage, with relation to P7, i.e. "P7 + P65" (with reference to the cabinet probe) 0 = no alarm
P66 temperature below which the minimum temperature alarm is
activated during post-freezing storage, with relation to P8, i.e. "P8 + P66" (with reference to the cabinet probe)0 = no alarm
P67 temperature above which the maximum temperature alarm is
activated during post-freezing storage, with relation to P8, i.e. "P8 + P67" (with reference to the cabinet probe) 0 = no alarm
P68 P64, P65, P66 and P67 differential 2 P69 storage operation start-up temperature alarm delay 0 P70 temperature alarm delay 0 P71 enable printing
1 = YES
P72 print interval 5 P73 HACCP alarm list deletion
1 = YES
P74 Baudrate
0=2400 1=4800 2=9600 3=19200
0
0
0
0
0
0
2
P75 Bit polarity
P76 Board address 1
15
0=no polarity 1=even 2=odd
Rev 07/04/2015
2
All GBF units from 5 to 18 Shelves (Hot gas Defrost)
Parameter
Description
Factory Value
P0 unit of temperature measurement
1 0 = °F 1 = °C
P1 cabinet probe offset 2 P2 evaporator probe offset 0 P3 needle probe offset 0 P4 operational setpoint during the second hard chill step; also,
0 operational setpoint during normal chilling (with reference to the cabinet probe)
P5 operational setpoint during freezing (with reference to the
-40
cabinet probe)
P6 operational setpoint during the first hard chill step (with
-20
reference to the cabinet probe)
P7 operational setpoint during post-chill storage (with reference to
3 the cabinet probe)
P8 operational setpoint during post-freeze storage (with reference
-20
to the cabinet probe)
P9 P4, P5, P6, P7 and P8 differential 1 P10 set temperature chill end temperature (with reference to the
3 needle probe)
P11 set temperature freeze end temperature (with reference to the
-18
needle probe)
P12 temperature at which the hard chill switches from the first step
20 to the second (with reference to the needle probe)
P13 temperature above which it is not possible to start a set-
99 temperature operational cycle (with reference to the needle probe)
P14 needle probe and the cabinet temperature for verification of
P15 duration of the second test to check correct needle probe
P16 maximum set temperature chill duration; also timed chill
P17 maximum set temperature freeze duration; also timed freeze
P18 first hard timed chill step duration 45 P19 compressor delay from device power on (from restoration of
P20 minimum elapsed time period between two consecutive
P21 minimum compressor shut-down time 0
correct needle probe insertion 0 = the test will not be performed
insertion; see also P14
duration
duration
power)
compressor start-up operations
0
60
90
240
0
0
Rev 07/04/2015
16
Blast chiller Service Manual
Parameter
Description
Factory Value
P22 defrost type
0 = electric (defrost on relay) 1 = hot gas (defrost compressor and relay on) 2 = air (evaporator fan on)
P23 defrost end temperature (with reference to the evaporator
probe)
P24 maximum defrost duration 10 P25 defrost interval during storage; see also P26
0 = intermittent defrosting will never be activated (only the first will be activated)
P26 first defrost delay from start of storage; see also P25 1 P27 defrosting at start of chilling and freezing
1 = YES
P28 drip-drain duration 2 P29 resetting of compressor protections at start of defrosting (only
if P22 = 1) 1 = YES
P30 elapsed time between the defrost request and switching on the
compressor (only if P22 = 1 and providing that the compressor is off when the defrost is requested); see P31 (7) (8)also
1
8
6
0
0
30
P31 elapsed time between the defrost request and activation of the
solenoid valve (only if P22 = 1 and on condition that the compressor is off when defrosting is requested); see also P30
P32 temperature above which the evaporator fan is switched off
during storage (with reference to the evaporator probe)
P33 P32 differential 1 P34 evaporator fan activity during defrosting (only if P22 = 0 or 1)
0 = on 1 = off
P35 evaporator stop time after dripping 3 P36 temperature above which the evaporator fan is switched off
(with reference to the cabinet probe)
P37 effect caused by activation of microport input on evaporator
fan 0 = no effect 1 = the evaporator fan will be switched off
P38 microport input contact type
0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P39 micro port input alarm delay 0 P40 high pressure input contact type
0 = NA (input active with contact closed) 1 = NC (input active with contact open)
0
3
0
90
1
1
1
P41 high pressure input alarm delay 120
17
Rev 07/04/2015
Parameter
Description
Factory Value
P42 low pressure input contact type
0 0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P43 low pressure input alarm delay 0 P44 compressor thermal protection input contact type
0 0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P45 compressor thermal protection input alarm delay 0 P46 UV light on duration (duration of cabinet sterilisation) 5 P47 needle probe heating end temperature (with reference to the
45 needle probe)
P48 maximum duration of needle probe heating 15 P49 the temperature, below which the door elements are switched
5 on (with reference to the cabinet probe)
P50 P49 differential 2 P51 condenser fan activity in the absence of the condenser probe
1 (P61 = 0) 0 = in parallel with compressor 1 = on
P52 the temperature below which the condenser fan is switched off
20 in the presence of the condenser probe (P61 = 1) and on condition that the compressor is on (with reference to the condenser probe); see also P54
P53 P52 differential 5 P54 condenser fan switch off delay on switching off the compressor
30 in the presence of the condenser probe (P61 = 1); see also P52
P55 chill and freeze cycle completion buzzer duration 3 P56 maximum buzzer duration during an alarm state 15 P57 elapsed time between switching on the compressor and pump
10 down valve activation (pump down in power up); also elapsed time between deactivation of the pump down valve and switching off the compressor (pump down in power down)
P58 defrost parameter units of measurement
0 0 = P25 h, P24, P26, P28 and P35 min 1 = P25 min, P24, P26, P28 and P35 s
P59 reserved 0 P60 probe type
0 0 = NTC 1 = PTC
P61 condenser probe enabling
P62 the temperature above which the condenser temperature
P63 P62 differential 10
1 = YES
alarm is activated (with reference to the condenser probe)
Rev 07/04/2015
0
70
18
Blast chiller Service Manual
Parameter
Description
Factory Value
P64 temperature below which the minimum temperature alarm is
activated during post-chill storage, with relation to P7, i.e. "P7 + P64" (with reference to the cabinet probe) 0 = no alarm
P65 temperature above which the maximum temperature alarm is
activated during post-chill storage, with relation to P7, i.e. "P7 + P65" (with reference to the cabinet probe) 0 = no alarm
P66 temperature below which the minimum temperature alarm is
activated during post-freezing storage, with relation to P8, i.e. "P8 + P66" (with reference to the cabinet probe) 0 = no alarm
P67 temperature above which the maximum temperature alarm is
activated during post-freezing storage, with relation to P8, i.e. "P8 + P67" (with reference to the cabinet probe) 0 = no alarm
P68 P64, P65, P66 and P67 differential 2 P69 storage operation start-up temperature alarm delay 0 P70 temperature alarm delay 0 P71 enable printing
1 = YES
P72 print interval 5 P73 HACCP alarm list deletion
1 = YES
P74 Baudrate
0=2400 1=4800 2=9600 3=19200
0
0
0
0
0
0
2
P75 Bit polarity
P76 Board address 1
19
0=no polarity 1=even 2=odd
Rev 07/04/2015
2
All GBC units from 5 to 18 Shelves (Hot gas Defrost)
Parameter
Description
Factory Value
P0 unit of temperature measurement
1 0 = °F 1 = °C
P1 cabinet probe offset 2 P2 evaporator probe offset 0 P3 needle probe offset 0 P4 operational setpoint during the second hard chill step; also,
0 operational setpoint during normal chilling (with reference to the cabinet probe)
P5 operational setpoint during freezing (with reference to the
0 cabinet probe)
P6 operational setpoint during the first hard chill step (with
-20
reference to the cabinet probe)
P7 operational setpoint during post-chill storage (with reference to
3 the cabinet probe)
P8 operational setpoint during post-freeze storage (with reference
3 to the cabinet probe)
P9 P4, P5, P6, P7 and P8 differential 1 P10 set temperature chill end temperature (with reference to the
3 needle probe)
P11 set temperature freeze end temperature (with reference to the
3 needle probe)
P12 temperature at which the hard chill switches from the first step
20 to the second (with reference to the needle probe)
P13 temperature above which it is not possible to start a set-
99 temperature operational cycle (with reference to the needle probe)
P14 needle probe and the cabinet temperature for verification of
P15 duration of the second test to check correct needle probe
P16 maximum set temperature chill duration; also timed chill
P17 maximum set temperature freeze duration; also timed freeze
P18 first hard timed chill step duration 45 P19 compressor delay from device power on (from restoration of
P20 minimum elapsed time period between two consecutive
P21 minimum compressor shut-down time 0
correct needle probe insertion 0 = the test will not be performed
insertion; see also P14
duration
duration
power)
compressor start-up operations
0
60
90
90
0
0
Rev 07/04/2015
20
Blast chiller Service Manual
Parameter
Description
Factory Value
P22 defrost type
0 = electric (defrost on relay) 1 = hot gas (defrost compressor and relay on) 2 = air (evaporator fan on)
P23 defrost end temperature (with reference to the evaporator
probe)
P24 maximum defrost duration 10 P25 defrost interval during storage; see also P26
0 = intermittent defrosting will never be activated (only the first will be activated)
P26 first defrost delay from start of storage; see also P25 1 P27 defrosting at start of chilling and freezing
1 = YES
P28 drip-drain duration 2 P29 resetting of compressor protections at start of defrosting (only
if P22 = 1) 1 = YES
P30 elapsed time between the defrost request and switching on the
compressor (only if P22 = 1 and providing that the compressor is off when the defrost is requested); see P31 (7) (8)also
1
8
6
0
0
30
P31 elapsed time between the defrost request and activation of the
solenoid valve (only if P22 = 1 and on condition that the compressor is off when defrosting is requested); see also P30
P32 temperature above which the evaporator fan is switched off
during storage (with reference to the evaporator probe)
P33 P32 differential 1 P34 evaporator fan activity during defrosting (only if P22 = 0 or 1)
0 = on 1 = off
P35 evaporator stop time after dripping 3 P36 temperature above which the evaporator fan is switched off
(with reference to the cabinet probe)
P37 effect caused by activation of microport input on evaporator
fan 0 = no effect 1 = the evaporator fan will be switched off
P38 microport input contact type
0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P39 micro port input alarm delay 0 P40 high pressure input contact type
0 = NA (input active with contact closed) 1 = NC (input active with contact open)
0
3
0
90
1
1
1
P41 high pressure input alarm delay 120
21
Rev 07/04/2015
Parameter
Description
Factory Value
P42 low pressure input contact type
0 0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P43 low pressure input alarm delay 0 P44 compressor thermal protection input contact type
0 0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P45 compressor thermal protection input alarm delay 0 P46 UV light on duration (duration of cabinet sterilisation) 5 P47 needle probe heating end temperature (with reference to the
45 needle probe)
P48 maximum duration of needle probe heating 15 P49 the temperature, below which the door elements are switched
5 on (with reference to the cabinet probe)
P50 P49 differential 2 P51 condenser fan activity in the absence of the condenser probe
1 (P61 = 0) 0 = in parallel with compressor 1 = on
P52 the temperature below which the condenser fan is switched off
20 in the presence of the condenser probe (P61 = 1) and on condition that the compressor is on (with reference to the condenser probe); see also P54
P53 P52 differential 5 P54 condenser fan switch off delay on switching off the compressor
30 in the presence of the condenser probe (P61 = 1); see also P52
P55 chill and freeze cycle completion buzzer duration 3 P56 maximum buzzer duration during an alarm state 15 P57 elapsed time between switching on the compressor and pump
10 down valve activation (pump down in power up); also elapsed time between deactivation of the pump down valve and switching off the compressor (pump down in power down)
P58 defrost parameter units of measurement
0 0 = P25 h, P24, P26, P28 and P35 min 1 = P25 min, P24, P26, P28 and P35 s
P59 reserved 0 P60 probe type
0 0 = NTC 1 = PTC
P61 condenser probe enabling
P62 the temperature above which the condenser temperature
P63 P62 differential 10
1 = YES
alarm is activated (with reference to the condenser probe)
Rev 07/04/2015
0
70
22
Blast chiller Service Manual
Parameter
Description
Factory Value
P64 temperature below which the minimum temperature alarm is
activated during post-chill storage, with relation to P7, i.e. "P7 + P64" (with reference to the cabinet probe) 0 = no alarm
P65 temperature above which the maximum temperature alarm is
activated during post-chill storage, with relation to P7, i.e. "P7 + P65" (with reference to the cabinet probe) 0 = no alarm
P66 temperature below which the minimum temperature alarm is
activated during post-freezing storage, with relation to P8, i.e. "P8 + P66" (with reference to the cabinet probe) 0 = no alarm
P67 temperature above which the maximum temperature alarm is
activated during post-freezing storage, with relation to P8, i.e. "P8 + P67" (with reference to the cabinet probe) 0 = no alarm
P68 P64, P65, P66 and P67 differential 2 P69 storage operation start-up temperature alarm delay 0 P70 temperature alarm delay 0 P71 enable printing
1 = YES
P72 print interval 5 P73 HACCP alarm list deletion
1 = YES
P74 Baudrate
0=2400 1=4800 2=9600 3=19200
0
0
0
0
0
0
2
P75 Bit polarity
P76 Board address 1
23
0=no polarity 1=even 2=odd
Rev 07/04/2015
2
All GBC Trolley Units (Cycle Off Defrost)
Parameter
Description
Factory Value
P0 unit of temperature measurement
1 0 = °F 1 = °C
P1 cabinet probe offset 0 P2 evaporator probe offset 0 P3 needle probe offset 0 P4 operational setpoint during the second hard chill step; also,
0 operational setpoint during normal chilling (with reference to the cabinet probe)
P5 operational setpoint during freezing (with reference to the
0 cabinet probe)
P6 operational setpoint during the first hard chill step (with
-20
reference to the cabinet probe)
P7 operational setpoint during post-chill storage (with reference to
3 the cabinet probe)
P8 operational setpoint during post-freeze storage (with reference
3 to the cabinet probe)
P9 P4, P5, P6, P7 and P8 differential 1 P10 set temperature chill end temperature (with reference to the
3 needle probe)
P11 set temperature freeze end temperature (with reference to the
3 needle probe)
P12 temperature at which the hard chill switches from the first step
20 to the second (with reference to the needle probe)
P13 temperature above which it is not possible to start a set-
99 temperature operational cycle (with reference to the needle probe)
P14 needle probe and the cabinet temperature for verification of
P15 duration of the second test to check correct needle probe
P16 maximum set temperature chill duration; also timed chill
P17 maximum set temperature freeze duration; also timed freeze
P18 first hard timed chill step duration 45 P19 compressor delay from device power on (from restoration of
P20 minimum elapsed time period between two consecutive
P21 minimum compressor shut-down time 0
correct needle probe insertion 0 = the test will not be performed
insertion; see also P14
duration
duration
power)
compressor start-up operations
0
60
90
90
0
0
Rev 07/04/2015
24
Blast chiller Service Manual
Parameter
Description
Factory Value
P22 defrost type
0 = electric (defrost on relay) 1 = hot gas (defrost compressor and relay on) 2 = air (evaporator fan on)
P23 defrost end temperature (with reference to the evaporator
probe)
P24 maximum defrost duration 10 P25 defrost interval during storage; see also P26
0 = intermittent defrosting will never be activated (only the first will be activated)
P26 first defrost delay from start of storage; see also P25 1 P27 defrosting at start of chilling and freezing
1 = YES
P28 drip-drain duration 2 P29 resetting of compressor protections at start of defrosting (only
if P22 = 1) 1 = YES
P30 elapsed time between the defrost request and switching on the
compressor (only if P22 = 1 and providing that the compressor is off when the defrost is requested); see P31 (7) (8)also
2
8
6
0
0
30
P31 elapsed time between the defrost request and activation of the
solenoid valve (only if P22 = 1 and on condition that the compressor is off when defrosting is requested); see also P30
P32 temperature above which the evaporator fan is switched off
during storage (with reference to the evaporator probe)
P33 P32 differential 1 P34 evaporator fan activity during defrosting (only if P22 = 0 or 1)
0 = on 1 = off
P35 evaporator stop time after dripping 3 P36 temperature above which the evaporator fan is switched off
(with reference to the cabinet probe)
P37 effect caused by activation of microport input on evaporator
fan 0 = no effect 1 = the evaporator fan will be switched off
P38 microport input contact type
0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P39 micro port input alarm delay 0 P40 high pressure input contact type
0 = NA (input active with contact closed) 1 = NC (input active with contact open)
0
3
0
90
1
1
0
P41 high pressure input alarm delay 120
25
Rev 07/04/2015
Parameter
Description
Factory Value
P42 low pressure input contact type
0 0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P43 low pressure input alarm delay 0 P44 compressor thermal protection input contact type
0 0 = NA (input active with contact closed) 1 = NC (input active with contact open)
P45 compressor thermal protection input alarm delay 0 P46 UV light on duration (duration of cabinet sterilisation) 5 P47 needle probe heating end temperature (with reference to the
45 needle probe)
P48 maximum duration of needle probe heating 15 P49 the temperature, below which the door elements are switched
5 on (with reference to the cabinet probe)
P50 P49 differential 2 P51 condenser fan activity in the absence of the condenser probe
1 (P61 = 0) 0 = in parallel with compressor 1 = on
P52 the temperature below which the condenser fan is switched off
20 in the presence of the condenser probe (P61 = 1) and on condition that the compressor is on (with reference to the condenser probe); see also P54
P53 P52 differential 5 P54 condenser fan switch off delay on switching off the compressor
30 in the presence of the condenser probe (P61 = 1); see also P52
P55 chill and freeze cycle completion buzzer duration 3 P56 maximum buzzer duration during an alarm state 15 P57 elapsed time between switching on the compressor and pump
10 down valve activation (pump down in power up); also elapsed time between deactivation of the pump down valve and switching off the compressor (pump down in power down)
P58 defrost parameter units of measurement
0 0 = P25 h, P24, P26, P28 and P35 min 1 = P25 min, P24, P26, P28 and P35 s
P59 reserved 0 P60 probe type
0 0 = NTC 1 = PTC
P61 condenser probe enabling
P62 the temperature above which the condenser temperature
P63 P62 differential 10
1 = YES
alarm is activated (with reference to the condenser probe)
Rev 07/04/2015
0
70
26
Blast chiller Service Manual
Parameter
Description
Factory Value
P64 temperature below which the minimum temperature alarm is
activated during post-chill storage, with relation to P7, i.e. "P7 + P64" (with reference to the cabinet probe) 0 = no alarm
P65 temperature above which the maximum temperature alarm is
activated during post-chill storage, with relation to P7, i.e. "P7 + P65" (with reference to the cabinet probe) 0 = no alarm
P66 temperature below which the minimum temperature alarm is
activated during post-freezing storage, with relation to P8, i.e. "P8 + P66" (with reference to the cabinet probe) 0 = no alarm
P67 temperature above which the maximum temperature alarm is
activated during post-freezing storage, with relation to P8, i.e. "P8 + P67" (with reference to the cabinet probe) 0 = no alarm
P68 P64, P65, P66 and P67 differential 2 P69 storage operation start-up temperature alarm delay 0 P70 temperature alarm delay 0 P71 enable printing
1 = YES
P72 print interval 5 P73 HACCP alarm list deletion
1 = YES
P74 Baudrate
0=2400 1=4800 2=9600 3=19200
0
0
0
0
0
0
2
P75 Bit polarity
P76 Board address 1
27
0=no polarity 1=even 2=odd
Rev 07/04/2015
2
1.3.3 Temperature Probes Display
DISPLAY
PROBE
To check the reading of the unit’s temperature sensing probes, first make sure the unit is in the OFF mode.
1. Press the NEDLE PROBE key and the DOWN arrow key together and hold for five (5) seconds.
2. T o scroll through the reading use the UP or DOWN arrow key. Tab 2
Pr1 Cabinet Probe Pr2 Needle Probe Pr3 Evaporator Probe
Valuable information can be obtained by checking the evaporator probe when the unit is struggling to reach the cabinet temperature setpoint, (i.e. -40°F). This may indicate that the evaporator coil is not being supplied with sufficient refrigerant. With a cabinet setpoint of -40°F the actual evaporator temperature is approximately -45°C at 0 Barg. In this case, the controller evaporator probe reading MUST BE at least -42°C, which is the minimum readable temperature. HACCP PRINTER Blast Chillers can be ordered with an optional printer, or one can be installed as a retrofit. The printer has its own power supply connection (110VAC – 240VAC 50/60 Hz). The printer is connected to the Main Board at the second RS 485 connection port (shown).
Rev 07/04/2015
28
Blast chiller Service Manual
45 46 47
PRINTER TERMINAL BLOCK
MAIN BOARD
TERMINAL BLOCK
A belden shielded cable (3 wires) must be used.
Connect the printer to the Main Board using coaxial shielded cables. The main controller must be set to recognize the printer and enable communication. Set configuration parameter P71 to 1 to enable the printer port on the Main Board. In addition, ensure that the following parameters are set as shown:
P76 – 1 P75 – 2
An LED on the printer will indicate its status: RED = ON. Press the feed key to output blank paper in either ON or OFF status.
Printing alarm list
RS485 (2)
29
Rev 07/04/2015
To print the alarm list, the controller must be in the OFF mode.
Press the PROGRAM key for five (5) seconds.
f the printer communication has been enabled, the first display shown is
the alarm code, press the PROGRAM key.
To exit from printing, press either the UP or DOWN arrow key and the alarm
list will be shown in the display.
The controller will only save the previous 10 alarms.
Printed codes will be as shown:
With the HACCP printer, it is also possible to print data history related to the
If the printer is left ON and a cycle is started, the
capture frequency is set in Parameter P72 (example: If P72 = 1, device will print
every minute) and give the following information:
• Time, Cabinet and Needle Probe temperatures (each capt
ev
data will be captured. Data
I To print
• Alarm duration
• Max/Min Temperature
• Date /Time
• Alarm Code
Printing Cycle Data
freezing and chilling cycles.
• Type of cycle
• Start date and time
“Prt”.
ure line)
R
07/04/2015
30
Loading...
+ 70 hidden pages