Illustrated Parts Breakdown and Parts List........ 28
Warranty Information ...........................Back Cover
WARNING: Improper instal-
lation, adjustment, alteration,
service or maintenance can
cause injury or property damage.
Refer to this manual for correct
installation and operational
procedures. For assistance or
additional information consult
a qualified installer, service
agency or the gas supplier.
This appliance is only for use
with the type of gas indicated on
the rating plate. This appliance
is not convertible for use with
other gases, unless a certied
kit is used.
State of Massachusetts: The
installation must be made by a
licensed plumber or gas tter
in the Commonwealth of Mas-
sachusetts.
WARNING: This product
contains and/or generates
chemicals known to the State
of California to cause cancer or
birth defects or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or death
from burns, fire, explosion,
electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This vented gas replace is a sealed combustion gas replace designed for residential
applications. This replace must be installed
with DESA vent pipe components and terminations.
Outside airex installation is
required for both horizontal and
vertical installation.
This replace complies with the National Safety Standards and is listed and tested by OMNI
Test Laboratories, Inc. to ANSI Z21.50b-2005
standard as vented gas replace.
This replace must be installed by a qualied
(certied or licensed) service person. It brings
in fresh air for combustion through the outer
pipe and combustion gases are exhausted
through the inner pipe. If the glass door assembly and venting pipe are not properly
seated, connected and sealed, carbon mon-
oxide leakage (spillage) can occur.
www.desatech.com
120441-01A2
Page 3
SAFETY INFORMATION
Continued
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If
you have these signs, the replace may not
be working properly. Get fresh air at once!
Have replace serviced. Some people are
more affected by carbon monoxide than others. These include pregnant women, people
with heart or lung disease or anemia, those
under the inuence of alcohol and those at
high altitudes.
Natural and Propane/LP Gas: Natural and
propane/LP gas are odorless. An odor-making
agent is added to the gas. The odor helps you
detect a gas leak. However, the odor added to
the gas can fade. Gas may be present even
though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
WARNING: Any change to
this replace or it’s controls can
be dangerous. Do not modify
this replace under any circumstances. Any parts removed for
servicing must be replaced prior
to operating replace.
WARNING: Do not use a blower insert, heat exchanger insert
or other accessory not approved
for use with this replace.
WARNING: This appliance
is only for use with the type of
gas indicated on the rating plate.
This appliance is not convertible
for use with other gases unless
a certied kit is used.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects on the appliance.
Do not use this replace to cook
food or burn paper or other ammable material.
This replace reaches high temperatures. Keep children and
adults away from hot surface to
avoid burns or clothing ignition.
Fireplace will remain hot for a
time after shutdown. Allow surface to cool before touching.
Carefully supervise young chil-
dren when they are in the room
with replace.
Keep the area around your
replace clear of combustible
materials, gasoline and other
ammable vapor or liquids. Do
not run replace where these
are used or stored.
1. For propane/LP replace, do not place
propane/LP supply tank(s) inside any
struc tu re. Locate prop an e/ LP supply
tank(s) outdoors. To prevent performance
problems, do not use propane/LP fuel tank
of less than 100 lb. capacity.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor ’s phone. Follow the gas
supplier's instructions
• if you cannot reach you gas supplier, call
the re department.
120441-01A3
www.desatech.com
Page 4
SAFETY INFORMATION
Continued
3. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains
or other combustible (ammable) objects
can make contact with the fireplace
front
• in high trafc areas
4. Turn fireplace off and let cool before
servicing, installing or repairing. Only a
qualied service person should install,
service or repair this replace. Have replace inspected annually by a qualied
service person.
5. You must keep control compartments,
burners and circulating air passages
clean. More frequent cleaning may be
needed due to excessive lint and dust
from carpeting, bedding material, etc.
Turn off the gas valve and pilot light before
cleaning replace.
6. Have venting system inspected annually by
a qualied service person. If needed, have
venting system cleaned or repaired. See
Cleaning and Maintenance, page 23.
7. Do not use any solid fuels (wood, coal,
paper, cardboard, etc.) in this replace.
Use only the gas type indicated on re-
place nameplate.
8. This appliance, when installed, must be
electrically grounded in accordance with
local codes or, in the absence of local
codes, with the National Electrical Code,
ANSI/NFPA 70 or the Canadian Electrical
Code, CSA C22.1.
9. Do not use replace if any part has been
exposed to or under water. Immediately
call a qualied service person to arrange
for replacement of the unit.
10. Do not operate replace if any log is
broken.
11. Do not operate replace with glass door
removed, cracked or broken.
12. Provide adequate clearances around air
openings.
PRODUCT
IDENTIFICATION
Nailing
Flange
Outer
Glass
Door
Aniron
Standard
Brick
Refractories
Center Brick/
Control Cover
Figure 1 - Direct Vent Fireplace
(DVF-36SC Shown)
Flue
Collar
Log Set
LOCAL CODES
Install and use replace with care. Follow all
local codes. In the absence to local codes,
use the current National Fuel Gas Code ANSI
Z223.1/NFPA 54* (USA) or the current CSAB149.1 Installation Code (Canada).
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
PRODUCT FEATURES
These are a few facts that can help you under-
stand and enjoy your direct vent replace:
• The venting system may be routed to the
outside of your home in several ways. It
may vent through the roof (vertical) or it
may vent to an outside/exterior wall (hori-
zontal). The vent pipe installation is very
important to allow for proper operation.
You must follow the venting instructions
very carefully for either vertical or horizontal
applications.
www.desatech.com
120441-01A4
Page 5
D
RW
PRODUCT FEATURES
Continued
• This replace may be installed in any room
of your house provided all local codes and
these installation instructions are followed.
• Each time you turn on your replace, you
may notice some amount of condensation
on the inside of the replace glass. This
is normal and will disappear after 10-20
minutes of operation.
• Your direct vent gas fireplac e system
(replace and venting) is a balanced and
sealed gas operating unit. It requires ap-
proximately 10-20 minutes of operating
time before the ame pattern stabilizes.
• Models DVF-36S and DVF-36H have a
standard glass inner door. Models DVF36SC and DVF-36HC have the standard
glass inner door with a middle glass door
and outer cool touch glass door.
PREINSTALLATION
LOCATION AND SPACE
REQUIREMENTS
Determine the safest and most efcient location for your direct vent replace. Make sure
that rafters and wall studs are not in the way of
the venting system. Choose a location where
the heat output is not affected by drafts, air
conditioning ducts, windows or doors. Figure
2 shows some common locations. Be aware
of all restrictions and precautions before
deciding the exact location for your replace
and termination cap.
When deciding the location of your replace,
follow these rules:
• Do not connect this replace venting to a
chimney ue serving a separate solid-fuel
burning replace or appliance.
• Due to high temperatures, do not locate this
replace in high trafc areas, windy or drafty
areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your replace is to be installed directly on
carpeting, vinyl tile or any combustible material other than wood, it must be installed on a
metal or wood panel extending the full width
and depth of the replace (see Figure 3).
• Your replace is designed to be used in
zero clearance installations. Wall or framing
material can be placed directly against any
exterior surface on the back, sides or top of
your replace, except where standoff spacers are integrally attached. If standoff spac-
ers are attached to your replace, these
spacers can be placed directly against wall
or framing material. See framing details on
page 6.
• When locating termination cap, it is important to observe the minimum clearances
shown in Figure 7, page 7.
• If recessing into a wall, you can avoid extra
framing by positioning your replace against
an already existing framing member.
• Do not recess termination cap into a wall
or siding.
• You may paint the termination cap with
450º F (232º C) heat-resistant paint to
coordinate with the exterior nish.
• There must not be any obstruction such as
bushes, garden sheds, fences, decks or
utility buildings within 24" from the front of
the termination cap and the front of outside
air vent.
• Do not locate termination cap and outside air
vent where excessive snow or ice build up
may occur. Be sure to clear vent termination
area after snow falls to prevent accidental
blockage of venting system. When using
snow blowers, do not direct snow towards
vent termination area.
26"
Flush with a wall
Through exterior wall
enclosed in a chase
Corner
installation
27 5/8"
43"
Figure 3 - Fireplace Bottom Dimensions
Figure 2 - Common Fireplace Locations
120441-01A5
www.desatech.com
Page 6
PREINSTALLATION
56 3/4"
43 1/4"
33"28"
41 3/8"
82 1/8"
43 1/4"
43"
199/16"
58 1/4"
Nailing
Tabs
C
B
A
D
E
F
G
3
2
1
4
5
6
7
Wall
Continued
CLEARANCES
Minimum clearances to combustibles for the
replace are as follows:
*Back and sides 0"
Perpendicular walls 6"
Floor 0"
Ceiling to louver opening 42"
Front 36"
Top of Standoffs 0"
Vent (See venting instructions
for specic venting clearances.)
Combustible material with a maximum thick-
ness of 5/8" may be ush with the top front
of replace.
* For back and sides of replace, do not pack
with insulation or other materials. 0" clearance to combustible materials are for framing
purpose only.
NOTICE: This replace is intended for use as supplemental heat.
Use this replace along with
your primary heating system.
Do not install this replace as
your primary heat source. If you
have a central heating system,
you may run system’s circulating blower while using replace.
This will help circulate the heat
throughout the house.
Figure 4 - Framing Clearances with
Outside Air Flex Duct
Figure 5 - Framing Clearances for
Corner Installation
FRAMING AND FINISHING
Figure 4 shows typical framing of this replace.
Figure 5 shows framing for corner installation.
All minimum clearances must be met.
If you are using a separate combustible mantel piece, refer to Figure 6 for proper installation height. You can install noncombustible
A = clearance above grade, veranda, porch, deck, or
balcony [*12" (30.5 cm) minimum]
B = clearance to window or door that may be opened
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
C = clearance to permanently closed window
[minimum 12" (30.5 cm) recommended to prevent
condensation on window]
D = vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 24" (61 cm) from
the center-line of the terminal [18" (45.7 cm) minimum]
E = clearance to unventilated soffit [12" (30.5 cm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly
within 36" (91.4 cm) horizontally from the center line
of the regulator
I = clearance to service regulator vent outlet [*72" (182.9 cm)
minimum]
J = clearance to non-mechanical air supply inlet to building
or the combustion air inlet to any other fireplace
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
K = clearance to a mechanical air supply inlet [*In Canada,
6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within
10 ft. (3 m) horizontally]
L = † clearance above paved side-walk or a paved driveway
located on public property [*84" (213.3 cm) minimum]
M = clearance under veranda, porch, deck
[*12" (30.5 cm) minimum ‡]
N = clearance above a roof shall extend a minimum of
24" (61 cm) above the highest point when it passes
through the roof surface and any other obstruction within
a horizontal distance of 18" (45.7 cm)
† vent shall not terminate directly above a side-walk or paved driveway which is located between tw o
single family dwellings and serves both dwellings*
‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
* as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note: Local codes or regulations may require different clearances
A = 6" (15.2 cm)
Inside Corner
V
B
E
V
B = 6" (15.2 cm)
C = Maximum depth of 48" (121.9 cm)
for recessed location
D = Minimum width for back wall of
recessed location Combustible - 38" (965 mm)
Noncombustible - 24" (61 cm)
E = Clearance from corner in
recessed location Combustible - 6" (15.2 cm)
Noncombustible - 2" (5.1 cm)
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Openable
LOCATION OF TERMINATION CAP
120441-01A7
Figure 7 - Minimum Clearances for Termination Cap
www.desatech.com
Page 8
VENTING INSTALLATION
NOTICE: Read these instruc-
tions completely before attempting installation.
These models are tested and approved for
use with DESA (direct vent) pipe components
and terminations.
The venting system must terminate on the
outside of the structure and can not be at-
tached to a chimney or ue system serving a
separate solid fuel or gas burning appliance.
A direct vent appliance must have its own
venting system. DO NOT common vent this
appliance.
These models are approved to be vented
either horizontally through an outside wall or
vertically through a roof or chase enclosure
using the following guidelines:
• When venting system terminates horizontally on an outside wall, you may install
a standoff if the termination cap is to be
installed directly on a combustible nish
such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may
cause excessive temperatures which could
cause a re.
• Vent pipe air space clearances to combustibles are 1" on all sides except on the
horizontal sections, which requires 2" clearance from the top of the pipe. Where the
termination cap penetrates a combustible
wall, 1" air space clearance is required.
• Have replace and selected vent compo-
nents on hand to help determine the exact
measurements when elbowing or offsetting.
Always use wall restops when penetrating
walls and restops when penetrating ceil-
ings or attic spaces.
• For installation of replace at elevations of
4000 feet or greater, pay special attention
to venting requirement recommendations.
WARNING: Read all instruc-
tions completely and thoroughly
before attempting installation.
Failure to do so could result in
serious injury, property damage
or loss of life.
NOTICE: Failure to follow these in-
structions will void the warranty.
NOTICE: Do not seal termination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
INSTALLATION PRECAUTIONS
• We ar glo ves an d safe t y gla s ses fo r
protection
• Use extreme caution when using ladders
or when on roof tops
• Be aware of electrical wiring locations in
walls and ceilings
The following actions will void the warranty
on your venting system:
• In s tal lati on of any da mage d ven tin g
component
• Unauthorized modication of the venting system (Do not cut or alter vent components)
• Installation of any component part not
manufactured or approved by DESA
• Installation other than as instructed by
these instructions
WARNING: This gas replace
and vent assembly must be
vented directly to the outside.
The venting system must NEVER
be attached to a chimney serving a separate solid fuel burning
appliance. Each direct vent gas
appliance must use a separate
vent system. Do not use common vent systems.
WARNING: Vent pipe air
space clearances to combustibles are 1" on all sides except
on the horizontal sections,
which require 2" clearances
from the top of the pipe. Where
the termination cap penetrates
a combustible wall, 1" air space
clearance is required.
www.desatech.com
120441-01A8
Page 9
(Framing
Detail)
111/2"
111/2" Inside Framing
111/2"
8 1/2"
Vent Opening
Combustible Wall
Vent Opening
Noncombustible Wall
VENTING INSTALLATION
Continued
INSTALLATION PLANNING
There are two basic types of direct vent
installation:
• Horizontal Termination
• Vertical Termination
Outside air ex installation is required for
both horizontal and vertical installation (see
page 13).
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations
require only inner portion of wall restop. Horizontal installations using round termination
require exterior portion of wall restop.
1. Set the replace in its desired location and
determine the route your horizontal venting will take. Do not secure the replace
until all venting has been installed. Some
installations require sliding the replace
in and out of position to make nal vent-
ing connections. Figures 14 and 15 on
page 11 show different congurations for
venting with horizontal termination that
will help you decide which application
best suits your installation. Check to see
if wall studs or roof rafters are in the path
of your desired venting route. If they are,
you may want to adjust the location of the
replace.
2. Direct vent pipe sections and components are designed with special twist-lock
connections.
Twist- Lo ck Procedure: The female
ends of the pipes have locking lugs (in-
dentations). These lugs will slide straight
into matching slots on the male ends
of adjacent pipes. Push pipe sections
together and twist one section clockwise
approximately one-quarter turn until the
sections are fully locked (see Figure 8).
Note: Horizontal runs of vent must be sup-
ported every three feet. Use wall straps
for this purpose.
3. Assemble the desired combination of pipe
and elbows to the replace ue collar. If
there are long portions of venting run, preassembled pipe sections may be installed
as subassemblies for convenience.
4. Carefully determine the location where
the vent pipe assembly will penetrate
the outside wall. The center of the hole
should line up with the center-line of the
horizontal vent pipe. Mark the wall for
an 11 1/2" x 11 1/2" square hole. Cut and
frame the square hole in the exterior
wall where the vent will be terminated. If
the wall being penetrated is constructed
of noncombustib le material, such as
masonry block or concrete, a 8 1/2" hole
with zero clearance is acceptable (see
Figure 9).
Female
Locking Lugs
Male
Slots
Figure 8 - Vent Pipe Connections
Center of
Hole
120441-01A9
Figure 9 - Vent Opening Requirements
www.desatech.com
Page 10
VENTING INSTALLATION
Continued
WARNING: Do not recess
vent termination into any wall.
This will cause a re hazard.
5. Noncombustible Exterior Wall: Position
the horizontal vent cap in the center of the
8 1/2" round hole and attach to the exterior
wall with four wood screws provided.
Before attaching the vent cap to exterior
wall, run a bead of non-hardening mastic
(pliable sealant) around the outside edges
to make a seal between it and the outside
wall. Note: The four wood screws provided
should be replaced with appropriate fasteners for stucco, brick, concrete or other
types of sidings (see Figure 10).
Combustible Exterior Wall: For vinyl
siding, stucco or wood exteriors, a siding
standoff may be installed between the
vent cap and exterior wall. The siding
standoff prevents excessive heat from
damaging the siding materials. Siding
material must be cut to accommodate
standoff. Bolt the vent cap to the standoff. Apply non-hardening mastic around
outside edge of standoff. Position the
standoff/cap assembly in the center of the
11 1/2" square hole and attach to exterior
wall with wood screws provided (see Fig-
ure 11). The siding standoff must sit ush
against the exterior fascia material.
6. Combustible Exterior Wall Only: Slide
the wall restop over the vent pipe before
connecting horizontal run to vent cap (see
Figure 12).
7. Carefully move replace, with vent as-
sembly attached, toward wall and insert
vent pipe into horizontal termination. The
pipe overlap should be a minimum of 1 1/4"
(see Figure 13, page 11).
8. Combustible Exterior Wall Only: Slide
wall restop against interior wall surface
and attach with screws provided. See Fig-
ure 13, page 11, for horizontal termination
details.
9. Place replace into position and shim with
noncombustible material if needed. Nail or
screw side anges to framing to secure
unit in place. IMPORTANT: Make sure re-
place is level before securing. If replace
is not level it will not work properly.
Cut Siding Away to
Fit Standoff
Standoff
Apply Mastic
to All Four Sides
Figure 11 - Installing Siding Standoff
(Combustible Exterior Wall)
Wood
Screw
Vent
Cap
Screws
Interior Wall
Surface
Apply
Mastic to All
Four Sides
Vent Cap
Wood
Screw
Figure 10 - Installing Horizontal Vent Cap
(Noncombustible Exterior)
www.desatech.com
Wall
Firestop
Vent Cap
(Horizontal
Termination)
Screw
Figure 12 - Connecting Vent Cap with
Horizontal Vent Pipe
Horizontal
Vent Pipe
120441-01A10
Page 11
2' Min.
2' Pipe Min.
+ 90° Elbow
7' Min.
VENTING INSTALLATION
Continued
Minimum
Pipe
Direct
Vent
Pipe
Maintain 1"
Minimum Air
Space Around
Outer Pipe When
Penetrating a Wall
11 1/2" x 11 1/2"
Framed Opening
Horizontal Termination Congurations
Figu res 14 and 15 show diffe rent con-
gurations and alternatives for venting with
horizontal termination. Each gure includes
a chart with critical minimum and maximum
dimensions which MUST be met.
Overlap
11/4"
Wall
Firestop
Exterior Wall with Vinyl Siding
Figure 13 - Typical Horizontal
Termination Cap Mounting with
Additional Siding Standoff Installed
NOTICE: Do not seal termination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
Siding
Standoff
Screws
High Wind
Termination
Apply
Mastic to
Outside
Edge of
Standoff
GROUND FLOOR INSTALLATION
Recommended Applications:
• Installation using cabinet surrounds
• Through the wall using round or square
termination (up to 12" horizontal pipe)
• NOT FOR CORNER INSTALLATION
Wall
Firestop
Horizontal High
Wind Square
Termination
Figure 14 - Horizontal Termination Using
One 90° Elbow
90° Elbow
WARNING: Never run vent
downward as this may cause
excessive temperatures which
could cause a re. Operation of
improperly installed and maintained venting system could
result in serious injury, property
damage or loss of life.
120441-01A11
Venting with Two 90° Elbows
Vertical (V)
7' min.18' max.
8' min.20' max.
20' max.20' max.
Figure 15 - Horizontal Termination Using
www.desatech.com
Horizontal (H1) +
Horizontal (H2)
Two 90° Elbows
Page 12
VENTING INSTALLATION
Continued
Vertical Termination Installation
Note: Vertical restrictor must be installed in
all vertical installations.
1. Determine the route your vertical venting
will take. If ceiling joists, roof rafters or
other framing will obstruct the venting
system, consider an offset (see Figure 16)
to avoid cutting load bearing members.
Note: Pay special attention to these instal-
lation instructions for required clearances
(air space) to combustibles when passing
through ceilings, walls, roofs, enclosures,
attic rafters, etc. Do not pack air spaces
with insulation. Also note maximum vertical rise of the venting system and any
maximum horizontal offset limitations.
2. Set the replace in desired location. Drop
a plumb line down from the ceiling to the
position of the replace exit ue. Mark the
center point where the vent will penetrate
the ceiling. Drill a small locating hole at
this point.
Drop a plumb line from the inside of the
roof to the locating hole in the ceiling.
Mark the center point where the vent will
penetrate the roof. Drill a small locating
hole at this point.
Roof Flashing
Wall Strap
Flat Ceiling Installation
1. Cut a 11 1/2" square hole in the ceiling
using the locating hole as a center point.
The opening should be framed to 11 1/2"
x 11 1/2" inside dimensions, as shown in
Figure 8 on page 9 using framing lumber
the same size as the ceiling joists. If the
area above the ceiling is an insulated
ceiling or an attic, nail restop from the
top side. This prevents loose insulation
from falling into the required clearance
space. Of the area above the ceiling
is a living space, install restop below
the framed hole. The restop should be
installed with no less than three nails
per side (see Figure 17).
2. Assemble the desired lengths of pipe
and elbows necessary to reach from the
replace ue up through the restop. Be
sure all pipe and elbow connections are
fully twist-locked (see Figure 7, page 9).
3. Cut a hole in the roof using the locating
hole as a center point. (Cover any exposed
open vent pipes before cutting hole in roof.)
The 11 1/2" x 11 1/2" hole must be measured
on the horizontal; actual length may be
larger depending on the pitch of the roof.
There must be a 1" clearance from the vent
pipe to combustible materials. Frame the
opening as shown in Figure 9, page 9.
4. Connect a section of pipe and extend up
through the hole.
Note: If an offset is needed to avoid
obstructions, you must support the vent
pipe every 3 feet. Use wall straps for this
purpose (see Figure 15, page 11). Whenever possible, use 45° elbows instead of
90° elbows. The 45° elbow offers less
restriction to the ow of the ue gases.
If area above is an attic or insulated area,
install restop above framed hole.
45° Elbow
Ceiling Firestop
Figure 16 - Offset with Wall Strap and 45°
Elbows
www.desatech.com
If area above is a living space, install
restop below framed hole.
Figure 17 - Installing Firestop
120441-01A12
Page 13
VENTING INSTALLATION
Continued
5. Place the ashing over the pipe section(s)
extending through the roof. Secure the
base of the ashing to the roof and framing with roong nails. Be sure roong
material overlaps the top edge of the
ashing as shown in Figure 16, page 12.
There must be a 1" clearance from the
vent pipe to combustible materials.
6. Continue to add pipe sections until the
height of the vent cap meets the minimum
building code requirements described in
Figure 6 on page 7. Note: You must increase vent height for steep roof pitches.
Nearby trees, adjoining rooines, steep
pitched roofs and other similar factors
may cause poor draft or down-drafting
in high winds. Increasing the vent height
may solve this problem.
7. Twist-lock the vent cap onto the last section of vent pipe.
Note: If the vent pipe passes through any oc-
cupied areas above the rst oor, including
storage spaces and closets, you must enclose
pipe. You may frame and sheetrock the enclosure with standard construction material.
Make sure and meet the minimum allowable
clearances to combustibles. Do not ll any of
the required air spaces with insulation.
Vertical Termination Congurations
Figure 17 shows the congurations for vertical
termination.
OUTSIDE AIR FLEX INSTALLATION
Outside air ex installation is required for both
horizontal and vertical venting installation.
There are 2 outside air ex kits available for
purchase (see Parts List for Venting Kits and
Components, page 14).
Construct a 4 1/2" x 4 1/2" framing or opening
on exterior wall (see Figure 19). Install outside
air vent termination in a location that would
not eventually be obstructed by bushes, snow
or other obstructions. Locate outside air vent
near replace to make ex duct installation
easier.
Flex Venting
Outside Air Vent
Termination
Secure Both Ends
of Flex Using
Hi-Temp Duct Tape
Figure 19 - Outside Air Flex Duct
Vertical
Venting
V = 40' max.
Figure 18 - Vertical Venting
Conguration
120441-01A13
www.desatech.com
HIGH ALTITUDE INSTALLATION
Your DESA direct vent replace has been
tested and approved for elevations from 0-
2000 feet (USA) and elevations from 0-4500
feet (Canada).
When installing at an elevation above 2000
feet (in the USA), you may need to decrease
the input rating by changing the existing
burner orice to a smaller size. Reduce input
4% for each 1000 feet above sea level. Check
with your local gas company for proper orice
size identication.
WS-58 Wall Strap
CS-58 Cathedral Ceiling Support
FP-58 Firestop Plate
SF-58 Stucco Flashing For use with HTS-58
RF-58 Flat Roof Flashing
AK6-37 37" Outside Air Flex Vent Kit
AK6-75 75" Outside Air Flex Vent Kit
FIREPLACE
INSTALLATION
CHECK GAS TYPE
Use proper gas type for the replace unit you
are installing. If you have conicting gas types,
do not install replace. See retailer where you
purchased the replace for proper replace
according to your gas type.
INSTALLING GAS PIPING TO
FIREPLACE LOCATION
WARNI N G : A q u a li f i ed
service person must connect
replace to gas supply. Follow
all local codes.
CAUTION: For propane/LP
units, never connect replace
directly to the propane/LP supply. This heater requires an external regulator (not supplied).
Install the external regulator
between the replace and propane/LP supply.
WARNING: For natural gas,
ne ver connect f i replace to
private (non-utility) gas wells.
This gas is commonly known
as wellhead gas.
Installation Items Needed
Before installing replace, make sure you
have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas connector (if allowed by local codes)
* A CSA design-certied equipment shutoff
valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase
the CSA design-certied equipment shutoff
valve from your retailer.
www.desatech.com
120441-01A14
Page 15
FIREPLACE
INSTALLATION
Continued
For propane/LP connection only, the installer
must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure
to between 11" and 14" of w.c. pressure. If
you do not reduce incoming gas pressure,
replace regulator damage could occur. Install
external regulator with the vent pointing down
as shown in Figure 20. Pointing the vent down
protects it from freezing rain or sleet.
CAUTION: Use only new,
black iron or steel pipe. Internally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
1/2" diameter or greater to allow
proper gas volume to replace.
If pipe is too small, undue loss
of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from replace
(see Figure 21).
IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location.
The main gas valve is for turning on or shutting
off the gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff
valve to replaces.
Propane/LP
Supply Tank
External
Regulator
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged replace valves.
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
We recommend that you install a sediment
trap/drip leg in supply line as shown in Figure
21. Locate sediment trap/drip leg where it is
within reach for cleaning. Install in piping sys-
tem between fuel supply and replace. Locate
sediment trap/drip leg where trapped matter
is not likely to freeze. A sediment trap traps
moisture and contaminants. This keeps them
from going into replace gas controls. If sediment trap/drip leg is not installed or is installed
wrong, replace may not run properly.
CSA Design-Certied
Equipment Shutoff Valve
with 1/8" NPT Tap*
Approved
Flexible
Gas Line
3" Minimum
Cap Pipe Tee
Joint Nipple
Sediment Trap/
Figure 21 - Gas Connection
* The CSA design-certied equipment shutoff
valve may be supplied with the appliance or
you can purchase it from your retailer.
Natural - From
Gas Meter (5.5"
W.C. to 10.5" W.C.
Pressure)
Propane/LP From
External Regulator
(11" W.C. to 14"
W.C. Pressure)
Drip Leg
Vent
Pointing
Down
Figure 20 - External Regulator with Vent
Pointing Down (Propane/LP Only)
120441-01A15
www.desatech.com
Page 16
FIREPLACE
INSTALLATION
Continued
CONNECTING FIREPLACE TO GAS
SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not
provided)
1. Route exible gas line (provided by installer) from equipment shutoff valve to
replace. Route exible gas supply line
through one of the access holes on side
of replace.
2. Attach exible gas line from gas supply to
control valve (see Figure 22).
3. Check all gas connections for leaks. See
Checking Gas Connections.
Red Surface
Equipment
Shutoff
Valve
1/2" NPT
Incoming
Gas Line
Note: Wire Connections Not Shown for Clarity
Figure 22 - Connecting Flexible Gas Line
Flexible
Gas Line
Do NOT
Kink
to Electronic Valve
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
Indicates For
Propane/LP Use
Only
Inlet
Pressure
Tap
Outlet
Pressure
Tap
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect replace and its individual
equipment shutoff valve from gas supply
piping system. Pressures in excess of
1/2 psig (3.5 kPa) will damage replace
gas regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas replace or opening
main gas valve located on or near gas
meter for natural gas replace or using
compressed air.
4. Check all joints of gas supply piping system. Apply noncorrosive leak detection
uid to all joints. Bubbles forming show a
leak. Correct all leaks at once.
5. Reco nnect fir eplac e and equipme nt
shutoff valve to gas supply. Check recon-
nected ttings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Clos e equipm ent shutoff valve (see
Figure 23).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas replace or opening
main gas valve located on or near gas
meter for natural gas replace or using
compressed air.
3. Check all joints from propane/LP supply
tank or gas meter to equipment shutoff
valve (see Figure 24 or Figure 25, page
17). Apply noncorrosive leak detection
uid to all joints. Bubbles forming show a
leak.
4. Correct all leaks at once.
Equipment
Shutoff Valve
Open
WARNING: Never use an open
ame to check for a leak. Apply
noncorrosive leak detection uid
to all joints. Bubbles forming show
a leak. Correct all leaks at once.
www.desatech.com
Closed
Figure 23 - Equipment Shutoff Valve
120441-01A16
Page 17
FIREPLACE
INSTALLATION
Continued
Propane/LP
Supply Tank
Figure 24 - Checking Gas Joints for
Equipment Shutoff Valve
Gas Valve
Propane/LP Gas Fireplace
REMOVING/REPLACING GLASS
DOORS
CAUTION: Do not operate
this replace with a broken glass
door panel or without the glass
door panel securely in place.
For replacement part informa-
tion see Replacement Parts,
page 24.
CAUTION: Wear gloves and
safety glasses while handling
or removing broken glass. Do
not remove if glass is hot. Keep
children and pets away from
glass.
Equipment
Shutoff Valve
Gas
Meter
Gas Valve
Figure 25 - Checking Gas Joints for
Natural Gas Fireplace
PRESSURE TESTING FIREPLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 23, page 16).
2. Open propane/LP supply tank valve for
propane/LP replace or main gas valve
located on or near gas meter for natural
gas replace.
3. Make sure control knob of replace is in
the OFF position.
4. Check all joints from equipment shutoff
valve to gas valve (see Figure 24 or Figure
25). Apply noncorrosive leak detection
uid to all joints. Bubbles forming show a
leak. Correct all leaks at once.
5. Light replace (see Operating Fireplace,
page 21). Check all other internal joints
for leaks.
6. Turn off replace (see To Turn Off Gas to
Appliance, page 21).
WARNING: If replace has
been running, turn off replace.
Let cool before removing glass
doors.
WARNING: More than one
person is required when replacing glass.
Models DVF-36S and DVF-36H have only an
inner door to be removed/replaced. Models
DVF-36SC and DVF-36HC have an inner,
middle and outer door.
Installing Middle Door (DVF-36SC/HC
Models Only)
Middle door hangs on 2 hinges from top of
inner glass door (see Figure 26, page 18).
1. Remove middle door from packaging.
2. Angle middle door so top goes into replace
rst. Hang middle door on brackets at top
of inner door (see Figure 26, page 18).
Installing Outer Door (DVF-36SC/HC
Models Only)
1. Remove outer door from packaging.
2. There are three spring loaded pins on
outer door. Set pins to the locked position
(see Figure 26, page 18).
3. Position outer door so pins line up with
mating hinges on replace. Holding door
in place, release locks on spring loaded
pins (see Figure 26, page 18).
120441-01A17
www.desatech.com
Page 18
LOCK
UNLOCK
Spring
Loaded Pin
Outer
Door
Middle
Door
FIREPLACE INSTALLATION
Continued
Pin Located on
Middle Door
Hinge
Inner
Door
Hook Located
on Inner Door
Figure 26 - Removing/Installing Middle Door
Removing and Installing Inner Door
Inner door is factory installed.
1. Open outer door. Secure door in open
position to avoid accidental breakage.
2. Remo ve mid dle door by liftin g from
hinges (see Figure 26). Set aside to avoid
scratches or damage.
3. Remove screws from two side trims (see
Figure 27, page 19).
4. Remove side bricks from top to bottom
by prying out of housings(see Figure 27,
page 19).
5. Remove bottom bricks, starting with
middle section (see Figure 27, page 19).
6. Remove screen and rod (see Figure 27,
page 19).
www.desatech.com
7. While holding inner door, release 6 latches,
3 top and 3 bottom (see Figure 28, page
19).
8. Slowly tilt open glass at a 30° angle and lift
up to release glass from bottom retainer
(see Figure 28, page 19).
9. Follow these instructions in reverse to
reinstall.
120441-01A18
Page 19
Lock
Unlock
FIREPLACE INSTALLATION
Continued
Side
Bricks
Side Trim
Side
Trim
Screen
and Rod
Figure 27 - Removing/Installing Brick, Side Trim and Screen
Left
Bottom Brick
Middle Bottom Brick
Side Bricks
Right Bottom Brick
LAVA ROCK, EMBER FLAKES AND
SCRAP LOG INSTALLATION
Lava rock, ember akes and scrap log pieces
are included with your replace. Install these
items while glass doors are open and/or
removed.
120441-01A19
Inner Door
Figure 28 - Removing/Installing Inner Door
1. Follow instructions from Removing and
Installing Inner Door, page 18, to move
glass out of the way of this installation.
2. Place lava rock around base of burner.
Make sure burner ports are not covered
(see Figure 29, page 20).
www.desatech.com
Page 20
FIREPLACE
INSTALLATION
Continued
3. Place ember akes around front and sides
of burner and on burner ports (see Figure
30). This will create the glowing ember
appearance as the flame touches the
ember akes. Do not block burner ports
by overlapping ember akes in one area. It
is not necessary to use all ember material
provided.
4. Place scrap log pieces randomly as shown
in Figure 31 on lava rock and around (but
not on) burner ports.
Lava
Rock
Figure 29 - Installing Lava Rock
WALL SWITCH INSTALLATION
Installation of a wall switch allows you to
activate gas control valve and turn replace
on and off. Wall switch is to be connected to
incoming 120 volt regular household wiring
that supplies electricity to replace.
REMOTE CONTROL INSTALLATION
(MODEL WRC)
Note: If using wireless hand-held remote
control, the wall switch must be in the ON
position to be operational. The remote control
then becomes the switching mechanism for
replace operation.
1. Remove center brick/control cover.
2. The WRC model receiver does not require
a battery. To install receiver:
a. Plug short extension cord into replace
receptacle.
b. Plug receiver uinit into extension cord.
c. Plug ignition module into receiver unit
(see Figure 32).
3. Activate remote handset battery by removing insulating tab on back of handset
(see Figure 33). Battery is included pre-
installed.
4. Once battery is activated, the unit is ready
to use.
5. Replace center brick/control cover.
Ember
Flakes
Figure 30 - Installing Ember Flakes
Scrap Log Pieces
Figure 31 - Installing Scrap Log Pieces
www.desatech.com
Fireplace
Receptacle
Extension
Cord
Figure 32 - Installing the WRC Remote
Receiver
Battery Cover
12 Volt Battery
Back of
Handset
Figure 33 - Installing Battery into Back of
Handset
Remote
Control
Receiver
Ignition
Module Plug
Pull to Remove
Insulation Tab
120441-01A20
Page 21
EV2
EV1
ORANGE
IGNITOR LEAD
GREEN
PILOT
TRANSFORMER
IS1070B
SYNETEK CONTROLS INC
24V AC
E4
E2
E3
E6
RED
E8
E12
BLUE
120V AC
GROUND
120
VAC
ADAPTER/
REMOTE
RECEIVER
J-BOX
BLACK
WHITE
WIRING DIAGRAM
OPERATION
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not fol-
low these instructions exactly,
a re or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance is equipped with an igni-
tion device which automatically lights
the pilot. Do not light pilot by hand.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to
smell next to the oor because some
gas is heavier than air and will settle
on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor's phone. Follow the
gas supplier's instructions.
120441-01A21
www.desatech.com
C. Do not use this appliance if any part
has been under water. Immediately call
a qualied service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
LIGHTING
INSTRUCTIONS
NOTICE: During initial operation
of new replace, burning logs
will give off a paper-burning
smell. Orange ame will also
be present. Open damper or
window to vent smell. This will
only last a few hours.
1. STOP! Read the safety information
above.
2. Turn off all elect ric powe r to the
fireplace.
3. Turn wall switch to the OFF position.
4. Remove center brick/control cover.
5. Turn equipment shutoff valve clockwise to the OFF position (see
Figure 34, page 22). Do not force.
Page 22
OPERATION
Continued
6. Wait ve (5) minutes to clear out any
gas. Then smell for gas, including near
the oor. If you smell gas, STOP! Follow “B” in the safety information on
page 21. If you don't smell gas, go to
the next step.
7. Turn the equipment shutoff valve counterclockwise to the ON position.
Do not force.
8. Replace center brick/control cover.
9. Turn on all electric power to appliance.
10. Turn wall switch to the ON position.
11. Visually locate pilot. Ignitor should
begin to spark and main burner should
ignite once ame appears at pilot.
• If lighting appliance for the rst time
each season, it may take several at-
tempts before supply gas can reach
pilot and main burners.
• If appliance will not stay lit after several
attempts, follow instructions under To
Turn Off Gas To Appliance and call your
service technician or gas supplier.
Equipment
Shutoff Valve
Figure 34 - Turning Equipment Shutoff
Valve to the OFF Position
Pilot
Burner
Pilot Adjustment
Screw
Sensing
Rod
Ignitor
REMOTE
OPERATION
1. Turn equipment shutoff valve to ON position. You can now turn the burner on and
off with hand-held remote control unit.
IMPORTANT: Be sure to press ON/OFF
buttons on hand-held remote control
unit for up to 3 seconds to assure
proper operation.
2. Press ON/OFF button to turn burner on
and off.
INSPECTING BURNERS
Check pilot ame pattern and burner ame
patterns often.
PILOT ASSEMBLY
The pilot assembly is factory preset for the
proper ame. Alterations may have occurred
during shipping and handling. The pilot is
located on the right hand side of the burner.
The ame must envelope 1/4" of top of the
ignitor/sensor and grounding stem.
If your pilot assembly does not meet these
requirements:
• Turn the adjustment screw marked PILOT
clockwise to decrease or counterclockwise
to increase the ame to proper size (see
Figure 34). Do not remove the adjustment
screw.
• see Troubleshooting, page 25
Pilot
Burner
Sensing
Rod
Ignitor/
Sensor
Figure 35 - Pilot
TO TURN OFF GAS
TO APPLIANCE
1. Turn off the wall switch.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove center brick/control cover.
4. Turn equipment shutoff valve clockwise to OFF. Do not force.
5. Replace center brick/control cover.
www.desatech.com
Figure 36 - Correct Pilot Flame Pattern
BURNER FLAME PATTERN
Burner ames will be steady; not lifting or oating. Flame patterns will be different from unit
to unit and will vary depending on installation
type and weather conditions.
If the vent conguration is installed incorrectly,
the ames will lift or "ghost". This can be dangerous. Inspect the ames after installation to
ensure proper installation and performance.
120441-01A22
Page 23
INSPECTING BURNERS
Continued
Figure 37 shows a typical ame pattern.
If burner ame pattern differs from that de-
scribed:
• turn replace off (see To Turn Off Gas to
Appliance, page 21)
• see Troubleshooting, page 25
Figure 37 - Typical Flame Pattern
CLEANING AND
MAINTENANCE
WARNING: Turn off replace
and let cool before cleaning.
CAUTION: You must keep control areas, burners and circulating
air passageways of replace clean.
Inspect these areas of replace
before each use. Have replace
inspected yearly by a qualied
service person. Fireplace may
need more frequent cleaning due
to excessive lint from carpeting,
bedding material, pet hair, etc.
GLASS DOORS
WARNI N G : Do not use
abrasive cleaners as this may
damage glass. Use a nonabrasive household glass cleaner to
clean glass. Do not clean glass
when hot.
Glass must be cleaned periodically. During
start-up it is normal for condensation to form
on the inside of the glass causing lint, dust and
other airborne particles to cling to the glass
surface. During initial start-up a slight lm may
form on the glass due to paint curing. The
glass should be cleaned several times with a
non-ammonia, nonabrasive household clean-
er and warm water after the rst two weeks
of operation. Thereafter, clean the glass two
or three times during each heating season,
depending on the usage and circumstances
present. Refer to Removing/Replacing Glass Door, page 17 of this manual when removing
glass door for cleaning.
WARNING: Only parts supplied by the ma n u f a c t u r e r
should be used when replacing
broken or damaged glass door
panels (see Replacement Parts,
page 24). Glass door panel are
complete units. No substitute
materials may be used.
CAUTION: Wear gloves and
safety glasses while handling
or removing broken glass. Do
not remove if glass is hot. Keep
children and pets away from
glass.
If glass has been broken, carefully remove
glass door (see Removing/Replacing Glass
Doors, page 17). Vacuum all glass pieces
with a shop vac.
WARNING: Handle glass door
panels with care. Do not strike,
slam or otherwise abuse glass.
Do not operate replace with the
glass door unlatched, removed,
cracked or broken.
120441-01A23
www.desatech.com
CAUTION: Do not vacuum if
pieces are hot.
Use only glass door replacement intended for
this replace (see Replacement Parts, page
24 for detail on ordering). No substitutions
may be made. See Removing/Replacing
Glass Doors, page 17 for instructions for
replacing glass doors.
Page 24
CLEANING AND
MAINTENANCE
Continued
WARNING: Do not operate replace with glass door unlatched,
removed, cracked or broken.
PILOT AND BURNERS
• Remove material before cleaning burners
and replace when cleaning is complete.
• Burner and controls should be cleaned
with compressed air to remove dust, dirt
or lint.
• Use a vacuum cleaner or small, soft bristled
brush to remove excess dust, dirt or lint.
LOGS
• Use a vacuum cleaner to remove any
carbon buildup on logs.
• Replace material periodically as needed.
See Replacement Parts.
VENTING SYSTEM
Conduct annual inspection of the venting
system following these guidelines:
1. Check areas of venting system that are
exposed to the weather for corrosion (rust
spots or streaks and, in extreme cases,
holes). Have these items replaced immediately by a qualied service person.
2. Remove the vent cap and shine a ash-
light into the vent. Remove any foreign
material.
3. Check for evidence of excessive con-
densation. Continuous condensation can
cause corrosion of caps, pipes and ttings
and can be caused by having excessive
lateral runs, too many elbows or exterior
portions of the system being exposed to
cold weather.
4. Inspect joints to verify that no pipe section
or tting has been disturbed and loos-
ened. Check mechanical supports such
as wall straps for rigidity.
TECHNICAL SERVICE
You may have further questions about installation, operation or troubleshooting. If so,
contact DESA’s Customer Service Department at 1-866-672-6040. When calling, please
have your model and serial numbers of your
heater ready.
You can also visit DESA’s technical service
web site at www.desatech.com.
SPECIFICATIONS
DVF-36S-N, DVF-36H-N, DVF-36SC-N,
DVF-36HC-N
• Rating: 66,000 Btu/hr
• Gas Type: Natural Gas Only
• Ignition: Electronic
• Manifold Pressure: 3.5" w.c.
• Minimum Inlet Supply Pressure: 7.0" w.c.
DVF-36S-P, DVF-36H_P, DVF-36SC-P,
DVF-36SH-P
• Rating: 62,000 Btu/hr
• Gas Type: Propane/LP Gas Only
• Ignition: Electronic
• Manifold Pressure: 10.0" w.c.
• Minimum Inlet Supply Pressure: 11.0" w.c.
REPLACEMENT PARTS
Note: Use only original replacement parts.
This will protect your warranty coverage for
parts replaced under warranty.
PARTS UNDER WARRANTY
Contact authorized retailers of this product.
If they can not supply original replacement
part(s), call DESA’s Customer Service Department at 1-866-672-6040.
When calling DESA, have ready
• your name
• your address
• model and serial numbers of your replace
• how replace was malfunctioning
• type of gas used (propane/LP or natural
gas)
• purchase date
Usually, we will ask you to return the part to
the factory.
PARTS NOT UNDER WARRANTY
Contact authorized retailers of this product.
If they can not supply original replacement
part(s), call DESA at 1-866-672-6040 for
referral information.
When calling DESA, have ready
• model number of your replace
• the replacement part number
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• replace will not produce specied heat
• propane/LP gas supply might be low (pro-
pane/LP units only)
You may feel your gas pressure is too low. If
so, contact your local gas supplier.
www.desatech.com
120441-01A24
Page 25
TROUBLESHOOTING
WARNING: Turn off replace and let cool before servicing. Only
a qualied service person should service and repair replace.
CAUTION: Never use a wire, needle or similar object to clean
pilot. This can damage pilot unit.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
Ignitor will not spark or pilot
will not light
POSSIBLE CAUSE
1. No gas supply or shutoff
valve is OFF
2. Air in gas line
3. Construction debris clog-
ging pilot orice
4. Low gas pressure
5. Kinked pilot line
6. C o n tr o l v al v e is n ot
opening
7. No power to unit or the
ignition module or power
transformer is bad
REMEDY
1. Check to see if you have gas
supply and that equipment
shutoff valve is opened
2. Repeat lighting procedure
several times to purge all air
out of lines. If after repeated
attempts appliance does
not light, call for qualied
service and repair
3. Remove debris and dirt,
inspect and clean any other
possible obstructions
4. Contact your gas supplier to
check pressure
5. Have a qualied technician
replace pilot line
6. Replace control valve (Refer to Replacement Parts,
page 24)
7. Check that main power is
on and that all wire connections are made correctly
to the ignition model (see
Wiring Diagram, page 21).
Check for 24 VAC at the
secondary side of the transformer. If 24 VAC is present
and the module does not
operate, have the module
replaced otherwise have
the transformer replaced
120441-01A25
www.desatech.com
Page 26
OBSERVED PROBLEM
Pilot will not stay lit
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Loose wiring on ignitor wire
to ignition module and/or
poor groun d to ignit ion
module
2. Pilo t flame too lo w to
sense
REMEDY
1. Check wiring connection.
Refe r to wir ing diagram
(see Wiring Diagram, page
21) and/or check ground
wire to ignition module
2. Clean and adjust pilot burner and check gas supply
and inlet pressure to unit
Note: Have a qualied tech-
nician replace pilot assembly if broken or corroded
No gas to burner, although wall
switch and valve are set to the
ON position
Frequent pilot outage
Fireplace produces a clicking/
ticking noise just after burner
is lit or shut off
Slight smoke or odor during
initial operation
1. Wall switch wires defective
or too long
1. Pilo t flam e may be too
low, causing safety pilot to
“drop out”
2. Improper venting or excessive blockage
1. Me t al exp a ndi n g whil e
heating or contracting while
cooling
1. Residues from manufacturing processes and logs
curing
1. Check electrical connections
1. Clean and adjust pilot ame
for maximum ame impinge-
ment on thermopile
2. Have the vent system inspected, including the termination cap. Remove any
restriction or obstruction
1. This is normal with most
fireplaces. If noise is ex-
cessive, contact qualied
service person
1. Problem will stop after a few
hours of operation
www.desatech.com
120441-01A26
Page 27
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
OBSERVED PROBLEM
Gas odor even when control
knob is in OFF position
Gas odor during combustion
Glass soots
Dark residue on logs or
inside of replace
POSSIBLE CAUSE
1. Gas le ak. See Warn -
ing statement at top of
page
2. Control valve defective
1. Foreign matter between
control valve and burner
2. Gas le ak. See Warn -
ing statement at top of
page
1. Debris around burner air
mixer
2. Improper vent
conguration
1. Air holes at burner inlet
blocked
2. B u rn e r f la m e h ol e s
blocked
3. Improper venting or excessive blockage
4. Ex ces sive amou nts of
embers and pan material
REMEDY
1. Locate and correct all leaks
(see Checking Gas Connec-
tions, page 16)
2. Replace control valve
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks
(see Checking Gas Connec-
tions, page 16)
1. Inspect the opening at the base
of the burner to see that it is
NOT packed with any type of
material
2. Check vent conguration specication (see Venting Installation,
page 8)
1. Clean out air holes at burner
inlets. Periodically repeat as
needed
2. Remove blockage
3. Have the vent system inspected, including the termination
cap. Remove any restrictions
or obstruction
4. Clear excess embers until a
minimum gap of 1/2" remains
under the grate
Always specify model and serial numbers when communicating with the factory.
The only warranty applicable is our standard written warranty. We make no other warranty, expressed or
implied.
LIMITED WARRANTY
DIRECT VENT FIREPLACE
DESA Heating, LLC warrants this product to be free from defects in materials and components for two
(2) years from the date of rst purchase, provided that the product has been properly installed, operated
and maintained in accordance with all applicable instructions. To make a claim under this warranty the
Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s)
required to restore this heater to proper operating condition and an allowance for labor when provided by
a DESA Heating, LLC Authorized Service Center. Warranty part(s) MUST be obtained through authorized
retailers of this product and/or DESA Heating, LLC who will provide original factory replacement parts.
Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by
a qualied installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear
or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or
defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all
such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE
OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED
WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO TWO (2)
YEARS ON ALL COMPONENTS FROM THE DATE OF FIRST PURCHASE; AND DESA HEATING,
LLC’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA
HEATING, LLC SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING
INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation
of incidental or consequential damages, so the above limitation on implied warranties or exclusion or
limitation on damages may not apply to you.
This warranty gives you specic legal rights and you may also have other rights that vary from state
to state.
For information about this warranty write:
Desa Heating, LLC
2701 Industrial Drive
P.O. Box 90004
Bowling Green, KY 42102-9004
www.desatech.com
NOT A UPC
120441-01
Rev. A
02/07
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.