Design Dynamics DVF-36S-N User Manual

Page 1
DIRECT VENT FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
NATURAL PROPANE/LP GAS MODELS GAS MODELS DVF-36S-N DVF-36S-P Stacked Brick/Standard Glass DVF-36H-N DVF-36H-P Herringbone Brick/Standard Glass DVF-36SC-N DVF-36SC-P Stacked Brick/Cool Touch Glass DVF-36HC-N DVF-36HC-P Herringbone Brick/Cool Touch Glass
WARNING: If the information in this manual is not fol-
lowed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a quali-
ed installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance CONSUMER: Retain this manual for future reference.
For more information, visit www.desatech.com
Page 2
TABLE OF CONTENTS
Safety Information ............................................... 2
Product Identication ........................................... 4
Local Codes......................................................... 4
Product Features ................................................. 4
Preinstallation ...................................................... 5
Location of Termination Cap ................................ 7
Venting Installation............................................... 8
Fireplace Installation.......................................... 14
Wiring Diagram .................................................. 21
Operation ........................................................... 21

SAFETY INFORMATION

Inspecting Burners............................................. 22
Cleaning and Maintenance ................................ 23
Specications .................................................... 24
Replacement Parts ............................................ 24
Service Hints ..................................................... 24
Technical Service............................................... 24
Troubleshooting ................................................. 25
Illustrated Parts Breakdown and Parts List........ 28
Warranty Information ...........................Back Cover
WARNING: Improper instal-
lation, adjustment, alteration,
service or maintenance can
cause injury or property damage.
Refer to this manual for correct
installation and operational procedures. For assistance or
additional information consult
a qualified installer, service agency or the gas supplier.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certied kit is used.
State of Massachusetts: The
installation must be made by a licensed plumber or gas tter
in the Commonwealth of Mas-
sachusetts.
WARNING: This product
contains and/or generates
chemicals known to the State of California to cause cancer or
birth defects or other reproduc­tive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op­erate or service this replace. Improper use of this replace can cause serious injury or death from burns, fire, explosion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This vented gas replace is a sealed combus­tion gas replace designed for residential applications. This replace must be installed
with DESA vent pipe components and ter­minations.
Outside airex installation is required for both horizontal and vertical installation.
This replace complies with the National Safe­ty Standards and is listed and tested by OMNI Test Laboratories, Inc. to ANSI Z21.50b-2005
standard as vented gas replace. This replace must be installed by a qualied
(certied or licensed) service person. It brings
in fresh air for combustion through the outer pipe and combustion gases are exhausted through the inner pipe. If the glass door as­sembly and venting pipe are not properly seated, connected and sealed, carbon mon-
oxide leakage (spillage) can occur.
www.desatech.com
120441-01A2
Page 3
SAFETY INFORMATION
Continued
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If you have these signs, the replace may not
be working properly. Get fresh air at once!
Have replace serviced. Some people are
more affected by carbon monoxide than oth­ers. These include pregnant women, people with heart or lung disease or anemia, those
under the inuence of alcohol and those at
high altitudes. Natural and Propane/LP Gas: Natural and
propane/LP gas are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of
this replace.
WARNING: Any change to this replace or it’s controls can be dangerous. Do not modify this replace under any circum­stances. Any parts removed for servicing must be replaced prior to operating replace.
WARNING: Do not use a blow­er insert, heat exchanger insert or other accessory not approved for use with this replace.
WARNING: This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certied kit is used.
WARNING: Do not allow fans
to blow directly into the replace. Avoid any drafts that alter burner ame patterns.
Due to high temperatures, the appliance should be located out of trafc and away from furniture and draperies.
Do not place clothing or other ammable material on or near the appliance. Never place any objects on the appliance.
Do not use this replace to cook food or burn paper or other am­mable material.
This replace reaches high tem­peratures. Keep children and
adults away from hot surface to
avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow sur­face to cool before touching.
Carefully supervise young chil-
dren when they are in the room
with replace.
Keep the area around your replace clear of combustible materials, gasoline and other ammable vapor or liquids. Do not run replace where these are used or stored.
1. For propane/LP replace, do not place propane/LP supply tank(s) inside any
struc tu re. Locate prop an e/ LP supply
tank(s) outdoors. To prevent performance
problems, do not use propane/LP fuel tank of less than 100 lb. capacity.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor ’s phone. Follow the gas supplier's instructions
• if you cannot reach you gas supplier, call
the re department.
120441-01A 3
www.desatech.com
Page 4
SAFETY INFORMATION
Continued
3. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains
or other combustible (ammable) objects
can make contact with the fireplace front
• in high trafc areas
4. Turn fireplace off and let cool before servicing, installing or repairing. Only a
qualied service person should install, service or repair this replace. Have re­place inspected annually by a qualied
service person.
5. You must keep control compartments, burners and circulating air passages
clean. More frequent cleaning may be
needed due to excessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before
cleaning replace.
6. Have venting system inspected annually by
a qualied service person. If needed, have
venting system cleaned or repaired. See Cleaning and Maintenance, page 23.
7. Do not use any solid fuels (wood, coal,
paper, cardboard, etc.) in this replace. Use only the gas type indicated on re-
place nameplate.
8. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code,
ANSI/NFPA 70 or the Canadian Electrical Code, CSA C22.1.
9. Do not use replace if any part has been
exposed to or under water. Immediately
call a qualied service person to arrange
for replacement of the unit.
10. Do not operate replace if any log is
broken.
11. Do not operate replace with glass door
removed, cracked or broken.
12. Provide adequate clearances around air
openings.
PRODUCT
IDENTIFICATION
Nailing Flange
Outer Glass Door
Aniron
Standard Brick Refractories
Center Brick/ Control Cover
Figure 1 - Direct Vent Fireplace
(DVF-36SC Shown)
Flue Collar
Log Set

LOCAL CODES

Install and use replace with care. Follow all
local codes. In the absence to local codes, use the current National Fuel Gas Code ANSI
Z223.1/NFPA 54* (USA) or the current CSA­B149.1 Installation Code (Canada).
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269

PRODUCT FEATURES

These are a few facts that can help you under-
stand and enjoy your direct vent replace:
• The venting system may be routed to the outside of your home in several ways. It
may vent through the roof (vertical) or it
may vent to an outside/exterior wall (hori-
zontal). The vent pipe installation is very
important to allow for proper operation. You must follow the venting instructions
very carefully for either vertical or horizontal
applications.
www.desatech.com
120441-01A4
Page 5
D
RW
PRODUCT FEATURES
Continued
• This replace may be installed in any room
of your house provided all local codes and these installation instructions are followed.
• Each time you turn on your replace, you
may notice some amount of condensation
on the inside of the replace glass. This
is normal and will disappear after 10-20 minutes of operation.
• Your direct vent gas fireplac e system
(replace and venting) is a balanced and sealed gas operating unit. It requires ap-
proximately 10-20 minutes of operating
time before the ame pattern stabilizes.
• Models DVF-36S and DVF-36H have a standard glass inner door. Models DVF­36SC and DVF-36HC have the standard glass inner door with a middle glass door and outer cool touch glass door.

PREINSTALLATION

LOCATION AND SPACE REQUIREMENTS
Determine the safest and most efcient loca­tion for your direct vent replace. Make sure
that rafters and wall studs are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some common locations. Be aware of all restrictions and precautions before
deciding the exact location for your replace
and termination cap.
When deciding the location of your replace,
follow these rules:
• Do not connect this replace venting to a chimney ue serving a separate solid-fuel burning replace or appliance.
• Due to high temperatures, do not locate this
replace in high trafc areas, windy or drafty
areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your replace is to be installed directly on
carpeting, vinyl tile or any combustible mate­rial other than wood, it must be installed on a metal or wood panel extending the full width
and depth of the replace (see Figure 3).
• Your replace is designed to be used in zero clearance installations. Wall or framing
material can be placed directly against any exterior surface on the back, sides or top of your replace, except where standoff spac­ers are integrally attached. If standoff spac-
ers are attached to your replace, these
spacers can be placed directly against wall or framing material. See framing details on page 6.
• When locating termination cap, it is impor­tant to observe the minimum clearances shown in Figure 7, page 7.
• If recessing into a wall, you can avoid extra
framing by positioning your replace against
an already existing framing member.
• Do not recess termination cap into a wall or siding.
• You may paint the termination cap with
450º F (232º C) heat-resistant paint to coordinate with the exterior nish.
• There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24" from the front of the termination cap and the front of outside air vent.
• Do not locate termination cap and outside air vent where excessive snow or ice build up may occur. Be sure to clear vent termination area after snow falls to prevent accidental blockage of venting system. When using snow blowers, do not direct snow towards vent termination area.
26"
Flush with a wall
Through exterior wall enclosed in a chase
Corner installation
27 5/8"
43"
Figure 3 - Fireplace Bottom Dimensions
Figure 2 - Common Fireplace Locations
120441-01A 5
www.desatech.com
Page 6
PREINSTALLATION
56 3/4"
43 1/4"
33" 28"
41 3/8"
82 1/8"
43 1/4"
43"
199/16"
58 1/4"
Nailing Tabs
C
B
A
D
E
F
G
3
2
1
4
5
6
7
Wall
Continued
CLEARANCES
Minimum clearances to combustibles for the
replace are as follows:
*Back and sides 0" Perpendicular walls 6" Floor 0" Ceiling to louver opening 42" Front 36" Top of Standoffs 0" Vent (See venting instructions
for specic venting clearances.)
Combustible material with a maximum thick-
ness of 5/8" may be ush with the top front of replace.
* For back and sides of replace, do not pack
with insulation or other materials. 0" clear­ance to combustible materials are for framing purpose only.
NOTICE: This replace is intend­ed for use as supplemental heat. Use this replace along with your primary heating system. Do not install this replace as your primary heat source. If you have a central heating system, you may run system’s circulat­ing blower while using replace. This will help circulate the heat throughout the house.
Figure 4 - Framing Clearances with
Outside Air Flex Duct
Figure 5 - Framing Clearances for
Corner Installation
FRAMING AND FINISHING
Figure 4 shows typical framing of this replace.
Figure 5 shows framing for corner installation. All minimum clearances must be met.
If you are using a separate combustible man­tel piece, refer to Figure 6 for proper instal­lation height. You can install noncombustible
mantels at any height above the replace.
Note: Noncombustible mantels may discolor!
Mantel
Ref.
Depth Ref.
1 14" A 16" 2 12" B 14" 3 10" C 12" 4 8" D 10" 5 6" E 8" 6 4" F 6" 7 2" G 4"
Mantel
from Top of
Opening
Figure 6 - Clearances for Combustible
Mantels
www.desatech.com
120441-01A6
Page 7
Fixed
Closed
Openable
Fixed
Closed
V
V
V
V
V
V
V
V
X
X
V
X
G
G
J
F
B
B
K
N
H
I
A
N
E
L
D
B
M
A
C
B
V
V
A
G
G
B
TERMINATION CAP
AIR SUPPLY INLET
GAS METER RESTRICTED AREA
(TERMINATION PROHIBITED)
A = clearance above grade, veranda, porch, deck, or balcony [*12" (30.5 cm) minimum] B = clearance to window or door that may be opened [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] C = clearance to permanently closed window [minimum 12" (30.5 cm) recommended to prevent condensation on window] D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24" (61 cm) from the center-line of the terminal [18" (45.7 cm) minimum] E = clearance to unventilated soffit [12" (30.5 cm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within 36" (91.4 cm) horizontally from the center line of the regulator
I = clearance to service regulator vent outlet [*72" (182.9 cm) minimum] J = clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] K = clearance to a mechanical air supply inlet [*In Canada, 6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within 10 ft. (3 m) horizontally] L = † clearance above paved side-walk or a paved driveway located on public property [*84" (213.3 cm) minimum] M = clearance under veranda, porch, deck [*12" (30.5 cm) minimum ‡] N = clearance above a roof shall extend a minimum of 24" (61 cm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18" (45.7 cm)
† vent shall not terminate directly above a side-walk or paved driveway which is located between tw o single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A. Note: Local codes or regulations may require different clearances
A = 6" (15.2 cm)
Inside Corner
V
B
E
V
B = 6" (15.2 cm)
C = Maximum depth of 48" (121.9 cm) for recessed location D = Minimum width for back wall of recessed location ­ Combustible - 38" (965 mm) Noncombustible - 24" (61 cm) E = Clearance from corner in recessed location­ Combustible - 6" (15.2 cm) Noncombustible - 2" (5.1 cm)
Outside Corner Recessed Location
G
H
G = 12" (30.5 cm) minimum clearance
Balcony with No Side Wall
V
J
Combustible & Noncombustible H = 24" (61 cm) J = 20" (50.8 cm)
Balcony with Perpendicular Side Wall
C
D
C
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Openable

LOCATION OF TERMINATION CAP

120441-01A 7
Figure 7 - Minimum Clearances for Termination Cap
www.desatech.com
Page 8

VENTING INSTALLATION

NOTICE: Read these instruc-
tions completely before at­tempting installation.
These models are tested and approved for
use with DESA (direct vent) pipe components
and terminations. The venting system must terminate on the
outside of the structure and can not be at-
tached to a chimney or ue system serving a
separate solid fuel or gas burning appliance. A direct vent appliance must have its own venting system. DO NOT common vent this appliance.
These models are approved to be vented
either horizontally through an outside wall or
vertically through a roof or chase enclosure using the following guidelines:
• When venting system terminates horizon­tally on an outside wall, you may install a standoff if the termination cap is to be
installed directly on a combustible nish
such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may cause excessive temperatures which could
cause a re.
• Vent pipe air space clearances to com­bustibles are 1" on all sides except on the horizontal sections, which requires 2" clear­ance from the top of the pipe. Where the termination cap penetrates a combustible
wall, 1" air space clearance is required.
• Have replace and selected vent compo-
nents on hand to help determine the exact measurements when elbowing or offsetting.
Always use wall restops when penetrating walls and restops when penetrating ceil-
ings or attic spaces.
• For installation of replace at elevations of
4000 feet or greater, pay special attention
to venting requirement recommendations.
WARNING: Read all instruc-
tions completely and thoroughly before attempting installation.
Failure to do so could result in
serious injury, property damage or loss of life.
NOTICE: Failure to follow these in-
structions will void the warranty.
NOTICE: Do not seal termination
cap to vent pipe. Cap must be removable for vent inspection and maintenance.
INSTALLATION PRECAUTIONS
• We ar glo ves an d safe t y gla s ses fo r protection
• Use extreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the warranty on your venting system:
• In s tal lati on of any da mage d ven tin g component
• Unauthorized modication of the venting sys­tem (Do not cut or alter vent components)
• Installation of any component part not manufactured or approved by DESA
• Installation other than as instructed by these instructions
WARNING: This gas replace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serv­ing a separate solid fuel burning appliance. Each direct vent gas appliance must use a separate vent system. Do not use com­mon vent systems.
WARNING: Vent pipe air space clearances to combus­tibles are 1" on all sides except on the horizontal sections, which require 2" clearances from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
www.desatech.com
120441-01A8
Page 9
(Framing
Detail)
111/2"
111/2" Inside Framing
111/2"
8 1/2"
Vent Opening
Combustible Wall
Vent Opening
Noncombustible Wall
VENTING INSTALLATION
Continued
INSTALLATION PLANNING
There are two basic types of direct vent installation:
• Horizontal Termination
• Vertical Termination
Outside air ex installation is required for both horizontal and vertical installation (see page 13).
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations require only inner portion of wall restop. Hori­zontal installations using round termination require exterior portion of wall restop.
1. Set the replace in its desired location and determine the route your horizontal vent­ing will take. Do not secure the replace
until all venting has been installed. Some
installations require sliding the replace in and out of position to make nal vent-
ing connections. Figures 14 and 15 on
page 11 show different congurations for venting with horizontal termination that
will help you decide which application best suits your installation. Check to see if wall studs or roof rafters are in the path of your desired venting route. If they are,
you may want to adjust the location of the replace.
2. Direct vent pipe sections and compo­nents are designed with special twist-lock connections.
Twist- Lo ck Procedure: The female
ends of the pipes have locking lugs (in-
dentations). These lugs will slide straight
into matching slots on the male ends
of adjacent pipes. Push pipe sections
together and twist one section clockwise
approximately one-quarter turn until the sections are fully locked (see Figure 8).
Note: Horizontal runs of vent must be sup- ported every three feet. Use wall straps for this purpose.
3. Assemble the desired combination of pipe
and elbows to the replace ue collar. If
there are long portions of venting run, pre­assembled pipe sections may be installed as subassemblies for convenience.
4. Carefully determine the location where the vent pipe assembly will penetrate the outside wall. The center of the hole should line up with the center-line of the
horizontal vent pipe. Mark the wall for
an 11 1/2" x 11 1/2" square hole. Cut and
frame the square hole in the exterior
wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustib le material, such as masonry block or concrete, a 8 1/2" hole
with zero clearance is acceptable (see Figure 9).
Female Locking Lugs
Male Slots
Figure 8 - Vent Pipe Connections
Center of Hole
120441-01A 9
Figure 9 - Vent Opening Requirements
www.desatech.com
Page 10
VENTING INSTALLATION
Continued
WARNING: Do not recess
vent termination into any wall. This will cause a re hazard.
5. Noncombustible Exterior Wall: Position
the horizontal vent cap in the center of the
8 1/2" round hole and attach to the exterior wall with four wood screws provided. Before attaching the vent cap to exterior wall, run a bead of non-hardening mastic
(pliable sealant) around the outside edges
to make a seal between it and the outside wall. Note: The four wood screws provided should be replaced with appropriate fas­teners for stucco, brick, concrete or other
types of sidings (see Figure 10).
Combustible Exterior Wall: For vinyl
siding, stucco or wood exteriors, a siding standoff may be installed between the vent cap and exterior wall. The siding standoff prevents excessive heat from damaging the siding materials. Siding material must be cut to accommodate standoff. Bolt the vent cap to the stand­off. Apply non-hardening mastic around outside edge of standoff. Position the standoff/cap assembly in the center of the 11 1/2" square hole and attach to exterior wall with wood screws provided (see Fig-
ure 11). The siding standoff must sit ush
against the exterior fascia material.
6. Combustible Exterior Wall Only: Slide
the wall restop over the vent pipe before connecting horizontal run to vent cap (see Figure 12).
7. Carefully move replace, with vent as-
sembly attached, toward wall and insert
vent pipe into horizontal termination. The
pipe overlap should be a minimum of 1 1/4"
(see Figure 13, page 11).
8. Combustible Exterior Wall Only: Slide
wall restop against interior wall surface
and attach with screws provided. See Fig-
ure 13, page 11, for horizontal termination
details.
9. Place replace into position and shim with
noncombustible material if needed. Nail or
screw side anges to framing to secure unit in place. IMPORTANT: Make sure re- place is level before securing. If replace
is not level it will not work properly.
Cut Siding Away to Fit Standoff
Standoff
Apply Mastic to All Four Sides
Figure 11 - Installing Siding Standoff
(Combustible Exterior Wall)
Wood Screw
Vent Cap
Screws
Interior Wall Surface
Apply Mastic to All Four Sides
Vent Cap
Wood Screw
Figure 10 - Installing Horizontal Vent Cap
(Noncombustible Exterior)
www.desatech.com
Wall Firestop
Vent Cap
(Horizontal Termination)
Screw
Figure 12 - Connecting Vent Cap with
Horizontal Vent Pipe
Horizontal
Vent Pipe
120441-01A10
Page 11
2' Min.
2' Pipe Min. + 90° Elbow
7' Min.
VENTING INSTALLATION
Continued
Minimum Pipe
Direct Vent Pipe
Maintain 1" Minimum Air Space Around Outer Pipe When Penetrating a Wall
11 1/2" x 11 1/2" Framed Opening
Horizontal Termination Congurations
Figu res 14 and 15 show diffe rent con-
gurations and alternatives for venting with horizontal termination. Each gure includes
a chart with critical minimum and maximum dimensions which MUST be met.
Overlap 11/4"
Wall Firestop
Exterior Wall with Vinyl Siding
Figure 13 - Typical Horizontal
Termination Cap Mounting with
Additional Siding Standoff Installed
NOTICE: Do not seal termination
cap to vent pipe. Cap must be removable for vent inspection and maintenance.
Siding Standoff
Screws
High Wind Termination
Apply Mastic to Outside Edge of Standoff
GROUND FLOOR INSTALLATION
Recommended Applications:
• Installation using cabinet surrounds
• Through the wall using round or square
termination (up to 12" horizontal pipe)
• NOT FOR CORNER INSTALLATION
Wall Firestop
Horizontal High Wind Square
Termination
Figure 14 - Horizontal Termination Using
One 90° Elbow
90° Elbow
WARNING: Never run vent
downward as this may cause
excessive temperatures which could cause a re. Operation of improperly installed and main­tained venting system could result in serious injury, property damage or loss of life.
120441-01A 11
Venting with Two 90° Elbows
Vertical (V)
7' min. 18' max. 8' min. 20' max.
20' max. 20' max.
Figure 15 - Horizontal Termination Using
www.desatech.com
Horizontal (H1) +
Horizontal (H2)
Two 90° Elbows
Page 12
VENTING INSTALLATION
Continued
Vertical Termination Installation
Note: Vertical restrictor must be installed in all vertical installations.
1. Determine the route your vertical venting
will take. If ceiling joists, roof rafters or
other framing will obstruct the venting
system, consider an offset (see Figure 16)
to avoid cutting load bearing members. Note: Pay special attention to these instal-
lation instructions for required clearances (air space) to combustibles when passing
through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation. Also note maximum verti­cal rise of the venting system and any
maximum horizontal offset limitations.
2. Set the replace in desired location. Drop
a plumb line down from the ceiling to the
position of the replace exit ue. Mark the
center point where the vent will penetrate the ceiling. Drill a small locating hole at this point.
Drop a plumb line from the inside of the
roof to the locating hole in the ceiling. Mark the center point where the vent will penetrate the roof. Drill a small locating hole at this point.
Roof Flashing
Wall Strap
Flat Ceiling Installation
1. Cut a 11 1/2" square hole in the ceiling using the locating hole as a center point. The opening should be framed to 11 1/2" x 11 1/2" inside dimensions, as shown in Figure 8 on page 9 using framing lumber
the same size as the ceiling joists. If the
area above the ceiling is an insulated
ceiling or an attic, nail restop from the
top side. This prevents loose insulation
from falling into the required clearance
space. Of the area above the ceiling
is a living space, install restop below the framed hole. The restop should be
installed with no less than three nails
per side (see Figure 17).
2. Assemble the desired lengths of pipe and elbows necessary to reach from the
replace ue up through the restop. Be
sure all pipe and elbow connections are
fully twist-locked (see Figure 7, page 9).
3. Cut a hole in the roof using the locating hole as a center point. (Cover any exposed
open vent pipes before cutting hole in roof.)
The 11 1/2" x 11 1/2" hole must be measured
on the horizontal; actual length may be
larger depending on the pitch of the roof. There must be a 1" clearance from the vent pipe to combustible materials. Frame the opening as shown in Figure 9, page 9.
4. Connect a section of pipe and extend up through the hole.
Note: If an offset is needed to avoid
obstructions, you must support the vent pipe every 3 feet. Use wall straps for this purpose (see Figure 15, page 11). When­ever possible, use 45° elbows instead of 90° elbows. The 45° elbow offers less
restriction to the ow of the ue gases.
If area above is an attic or insulated area,
install restop above framed hole.
45° Elbow
Ceiling Firestop
Figure 16 - Offset with Wall Strap and 45°
Elbows
www.desatech.com
If area above is a living space, install
restop below framed hole.
Figure 17 - Installing Firestop
120441-01A12
Page 13
VENTING INSTALLATION
Continued
5. Place the ashing over the pipe section(s)
extending through the roof. Secure the
base of the ashing to the roof and fram­ing with roong nails. Be sure roong
material overlaps the top edge of the
ashing as shown in Figure 16, page 12.
There must be a 1" clearance from the vent pipe to combustible materials.
6. Continue to add pipe sections until the height of the vent cap meets the minimum
building code requirements described in
Figure 6 on page 7. Note: You must in­crease vent height for steep roof pitches.
Nearby trees, adjoining rooines, steep
pitched roofs and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve this problem.
7. Twist-lock the vent cap onto the last sec­tion of vent pipe.
Note: If the vent pipe passes through any oc-
cupied areas above the rst oor, including
storage spaces and closets, you must enclose pipe. You may frame and sheetrock the en­closure with standard construction material. Make sure and meet the minimum allowable
clearances to combustibles. Do not ll any of the required air spaces with insulation.
Vertical Termination Congurations
Figure 17 shows the congurations for vertical
termination.
OUTSIDE AIR FLEX INSTALLATION
Outside air ex installation is required for both horizontal and vertical venting installation. There are 2 outside air ex kits available for
purchase (see Parts List for Venting Kits and Components, page 14).
Construct a 4 1/2" x 4 1/2" framing or opening
on exterior wall (see Figure 19). Install outside
air vent termination in a location that would not eventually be obstructed by bushes, snow or other obstructions. Locate outside air vent
near replace to make ex duct installation
easier.
Flex Venting
Outside Air Vent Termination
Secure Both Ends of Flex Using Hi-Temp Duct Tape
Figure 19 - Outside Air Flex Duct
Vertical
Venting
V = 40' max.
Figure 18 - Vertical Venting
Conguration
120441-01A 13
www.desatech.com
HIGH ALTITUDE INSTALLATION
Your DESA direct vent replace has been
tested and approved for elevations from 0-
2000 feet (USA) and elevations from 0-4500 feet (Canada).
When installing at an elevation above 2000
feet (in the USA), you may need to decrease
the input rating by changing the existing
burner orice to a smaller size. Reduce input
4% for each 1000 feet above sea level. Check
with your local gas company for proper orice size identication.
When installing this replace at an elevation
above 4500 feet, check with local authori­ties.
Installation
Page 14
VENTING INSTALLATION
Continued
PARTS LIST FOR VENTING KITS
AND COMPONENTS
DESA (5"/8") Pipe & Vent Kits Number Description
P58-6 6" Section Double Wall Pipe,
Galvanized
P58-12 12" Section Double Wall Pipe,
Galvanized
P58-24 24" Section Double Wall Pipe,
Galvanized
P58-36 36" Section Double Wall Pipe,
Galvanized
P58-48 48" Section Double Wall Pipe,
Galvanized PA58-712 Adjustable 7"-12" Section Double
Wall Pipe, Galvanized E58-45 45° Elbow, Galvanized E58-90 90° Elbow, Galvanized HTS-58 Horizontal Square Termination,
Galvanized
VT-58 Vertical Round Termination,
Galvanized SC-58 Storm Collar, Galvanized
WF-58 Wall Firestop, Galvanized
RF-58-6 Roof Flashing - 0 to 6/12 Pitch,
Galvanized
RF-58-12 Roof Flashing - 6/12 to 12/12 Pitch,
Galvanized VR-58 Vertical Restrictor, Galvanized
S-58 Vinyl Siding Standoff,
Galvanized
WS-58 Wall Strap CS-58 Cathedral Ceiling Support FP-58 Firestop Plate SF-58 Stucco Flashing ­ For use with HTS-58 RF-58 Flat Roof Flashing AK6-37 37" Outside Air Flex Vent Kit AK6-75 75" Outside Air Flex Vent Kit
FIREPLACE
INSTALLATION
CHECK GAS TYPE
Use proper gas type for the replace unit you are installing. If you have conicting gas types, do not install replace. See retailer where you purchased the replace for proper replace
according to your gas type.
INSTALLING GAS PIPING TO FIREPLACE LOCATION
WARNI N G : A q u a li f i ed service person must connect replace to gas supply. Follow all local codes.
CAUTION: For propane/LP units, never connect replace directly to the propane/LP sup­ply. This heater requires an ex­ternal regulator (not supplied). Install the external regulator between the replace and pro­pane/LP supply.
WARNING: For natural gas, ne ver connect f i replace to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
Installation Items Needed
Before installing replace, make sure you
have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas connec­tor (if allowed by local codes)
* A CSA design-certied equipment shutoff
valve with 1/8" NPT tap is an acceptable al­ternative to test gauge connection. Purchase
the CSA design-certied equipment shutoff
valve from your retailer.
www.desatech.com
120441-01A14
Page 15
FIREPLACE
INSTALLATION
Continued
For propane/LP connection only, the installer must supply an external regulator. The exter­nal regulator will reduce incoming gas pres­sure. You must reduce incoming gas pressure to between 11" and 14" of w.c. pressure. If you do not reduce incoming gas pressure,
replace regulator damage could occur. Install
external regulator with the vent pointing down as shown in Figure 20. Pointing the vent down
protects it from freezing rain or sleet.
CAUTION: Use only new,
black iron or steel pipe. Inter­nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to replace. If pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up.
NPT tap must be upstream from replace (see Figure 21).
IMPORTANT: Install main gas valve (equip­ment shutoff valve) in an accessible location.
The main gas valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special
requirements for locating equipment shutoff valve to replaces.
Propane/LP Supply Tank
External Regulator
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could
result in clogged replace valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure
21. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping sys-
tem between fuel supply and replace. Locate
sediment trap/drip leg where trapped matter
is not likely to freeze. A sediment trap traps
moisture and contaminants. This keeps them from going into replace gas controls. If sedi­ment trap/drip leg is not installed or is installed
wrong, replace may not run properly.
CSA Design-Certied Equipment Shutoff Valve
with 1/8" NPT Tap*
Approved Flexible Gas Line
3" Minimum
Cap Pipe Tee Joint Nipple
Sediment Trap/
Figure 21 - Gas Connection
* The CSA design-certied equipment shutoff
valve may be supplied with the appliance or you can purchase it from your retailer.
Natural - From Gas Meter (5.5" W.C. to 10.5" W.C.
Pressure)
Propane/LP From External Regulator (11" W.C. to 14"
W.C. Pressure)
Drip Leg
Vent Pointing Down
Figure 20 - External Regulator with Vent
Pointing Down (Propane/LP Only)
120441-01A 15
www.desatech.com
Page 16
FIREPLACE
INSTALLATION
Continued
CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not
provided)
1. Route exible gas line (provided by in­staller) from equipment shutoff valve to replace. Route exible gas supply line
through one of the access holes on side
of replace.
2. Attach exible gas line from gas supply to control valve (see Figure 22).
3. Check all gas connections for leaks. See Checking Gas Connections.
Red Surface
Equipment
Shutoff Valve
1/2" NPT Incoming Gas Line
Note: Wire Connections Not Shown for Clarity
Figure 22 - Connecting Flexible Gas Line
Flexible Gas Line Do NOT Kink
to Electronic Valve
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and external to unit, for leaks after
installing or servicing. Correct all leaks at once.
Indicates For Propane/LP Use Only
Inlet Pressure Tap
Outlet Pressure Tap
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect replace and its individual equipment shutoff valve from gas supply
piping system. Pressures in excess of
1/2 psig (3.5 kPa) will damage replace
gas regulator.
2. Cap off open end of gas pipe where equip­ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas replace or opening
main gas valve located on or near gas
meter for natural gas replace or using
compressed air.
4. Check all joints of gas supply piping sys­tem. Apply noncorrosive leak detection
uid to all joints. Bubbles forming show a
leak. Correct all leaks at once.
5. Reco nnect fir eplac e and equipme nt
shutoff valve to gas supply. Check recon-
nected ttings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Clos e equipm ent shutoff valve (see Figure 23).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas replace or opening
main gas valve located on or near gas
meter for natural gas replace or using
compressed air.
3. Check all joints from propane/LP supply tank or gas meter to equipment shutoff
valve (see Figure 24 or Figure 25, page
17). Apply noncorrosive leak detection uid to all joints. Bubbles forming show a
leak.
4. Correct all leaks at once.
Equipment
Shutoff Valve
Open
WARNING: Never use an open ame to check for a leak. Apply noncorrosive leak detection uid to all joints. Bubbles forming show a leak. Correct all leaks at once.
www.desatech.com
Closed
Figure 23 - Equipment Shutoff Valve
120441-01A16
Page 17
FIREPLACE
INSTALLATION
Continued
Propane/LP Supply Tank
Figure 24 - Checking Gas Joints for
Equipment Shutoff Valve
Gas Valve
Propane/LP Gas Fireplace
REMOVING/REPLACING GLASS
DOORS
CAUTION: Do not operate this replace with a broken glass door panel or without the glass door panel securely in place. For replacement part informa-
tion see Replacement Parts,
page 24.
CAUTION: Wear gloves and safety glasses while handling or removing broken glass. Do not remove if glass is hot. Keep children and pets away from glass.
Equipment
Shutoff Valve
Gas Meter
Gas Valve
Figure 25 - Checking Gas Joints for
Natural Gas Fireplace
PRESSURE TESTING FIREPLACE GAS CONNECTIONS
1. Open equipment shutoff valve (see Fig­ure 23, page 16).
2. Open propane/LP supply tank valve for
propane/LP replace or main gas valve
located on or near gas meter for natural
gas replace.
3. Make sure control knob of replace is in
the OFF position.
4. Check all joints from equipment shutoff
valve to gas valve (see Figure 24 or Figure
25). Apply noncorrosive leak detection uid to all joints. Bubbles forming show a
leak. Correct all leaks at once.
5. Light replace (see Operating Fireplace, page 21). Check all other internal joints
for leaks.
6. Turn off replace (see To Turn Off Gas to Appliance, page 21).
WARNING: If replace has been running, turn off replace. Let cool before removing glass doors.
WARNING: More than one
person is required when replac­ing glass.
Models DVF-36S and DVF-36H have only an inner door to be removed/replaced. Models DVF-36SC and DVF-36HC have an inner, middle and outer door.
Installing Middle Door (DVF-36SC/HC Models Only)
Middle door hangs on 2 hinges from top of
inner glass door (see Figure 26, page 18).
1. Remove middle door from packaging.
2. Angle middle door so top goes into replace rst. Hang middle door on brackets at top of inner door (see Figure 26, page 18).
Installing Outer Door (DVF-36SC/HC Models Only)
1. Remove outer door from packaging.
2. There are three spring loaded pins on outer door. Set pins to the locked position
(see Figure 26, page 18).
3. Position outer door so pins line up with
mating hinges on replace. Holding door
in place, release locks on spring loaded
pins (see Figure 26, page 18).
120441-01A 17
www.desatech.com
Page 18
LOCK
UNLOCK
Spring Loaded Pin
Outer Door
Middle Door
FIREPLACE INSTALLATION
Continued
Pin Located on Middle Door
Hinge
Inner Door
Hook Located on Inner Door
Figure 26 - Removing/Installing Middle Door
Removing and Installing Inner Door
Inner door is factory installed.
1. Open outer door. Secure door in open position to avoid accidental breakage.
2. Remo ve mid dle door by liftin g from
hinges (see Figure 26). Set aside to avoid
scratches or damage.
3. Remove screws from two side trims (see
Figure 27, page 19).
4. Remove side bricks from top to bottom by prying out of housings(see Figure 27,
page 19).
5. Remove bottom bricks, starting with
middle section (see Figure 27, page 19).
6. Remove screen and rod (see Figure 27,
page 19).
www.desatech.com
7. While holding inner door, release 6 latches, 3 top and 3 bottom (see Figure 28, page
19).
8. Slowly tilt open glass at a 30° angle and lift up to release glass from bottom retainer
(see Figure 28, page 19).
9. Follow these instructions in reverse to reinstall.
120441-01A18
Page 19
Lock
Unlock
FIREPLACE INSTALLATION
Continued
Side Bricks
Side Trim
Side Trim
Screen and Rod
Figure 27 - Removing/Installing Brick, Side Trim and Screen
Left Bottom Brick
Middle Bottom Brick
Side Bricks
Right Bottom Brick
LAVA ROCK, EMBER FLAKES AND
SCRAP LOG INSTALLATION
Lava rock, ember akes and scrap log pieces are included with your replace. Install these
items while glass doors are open and/or removed.
120441-01A 19
Inner Door
Figure 28 - Removing/Installing Inner Door
1. Follow instructions from Removing and Installing Inner Door, page 18, to move
glass out of the way of this installation.
2. Place lava rock around base of burner. Make sure burner ports are not covered
(see Figure 29, page 20).
www.desatech.com
Page 20
FIREPLACE
INSTALLATION
Continued
3. Place ember akes around front and sides
of burner and on burner ports (see Figure
30). This will create the glowing ember
appearance as the flame touches the
ember akes. Do not block burner ports by overlapping ember akes in one area. It
is not necessary to use all ember material provided.
4. Place scrap log pieces randomly as shown in Figure 31 on lava rock and around (but
not on) burner ports.
Lava Rock
Figure 29 - Installing Lava Rock
WALL SWITCH INSTALLATION
Installation of a wall switch allows you to
activate gas control valve and turn replace
on and off. Wall switch is to be connected to incoming 120 volt regular household wiring
that supplies electricity to replace.
REMOTE CONTROL INSTALLATION
(MODEL WRC)
Note: If using wireless hand-held remote control, the wall switch must be in the ON position to be operational. The remote control then becomes the switching mechanism for
replace operation.
1. Remove center brick/control cover.
2. The WRC model receiver does not require
a battery. To install receiver:
a. Plug short extension cord into replace
receptacle. b. Plug receiver uinit into extension cord. c. Plug ignition module into receiver unit
(see Figure 32).
3. Activate remote handset battery by re­moving insulating tab on back of handset
(see Figure 33). Battery is included pre-
installed.
4. Once battery is activated, the unit is ready to use.
5. Replace center brick/control cover.
Ember Flakes
Figure 30 - Installing Ember Flakes
Scrap Log Pieces
Figure 31 - Installing Scrap Log Pieces
www.desatech.com
Fireplace Receptacle
Extension Cord
Figure 32 - Installing the WRC Remote
Receiver
Battery Cover
12 Volt Battery
Back of Handset
Figure 33 - Installing Battery into Back of
Handset
Remote Control Receiver
Ignition Module Plug
Pull to Remove Insulation Tab
120441-01A20
Page 21
EV2
EV1
ORANGE
IGNITOR LEAD
GREEN
PILOT
TRANSFORMER
IS1070B
SYNETEK CONTROLS INC
24V AC
E4
E2
E3
E6
RED
E8
E12
BLUE
120V AC
GROUND
120 VAC
ADAPTER/ REMOTE RECEIVER
J-BOX
BLACK
WHITE

WIRING DIAGRAM

OPERATION

FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not fol-
low these instructions exactly,
a re or explosion may result causing property damage, per­sonal injury or loss of life.
A. This appliance is equipped with an igni-
tion device which automatically lights the pilot. Do not light pilot by hand.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
120441-01A 21
www.desatech.com
C. Do not use this appliance if any part
has been under water. Immediately call a qualied service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
LIGHTING
INSTRUCTIONS
NOTICE: During initial operation of new replace, burning logs will give off a paper-burning smell. Orange ame will also be present. Open damper or window to vent smell. This will only last a few hours.
1. STOP! Read the safety information above.
2. Turn off all elect ric powe r to the fireplace.
3. Turn wall switch to the OFF position.
4. Remove center brick/control cover.
5. Turn equipment shutoff valve clock­wise to the OFF position (see Figure 34, page 22). Do not force.
Page 22
OPERATION
Continued
6. Wait ve (5) minutes to clear out any gas. Then smell for gas, including near the oor. If you smell gas, STOP! Fol­low “B” in the safety information on page 21. If you don't smell gas, go to the next step.
7. Turn the equipment shutoff valve coun­terclockwise to the ON position. Do not force.
8. Replace center brick/control cover.
9. Turn on all electric power to appliance.
10. Turn wall switch to the ON position.
11. Visually locate pilot. Ignitor should begin to spark and main burner should ignite once ame appears at pilot.
• If lighting appliance for the rst time
each season, it may take several at-
tempts before supply gas can reach pilot and main burners.
• If appliance will not stay lit after several
attempts, follow instructions under To
Turn Off Gas To Appliance and call your
service technician or gas supplier.
Equipment
Shutoff Valve
Figure 34 - Turning Equipment Shutoff
Valve to the OFF Position
Pilot Burner
Pilot Adjustment
Screw
Sensing Rod
Ignitor
REMOTE
OPERATION
1. Turn equipment shutoff valve to ON posi­tion. You can now turn the burner on and off with hand-held remote control unit.
IMPORTANT: Be sure to press ON/OFF
buttons on hand-held remote control unit for up to 3 seconds to assure proper operation.
2. Press ON/OFF button to turn burner on and off.

INSPECTING BURNERS

Check pilot ame pattern and burner ame
patterns often.
PILOT ASSEMBLY
The pilot assembly is factory preset for the
proper ame. Alterations may have occurred
during shipping and handling. The pilot is located on the right hand side of the burner.
The ame must envelope 1/4" of top of the
ignitor/sensor and grounding stem. If your pilot assembly does not meet these
requirements:
• Turn the adjustment screw marked PILOT
clockwise to decrease or counterclockwise
to increase the ame to proper size (see Figure 34). Do not remove the adjustment
screw.
• see Troubleshooting, page 25
Pilot Burner
Sensing Rod
Ignitor/ Sensor
Figure 35 - Pilot
TO TURN OFF GAS
TO APPLIANCE
1. Turn off the wall switch.
2. Turn off all electric power to the appli­ance if service is to be performed.
3. Remove center brick/control cover.
4. Turn equipment shutoff valve clock­wise to OFF. Do not force.
5. Replace center brick/control cover.
www.desatech.com
Figure 36 - Correct Pilot Flame Pattern
BURNER FLAME PATTERN
Burner ames will be steady; not lifting or oat­ing. Flame patterns will be different from unit to unit and will vary depending on installation type and weather conditions.
If the vent conguration is installed incorrectly, the ames will lift or "ghost". This can be dan­gerous. Inspect the ames after installation to
ensure proper installation and performance.
120441-01A22
Page 23
INSPECTING BURNERS
Continued
Figure 37 shows a typical ame pattern. If burner ame pattern differs from that de-
scribed:
• turn replace off (see To Turn Off Gas to
Appliance, page 21)
• see Troubleshooting, page 25
Figure 37 - Typical Flame Pattern
CLEANING AND
MAINTENANCE
WARNING: Turn off replace
and let cool before cleaning.
CAUTION: You must keep con­trol areas, burners and circulating air passageways of replace clean. Inspect these areas of replace before each use. Have replace inspected yearly by a qualied service person. Fireplace may need more frequent cleaning due to excessive lint from carpeting, bedding material, pet hair, etc.
GLASS DOORS
WARNI N G : Do not use
abrasive cleaners as this may damage glass. Use a nonabra­sive household glass cleaner to clean glass. Do not clean glass when hot.
Glass must be cleaned periodically. During start-up it is normal for condensation to form on the inside of the glass causing lint, dust and other airborne particles to cling to the glass
surface. During initial start-up a slight lm may
form on the glass due to paint curing. The glass should be cleaned several times with a non-ammonia, nonabrasive household clean-
er and warm water after the rst two weeks
of operation. Thereafter, clean the glass two or three times during each heating season, depending on the usage and circumstances present. Refer to Removing/Replacing Glass Door, page 17 of this manual when removing glass door for cleaning.
WARNING: Only parts sup­plied by the ma n u f a c t u r e r should be used when replacing broken or damaged glass door panels (see Replacement Parts, page 24). Glass door panel are complete units. No substitute materials may be used.
CAUTION: Wear gloves and safety glasses while handling or removing broken glass. Do not remove if glass is hot. Keep children and pets away from glass.
If glass has been broken, carefully remove glass door (see Removing/Replacing Glass
Doors, page 17). Vacuum all glass pieces
with a shop vac.
WARNING: Handle glass door panels with care. Do not strike, slam or otherwise abuse glass. Do not operate replace with the glass door unlatched, removed, cracked or broken.
120441-01A 23
www.desatech.com
CAUTION: Do not vacuum if
pieces are hot.
Use only glass door replacement intended for
this replace (see Replacement Parts, page 24 for detail on ordering). No substitutions
may be made. See Removing/Replacing Glass Doors, page 17 for instructions for
replacing glass doors.
Page 24
CLEANING AND
MAINTENANCE
Continued
WARNING: Do not operate re­place with glass door unlatched, removed, cracked or broken.
PILOT AND BURNERS
• Remove material before cleaning burners and replace when cleaning is complete.
• Burner and controls should be cleaned with compressed air to remove dust, dirt or lint.
• Use a vacuum cleaner or small, soft bristled brush to remove excess dust, dirt or lint.
LOGS
• Use a vacuum cleaner to remove any carbon buildup on logs.
• Replace material periodically as needed. See Replacement Parts.
VENTING SYSTEM
Conduct annual inspection of the venting system following these guidelines:
1. Check areas of venting system that are
exposed to the weather for corrosion (rust spots or streaks and, in extreme cases,
holes). Have these items replaced im­mediately by a qualied service person.
2. Remove the vent cap and shine a ash-
light into the vent. Remove any foreign material.
3. Check for evidence of excessive con-
densation. Continuous condensation can
cause corrosion of caps, pipes and ttings
and can be caused by having excessive lateral runs, too many elbows or exterior portions of the system being exposed to cold weather.
4. Inspect joints to verify that no pipe section
or tting has been disturbed and loos-
ened. Check mechanical supports such as wall straps for rigidity.

TECHNICAL SERVICE

You may have further questions about instal­lation, operation or troubleshooting. If so, contact DESA’s Customer Service Depart­ment at 1-866-672-6040. When calling, please have your model and serial numbers of your heater ready.
You can also visit DESA’s technical service web site at www.desatech.com.

SPECIFICATIONS

DVF-36S-N, DVF-36H-N, DVF-36SC-N, DVF-36HC-N
• Rating: 66,000 Btu/hr
• Gas Type: Natural Gas Only
• Ignition: Electronic
• Manifold Pressure: 3.5" w.c.
• Minimum Inlet Supply Pressure: 7.0" w.c.
DVF-36S-P, DVF-36H_P, DVF-36SC-P, DVF-36SH-P
• Rating: 62,000 Btu/hr
• Gas Type: Propane/LP Gas Only
• Ignition: Electronic
• Manifold Pressure: 10.0" w.c.
• Minimum Inlet Supply Pressure: 11.0" w.c.

REPLACEMENT PARTS

Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
PARTS UNDER WARRANTY
Contact authorized retailers of this product.
If they can not supply original replacement part(s), call DESA’s Customer Service Depart­ment at 1-866-672-6040.
When calling DESA, have ready
• your name
• your address
• model and serial numbers of your re­place
• how replace was malfunctioning
• type of gas used (propane/LP or natural
gas)
• purchase date
Usually, we will ask you to return the part to the factory.
PARTS NOT UNDER WARRANTY
Contact authorized retailers of this product.
If they can not supply original replacement
part(s), call DESA at 1-866-672-6040 for
referral information. When calling DESA, have ready
• model number of your replace
• the replacement part number

SERVICE HINTS

When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• replace will not produce specied heat
• propane/LP gas supply might be low (pro-
pane/LP units only)
You may feel your gas pressure is too low. If so, contact your local gas supplier.
www.desatech.com
120441-01A24
Page 25

TROUBLESHOOTING

WARNING: Turn off replace and let cool before servicing. Only
a qualied service person should service and repair replace.
CAUTION: Never use a wire, needle or similar object to clean
pilot. This can damage pilot unit.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
Ignitor will not spark or pilot will not light
POSSIBLE CAUSE
1. No gas supply or shutoff valve is OFF
2. Air in gas line
3. Construction debris clog-
ging pilot orice
4. Low gas pressure
5. Kinked pilot line
6. C o n tr o l v al v e is n ot opening
7. No power to unit or the ignition module or power transformer is bad
REMEDY
1. Check to see if you have gas
supply and that equipment
shutoff valve is opened
2. Repeat lighting procedure several times to purge all air out of lines. If after repeated attempts appliance does
not light, call for qualied
service and repair
3. Remove debris and dirt, inspect and clean any other possible obstructions
4. Contact your gas supplier to check pressure
5. Have a qualied technician
replace pilot line
6. Replace control valve (Re­fer to Replacement Parts,
page 24)
7. Check that main power is on and that all wire con­nections are made correctly to the ignition model (see
Wiring Diagram, page 21).
Check for 24 VAC at the secondary side of the trans­former. If 24 VAC is present and the module does not operate, have the module replaced otherwise have the transformer replaced
120441-01A 25
www.desatech.com
Page 26
OBSERVED PROBLEM
Pilot will not stay lit
TROUBLESHOOTING
Continued
POSSIBLE CAUSE
1. Loose wiring on ignitor wire to ignition module and/or poor groun d to ignit ion module
2. Pilo t flame too lo w to sense
REMEDY
1. Check wiring connection. Refe r to wir ing diagram (see Wiring Diagram, page
21) and/or check ground
wire to ignition module
2. Clean and adjust pilot burn­er and check gas supply and inlet pressure to unit
Note: Have a qualied tech-
nician replace pilot assem­bly if broken or corroded
No gas to burner, although wall switch and valve are set to the ON position
Frequent pilot outage
Fireplace produces a clicking/
ticking noise just after burner
is lit or shut off
Slight smoke or odor during initial operation
1. Wall switch wires defective or too long
1. Pilo t flam e may be too low, causing safety pilot to “drop out”
2. Improper venting or exces­sive blockage
1. Me t al exp a ndi n g whil e heating or contracting while cooling
1. Residues from manufac­turing processes and logs curing
1. Check electrical connec­tions
1. Clean and adjust pilot ame for maximum ame impinge-
ment on thermopile
2. Have the vent system in­spected, including the ter­mination cap. Remove any restriction or obstruction
1. This is normal with most fireplaces. If noise is ex-
cessive, contact qualied
service person
1. Problem will stop after a few hours of operation
www.desatech.com
120441-01A26
Page 27
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Fol­low the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
OBSERVED PROBLEM
Gas odor even when control knob is in OFF position
Gas odor during combus­tion
Glass soots
Dark residue on logs or
inside of replace
POSSIBLE CAUSE
1. Gas le ak. See Warn -
ing statement at top of page
2. Control valve defective
1. Foreign matter between control valve and burner
2. Gas le ak. See Warn -
ing statement at top of page
1. Debris around burner air mixer
2. Improper vent
conguration
1. Air holes at burner inlet blocked
2. B u rn e r f la m e h ol e s blocked
3. Improper venting or ex­cessive blockage
4. Ex ces sive amou nts of embers and pan material
REMEDY
1. Locate and correct all leaks (see Checking Gas Connec-
tions, page 16)
2. Replace control valve
1. Take apart gas tubing and re­move foreign matter
2. Locate and correct all leaks (see Checking Gas Connec-
tions, page 16)
1. Inspect the opening at the base of the burner to see that it is NOT packed with any type of material
2. Check vent conguration speci­cation (see Venting Installation, page 8)
1. Clean out air holes at burner inlets. Periodically repeat as needed
2. Remove blockage
3. Have the vent system inspect­ed, including the termination cap. Remove any restrictions or obstruction
4. Clear excess embers until a minimum gap of 1/2" remains under the grate
120441-01A 27
www.desatech.com
Page 28
10
14
9
7
21
11
32
23
24
26 25
41
8
22
15
16
17
18
19
33
34
20
30
13
40
2
1
3
27
31
38
37
4
29
28
12
6
43
42
35
36
39
ILLUSTRATED PARTS BREAKDOWN
MODELS DVF-36S-N, DVF-36S-P, DVF-36H-N, DVF-36H-P, DVF-36SC-N, DVF-36SC-P, DVF-36HC-N, DVF-36HC-P
www.desatech.com
120441-01A28
Page 29
This list contains replaceable parts used in your replace. When ordering parts, follow the
PARTS LIST
instructions listed under Replacement Parts on page 24 of this manual.
KEY NO. PART NO. DESCRIPTION QTY.
DVF-36S-N
DVF-36S-P
1 120150-01 Outer Glass Assembly • • • 1 2 120155-01 Middle Glass Assembly • • • • 1 3 118003-01 Glass Door Assembly • • • 1
118003-02 Glass Door Assembly • • • 1 4 ** Face Weldment • • • • • • • • 1 5 17327 Latch Spring • • • • • • • • 6 6 ** Left Side Surround • • • • • • • • 1 7 ** Right Side Surround • • • • • • • • 1 8 ** Fireplace Bottom • • • • • • • • 1 9 ** Rear Fireplace Surround • • • • • • • • 1 10 ** Firebox Surround • • • • • • • • 1 11 ** Firebox Bottom • • • • • • • • 1 12 ** Firebox Top Assembly • • • • • • • • 1 13 120244-01 Air Plenum • • • • • • • • 1 14 117479-01 Air Exchange • • • • • • • • 1 15 ** Top Insulation • • • • • • • • 1 16 120261-01 Fireplace Top • • • • • • • • 1 17 23490SA Fireplace Top Spacer • • • • • • • • 4 18 120243-01 8" Outer Pipe • • • • • • • • 1 19 111554-05 5" Inner Connector • • • • • • • 1 20 106702-01 5" Gasket • • • • • • • 1 21 120431-01 Burner Base Gasket • • • • • • • • 1 22 117997-01 Glass Door Retainer • • • • • • • • 1 23 120142-01 Firebox Leg • • • • • • • • 4 24 117891-01 Fireplace Handle • • • • • • • 4 25 21171 Gas Conduit Cover • • • • • • • • 1 26 24460 Gas Conduit Assembly • • • • • • • • 1 27 120152-02 Frame Leaf Hinge • • • • • • • • 3 28 120454-01 Ignition Valve Assembly 1
120454-02 Ignition Valve Assembly 1 29 120154-01 Door Latch Bracket • • • 2 30 120687-01 Plenum Bracket • • • • • • • • 1 31 120461-01 Screen • • • • • • • • 2 32 120411-01 Log Burner Assembly, NG (See page 30) • 1
120411-02 Log Burner Assembly, LP (See page 30) 1 33 120895-01 Relief Plate • • • • • • • • 2 34 120902-02 Gasket • • • • • • • • 2 35 120899-01 Thumb Screw • • • • • • • 6 36 120898-01 Spring • • • • • • • 6 37 11418 Push Nut • • • • • • • • 2 38 120462-01 Screen Rod • • • • • • • • 1 39 121126-01 Screen Rod Bracket • • • • • • • • 1 40 121063-01 Aniron • • • • • • • 2 41 110037-01 Electrical Duct ASM • • • • • • • • 1 42 11192 Hex Spacer Screw • • • • • • • • 4 43 121127-01 Access Cover Plate • • • • • • • • 1
**Not a eld replaceable part.
DVF-36SC-N
DVF-36H-N
DVF-36H-P
DVF-36SC-P
DVF-36HC-N
DVF-36HC-P
120441-01A 29
www.desatech.com
Page 30
ILLUSTRATED PARTS BREAKDOWN
23
1
22
32
37
17
16
18
2
19
6
20
12
13
11
7
10
9
19
14
28
8
5
3
4
15
27
21
25
24
34
33
30
31
29
26
26
35
BURNER ASSEMBLY FOR MODELS DVF-36S-N, DVF-36S-P, DVF-36H-N, DVF-36H-P, DVF-36SC-N, DVF-36SC-P, DVF-36HC-N, DVF-36HC-P
www.desatech.com
120441-01A30
Page 31
PARTS LIST
BURNER ASSEMBLY FOR MODELS DVF-36SC-N, DVF-36SC-P, DVF-36SH-N, DVF-36SH-P, DVF-36S-N, DVF-36S-P, DVF-36H-N, DVF-36H-P
This list contains replaceable parts used in your replace. When ordering parts, follow the
instructions listed under Replacement Parts on page 24 of this manual.
KEY NO. PART NO. DESCRIPTION QTY.
1 ** Bottom Pan Weldment • • 1 2 120402-01 Burner Plate Weldment • • 1 3 120637-01 Log Bracket 2 4 120405-01 Right Bracket • • 1 5 120408-01 Burner Tube • • 1 6 108866-01 Pilot Assembly (Natural Gas) 1
108866-02 Pilot Assembly (Propane/LP Gas) 1
7 114365-13 Brass Orice, NG 1
114365-14 Brass Orice, LP 1 8 112370-01 Venturi Gasket • • 1 9 120406-01 Left Bracket • • 1 10 112829-01 Air Shutter • • 1 11 111824-01 Compression Nut/Sleeve 3/8" 2 12 111817-05 Flextube, 3/8" x 7" • • 1 13 114027-01 Grommet • • 1 14 112372-07 Venturi, 1 1/4" x 6.0" x 2.27" • • 1 15 116559-01 Air Shutter • • 1 16 11214 Bulkhead Fitting • • 1 17 14399 Brass Elbow • • 1 18 116573-01 Flat Washer • • 1 19 11209 Hex Nut 10-12 20 112823-01 Brass T-Fitting • • 1 21 111817-06 Flextube 3/8" x 11" • • 1 22 ** Burner Base Gasket • • 1 23 ** Firebox Bottom • • 1 24 111817-08 Flextube 3/8" x 18" • • 1 25 120454-01 Valve Ignition Assembly • • 1 26 11105 Hex Screw 26 27 114365-15 Brass Orice, NG 1
114365-16 Brass Orice, LP 1 28 120514-01 Log Assembly • • 1 29 14569 Valve, NG 1
14570 Valve, LP 1 30 110286-01 Ignition Module • • 1 31 14129 Transformer • • 1 32 14399 90° Elbow • • 1 33 11146 Screw 8-32 x 7/8 • • 4 34 11109 Screw 8-32 x 1/2 • • 2 35 11201 Nut 6 36 M12461-26 Screw • • 4
PARTS AVAILABLE NOT SHOWN
14162 Remote Adapter • • 1
112799-01 Ember Flake Kit 1
117501-01 Log Scrap Kit • • 1
**Not a eld replaceable part.
120411-01 (NG)
120411-02 (LP)
120441-01A 31
www.desatech.com
Page 32
ILLUSTRATED PARTS BREAKDOWN
14
20
15
19
17
13
11
6
8
4
2
1
9
5
9
1
3
7
11
12
16
18
10
REFRACTORY PARTS FOR MODELS DVF-36S-N, DVF-36S-P, DVF-36H-N, DVF-36H-P, DVF-36SC-N, DVF-36SC-P, DVF-36HC-N, DVF-36HC-P
www.desatech.com
120441-01A32
Page 33
This list contains replaceable parts used in your replace. When ordering parts, follow the
PARTS LIST
instructions listed under Replacement Parts on page 24 of this manual.
KEY NO. PART NO. DESCRIPTION QTY.
DVF-36S-N
DVF-36S-P
1 102520-01 Refractory Retainer • • • • • • • • 2 2 120248-01 Left Refractory • • • • 1
120449-01 Left Refractory • • • • 1
3 120247-01 Right Refractory • • • • 1
120448-01 Right Refractory • • • • 1
4 120278-01 Rear Refractory • • • • 1
120447-01 Rear Refractory • • • • 1
5 120277-01 Top Refractory • • • • 1
120446-01 Top Refractory • • • • 1 6 120249-01 Hearth Refractory, LH • • • • • • • • 1 7 120249-02 Hearth Refractory, RH • • • • • • • 1 8 120249-03 Hearth Refractory, Front • • • • • • • • 1 9 121128-01 Top Refractory Bracket • • • • • • • • 2 10 121182-01 Rear Refractory Bracket • • • • • • • • 1 11 120149-01 Refractory Housing • • • • • • • • 8 12 120148-03 Top Left Side Refractory • • • • • • • • 1 13 120148-02 Top Right Side Refractory • • • • • • • 1 14 120148-01 Side Refractory • • • • • • • • 6 15 120146-01 Bottom Left Refractory • • • • • • • 1 16 120145-01 Bottom Right Refractory • • • • • • • • 1 17 120144-01 Bottom Center Refractory • • • • • • • • 1 18 120143-01 Bottom Refractory Bracket • • • • • • • • 2 19 120168-01 Refractory Trim, RH • • • • • • • • 1 20 120168-02 Refractory Trim, LH • • • • • • • • 1
DVF-36SC-N
DVF-36H-N
DVF-36H-P
DVF-36SC-P
DVF-36HC-N
DVF-36HC-P
120441-01A 33
www.desatech.com
Page 34
NOTES
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
www.desatech.com
120441-01A34
Page 35
NOTES
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
120441-01A 35
www.desatech.com
Page 36

WARRANTY INFORMATION

120441 01
KEEP THIS WARRANTY
Model ______________________________
Serial No. ___________________________
Date Purchased ______________________
Always specify model and serial numbers when communicating with the factory.
The only warranty applicable is our standard written warranty. We make no other warranty, expressed or implied.
LIMITED WARRANTY
DIRECT VENT FIREPLACE
DESA Heating, LLC warrants this product to be free from defects in materials and components for two
(2) years from the date of rst purchase, provided that the product has been properly installed, operated
and maintained in accordance with all applicable instructions. To make a claim under this warranty the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater to proper operating condition and an allowance for labor when provided by a DESA Heating, LLC Authorized Service Center. Warranty part(s) MUST be obtained through authorized
retailers of this product and/or DESA Heating, LLC who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty. The heater MUST be installed by
a qualied installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and any and all such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND ALL IMPLIED WARRANTIES, INCLUDING
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO TWO (2)
YEARS ON ALL COMPONENTS FROM THE DATE OF FIRST PURCHASE; AND DESA HEATING, LLC’S LIABILITY IS HEREBY LIMITED TO THE PURCHASE PRICE OF THE PRODUCT AND DESA HEATING, LLC SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation
of incidental or consequential damages, so the above limitation on implied warranties or exclusion or
limitation on damages may not apply to you.
This warranty gives you specic legal rights and you may also have other rights that vary from state
to state.
For information about this warranty write:
Desa Heating, LLC 2701 Industrial Drive P.O. Box 90004 Bowling Green, KY 42102-9004 www.desatech.com
NOT A UPC
120441-01 Rev. A 02/07
Loading...