Desa Tech CDV34N, CDV34P Owner's Manual

DIRECT-VENT FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
®
REMOTE REQUIRES
TWO 9-VOLT
ALKALINE
BATTERIES -
NOT INCLUDED
CDV34(N/P)
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
FOR YOUR SAFETY WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state or local codes. * Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
WARNING: Improper instal­lation, adjustment, altera­tion, service, or mainte­nance can cause injury or property damage. Refer to this manual for correct in­stallation and operational procedures. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
— Installation and service must be performed by a qualified installer, service agency, or the gas supplier.
Save this manual for future reference.
CDV34(N/P)
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
SAFETY INFORMATION
WARNINGS
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this fireplace. Im­proper use of this fireplace can cause serious injury or death from burns, fire, explosions, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This fireplace is a vented product. This fireplace will not produce any gas leakage into your home if properly installed. This fireplace must be properly installed by a qualified service person. The glass door must be properly seated and sealed. If this unit is not properly installed by a qualified service person with glass door properly seated and sealed, gas leakage can occur.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the fireplace may not have been installed properly. Get fresh air at once! Have fireplace inspected and ser­viced by a qualified service person. Some people are more affected by carbon monox­ide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Propane/LP gas and natural gas are both odorless. An odor-making agent is added to each of these gases. The odor helps you detect a gas leak. However, the odor added to these gases can fade. Gas may be present even though no odor exists.
Make certain you read and understand all Warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.
WARNING: Any change to this fireplace or its controls can be dangerous.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used.
2. For propane/LP fireplace, do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors. To prevent perfor­mance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do
not use any phone in your building
• immediately call your gas supplier
from a neighbor’s phone. F ollow the gas supplier's instructions
• if you cannot reach you gas supplier,
call the fire department.
4. Never install the fireplace
• in a recreational vehicle
• where curtains, furniture, clothing, or
other flammable objects are less than 42" from the front, top, or sides of the fireplace
• in high traffic areas
• in windy or drafty areas
5. This fireplace reaches high tempera­tures. Keep children and adults away from hot surfaces to avoid b urns or cloth­ing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
6. Carefully supervise young children when they are in the room with fireplace.
7. Do not modify this fireplace under any circumstances. Any parts removed for servicing must be replaced prior to op­erating fireplace.
8. Turn fireplace off and let cool before servicing, installing, or repairing. Only a qualified service person should in­stall, service, or repair this fireplace. Have fireplace inspected annually by a qualified service person.
9. You must keep control compartments, burners, and circulating air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before cleaning fireplace.
10. Have venting system inspected annu­ally by a qualified service person. If needed, have venting system cleaned or repaired. See Cleaning and Mainte- nance, page 26.
11. Keep the area around your fireplace clear of combustible materials, gaso­line, and other flammable vapor and liquids. Do not run fireplace where these are used or stored. Do not place items such as clothing or decorations on or around fireplace.
12. Do not use this fireplace to cook food or burn paper or other objects.
13. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this fireplace. Use only the gas type indicated on fire­place nameplate.
14. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electri-
cal Code, ANS/NFPA 70, or the Cana­dian Electrical Code, CSA C22.1.
15. Do not obstruct the flow of combus­tion and ventilation air in any way . Pro­vide adequate clearances around air openings into the combustion chamber along with adequate accessibility clear­ance for servicing and proper operation.
16. Do not install fireplace directly on car­peting, vinyl tile, or any combustible material other than wood. The fireplace must set on a metal or wood panel ex­tending the full width and depth of the fireplace.
17. Do not use fireplace if any part has been exposed to or under water . Immediately call a qualified service person to ar­range for replacement of the unit.
18. Do not operate fireplace if any log is broken.
19. Do not use a blower insert, heat ex­changer insert, or other accessory not approved for use with this fireplace.
20. Do not operate fireplace with glass door removed, cracked, or broken.
2
105455
OWNER’S MANUAL
PRODUCT IDENTIFICATION
Top Louver Panel
Nailing Flange
Glass Door Assembly
Front Burner
Piezo Ignitor
Valve
Lower Louver Panel
Glowing Embers
Vent Opening
Standoff
Rear Burner
Log Set
Pilot Assembly
Lava Rock
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the absence to local codes, use the current National Fuel Gas Code ANS Z223.1, also known as NFPA 54* (USA) or the current CAN/CGA-B149[.1 or .2] Installation Codes (Canada).
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
PRODUCT FEATURES
OPERATION
This direct-vent fireplace is clean burning and vents easily through outside walls or vertically using outside air for combustion. Heat is generated by both realistic flames and glowing embers. When used without the blower accessory, the fireplace requires no electricity making it ideal for emergency backup heat.
Blower Adjustment (Optional Installation)
Figure 1 - Comfort Glow Direct-Vent Fireplace CDV Series
ON/OFF Remote Switch (Optional Installation)
Grate Assembly
PIEZO IGNITOR
This fireplace has a piezo ignitor. This sys­tem requires no matches, batteries, or other sources to light fireplace.
GLOSSARY OF TERMS
Chase - A boxlike enclosure to protect venting from the elements when the venting run is on the outside of a structure.
Mastic - A pliable sealant for use around the vent terminal.
Snorkel Termination - A box that raises the horizontal termination above ground level clearances.
Vent Terminal - Mounted on an outside wall or roof to separate the inlet and outlet of the vent system and protect it from weather.
Vinyl Siding Standoff - A metal box that separates the vent cap from vinyl siding.
Wall Thimble/Firestop - A metal plate used to secure the vent pipe when it passes through a wall or ceiling.
105455
3
CDV34(N/P)
34 1/2"
34
3
/4"
20" Vertical Termination 19" Horizontal Termination
D
RW
FW
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
PRE-INSTALLATION PREPARATION
LOCATION AND SPACE REQUIREMENTS
Determine the safest and most efficient loca­tion for your Comfort Glow direct-vent fire­place. Make sure that rafters and wall studs are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some common locations. Read all venting infor­mation in this manual. Be aware of all re­strictions and precautions before deciding the exact location for your fireplace.
When deciding the location of your fire­place, follow these rules:
1. Do not connect this fireplace to a chim­ney flue serving a separate solid-fuel burning fireplace or appliance.
2. Due to high temperatures, do not lo­cate this fireplace in high traffic areas or near furniture or draperies.
3. Proper clearances must be maintained.
4. If your fireplace is to be installed di­rectly on carpeting, vinyl tile, or any combustible material other than wood, it must be installed on a metal or wood panel extending the full width and depth of the fireplace. See Figure 3.
CLEARANCES
Minimum clearances to combustibles for the fireplace are as follows:
Back, and sides 0"/mm Perpendicular walls 6" (152mm) Floor 0"/mm Ceiling to louver opening 42" (1067mm) Front 36" (914mm) Top of Standoffs 0"/mm
See General Venting on page 5 for specific venting clearances.
FRAMING AND FINISHING
Figures 4 and 5 show typical framing of this fireplace. Figure 6 on page 5 shows framing for corner installation. All minimum clear­ances must be met. Do not install fireplace directly on carpeting, vinyl tile, or any com­bustible material other than wood. The fire­place must set on a metal or wood panel extending the full width and depth of the fireplace.
See Accessories on page 31 for mantel kits available for this fireplace. If you are using a separate combustible mantel piece, refer to Figure 7 on page 5 for proper installation height. You can install noncombustible mantels at any height above the fireplace.
Must maintain a minimum 1" clearance to combustibles
3
34
/
4
"
20"
5/8" for drywall facing
Figure 5 - Framing Clearances for Typical Fireplace Installation
Flush with a wall
Through exterior wall enclosed in a chase
Corner installation
Figure 2 - Common Fireplace Locations
Fireplace size D x FW x RW
34" 18 1/2" 34" 14"
Figure 3 - Fireplace Bottom Dimensions
Figure 4 - Framing Clearances for Installation Against an Exterior Wall
4
105455
OWNER’S MANUAL
PRE-INST ALLATION PREP ARATION
Continued
13"
29"
5
/8"
12
34
58"
Figure 6 - Framing Clearances for Corner Installation
A
B
C
Ref. Mantel Depth Ref. Mantel from Top
1 14" (356mm) A 16" (406mm) 2 12" (305mm) B 14" (356mm) 3 10" (254mm) C 12" (305mm) 4 8" (203mm) D 10" (254mm) 5 6" (152mm) E 8" (203mm) 6 4" (101mm) F 6" (152mm) 7 2" (51mm) G 4" (101mm)
Figure 7 - Clearances for Combustible Mantels
of Louver Opening
1
9
/4"
1
/4"
3
/4"
34
D
E
F
G
Top of Louver Opening
GENERAL VENTING
These models are approved for use with Simpson Dura-Vent 6 5/8" direct-vent pipe components and terminations as well as both flex and rigid Comfort Glow vent components.
Your fireplace is approved to be vented either
41"
Nailing Tabs
1 2
3
4
5 6 7
Wall
through the side wall, or vertically using the following guidelines:
• Only use Comfort Glow or Simpson Dura­Vent GS venting components or kits spe­cifically approved for this fireplace.
• Minimum clearance between v ent pipes and combustible materials is 1" (25 mm), except where stated otherwise.
• Comb ustible material may be flush with the top front of fireplace with a maxi­mum thickness of 3/4".
• Do not recess venting terminals into a wall or siding.
• Install horizontal venting with a 1/4" rise for every 12" of run to ward the termination.
• You may paint the vent terminal with 450ºF (232ºC) heat-resistant paint to co­ordinate with the exterior finish.
• There must not be any obstruction such as bushes, garden sheds, fences, decks, or utility buildings within 24" from the front of the termination cap.
• Do not locate termination cap where e x­cessive snow or ice build up may occur. Be sure to clear vent termination area af­ter snow falls to prev ent accidental block­age of venting system. When using sno w blowers, do not direct snow to wards vent termination area.
LOCATION OF VENT TERMINATION
When locating vent termination, it is impor­tant to observe the minimum clearances shown in Figure 8, page 6. You will avoid extra framing by positioning your fireplace against an already existing framing mem­ber. The sides of the fireplace may be posi­tioned directly against combustible walls.
*Check with local codes or with the current
CAN/CGA B149 [.1 or .2] Installation Codes
for Canada or the USA Installations follow the current National Fuel Gas Code, ANS
Z223.1, also known as NFPA 54.
Continued
105455
5
CDV34(N/P)
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
GENERAL VENTING
D
E
V
B
L
V
A = clearance above grade, veranda, porch, deck, or balcony
[*12 inches (305mm) minimum]
B = clearance to window or door that may be opened
[12 inches (305mm) minimum]
C = clearance to permanently closed window [minimum 12 inches
(305mm) recommended to prevent condensation on window]
D = vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 24 inches (610mm) from the
center-line of the terminal [18 inches (457mm) minimum] E = clearance to unventilated soffit [12 inches (305mm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within
36 inches (914mm) horizontally from the center-line of the regulator
† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/SGA B149 (.1 or .2) Installation Codes (1991) for Canada or for U.S.A. installation follow
the current Note: Local codes or regulations may require different clearances
C
F
V
B
TERMINATION CAP
National Fuel Gas Code, ANS Z223.1
Continued
Fixed
Closed
Openable
V
Openable
B
AIR SUPPLY INLET
X
B
Fixed
Closed
J
V A
X
I = clearance to service regulator vent outlet [*72 inches (1829mm)
minimum]
J = clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other fireplace [*12 inches (305mm) minimum]
K = clearance to a mechanical air supply inlet [*72 inches (1829mm)
minimum]
L = † clearance above paved side-walk or a paved driveway located on
public property [*84 inches (2133mm) minimum] M = clearance under veranda, porch, deck [*12 inches (305mm) minimum ‡] N = clearance above a roof shall extend a minimum of 24 inches (610mm)
above the highest point when it passes through the roof surface and
any other obstruction within a horizontal distance of 18 inches (457mm)
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Inside Corner
Outside Corner Recessed Location
N
H
V
B
G
G
GAS METER RESTRICTED AREA
I
M
V
(TERMINATION PROHIBITED)
N
G
V
G
X
K
V
A
A
Balcony with No Side Wall
G = Combustible 24" (610mm)
Noncombustible 18" (457mm)
V
G V
A = 6" (152mm)
V
Balcony with Perpendicular Side Wall
H
Combustible & Noncombustible H = 24" (610mm) J = 20" (508mm)
Figure 8 - Minimum Clearances for Vent Terminations
B
V
J
B = 6" (152mm)
6
D
C
V
C = Maximum depth of 48" (1219mm) for
recessed location
D = Minimum width for back wall of
recessed location ­Combustible - 38" (965mm) Noncombustible - 24" (610mm)
E = Clearance from corner in
recessed location­Combustible - 6" (152mm) Noncombustible - 2" (51mm)
C
E
105455
OWNER’S MANUAL
VENTING INSTALLATION
WARNING: Read all instruc­tions completely and thoroughly before attempting installation. Fail­ure to do so could result in serious injury, property damage or loss of life. Operation of improperly in­stalled and maintained venting sys­tem could result in serious injury, property damage or loss of life.
WARNING: Seal all of the con­nections with high temperature silicone (600°F/316° C) every time a vent connection is made. Be­fore joining elbows and pipes, apply a bead of high temperature silicone sealant (GE RTV 106/ Loctite RTV 81585) to the end of the elbow or pipe. High tempera­ture silicone must also be used to reseal any connections after maintenance to venting system.
NOTICE: Failure to follow these instructions will void the warranty.
INSTALLATION PRECAUTIONS
Consult local building codes before beginning the installation. The installer must make sure to select the proper vent system for installa­tion. Before installing vent kit, the installer must read this fireplace manual and vent kit instructions.
Only a qualified service person should in­stall venting system. The installer must fol­low these safety rules:
• Wear gloves and safety glasses for protection
• Use e xtreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the war­ranty on your venting system:
• Installation of any damaged venting component
• Unauthorized modification of the vent­ing system
• Installation of any component part not manufactured or approved by DESA International
• Installation other than as instructed by these instructions
WARNING: This gas fireplace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning ap­pliance. Each gas appliance must use a separate vent system. Do not use common vent systems.
WARNING: Horizontal sec­tions of this vent system require a minimum clearance of 2" from the top of the pipe and 1" mini­mum to the sides and bottom. Vertical sections of this system require a minimum of 1" clear­ance to combustible materials on all sides of the pipe.
INSTALLATION PLANNING
There are two basic types of direct-vent installation:
• Horizontal Termination
• Vertical Termination It is important to select the proper length of
vent pipe for the type of termination you choose. It is also important to note the wall thickness.
For Horizontal Termination: Select the amount of vertical rise desired. The horizon­tal run of venting must have 1/4" rise for every 12" of run towards the termination.
WARNING: Never run the vent downward as this may cause ex­cessive temperatures which could cause a fire.
You may use one or two 90° elbows in this vent configuration. See Horizontal Termina- tion Configurations on pages 10 and 11.
For Vertical Termination: Measure the distance from the fireplace flue outlet to the ceiling. Add the ceiling thickness, the verti­cal rise in an attic or second story, and allow for sufficient vent height above the roofline.
You may use one or two 90° elbows in this vent configuration. See Vertical Termination Configurations on pages 13 and 14.
Note:
You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when using 45° elbows.
For two-story applications, firestops are re­quired at each floor level. If an offset is needed in the attic, additional pipe and el­bows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. See Installing Vent System in a Chase, below.
Your Comfort Glow direct-vent fireplace has been tested for a minimum 3' rise with a maximum 10" wall thickness. The maxi­mum horizontal run is 20' with 8' vertical rise (see Installation for Horizontal Termi- nation, page 8). The maximum vertical run is 30' (see Installation for Vertical Termina- tion, page 12).
It is very important that the venting system maintain its balance between the combus­tion air intake and the flue gas exhaust. Certain limitations apply to vent configura­tions and must be strictly followed.
Installing Vent System in a Chase
A chase is a vertical boxlike structure built to enclose venting that runs along the out­side of a building. A chase is not required for such venting.
NOTICE: Treatment of firestops and construction of the chase may vary from building type to building type. These instructions are not substitutes for the requirements of local building codes. You must follow all local building codes .
Note:
When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially im­portant in cold climates. Minimum clear­ance between vent pipes and combustible materials such as insulation is 1".
After framing the chase (see Framing and Finishing on page 4) install the vent system by following the installation instructions.
Continued
105455
7
CDV34(N/P)
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
VENTING INSTALLATION
Continued
INSTALLATION FOR HORIZONTAL TERMINATION
1. Determine the route your horizontal venting will take. of the horizontal vent termination on the exterior wall must meet all local and national building codes and must not be easily blocked or obstructed.
WARNING: Do not recess vent
terminal into a wall or siding.
Snorkel terminations are available for terminations requiring a vertical rise on the exterior of the building (see Figures 9 and 10). Snorkel kit CSVK is also available (see page 15). Follow the same installation procedures as used for stan­dard horizontal terminations. If install­ing the snorkel termination belo w grade (basement applications), you must pro­vide proper drainage to prevent water from entering the snorkel termination (see Figure 10). Do not back fill around the snorkel termination.
2. Rigid vent pipes and fittings have spe­cial twist-lock connections. Assemble the desired combination of pipe and el­bows to the appliance adaptor with pipe seams oriented towards the wall or floor .
Twist-lock Procedure: The female ends of the pipes and fittings have four locking lugs (indentations). These lugs will slide straight into matching slots on the male ends of adjacent pipes and fit­tings. (All connections must be sealed with high temperature silicone sealant as specified in the second warning state­ment on page 7.) Push the pipe sections together and twist one section clockwise approximately one-quarter turn until the sections are fully locked. See Figure 11, page 9. must be supported every three feet. Use wall straps for this purpose.
Flexible vent pipe must be installed with spacer springs every 12". See Figure 11, page 9. All connections must be clamped tightly and sealed with high temperature silicone sealant as specified in the sec­ond warning statement on page 7.
Note:
Note:
The location
Horizontal runs of vent
Snorkel
12" Minimum
Figure 9 - Snorkel Termination
Snorkel
12" Minimum
Adequate Drainage
Figure 10 - Snorkel Termination with Drainage Pipe
8
105455
OWNER’S MANUAL
VENTING INSTALLATION
Continued
3. Attach vent pipe assembly to the fire­place. Set fireplace in front of it’ s perma­nent location to insure minimum clear­ances. Mark the wall for a 10" square hole (for noncombustible material such as masonry block or concrete, a 7 1/2" diam­eter hole is acceptable). See Figure 12. The center of the hole should line up with the center-line of the horizontal rigid vent pipe. Cut a 10"x10" (254mm x 254mm) square hole through combustible exterior wall (7 1/2" [190mm] diameter hole if non­combustible). Frame as necessary (see Figure 12).
4" Clamp
Female Locking Lugs
Male Slots
7" Clamp
Spacer Spring
4" Flex Pipe
7" Flex Pipe
4. Apply a bead of non-hardening mastic around the outside edge of the vent cap. Position the vent cap in the center of the 7 1/2" or 10" hole on the exterior wall with the arrow on the vent cap pointing up. Insure proper clearance of 1" to combustibles is maintained. At­tach the vent cap with four wood screws supplied (see Figure 13).
Note
: Re­place the wood screws with appropri­ate fasteners for stucco, brick, concrete, or other types of siding.
WARNING: Do not recess vent termination in to any wall. This will cause a fire hazard.
For vinyl siding use vinyl siding stand­offs between vent cap and exterior wall. The vinyl siding standoff prevents ex­cessive heat from melting the vinyl sid­ing material. Bolt the vent cap to the standoff. Apply non-hardening mastic around outside edge of the standoff in­stead of the vent cap assembly. Use wood screws provided to attach the standoff. See Figure 14.
5. Slide the wall thimble over the vent pipe before connecting the horizontal run to the vent cap (see Figure 15).
6. Carefully move the fireplace with v ent assembly attached toward the wall and insert the vent pipe into the horizontal termination. The pipe overlap should be a minimum of 1 1/4". Apply silicone to the connection. Fasten all vent con­nections with screws provided. Refer to Fir eplace Installation on page 16 for instructions on securing unit to fram­ing or floor.
7. Slide the wall thimble against the inte­rior wall surface and attach with screws provided (see Figure 15).
Cut Vinyl Siding Away to Fit Standoff
Wood Screw
Standoff
UP
Nut
Apply Mastic to All Four Sides
Figure 14 - Installing Vinyl Siding Standoff
Vent Cap
Bolt
Rigid Vent Pipe Flexible Vent Pipe
Figure 11 - Vent Pipe Connections
Vent Opening
Combustible Wall
10"
(254mm)
10"
(254mm)
(Framing
Vent Opening
Noncombustible Wall
7 1/2"
(190mm)
Figure 12 - Vent Opening Requirements
105455
Detail)
Apply Mastic to All Four Sides
UP
Wood Screw
Vent Cap
Figure 13 - Installing Horizontal Vent Cap
9
Interior Wall Surface
Wall Thimble
Vent Cap (Horizontal Termination)
Figure 15 - Connecting Vent Cap with Horizontal Vent Pipe
Screw
Horizontal Vent Pipe
Continued
CDV34(N/P)
UP
DIRECT-VENT FIREPLACE (NATURAL/PROPANE/LP)
VENTING INSTALLATION
Continued
Horizontal Termination Configurations
Figures 16 through 20 show different con­figurations for venting with horizontal ter­mination. Each figure includes a chart with vertical minimum/maximum and horizon­tal maximum dimensions which must be met. All connections must be sealed with high temperature silicone sealant as speci­fied in the second warning statement on page 7. All horizontal terminations require 1/4" rise per 12" of horizontal run.
(30° and 90° only, no vertical pipe)
(30° elbow, 1' vertical pipe, 90° elbow)
Note:
corner installation.
Figure 17 - Horizontal Termination Configuration for Rigid Venting Using One 90° Elbow
Horizontal Venting
Vertical (V) Horizontal (H)
44" min. 29" max.
55" min. 41" max.
67" min. 60" max. 79" min. 84" max. 96" min. 20' max.
This configuration for use with
UP
CBVK Vent Kit Shown
UP
CGFVK Vent Kit Shown (recommended for use with cabinet mantels)
Horizontal Venting
Vertical (V) Horizontal (H)
37" min. 10" max.
Figure 16 - Horizontal Termination Configuration for Rigid Venting
Horizontal Venting
See information in Figures 16 and 17 for Vertical(V) and Horizontal(H) maxi­mums and minimums. The same amounts apply for flexible venting.
Figure 18 - Horizontal Termination Using Flexible Venting
10
105455
VENTING INSTALLATION
Continued
Venting with Two 90° Elbows
Vertical (V) Horizontal (H1) Horizontal (H1) +
Horizontal (H2)
5' min. 2' max. 6' max. 6' min. 4' max. 12' max. 7' min. 6' max. 18' max. 8' min. 8' min. 20' max.
20' max. 8' max. 20' max.
OWNER’S MANUAL
UP
Figure 19 - Horizontal Termination Configuration for Rigid Venting Using Two 90° Elbows
Venting with Two 90° Elbows
Vertical (V) Horizontal (H1) +
Horizontal (H2)
5' min. 6' max. 6' min. 12' max. 7' min. 18' max. 8' min. 20' max.
20' max. 20' max.
°
Figure 20 - Horizontal Termination Configuration for Rigid Venting Using Two 90
Elbows with Termination at 90° with Fireplace
105455
Continued
11