Also Design-Certified As A Vented Decorative Appliance
OWNER’S OPERATION AND INSTALLATION MANUAL
FLAME-MAX
®
Multi-Sided
Log Design
VYM27PR
Remote Control
Ready Model
WARNING: If the information in this
manual is not followed exactly, a fire or
explosion may result causing property
damage, personal injury, or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the
vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do
not use any phone in your building.
• Immediately call your gas supplier from
a neighbor’s phone. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier,
call the fire department.
— Installation and service must be per-
formed by a qualified installer, service
agency, or the gas supplier.
®
HI
O
F
F
REMOTE
OFF
N
O
P
I
T
L
O
LO
Patent Pending
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property
damage. Refer to this manual for correct installation and operational procedures. For assistance or additional
information consult a qualified installer,
service agency, or the gas supplier.
WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built fireplace,
or in an approved ventless firebox. It is
design certified for these installations
in accordance with ANS Z21.11.2.
Exception: Do not install this appliance in a factory-built fireplace that
includes instructions stating it has not
been tested or should not be used with
unvented gas logs.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in
which it is installed. Provisions for adequate combustion and ventilation air must be
provided. Refer to
This appliance may be installed in an aftermarket* manufactured (mobile) home, where not prohibited by state
or local codes.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Air for Combustion and Ventilation
Save this manual for future reference.
section on page 4 of this manual.
VANGUARD FLAME-MAX
®
UNVENTED PROPANE/LP GAS LOG HEATER
SAFETY
INFORMATION
WARNINGS
WARNING ICON G 001
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate, or service this heater. Improper use of this heater can cause
serious injury or death from burns,
fire, explosion, electrical shock,
and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
flu, with headaches, dizziness, or nausea. If you
have these signs, the heater may not be working
properly. Get fresh air at once! Have heater
serviced. Some people are more affected by
carbon monoxide than others. These include
pregnant women, people with heart or lung
disease or anemia, those under the influence of
alcohol, and those at high altitudes.
Propane Gas: Propane gas is odorless.
An odor-making agent is added to the gas.
The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas
may be present even though no odor exists.
Make certain you read and understand all Warnings. Keep this manual for reference. It is your
guide to safe and proper operation of this heater.
WARNING: Any change to
this heater or its controls can be
dangerous.
1.This appliance is only for use with the
type of gas indicated on the rating plate.
This appliance is not convertible for use
with other gases.
2.Do not place propane supply tank(s)
inside any structure. Locate propane
supply tank(s) outdoors.
3.To prevent performance problems, the
use of a propane tank of less than 100
lbs. capacity is not recommended.
4.If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do
not use any phone in your building
• immediately call your gas supplier
from a neighbor’s phone. F ollow the
gas supplier’s instructions
• if you cannot reach your gas supplier ,
call the fire department
5.This heater shall not be installed in a
bedroom or bathroom unless installed
as a vented appliance (see InstallingDamper Clamp Accessory, page 10).
6.Never install the heater
• in a recreational vehicle
• where curtains, furniture, clothing, or
other flammable objects are less than
42 inches from the front, top, or sides
of the heater
• in high traffic areas
• in windy or drafty areas
7.Before installing in a solid fuel burning fireplace, the chimney flue and firebox must be cleaned of soot, creosote,
ashes and loose paint by a qualified
chimney cleaner. Creosote will ignite
if highly heated. Inspect chimney flue
for damage. If damaged, operate heater
with flue damper closed.
8.If fireplace has glass doors, never operate this heater with glass doors closed.
If you operate heater with doors closed,
heat buildup inside fireplace will cause
glass to burst. Also if fireplace opening has vents at the bottom, you must
open the vents before operating heater .
9.Y ou must operate this heater with fireplace
screens in place. Make sure fireplace
screens are closed while running heater.
10. This log heater is designed to be smokeless. If logs ever appear to smoke, turn of f
heater and call a qualified service person.
Note:
During initial operation, slight
smoking could occur due to log curing and
heater burning manufacturing residues.
11. To prevent the creation of soot, follow
the instructions in Cleaning and Main-tenance, page 21.
12. Do not allow fans to blow directly into the
fireplace. Avoid an y drafts that alter burner
flame patterns. Ceiling fans can create
drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
12. Before using furniture polish, wax, carpet cleaner, or similar products, turn
heater off. If heated, the vapors from
these products may create a white powder residue within burner box or on
adjacent walls or furniture.
13. Do not use a blower insert, heat exchanger insert or other accessory not
approved for use with this heater.
14. This heater needs fresh, outside air ventilation to run properly. This heater has
an oxygen depletion sensor (ODS) pilot light safety system. The ODS shuts
down the heater if not enough fresh air
is available. See Air for Combustionand Ventilation, pages 4 through 6. If
heater keeps shutting off, see Trouble-shooting, pages 17 through 19.
15. Do not run heater
• where flammable liquids or vapors
are used or stored
• under dusty conditions
16. Do not use this heater to cook food or
burn paper or other objects.
17. Never place any objects on the heater.
18. Heater base assembly becomes very hot
when running heater. K eep children and
adults away from hot surface to avoid
burns or clothing ignition. Heater will
remain hot for a time after shutdown.
Allow surface to cool before touching.
19. Carefully supervise young children
when they are in the room with heater .
When using the hand-held remote accessory, keep selector switch in the
OFF position to prevent children from
turning on burner with remote.
20. Do not use heater if any part has been
exposed to or under water . Immediately
call a qualified service technician to inspect the room heater and to replace any
part of the control system and any gas
control which has been under water.
21. Do not operate heater if any log is broken. Do not operate heater if a log is
chipped (dime-sized or larger).
22. Turn heater off and let cool before servicing, installing, or repairing. Make sure
the selector switch is in the OFF position. Only a qualified service person
should install, service, or repair heater.
23. Make sure the selector switch is in the
OFF position when you are away from
home for long periods of time.
24. Operating heater above elevations of
4,500 feet could cause pilot outage.
2
104675
OWNER’S MANUAL
PRODUCT
IDENTIFICATION
Flame-Max
VYM27PR
Optional
Remote
Control
Optional Selector
Switch
Figure 1 - Product Identification
®
Piezo
Ignitor
MAN
AUTO
ONLO
OFF
STATUS
HI
TEMP
Flame
Adjustment
Knob
Control Knob
Log Set
Base Assembly
PRODUCT
FEATURES
OPERATION
This heater is clean burning. It requires no
outside venting. There is no heat loss out a
vent or up a chimney. Heat is generated by
realistic, dancing yellow flames. This heater
is designed for vent-free operation with flue
damper closed. It has been tested and approved to ANS Z21.11.2 standard for
unvented heaters. State and local codes in
some areas prohibit the use of vent-free
heaters. This heater may also be operated as
a vented decorative product (ANS Z21.60)
by opening flue damper (non-thermostat
operation only).
APPLICATION
These multisided logs are designed to be
equally beautiful when viewed from any angle.
They are designed specifically for use in
see-through, peninsula, and island fireboxes
with multiple openings. You may also install this log heater in a standard firebox.
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes, use
the latest edition of The National Fuel GasCode ANS Z223.1, also known as NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
NOTE:
are required, thermostat operation is not
permitted.
Where listed vented decorative logs
UNPACKING
CAUTION: Do not remove the
metal Data Plates from the grate
assembly. The Data Plates contain
important product information.
1.Remove logs and heater base assembly from carton.
heater base assembly by the burner.
This could damage heater. Always
handle base assembly by grate.
2.Remove all protective packaging applied to logs and heater for shipment.
3.Check all items for any shipping damage. If damaged, promptly inform
dealer where you bought heater.
Note:
Do not pick up
SAFETY PILOT
This heater has a pilot with an Oxygen
Depletion Sensor Shutoff System (ODS).
The ODS/pilot is a required feature for ventfree room heaters. The ODS/pilot shuts off
the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor. This system
requires no matches, batteries, or other
sources to light heater.
REMOTE CONTROL
ACCESSORIES
There are four optional remote controls that
can be purchased separately for this log
heater:
• wall switch
• wall thermostat
• hand held ON/OFF remote
• hand held thermostat remote
See Accessories, page 24.
NOTE:
thermostat may not be used where vented
decorative listing is required.
The wall thermostat or hand-held
104675
3
VANGUARD FLAME-MAX
®
UNVENTED PROPANE/LP GAS LOG HEATER
AIR FOR
COMBUSTION AND
VENTILATION
WARNING: This heater shall
not be installed in a confined space
or unusually tight construction
unless provisions are provided
for adequate combustion and ventilation air. Read the following instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
Today’s homes are built more energy efficient than ever. New materials, increased
insulation, and new construction methods
help reduce heat loss in homes. Home owners
weather strip and caulk around windows and
doors to keep the cold air out and the warm air
in. During heating months, home owners
want their homes as airtight as possible.
While it is good to make your home energy
efficient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning
appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and
fuel burning appliances draw air from the
house to operate. You must provide adequate fresh air for these appliances. This
will insure proper venting of vented fuelburning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National
Fuel Gas Code. NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classifications:
1.Unusually Tight Construction
2.Unconfined Space
3.Confined Space
The information on pages 4 through 6 will
help you classify your space and provide
adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for
combustion and ventilation. However, in
buildings of unusually tight construction,
you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to the
outside atmosphere have a continuous water vapor retarder with
a rating of one perm (6x10
per pa-sec-m2) or less with openings gasketed or sealed
b. weather stripping has been
added on openable windows and
doors
c. caulking or sealants are applied
to areas such as joints around
window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and
gas lines, and at other openings.
If your home meets all of the three
criteria above, you must provide additional fresh air. See
From Outdoors
If your home does not meet all of the
three criteria above, proceed to
termining Fresh-Air Flow For Heater
Location
and
Ventilation Air
, page 6.
, page 5.
and
-11
kg
De-
Confined and Unconfined Space
The National Fuel Gas Code (ANS Z223.1,
1992 Section 5.3) defines a confined space
as a space whose volume is less than 50
cubic feet per 1,000 Btu per hour (4.8 m3 per
kw) of the aggregate input rating of all
appliances installed in that space and an
unconfined space as a space whose volume
is not less than 50 cubic feet per 1,000 Btu
per hour (4.8 m3 per kw) of the aggregate
input rating of all appliances installed in that
space. Rooms communicating directly with
the space in which the appliances are installed*, through openings not furnished
with doors, are considered a part of the
unconfined space.
This heater shall not be installed in a confined space or unusually tight construction
unless provisions are provided for adequate
combustion and ventilation air.
* Adjoining rooms are communicating only
if there are doorless passageways or ventilation grills between them.
4
104675
OWNER’S MANUAL
AIR FOR
COMBUSTION AND
VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1.Determine the volume of the space (length x width x height).
Length x Width x Height = _____________ cu. ft. (volume of space)
Example:
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.
2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
_______________ (volume of space) ÷ 50 cu. ft. = (maximum Btu/Hr the space can support)
Example:
3.Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater_____________ Btu/Hr
Gas water heater*_____________ Btu/Hr
Gas furnace_____________ Btu/Hr
Vented gas heater_____________ Btu/Hr
Gas fireplace logs_____________ Btu/Hr
Other gas appliances* +_____________ Btu/Hr
Total =_____________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
____________Btu/Hr (maximum the space can support)
____________Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-
ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)
Example:
Gas water heater40,000 Btu/Hr
Vent-free heater + 39,000 Btu/Hr
Total= 79,000 Btu/Hr
51,200 Btu/Hr (maximum the space can support)
79,000 Btu/Hr (actual amount of Btu/Hr used)
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space
or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the
104675
National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3
5
or applicable local codes.
Continued
VANGUARD FLAME-MAX
®
UNVENTED PROPANE/LP GAS LOG HEATER
AIR FOR
COMBUSTION AND
VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside
Building
This fresh air would come from an adjoining
unconfined space. When ventilating to an
adjoining unconfined space, you must provide two permanent openings: one within
12" of the ceiling and one within 12" of the
floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also
remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel
Gas Code NFPA 54/ANS Z223.1, Section
5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
Ventilation
Grills
Into Adjoining
Room,
Option 1
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
12"
12"
Option 2
WARNING: Rework worksheet, adding the space of the
adjoining unconfined space. The
combined spaces must have
enough fresh air to supply all
appliances in both spaces.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the
ceiling and one within 12" of the floor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces.
IMPORTANT:
inlet or outlet air into attic if attic has a
thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.
Do not provide openings for
Figure 2 - Ventilation Air from Inside Building
Outlet
Air
Ventilated
Attic
Outlet
Air
Inlet
Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors
To Attic
To
Crawl
Space
Ventilated
Crawl Space
6
104675
OWNER’S MANUAL
42"
16"
Left and
Right Sides
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat. Use
this heater along with your primary heating system. Do not install this heater as your primary
heat source. If you have a central
heating system, you may run
system’s circulating blower while
using heater. This will help circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
NOTICE: A qualified service person must install heater. Follow
all local codes.
NOTICE: State or local codes may
only allow operation of this appliance in a vented configuration.
Check your state or local codes.
WARNING: Before installing
in a solid fuel burning fireplace,
the chimney flue and firebox must
be cleaned of soot, creosote,
ashes and loose paint by a qualified chimney cleaner. Creosote
will ignite if highly heated. A dirty
chimney flue may create and distribute soot within the house. Inspect chimney flue for damage. If
damaged, operate heater with flue
damper closed.
WARNING: Never install the
heater
• in a bedroom or bathroom unless installed as a vented appliance, see page 10
• in a recreational vehicle
• where curtains, furniture,
clothing, or other flammable
objects are less than 42 inches
from the front, top, or sides of
the heater
• in high traffic areas
• in windy or drafty areas
CAUTION: This heater creates warm air currents. These
currents move heat to wall surfaces next to heater. Installing
heater next to vinyl or cloth wall
coverings or operating heater
where impurities (such as tobacco smoke, aromatic candles,
cleaning fluids, oil or kerosene
lamps, etc.) in the air exist, may
discolor walls.
IMPORTANT:
ture to the air. Although this is beneficial,
installing heater in rooms without enough
ventilation air may cause mildew to form
from too much moisture. See Air for Com-bustion and Ventilation, pages 4 through 6.
Vent-free heaters add mois-
CHECK GAS TYPE
Use only propane gas. If your gas supply is
not propane, do not install heater. Call
dealer where you bought heater for proper
type heater.
INSTALLATION AND
CLEARANCES
(Vent-Free Operation Only)
WARNING: Maintain the minimum clearances. If you can, provide greater clearances from
floor, ceiling, and adjoining wall.
MINIMUM FIREPLACE
CLEARANCE TO
COMBUSTIBLE MATERIALS
Log SizeSide WallCeiling
27"16"42"
LOG SIZING REQUIREMENTS
LogMinimum Firebox
SizeHeightDepthWidth
27"17"19"32"
Carefully follow the instructions below. This
will ensure safe installation into a masonry,
UL127-listed manufactured fireplace, or
listed vent-free firebox.
Minimum Wall and Ceiling
Clearances (see Figure 4)
A. Clearances from the side of the fire-
place opening to any combustible wall
should not be less than 16 inches.
B. Clearances from the top of the fireplace
opening to the ceiling should not be less
than 42 inches.
WARNING: Seal any fresh air
vents or ash clean-out doors located on floor or wall of fireplace.
If not, drafting may cause pilot
outage or sooting. Use a heatresistant sealant. Do not seal
chimney flue damper.
104675
Figure 4 - Minimum Clearance to Wall and
Ceiling
Continued
7
VANGUARD FLAME-MAX
®
UNVENTED PROPANE/LP GAS LOG HEATER
INSTALLATION
Continued
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney flue damper open.
If running heater with damper
open, noncombustible material
above fireplace opening is not
needed.
Minimum Noncombustible
Material Clearances
If Not Using Mantel
Note:
If using a mantel, proceed to If Using
Mantel. If not using a mantel, follow the
information below.
You must have noncombustible material(s)
above both fireplace openings. Noncombustible materials (such as slate, marble,
tile, etc.) must be at least 1/2 inch thick.
With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8" up (for
all models). If noncombustible material is
less than 12", you must install the fireplace
hood accessory. See Figure 5 at right for
minimum clearances.
IMPORTANT:
minimum clearances, you must operate
heater with chimney flue damper open. Go
to Installing Damper Clamp Accessory forVented Operation, page 10.
If Using Mantel
You must have noncombustible material(s)
above the fireplace opening. Noncombustible materials (such as slate, marble, tile,
etc.) must be at least 1/2 inch thick. With
sheet metal, you must have noncombustible
material behind it. Noncombustible material must extend at least 8 inches up (for all
models). If noncombustible material is less
than 12", you must install the fireplace hood
accessory. Even if noncombustible material
is more than 12", you may need the hood
accessory to deflect heat away from your
mantel shelf. See Figure 5 and Figures 6 and
7, page 9, for minimum clearances.
If you cannot meet these
NoncombustibleRequirements for
Material Distance (A)Safe Installation
12" or moreNoncombustible material OK.
Between 8" and 12"Install fireplace hood accessory (GA6050, GA6052
or GA6053, see
Less than 8"Noncombustible material must be extended to at
least 8". See
cannot extend material, you must operate heater
with flue damper open.