WARNING: If the information in this manual is not
followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
WARNING: Improper installation,
adjustment, alteration, service, or
maintenance can cause injury or
property damage. Refer to this
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
manual for correct installation and
operational procedures. For assistance or additional information consult a qualified installer, service
agency, or the gas supplier.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
— Installation and service must be performed by a quali-
fied installer, service agency, or the gas supplier.
WARNING: This is an unvented gasfired heater. It uses air (oxygen)
from the room in which it is installed. Provisions for adequate
combustion and ventilation air
must be provided. Refer to
Combustion and Ventilation
Air for
sec-
tion on page 5 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured
(mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance
is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
Save this manual for future reference.
TABLE OF CONTENTS
SAFETY INFORMATION
2
TABLE OF CONTENTS
SAFETY INFORMATION ............................................................ 2
WARNING: This product contains and/or generates
chemicals known to the State of California to cause
cancer or birth defects, or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and
completely before trying to assemble, operate, or service this fireplace. Improper use of this fireplace can
cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
CLEANING AND MAINTENANCE ............................................ 24
WARNING: Do not use a blower insert, heat
exchanger insert, or other accessory not approved
for use with this fireplace.
WARNING: Do not allow fans to blow directly into
the fireplace. Avoid any drafts that alter burner flame
patterns. Ceiling fans can create drafts that alter
burner flame patterns. Altered burner patterns can
cause sooting.
DANGER: Carbon monoxide poisoning may lead
to death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide
poisoning resemble the flu, with headaches, dizziness, or nausea.
If you have these signs, the fireplace may not be working properly.
Get fresh air at once! Have fireplace serviced. Some people are
more affected by carbon monoxide than others. These include
pregnant women, people with heart or lung disease or anemia,
those under the influence of alcohol, and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/LP gases are
odorless. An odor-making agent is added to the gas. The odor
helps you detect a gas leak. However, the odor added to the gas can
fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this
manual for reference. It is your guide to safe and proper operation
of this fireplace.
WARNING: Any change to this fireplace or its
controls can be dangerous.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Due to high temperatures, the appliance should be
located out of traffic and away from furniture and
draperies.
Do not place clothing or other flammable material on
or near the appliance. Never place any objects on
the heater.
Fireplace front and screen become very hot when
running heater. Keep children and adults away from
hot surfaces to avoid burns or clothing ignition.
Fireplace will remain hot for a time after shutdown.
Allow surfaces to cool before touching.
Carefully supervise young children when they are in
the room with fireplace. When using the hand-held
remote accessory (Remote-Ready Models Only), keep
selector switch in the OFF position to prevent children from turning on burners with remote.
You must operate this fireplace with the fireplace
screen in place. Make sure fireplace screen is closed
before running fireplace.
111244-01A
SAFETY INFORMATION
Continued
Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors
and liquids.
1.This appliance is only for use with the type of gas indicated on
the rating plate. This appliance is not convertible for use with
other gases.
2.Do not place propane/LP supply tank(s) inside any structure.
Locate propane/LP supply tank(s) outdoors.
3.If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in
your building
• immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions
• if you cannot reach your gas supplier , call the fire department
4.This fireplace shall not be installed in a bathroom. RemoteReady Models shall not be installed in a bedroom.
5.Do not use this fireplace as a wood-burning fireplace. Use only
the logs provided with the fireplace.
6.Do not add extra logs or ornaments such as pine cones, vermiculite, or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could
fall into the control area of fireplace.
7.This fireplace is designed to be smokeless. If logs ever appear
to smoke, turn off fireplace and call a qualified service person.
Note:
During initial operation, slight smoking could occur due
to log curing and fireplace burning manufacturing residues.
8.To prevent the creation of soot, follow the instructions in Clean-ing and Maintenance, pages 24 and 25.
9.Before using furniture polish, wax, carpet cleaner, or similar
products, turn fireplace off. If heated, the vapors from these
products may create a white powder residue within burner box
or on adjacent walls or furniture.
10. This fireplace needs fresh air ventilation to run properly. This
fireplace has an Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the fireplace if not enough
fresh air is available. See Air for Combustion and Ventilation,
pages 5 through 7. If fireplace keeps shutting off, see Trouble-shooting, pages 26 through 28.
11. Do not run fireplace
• where flammable liquids or vapors are used or stored.
• under dusty conditions.
12. Do not use this fireplace to cook food or burn paper or other
objects.
13. Never place any objects in the fireplace or on logs.
14. Do not use fireplace if any part has been under water . Immediately call a qualified service technician to inspect the room
fireplace and to replace any part of the control system and any
gas control which has been under water.
SAFETY INFORMATION
PRODUCT IDENTIFICATION
3
3
15. Turn off and unplug fireplace and let cool before servicing. Only
a qualified service person should service and repair fireplace.
16. Operating fireplace above elevations of 4,500 feet could cause
pilot outage.
17. Do not operate fireplace if log is broken. Do not operate fireplace if log is chipped (dime-sized or larger).
18. T o prevent performance problems, do not use propane/LP fuel
tank of less than 100 lbs. capacity.
19. Provide adequate clearances around air openings.
PRODUCT IDENTIFICATION
Fireplace
Cabinet
Hood
Screen
Log
Ignitor Button
Control Knob
Fireplace
Cabinet
Hood
Logs
Ignitor Button
I
H
L
O
O
F
F
N
O
P
I
T
L
Remote
Control
(Optional)
Control
Knob
Figure 1 - Vent-Free Compact Dual Flame Fireplace
O
111244-01A
For more information, visit www.desatech.com
For more information, visit www.desatech.com
OPTIONAL REMOTE CONTROL ACCESSORIES
LOCAL CODES
4
PRODUCT FEATURES
UNPACKING
HOOD ASSEMBLY
OPTIONAL REMOTE
CONTROL ACCESSORIES
(For Remote-Ready Models Only)
There are four optional remote controls that can be purchased
separately for Remote-Ready Models only:
• wall switch• hand-held ON/OFF remote
• wall thermostat• hand-held thermostat remote
See Accessories, pages 36 and 37.
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the
absence of local codes, use the latest edition of The National FuelGas Code ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
PRODUCT FEATURES
SAFETY PILOT
HOOD ASSEMBLY
WARNING: Always have screen in place before
operating fireplace. This prevents excessive temperatures on fireplace surfaces.
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts
specifically approved with this fireplace may result in
property damage or personal injury.
Tools Required:
• Phillips screwdriver• slotted screwdriver
• 5/16" hex wrench• scissors
1.Lift fireplace screen up and pull out to remove (see Figure 2).
Set screen aside until installation has been completed.
2.Cut two plastic straps to remove the log from the firebox cavity.
Set log aside.
3.An optional blower is available. See Accessories, pages 36 and
37. Install optional blower now. Follow installation instructions provided with blower and see page 12 for Remote-Ready
Models or page 13 for Thermostat-Controlled Models.
4.Locate four black phillips sheet metal screws in hardware packet.
5.Slide hood between louver and firebox top and align screw holes.
6.Insert screws as shown in Figure 3. Tighten screws firmly.
This fireplace has a pilot with an Oxygen Depletion Sensing (ODS)
safety shutoff system. The ODS/pilot is a required feature for vent-free
room fireplaces. The ODS/pilot shuts off the fireplace if there is not
enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system requires no matches,
batteries, or other sources to light fireplace.
THERMOSTATIC HEAT CONTROL FOR
THERMOSTAT-CONTROLLED MODELS
Thermostat-Controlled models have a thermostat sensing bulb and
a control valve. The thermostat will automatically modulate the heat
output to maintain a consistent room temperature. This results in
greater fireplace comfort. This can also result in lower gas bills.
UNPACKING
1.Remove fireplace and hood from carton. Log is wrapped and
inside fireplace. Do not remove at this time.
2.Remove all protective packaging applied to fireplace for
shipment.
3.Make sure your fireplace includes one hardware packet.
4.Check fireplace for any shipping damage. If fireplace is damaged, promptly inform dealer where you bought fireplace.
Shoulder Screw
Screen
Figure 2 - Removing and Installing Screen
Hood
Figure 3 - Assembling Hood
Sheet Metal
Screws
Louver
Firebox Top
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111244-01A
AIR FOR COMBUSTION AND
VENTILATION
WARNING: This fireplace shall not be installed in
a confined space or unusually tight construction
unless provisions are provided for adequate combustion and ventilation air. Read the following instructions to insure proper fresh air for this and
other fuel-burning appliances in your home.
Today’s homes are built more energy efficient than ever. New materials, increased insulation, and new construction methods help reduce
heat loss in homes. Home owners weather strip and caulk around
windows and doors to keep the cold air out and the warm air in. During
heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home
needs to breathe. Fresh air must enter your home. All fuel-burning
appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances
draw air from the house to operate. You must provide adequate fresh
air for these appliances. This will insure proper venting of vented
fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation
classifications:
1.Unusually Tight Construction
2.Unconfined Space
3.Confined Space
The information on pages 5 through 7 will help you classify your
space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction
where:
a.walls and ceilings e xposed to the outside atmosphere
have a continuous water vapor retar der with a rating
of one perm (6 x 10
openings gasketed or sealed
b. weather stripping has been added on openable win-
dows and doors
-11
kg per pa-sec-m2) or less with
and
and
AIR FOR COMBUSTION AND VENTILATION
Determining Fresh-Air Flow for Fireplace Location
c. caulking or sealants are applied to areas such as
joints around window and door frames, between sole
plates and floors, between wall-ceiling joints, between
wall panels, at penetrations f or plumbing, electrical,
and gas lines, and at other openings.
If your home meets all of these three criteria, you
must provide ad ditional fresh air. See
From Outdoors
If your home does not meet all of the three criteria above,
proceed to
Location,
below.
Providing Adequate Ventilation
Ventilation Air
, page 8
.
Determining Fresh-Air Flow For Fireplace
5
5
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a
confined space as a space whose volume is less than 50 cubic feet
per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating
of all appliances installed in that space and an unconfined space as
a space whose volume is not less than 50 cubic feet per 1,000 Btu per
hour (4.8 m3 per kw) of the aggregate input rating of all appliances
installed in that space. Rooms communicating directly with the
space in which the appliances are installed*, through openings not
furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless
passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR
FIREPLACE LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install fireplace plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
1.Determine the volume of the space (length x width x height).
Length x Width x Height =___________ cu. ft. (volume of space)
Example:
height) = 1792 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.
2.Multiply the space volume by 20 to determine the maximum Btu/Hr
the space can support.
__________ (volume of space) x 20 = (Maximum Btu/Hr the space
Example:
Btu/Hr the space can support)
Space size 16 ft. (length) x 14 ft. (width) x 8 ft. (ceiling
can support)
1792 cu. ft. (volume of space) x 20 = 35,840 (maximum
111244-01A
For more information, visit www.desatech.com
For more information, visit www.desatech.com
AIR FOR COMBUSTION AND VENTILATION
6
Determining Fresh-Air Flow for Fireplace Location (Cont.)
Ventilation Air
AIR FOR COMBUSTION AND
VENTILATION
Continued
3.Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free fireplace_____________ Btu/Hr
Gas water heater*_____________ Btu/Hr
Gas furnace_____________ Btu/Hr
Vented gas heater_____________ Btu/Hr
Gas fireplace logs_____________ Btu/Hr
Other gas appliances* + _____________ Btu/Hr
Total = _____________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater_____________ Btu/Hr
Vent-free fireplace+ _____________ Btu/Hr
Total= _____________ Btu/Hr
4.Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.
__________________ Btu/Hr (maximum the space can support)
__________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. You must
provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See V entilation Air Fr omInside Building.
B. Vent room directly to the outdoors. See Ventilation Air From Out-
doors, page 7.
C. Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room
unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support,
the space is an unconfined space. You will need no additional fresh air ventilation.
35,840 Btu/Hr (maximum the space can support)
40,000 Btu/Hr (actual amount of Btu/Hr used)
30,000
10,000
40,000
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space.
When ventilating to an adjoining unconfined space, you must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting the two spaces
(see options 1 and 2, Figure 4). You can also remove door into
adjoining room (see option 3, Figure 4). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion
and Ventilation for required size of ventilation grills or ducts.
12"
Ventilation
Grills
Into Adjoining
Room,
Option 1
Or
Remove
Door into
Adjoining
Room,
Option
3
Figure 4 - Ventilation Air from Inside Building
Ventilation Grills
Into Adjoining Room,
Option 2
12"
WARNING: If the area in which the fireplace may
be operated is smaller than that defined as an unconfined space or if the building is of unusually tight
construction, provide adequate combustion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes
For more information, visit www.desatech.com
For more information, visit www.desatech.com
.
111244-01A
AIR FOR COMBUSTION AND VENTILATION INSTALLATION
Ventilation Air (Cont.)
INstallation
7
7
AIR FOR COMBUSTION AND
VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT:
attic if attic has a thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.
Outlet
Air
Do not provide openings for inlet or outlet air into
Outlet
Air
Ventilated
Attic
To Attic
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary
heating system. Do not install this heater as your
primary heat source. If you have a central heating
system, you may run system’s circulating blower
while using heater. This will help circulate the heat
throughout the house. In t he event of a power outage,
you can use this heater as your primary heat source.
WARNING: A qualified service person must in-
stall fireplace. Follow all local codes.
WARNING: Never install the fireplace
• in a bathroom
• in a recreational vehicle
• where curtains, furniture, clothing, or other flam-
mable objects are less than 36 inches from the
front, top, or sides of the fireplace
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
Inlet
Air
Inlet Air
Figure 5 - Ventilation Air from Outdoors
Ventilated
Crawl Space
To
Crawl
Space
WARNING: Never install the Remote-Ready Models in this manual in a bedroom. Any heating product
with a Btu/hr rating over 10,000 cannot be used in a
bedroom.
CAUTION: This fireplace creates warm air currents. These currents move heat to wall surfaces next
to fireplace. Installing fireplace next to vinyl or cloth
wall coverings or operating fireplace where impurities
(such as, but not limited to, tobacco smoke, aromatic
candles, cleaning fluids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls or cause odors.
IMPORTANT:
this is beneficial, installing fireplace in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air forCombustion and Ventilation, pages 5 through 7.
Note:
Your fireplace is designed to be used in zero clearance
installations. Wall or framing material can be placed directly against
any exterior surface on the rear, sides, or top of your fireplace,
except where standoff spacers are integrally attached. If standoff
spacers are attached to your fireplace, these spacers can be placed
directly against wall or framing materials.
Note:
When installing fireplace directly on carpeting, tile or other
combustible material, other than wood flooring, the fireplace shall
be installed on a metal or wood panel extending the full width and
depth of the fireplace.
Vent-free fireplaces add moisture to the air. Although
111244-01A
For more information, visit www.desatech.com
For more information, visit www.desatech.com
INSTALLATION
8
Check Gas Type
Installation Items
Fireplace Clearances
INSTALLATION
Continued
Use the dimensions shown for rough openings to create the easiest
installation (see Built-In Fireplace Installation, page 9).
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for your unit. If
your gas supply is not correct, do not install fireplace. Call dealer
where you bought fireplace for proper type fireplace.
INSTALLATION ITEMS
Before installing fireplace, make sure you have the items listed
below.
• external regulator (supplied by installer, for propane/LP units only)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection*
• ground joint union
• sediment trap
• tee joint
• pipe wrench
* A CSA design-certified equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge connection. Purchase
the optional CSA design-certified equipment shutoff valve from
your dealer. See Accessories, pages 36 and 37.
Note:
If desired, purchase a four-sided brass trim kit for built-in
installations. See Accessories, pages 36 and 37.
FIREPLACE CLEARANCES
CAUTION: If you install the fireplace in a home
garage
• fireplace pilot and burner must be at least 18
inches above floor.
• locate fireplace where moving vehicle will not hit it.
For convenience and efficiency, install fireplace
• where there is easy access for operation, inspection, and service
• in coldest part of room
An optional blower kit is available from your dealer. See Accesso-
ries, pages 36 and 37. If planning to use blower, follow instructions
provided with blower for power source.
Minimum Clearances For Side Combustible
Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabinet to any com-
bustible material and wall should follow diagram in Figure 6.
Example:
combustible material and protrudes 3 1/2" from the wall. This
combustible material must be 4" from the side of the fireplace
opening (see Figure 6).
B. Clearances from the top of the fireplace opening to the ceiling
should not be less than 36 inches.
C. For mantel clearances, see Figure 10 on page 10.
The face of a mantel, bookshelf, etc. is made of
MINIMUM CLEARANCE TO
COMBUSTIBLE MATERIALS
WARNING: Maintain the minimum clearances
shown in Figure 6. If you can, provide greater clearances from floor, ceiling, and joining wall.
NOTICE: If you install the fireplace in a bedroom
(Thermostat-Controlled Models only), some building
codes require that the fireplace/mantel system be
secured to (or within) a wall. You can position fireplace in an optional cabinet or corner mantel. You can
also recess fireplace into the wall.
If your fireplace is to be used with an optional mantel, the
installation instructions included with your mantel shows an CSA
approved method of attaching the fireplace/mantel system to a
wall.
IMPORTANT:
specified in this manual. Purchase the optional mantel from your
dealer (see Accessories, pages 36 and 37).
If your fireplace is to be recessed into the wall, see Built-In FireplaceInstallation on page 9 to secure your fireplace into the wall.
Only use optional cabinet or corner mantels
For more information, visit www.desatech.com
For more information, visit www.desatech.com
TopLeft andBottom
Right Sidesand Rear
36"6"0"
Example
*
*Minimum 16 inches from Side Wall
Figure 6 - Minimum Clearance for Combustible to Wall
111244-01A
INSTALLATION
Continued
Built-In Fireplace Installation
INSTALLATION
9
9
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves installing fireplace
into a framed-in enclosure. This makes the front of fireplace flush
with wall. An optional brass trim kit accessory is available (see
Accessories, pages 36 and 37). Brass trim will extend past sides of
fireplace approximately 1/2 inch. This will cover the rough edges of
the wall opening. If installing a built-in mantel above the fireplace,
you must follow the clearances shown in Figure 10, page 10. Follow
the instructions below to install the fireplace in this manner.
ActualFraming
Height26"26
Front Width26 3/4"26 7/8"
Depth14 1/4"15 1/4"
1.Frame in rough opening. Use dimensions shown in Figure 7 for
the rough opening. If installing in a corner, use dimensions
shown in Figure 8 for the rough opening. The height is 26 7/8"
which is the same as the wall opening above.
2.If installing GA3450TA blower accessory, do so at this time.
Follow instructions included with blower accessory.
Note:
If not installing blower accessory , you may wish to run
electrical wiring to your fireplace for future blower installation (see Accessories, pages 36 and 37). Use only approved
three-wire electrical wiring.
1
15
/
4
"
7
/
8
"
26
7
/8"
WARNING: If pre-wiring, do not connect wiring to
any electrical source at this time.
Install fireplace electrical outlet and connect wiring
to outlet before connecting to electrical source. The
fireplace electrical outlet is included with the
GA3450TA blower accessory.
Only use the fireplace electrical outlet supplied with
the GA3450TA blower accessory.
Note:
A qualified installer should make all electrical connections.
3.Install gas piping to fireplace location. This installation includes
an approved flexible gas line (if allowed by local codes) after
the equipment shutoff valve. The flexible gas line must be the
last item installed on the gas piping.
4.If you have not installed hood, follow i n s t r u c t i ons on page 4.
5.Carefully set fireplace in front of rough opening with back of
fireplace inside wall opening.
6.Attach flexible gas line to fireplace gas regulator. See Con-necting Equipment Shutoff Valve to Heater Control, page 15.
7.Bend four nailing flanges on outer casing with pliers (see
Figure 9).
8.Attach fireplace to wall studs using nails or wood screws
through holes in nailing flange.
9.Check all gas connections for leaks. See Checking Gas Con-nections, page 16.
10. If using optional brass trim kit, install the trim after final finishing and/or painting of wall. See instructions included with
brass trim accessory for attaching brass trim.
IMPORTANT:
When finishing your firebox, combustible materials
such as wall board, gypsum board, sheet rock, drywall, plywood, etc.
may be butted up next to the sides and top edge of the firebox.
Combustible materials should never overlap the firebox front facing.
Noncombustible materials such as brick, tile, etc.
may overlap the front facing, but should never cover any necessary
openings like louvered slots.
WARNING: Do not allow noncombustible materials
to cover any necessary openings like louvered slots.
WARNING: Never modify or cover the louvered
slots on the front of the firebox.
WARNING: Use only noncombustible mortar or
adhesives when overlapping the front facing with
noncombustible facing material.
Mantel Clearances for Built-In Installation
If placing mantel above built-in fireplace, you must meet minimum
clearance between mantel shelf and top of fireplace opening.
NOTICE: Surface temperatures of adjacent walls and
mantels become hot during operation. Walls and
mantels above the firebox may become hot to the
touch. If installed properly, these temperatures meet
the requirement of the national product standard.
Follow all minimum clearances shown in this manual.
Mantel Shelf
Note:
All vertical
measurements
are from top of
fireplace
opening to
bottom of
mantel shelf. All
measurements
are in inches.
10"
8"
6"
2 1/2"
NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the
following:
• raise the mantel to an acceptable height
• remove the mantel
OPTIONAL MANTEL INSTALLATION
Note:
Refer to instructions provided with the mantel for assembly
instructions. Refer to the following instructions for system installation. Refer to instructions on page 4 for hood assembly. Blower
accessory should be installed if it is being used (see InstallingOptional Blower Accessory GA3450TA, pages 11 through 13).
1.Unscrew four screws that attach top louver to fireplace. Re-
move louver from fireplace and set aside (see Figure 11).
2.Place base assembly next to wall at installation location.
3.Place fireplace on wood base (see Figure 12, page 11).
4.Place mantel around fireplace on base (see Figure 12, page 11).
5.Assemble perimeter trim kit. See Assembling Perimeter Trim,
page 11.
6.Firmly snap perimeter trim kit on shoulder screws. Shoulder
screws are located on fireplace cabinet (see Figure 12, page 11).
7.Align perimeter trim kit for flush fit around opening.
8.Center mantel left to right on base making sure mantel is flush
against wall.
9.Use two 3" wood screws provided and attach base of fireplace
to wooden mantel base (see Figure 12, page 11).
10. Remove perimeter trim kit and mantel. Be careful not to dam-
age wall or mantel.
11. Cut an access hole in base to run flexible gas line to fireplace
(see Figure 12, page 11). Make sure to locate access hole so
mantel will cover it when installed.
base to floor using wood screws. Countersink screw heads
and putty over.
12. Install gas line. See Connecting T o Gas Supply, pages 14 and 15.
Note:
You can secure
15"
18"
23"
21"
Side of Firebox
Figure 10 - Minimum Mantel Clearances for Built-In Installation
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Top Louver
Bottom Louver
Figure 11 - Removing Top Louver and Opening Bottom Louver
111244-01A
INSTALLATION
Continued
Optional Mantel Installation (Cont.)
INSTALLATION
Installing Optioanl Blower Accessory GA3450TA
11
11
13. Check for leaks. See Checking Gas Connections, page 16.
14. Place mantel around fireplace. Be careful not to damage wall
or mantel.
15. Place perimeter trim kit on the shoulder screws located on the
side and top of the fireplace. Firmly snap trim over shoulder
screws on fireplace (see Figure 12).
16. Adjust assembly to remove any gaps. Attach remaining two 3"
wood screws from hardware pack through openings inside of
fireplace sides into the mantel. The openings are located at top
behind the area for top louver (see Figure 12).
17. Reinstall top louver.
Assembling Perimeter Trim (Perimeter trim shipped
with mantel)
1.Remove packaging from three remaining pieces of trim.
2.Locate two adjusting plates with set screws, and two shims
in the hardware packet.
3.Align shim under adjusting plate as shown in Figure 13.
4.Slide one end of adjusting plate/shim in slot on mitered edge
of top brass trim (see Figure 13).
5.Slide other end of adjusting plate/shim in slot on mitered edge
of side perimeter trim (see Figure 13).
6.While firmly holding edges of perimeter trim together, tighten
both set screws on the adjusting plate with slotted screwdriver.
7.Repeat steps 1 through 6 for other corner.
8.Set perimeter trim assembly aside for later installation.
Set
Screws
Adjusting
Plate
Slot
Shim
Side Brass Trim
Figure 13 - Assembling Brass Trim
Top Brass Trim
Mitered Edge
Shoulder Screw
Mantel
Base
I
H
L
O
O
F
F
N
O
P
T
I
L
O
Assembled
Brass Trim
Hole for 3" Wood Screw for
Attaching Fireplace to
Wooden Base
Figure 12 - Attaching Brass Trim to Fireplace
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111244-01A
Hole for 3"
Wood Screw
for Attaching
Fireplace to
Mantel
Gas Line
Access Hole
Shoulder
Screws
INSTALLING OPTIONAL BLOWER ACCESSORY
GA3450TA
Removing Upper Louver
To install the blower accessory, you must first remove the upper
louver.
1.Lift screen off fireplace and remove log set if installed.
2.Remove 4 screws from upper louver (see Figure 11, page 10).
Save these screws.
3.Pull upper louver straight out from the cabinet. Be careful not to
scratch the paint. Set louver aside.
4.Open lower louver door by swinging door down (see Figure 11,
page 10).
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation.
CAUTION: Verify proper operation after servicing.
Note:
If you are using a mantel with your fireplace, use the
following instructions. If your fireplace is built-in, see For Built-InInstallation, page 13.
1.Install snap bushings found in blower kit into hole in left side
of outer casing and into one of the holes in rear of remote/
blower bracket.
2.Make sure the wire harness is firmly connected to the terminals on the blower bracket assembly.
3.Note the wire locations on back of AUTO/OFF/ON switch. The
terminals on back of switch are numbered 1, 2, and 3. Carefully
remove red wire from terminal 3 and blue wire from terminal 1.
Black wire can remain on middle terminal 2 (see Figure 14).
4.Carefully disconnect green and white wires at their insulated
connectors (see Figure 15).
Blower Bracket
Assembly
Screw
Wire
Harness
Wiring Routing
Hole in Baffle
Baffle
Blower
Mounting
Holes
5.In top of the fireplace cabinet, locate the four mounting holes
on the outer casing. Align these four holes with those on the
blower bracket assembly. Attach blower bracket assembly to
the outer casing with 4 #10 screws provided (see Figure 14).
6.Route the wire harness through the hole in left side of baffle
and between firebox wrapper and outer casing.
7.Insert the 4 wire harnesses from behind the remote/blower
bracket through hole in rear of bracket with bushing and through
the left rectangular hole to front of fireplace (see Figure 14).
8.Reconnect red wire to switch position 3. Reconnect blue wire
to switch position 1. Reconnect green and white wires.
9.Install the switch plate on the remote/blower bracket w it h 2 # 10
screws provided (see Figure 16). Route power cord out of the
cabinet by inserting it through the bushing on the outer casing
(see Figure 14). Plug fan kit into 120-Volt grounded power supply and test operation.
Note:
When switch is in the AUT O position, the fan will start after the fireplace has run for a few moments. The fan will continue to run for several moments after the
fireplace has been turned off. When switch is in the ON position,
the fan will run until turned to OFF .
10. Reinstall upper louver beginning with bottom screws (see Figure 11, page 10). Close lower louver door.
Fan Switch
110/115
V.A.C.
(Auto/Off/On)
Off
Black
White
Green
Auto
1
2
3
On
Red
Blue
Thermostat
Switch
(N.O.)
Blue
Red
White
Green
Blower
Motor
Switch
3
2
1
Power Cord
Blue
Switch
Plate
Black
Red
Wire Harness
I
H
L
O
O
F
F
N
O
P
T
I
L
O
Remote/Blower
Bracket
Lower Louver Door
Figure 14 - Installing Blower Bracket Assembly (Remote-Ready
Unit Shown)
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Figure 15 - Wiring Diagram For Blower Accessory Standard
Installation
Remote/Blower
Bracket
Switch
Plate
Screw
Figure 16 - Installing Switch Plate to Remote/Blower Bracket
111244-01A
INSTALLATION
Continued
For Built-In Installation
WARNING: A licensed electrician must connect the
wiring harness to electrical supply following all local
codes. Electrician must provide a clamp on the box cover
to secure the wiring. Wiring should be routed through the
bushing in the hole on the outer casing of fireplace.
1.Install snap bushing from blower kit into one hole on rear of remote/blower bracket (see Figure 17). The other hole is for a strain
relief clamp (not supplied) to secure incoming electrical supply .
2.Follow steps 2 through 6 in Installing Blower Accessory , page 12.
3.A licensed electrician must follow the wiring diagram to connect
incoming electrical supply to fan kit wiring harness (see Figure 18).
4.Plug power cord to outlet receptacle (not provided) as shown in
Figure 17. Wind extra cable of power cord and tie up with plastic wire strap (see Figure 17). Set cable bundle between the remote/blower bracket and outer casing, away from the burner .
5.Test to make sure blower is working properly.
6.Reinstall upper louver beginning with bottom screws (see Figure 11, page 10) and close lower louver .
Installing Blower Accessory GA3450TA (Cont.)
INSTALLATION
Fan Switch
(Auto/Off/On)
Auto
1
2
Off
110/115
V.A.C.
Black
White
Green
3
On
Red
Blue
Thermostat
Switch
(N.O.)
Blue
Red
White
Green
Blower
Motor
13
13
Figure 18 - Wiring Diagram For Blower Accessory Built-In
Installation
Extension Cord
Use extension cord if needed. The cord must have a three-prong,
grounding plug and a three-hole receptacle. Make sure cord is in good
shape. It must be heavy enough to carry the current needed. An
undersized cord will cause a drop in line voltage. This will result in
loss of power and overheating. Use a No. 16 AWG cord for lengths
less than 50 feet.
Blower Bracket
Wire Harness
Assembly
Screw
Switch
Plate
Switch
Blue
3
2
1
Red
Black
Power Cord
Plastic Wire
Strap
Outlet Receptacle
(not included)
Wire
Harness
Figure 17 - Installing Blower Bracket Assembly
Lower Louver Door
Clamp Connector
(not included)
Remote/ Blower
Bracket
I
H
L
O
O
F
F
N
O
P
T
I
L
O
111244-01A
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Loading...
+ 29 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.