WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury, or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch.
• Do not use any phone in your building.
• Immediatly call your gas wupplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
•
If you cannot reach your gas supplier, call the fire
department.
This appliance may be installed in an aftermarket*, permanently located, manufactured
(modile) home, where not prohibited by state or local codes.
This appliance is only for use with the type od gas indicated on the rating plate. This appliance
is not convertible for use with other gases, unless a certified kit is used.
WARNING: Improper installation
adjustment, alteration, service,
or maintenance can cause injury
or property damage. Refer to this
manual for correct installation and
operational procedures. For assistance or additional information
consult a qualified installer, service agency, or the gas supplier.
Installation and service must be
performed by a qualified installer, service agency, or the
gas supplier.
MODELS: (V) CD36T(N,P) (E)
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in
the Commonwealth of Massachusetts.
Save this manual for future reference.
For more information, visit www.desatech.com
TABLE OF CONTENTS
SAFETY INFORMATION
2
TABLE OF CONTENTS
SAFETY INFORMATION .......................................................... 2
HIGH ALTITUDE INSTALLATIONS ........................................ 21
SAFETY INFORMATION
WARNING: This product contains and/or generates
chemicals known to the State of California to cause
cancer or birth defects, or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully
and completely before trying to assemble, operate,
or service this fireplace. Improper use of this fireplace can cause serious injury or death from burns,
fire, explosions, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead
to death!
This fireplace must be installed by a qualified (certified or licensed)
service person. It has a sealed gas combustion chamber that uses a
coaxial pipe (pipe within a pipe and having the same center) venting
system. It brings in fresh air for combustion through the outer pipe and
combustion gases are exhausted through the inner pipe. If the glass
door assembly and venting pipe are not properly seated, connected,
and sealed, carbon monoxide leakage (spillage) can occur.
Carbon Monoxide Poisoning: Early signs of carbon monoxide
poisoning resemble the flu, with headaches, dizziness, or nausea. If
you have these signs, the fireplace may not have been installed
properly. Get fresh air at once! Have fireplace inspected and
serviced by a qualified service person. Some people are more
affected by carbon monoxide than others. These include pregnant
women, people with heart or lung disease or anemia, those under the
influence of alcohol, and those at high altitudes.
GAS SUPPLY AND PIPING .................................................. 21
HEARTH ACCESS AND ASSEMBLY ................................... 24
OWNER’S REGISTRATION FORM ......................................... 45
WARRANTY INFORMATION ...................................... Back Cover
Propane/LP and Natural Gas: Propane/LP and natural gases are
oderless. An odor-making agent is added to the gas. The odor helps
you detect a gas leak. However, the odor added to the gas can fade.
Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this
manual for reference. It is your guide to safe and proper operation
of this fireplace.
WARNING: Any change to this fireplace or its
controls can be dangerous.
1. This appliance is only for use with the type of gas indicated on
the rating plate. This appliance is not convertible for use with
other gases unless a certified kit is used.
2. For a propane/LP fireplace, do not place propane/LP supply
tank(s) inside any structure. Locate propane/LP tank(s)
outdoors. To prevent performance problems, do not use pro pane/LP fuel tank of less than 100 lbs. capacity.
3. If you smell gas:
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in
your building
• immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions
• if you cannot reach your gas supplier, call the fire department.
4. Never install the fireplace
• in a recreational vehicle
• in windy or drafty areas where curtains or other combustible
(flammable) objects can make contact with the fireplace front
• in high traffic areas
www.desatech.com
116035-01B
SAFETY INFORMATION
Rear Vent
Flue Collar
Top Vent
Flue Collar
Piezo Ignitor with
Optional Remote and
Blower Control Mount
Control Valve
Variable Input
Adjustment
Log
Set
Ember
Tray
Door Latch
Nailing
Flange
Lower
Louver
Panel
Junction Box
Glass
Door
Assembly
Upper
Louver
Panel
PRODUCT IDENTIFICATION
LOCAL CODES
3
SAFETY INFORMATION
Continued
5. This fireplace reaches high temperatures, Keep children and
adults away from hot surfaces to avoid burns or clothing igni tion. Fireplace will remain hot for a time after shutdown. Al low surfaces to cool before touching.
6. Carefully supervise young children when they are in the room
with fireplace.
7. Do not modify this fireplace under any circumstances. Any
parts removed for servicing must be replaced prior to operat ing fireplace.
8. Turn fireplace off and let cool before servicing, installing, or
repairing. Only a qualified service person should install, ser vice or repair this fireplace. Have fireplace inspected annu ally by a qualified service person.
9. You must keep control compartments, burners, and circulat ing air passages clean. More frequent cleaning may be needed
due to excessive lint and dust from carpeting, bedding mate rial, etc. Turn off the gas valve and pilot light before cleaning
fireplace.
10. Have venting system inspected annually by a qualified service
person. If needed, have venting system cleaned or repaired.
See Cleaning and Maintenance, page##.
11. Keep the area around your fireplace clear of combustible ma terials, gasoline, and other flammable vapor and liquids. Do
not run fireplace where these are used or stored. Do not place
items such as clothing or decorations on or around fireplace.
12. Do not use this fireplace to cook food or burn paper or other
objects.
13. Do not use any solid fuels (wood, coal, paper, cardboard, etc.)
in this fireplace. Use only the gas type indicated on the
nameplate.
14. This appliance, when installed, must be electrically grounded
in accordance with local codes or, in the absence of local codes,
with the National Electric Code, ANSI/NFPA 70, or the Ca-nadian Electric Code, CSA C22.1.
15. Do not use fireplace if any part has been exposed to or under
water. Immediately call a qualified service person to arrange
for replacement of the unit.
16. Do not operate fireplace if any log is broken or missing.
17. Do not use a blower insert, heat exchanger insert, or other ac cessory not approved for use with this fireplace.
18. Do not operate fireplace with glass door removed, cracked, or
broken.
19. Provide adequate clearances around air openings.
NOTICE: This product is intended only as a supplement to your central heating system and is not to be
installed as a primary source of heat. You may use this
product for emergency heating during a power outage.
PRODUCT IDENTIFICATION
Figure 1 - Rear / Top Direct-Vent Fireplace
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the
absence of local codes, use the current National Fuel Gas Code
ANSI Z223.1/NFPA 54* (USA) or the current CSA-B149.1 Installation Code (Canada).
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarh Park
Quincy, MA 02269
116035-01B
www.desatech.com
PRODUCT FEATURES
36"
(914 mm)
15"
(381 mm)
25"
(635 mm)
PRE-INSTALLATION PREPARATION
4
4
Location and Space Requirements
PRODUCT FEATURES
These are a few facts that can help you understand and enjoy your
direct-vent fireplace:
• The CD36R dedicated rear vent is best suited for flush or corner
installations when vented horizontally through an exterior wall
• The CD36T dedicated top vent is suited for any application
where height is necessary to terminate the venting system either
through the roof (vertical) or to gain sufficient height and offset
to vent to an outside/exterior wall (horizontal).
• The vent pipe installation is very important to allow for proper
operation. You must select the appropriate unit for your applica tion and follow the venting instructions to plan your installation.
• This fireplace may be installed in any room of your house provided
all local codes and these installation instructions are followed.
• Models (V)CD36R/T are equipped with a millivolt gas control
system that does not require electricity to operate. A piezo ignitor
is provided to light the pilot without using matches or lighters.
• Models (V)CD36RE/TE are equipped with an electronic ignition
system that requires 120VAC to operate. An electrode ignitor
automatically lights the pilot flame when the fireplace is turned on.
• All models can accept an optional circulating air blower when
120 VAC connection is supplied. If you plan to install an optional
blower, do not forget to wire the fireplace outlet when framing.
• Each time you turn on your fireplace, you may notice some
amount of condensation on the inside of the fireplace glass. This
is normal and will disappear after 10-20 minutes of operation.
• Your direct-vent gas fireplace system (fireplace and venting) is a
balanced and sealed gas operating unit. It is highly efficient
because it uses outside air for combustion while independantly
heating the indoor air.
• Your fireplace is designed to be used in zero clearance installa tions. Wall or framing material can be placed directly against
any exterior surface on the back, sides, or top of your fireplace,
except where stand-off spacers are integrally attached. If stand-
.
off spacers are attached to your fireplace, these spacers can be
placed directly against wall or framing material. See framing
details on page 5.
• If you plan on installing a television or entertainment center re cessed above your fireplace, it is recommended that you main tain a minimum 18” above the top of louver opening.
• When locating termination cap, it is important to observe the
minimum clearances shown in Figure 10, page 7.
• If recessed into a wall, you can avoid extra framing b position ing your fireplace against an already existing framing member.
• Do not recess termination cap into a wall or siding.
• You may paint the termination cap with 450°F (232°C) heat resistant paint to coordinate with the exterior finish.
• There must not be any obstruction such as bushes, garden sheds,
fences, decks, or utility buildings within 24” from the front of
the termination cap.
• Do not locate termination cap where excessive snow or ice build
up may occur. Be sure to clear vent terminal area after snow
falls to prevent accidental blockage of venting system. When
using snow blowers, do not direct snow towards vent termina tion area.
PRE-INSTALLATION
PREPARATION
LOCATION AND SPACE REQUIREMENTS
Determine the safest and most efficient location for your DESA
direct-vent fireplace. Make sure that rafters and wall studs are not
in the way of the venting system. Coose a location where the heat
output is not affected by drafts, air conditioning ducts, windows or
doors. Figure 2 shows some common locations. Be aware of all
restrictions and precautions before deciding the exact location for
your fireplace and termination cap.
When deciding the location of your fireplace, follow these rules:
• Do not connect this fireplace to a chimney flue servicing
a separate solid-fuel burning fireplace or appliance.
• Do to high temperatures, do not locate this fireplace in high traf-
fic areas, windy or drafty areas, or near furniture or draperies.
• Proper clearances must be maintained.
• If your fireplace is to be installed directly on carpeting, vinyl
tile, or any combustible material other than wood, it must be
installed on a metal or wood panel exttending the full width and
depth of the fireplace. See Figure 3.
www.desatech.com
Flush with a wall
Through exterior wall
enclosed in a chase
Figure 2 - Common Fireplace Locations
Figure 3 - Fireplace Bottom Dimensions
Corner
Installation
116035-01B
PRE-INSTALATION
14 3/4" (375 mm)
36 1/4" (921 mm)
36"
(914 mm)
2x - VERTICAL
DOUBLE STUD
FOR 1" OF CLEARANCE
AT THE SIDES AND BACK
OF THE FIREPLACE
IS ALSO PERMITTED AT
HOWEVER, 0" CLEARANCE
ALL SIDES WHEN FRAMED
THESE DIMENSIONS ALLOW
21" (533 mm)
TO CENTER OF
TOP VENT
14 3/4"
(375 mm)
TO NAILING
FLANGES
56 3/4"
(1441 mm)
12 1/4"
(311 mm)
TO
OPENING
28 5/8"
(727 mm)
6 5/8" ( 168 mm)
TO CENTER
OF REAR VENT
14 3/4"
2 1/2" (63 mm)
MIN. 1" (26 mm)
PREPARATION
Continued
PACKAGING AND REMOVAL
The (V)CD36R/T direct vent gas fireplace heater is packaged with:
- one box containg a 4-log set located on the burner in the firebox.
- one bag containing the owner’s manual with installation
instructions, operator’s guide, and warranty information.
- one bag of glowing ember material.
- one bag of vermiculite hearth treatments.
Remove the shrinkwrap securing the 2 carton trays to the unit.
Lift the top carton tray off and remove the four corner posts.
Discard the bottom tray once the unit is moved into position.
On rear vent models you must remove the fiberboard collar
protector located on the rear collar before installing the
fireplace and venting system. See Figure 4.
CLEARANCES
Minimum clearances to combustibles for the fireplace are as follows:
Back, and sides 0” (0 mm)
Perpendicular walls 12” (305 mm)
Floor 0” (0 mm)
Ceiling to louver opening 40” (1016 mm)
Front 36” (914 mm)
Top 0” (0 mm)
Vent Surfaces 1” (26 mm) (See venting instructions
for specifics on vent clearances.)
Mantel Clearances (See - Mantel Clearances for specific
clearances to combustible mantels.)
Combustible material with a maximum thickness of 5/8” (16 mm)
may be flush with the top and sides of the front face of the fireplace.
FRAMING AND FINISHING
Figure 5 shows typical framing of this fireplace. Figure 6 shows
framing for corner installation. All minimum clearances must be met.
For overall unit dimensions, framing allowances, and vent collar
locations, see Unit Dimensions, Figure 9 on page 6.
For available accessories for this fireplace, see Accessories on page
37. If you are using a seperate combustible mantel piece, refer to
Figures 7 and 8 for proper height and clearances. You can install a
noncombustible mantel at any height above the fireplace opening.
Note: Non-combustible mantels may discolor!
116035-01B
www.desatech.com
Figure 5 - Framing Clearances for Flush, Wall Installation
Figure 6 - Framing Clearances for Corner Installation
7 5/8" (194 mm)
TO CENTER OF
8" TOP VENT
14 3/4"
(375 mm)
TO NAILING
FLANGES
5/8"
(16 mm)
36"
(914 mm)
FACE DIM.
36 1/4"
(921 mm)
FACE DIM.
15 3/8"
(390 mm)
35 3/4"
(908 mm)
2.0 "
(51 mm)
25" (635 mm)
TO CENTER OF
8" REAR VENT
37" (940 mm)
TO NAILING
FLANGE
4 1/2"
(114 mm)
ELECTRICAL
INLET
8" (203 mm)
GAS SUPPLY
INLET
36 3/4"
(934 mm)
36 1/4"
(921 mm)
TO NAILING
FLANGE
2.0"
(51 mm)
2.0"
(51 mm)
38"
(965 mm)
4"
(102 mm)
TO
NAILING
FLANGE
WALL SWITCH
WIREWAY
WALL SWITCH
WIREWAY
2.5 "
(63.5 mm)
UNIT DIMENSIONS
C
B
A
D
E
F
G
Top of Louver Opening
3
2
1
4
5
6
7
Stud Wall
Ref. Mantel Depth Ref. Mantel from Top
of Louver Openin
g
5/8 Flue Pipe
2x Vertical
Header
@ 1” Min.
Clearance
7 2” (38mm) G 2” (51mm)
6 4” (76mm) F 4” (102mm)
5 8” (114mm) E 6” (152mm)
4 10” (152mm) D 8” (203mm)
3 12” (190mm) C 10” (254mm)
2 14” (229mm) B 12” (51mm)
1 16” (267mm) A 14” (51mm)
33°
SAFE
ZONE
1 1/2”
(38 mm)
3 3/4”
(95 mm)
6.0”
(152 mm)
5 1/2”
(140 mm)
12”
(305 mm)
Perpendicular
Side Wall
Combustible
Material May
Be Used
Outer Surround
To Fireplace
Opening
REAR / TOP VENT COMMON
6
CD36R, CD36T, VCD36R and VCD36T
MANTEL CLEARANCES
Figure 8 shows projected mantel depths at various heights above
the top of the louver opening. Figure 7 shows
able distances from various mantel components in relation to the
both sides of the fireplace opening.
WARNING: When finishing appliance, do not overlap
combustible materials onto the black front face. Brick,
tile, or other non-combustible materials may be applied
to the face provided that any fireplace openings are not
blocked and gaps in the material used and the face are
sealed with a non-combustible caulking.
the minimum allow-
Figure 7 - Side Clearances for Combustible Mantels
UNIT DIMENSIONS
Rear / Top Vent Common
Figure 9 - Rear / Top Vent Common Dimensions
Figure 8 - Clearances for Combustible Mantels
www.desatech.com
116035-01B
Fixed
Closed
Openabl
e
Fixed
Closed
Openable
V
V
V
V
V
V
V
V
X
X
V
X
G
G
J
F
B
B
K
N
H
I
A
N
E
L
D
B
M
A
C
B
V
V
A
G
G
B
TERMINATION CAP
AIR SUPP
LY INLET
GAS METE
RRESTRICTED AREA
(TERMIN
ATION PROHIBITED)
A = clearance above grade, veranda, porch, deck, or balcony
[*12 inches (30.5mc) minimum]
B = clearance to window or door that may be opened
[12 inches (30.5cm) minimum]
C = clearance to permanently closed window [minimum 12 inches
(30.5cm) recommended to prevent condensation on window]
D = vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 24 inches (61cm) from the
center-line of the terminal [18 inches (45.7cm) minimum]
E = clearance to unventilated soffit [12 inches (30.5cm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly within
36 inches (91.4cm) horizontally from the center-line of the regulator
I = clearance to service regulator vent outlet [*72 inches (182.9cm)
minimum]
J = clearance to non-mechanical air supply inlet to building or the
combustion air inlet to any other fireplace [*12 inches (30.5cm
)
minimum]
K = clearance to a mechanical air supply inlet [*72 inches (182.9cm)
minimum]
L = clearance above paved side-walk or a paved driveway located on
public property [*84 inches (213.3cm) minimum]
M = clearance under veranda, porch, deck [*12 inches (30.5cm) minimum ]
N = clearance above a roof shall extend a minimum of 24 inches (61cm)
above the highest point when it passes through the roof surface and
any other obstruction within a horizontal distance of 18 inches (45.7cm)
vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
*as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note
: Local codes or regulations may require different clearances
Figure 10 - Minimum Clearances for Termination Cap
116035-01B
www.desatech.com
VENTING INSTALLATION INSTRUCTIONS
8
Installation Planning
VENTING INSTALLATION
INSTRUCTIONS
NOTICE:
fore attempting installation.
These models are tested and approved for use with DESA (directvent) pipe components and terminations.
The venting system must terminate on the outside of the structure and
can not be attached to a chimney or flue system servicing a
solid fuel or gas burning appliance. A direct-vent appliance must have
its own venting system. DO NOT common vent this appliance.
These models are approved to be vented either horizontally through
an outside wall or vertically through a roof or chase enclosure
using the following:
• When venting system terminatates horizontally on an outside wall
you may install a standoff if the termination cap is to be in stalled directly on combustible finish such as vinyl, wood,
stucco, etc.
• Never run the vent downward as this may cause excessive tem peratures which could cause a fire.
• Vent pipe air space clearances to combustibles are 1” on all sides
except on the horizontal sections, which require 2” clearance
from the top of the pipe. Where the termination cap penetrates a
combustible wall, the use of a 2 piece wall firestop is required to
support the termination cap and maintain proper clearances.
• Have fireplace and selected vent components on hand to help
determine the exact measurements when elbowing or offsetting.
Always use wall firestops when penetrating walls and vertical
firestops when penetrating ceilings, floor joists or attic spaces.
• Install hoorizontal venting with a 1/4” rise for every 12” of run
towards the termination.
thoroughly before attempting installation. Failure to
do so could result in serious injury, property damage
loss of life.
Read these instructions completely be-
WARNING:
Read all instructions completely and
or
NOTICE: Failure to follow these instructions will void
the warranty.
INSTALLATION PRECAUTIONS
• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the warranty on your venting
system:
• Installation of any damaged venting component
• Unautorized modification of the venting system (Do not cut
or alter vent components)
• Installation of any component part not manufactured or ap proved by DESA.
• Installation other than as instructed by these instructions
WARNING:
must be vented directly to the outside. The venting
system must NEVER be attached to a chimney serving a separate solid fuel burning apppliance. Each
direct-vent gas appliance must use a separate vent
system Do not use common vent systems.
WARNING:
bustibles are 1” on all sides except on horizontal
sections, which require 2” clearance from the top of
the pipe. Where the termination cap penetrates a combustible wall 1”, air space clearance in required.
This gas fireplace and vent assembly
Vent pipe air space clearance to com-
IMPORTANT:
for servicing.
Do not seal vent cap to pipe. Cap must be removable
www.desatech.com
116035-01B
VENTING INSTALLATION
Female
Locking Lugs
Male
Slots
(Framing
Detail)
10
3
/4"
(273mm)
103/4" Inside Framing
(273mm)
10
3
/4"
(273mm)
8
1
/2"
(216mm)
Vent Opening
Combustible
Wall
Vent Opening
Noncombustible
Wall
Center
of
Hole
INSTRUCTIONS
Continued
INSTALLATION PLANNING
There are two basic types of direct-vent installations:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
VENTING INSTALLATION INSTRUCTIONS
Installation Planning (Cont.)
9
IMPORTANT:
portion of wall firestop. Horizontal installation using round termination require exterior portion of wall firestop (see Figure 18, page 11).
1. Set the fireplace in its desired location and determine the route
your horizontal venting will take. Do not secure the fireplace
until all venting has been installed. Some installations require
sliding the fireplace in and out of position to make final venting
connections. Figures 19 through 25 on pages11 through 13 showdifferent configurations for venting with horizontal termina tion that will help you decide which application best suits your
installation. Check to see if wall studs or roof rafters are in the
path of your desired venting route. If they are, you may want
to adjust the location of the fireplace.
2. Direct vent pipe sections and components are designed with
special twist-lock connections.
Twist-Lock Procedure: The female ends of the pipes havelocking lugs (indentations). These lugs will slide straight into
matching slots on the male ends of adjacent pipes. Push pipe
sections together and twist one section clockwise approximately
one-quarter turn until the sections are fully locked (see Figure
11).
feet. Use wall strap for this purpose.
3. Any straight pipe section, a 45°, or a 90° elbow can be used
when first connecting the venting system to the fireplace. Elbows
are designed to twist lock into any of four 90° positions to direct
the venting system to the desired location.
IMPORTANT:
elbows by cutting, twisting, bending, etc.
4. Assemble the desired combination of pipe and elbows to the
fireplace flue collar. If there are long portions of venting run,
pipe sections may be pre-assembled and installed for convenience.
5. Carefully determine the location where the vent pipe assembly
will penetrate the outside wall. The center of the hole should line
up with the center-line of the horizontal vent pipe. Mark the wall
for a 10 ¾” x10 ¾” square hole. Cut and frame the square hole
in the exterior wall where the vent will be terminated. If the wall
being penetrated is constructed of noncombustible material, such
as masonry block of concrete , a 8 ½” hole with zero clearance is
acceptable (see Figure 12).
any wall. This will cause a fire hazard.
Horizontal square terminations require only inner
Note:
Horizontal runs of vent must be supported every three
WARNING:
Do not attempt to alter the configuration of the
Do not recess vent termination into
Figure 11 - Vent Pipe Connection
Figure 12 - Vent Opening Requirements
WARNING:
Never run vent downward as this may
cause excessive temperatures which could cause a
fire. Operation of improperly installed and maintained venting system could result in serious injury,
property damage or loss of life.
116035-01B
www.desatech.com
VENTING INSTALLATION INSTRUCTIONS
VENT
CAP
INNER WALL
FIRESTOP
VINYL
SIDING
STANDOFF
HOT
APPLY
MASTIC
TO ALL SIDES
SCREWS
INNER WALL
FIRESTOP
VENT
CAP
OUTER WALL
FIRESTOP
HOT
INNER WALL
FIRESTOP
PIPE SECTION
VENT
CAP
SCREWS
VENT
CAP
HOT
10
Installation Planning (Cont.)
VENTING INSTALLATION
INSTRUCTIONS
Continued
6.
Noncombustible Exterior Wall: Position the horizontal vent
cap in the center of the 8 ½” round hole and attach to the exte rior wall with four wood screws provided. Before attaching
the vent cap to exterior wall, run a bead of non-hardening mastic
(pliable sealant) around the outside edges to make a seal be tween it and the outside wall.
provided should be replaced with appropriate fasteners for
stucco, brick, concrete, or other types of sidings. (See Figure 13).
Combustible Exterior Wall: For vinyl siding, stucco or wood
exteriors, a siding standoff may be installed between the vent
cap and exterior wall. The siding standoff prevents excessive
heat from damaging the siding materials. Siding material must
be cut to accommodate standoff. Bolt the vent cap to the stand off. Apply non-hardening mastic around outside edge of stand off. Position the standoff/cap assembly in the center of the
10 ¾ square hole and attach to exterior wall with wood
screws provided (see Figure 14). The siding standoff must sit
flush against the exterior fascia material.
7.
Combustible Exterior Wall Only: Fit the outer and inner wall
firestop
into the wall before connecting horizontal run to vent
cap (see Figure 15).
8. Carefully move fireplace, with vent assembly attached, toward
wall and insert vent pipe into horizontal termination. The pipe
overlap should be a minimum of 1 ¼”.
9. Combustible Exterior Wall Only: Slide wall firestop againstinterior wall surface and attach with screws provided (see Figure
16). See Figure 17 for horizontal termination details.
10. Place fireplace into position and shim with noncombustible ma terial, if needed. Nail or screw flanges to framing to secure
unit in place.
IMPORTANT:
securing. If fireplace is not level, it will not work properly.
Note:
The four wood screws
Make sure fireplace is level before
Figure 14 - Installing Siding Standoff
Figure 13 - Installing Horizontal Vent Cap (Noncombustible)
www.desatech.com
Figure 15 - Installing Outer Wall Firestop
Figure 16 - Installing Inner Wall Firestop
116035-01B
VENTING INSTALLATION
Siding Standoff
Screws
High
Wind
Termination
Apply Mastic to
Outside Edge of
Standoff
Exterior Wall
with
Vinyl Siding
10
3
/4" x 10 3/4"
Framed
Opening
Maintain
1"
Minimum Air
Space
Around
Outer
Pipe When
Penetrating
a Wall
Minimum
Pipe
Overlap
1
1
/4"
Wall
Firestop
Direct
Vent
Pipe
Vertical (V) Horizontal (H)
25
1
/2 " 22" max.
Square Termination
TOH
Horizontal
Square
Termination
Wall
Firestop
Straight / Adjustable
Pipe 18" Max.
Horizontal
Square
Termination
Wall
Firestop
Straight / Adjustable
Pipe 18" Max.
Corner Installation
Vertical (V)Horizontal (H)
25 ½”
24”
45°
Elbow
90° Elbow
Wall
Firesto
p
Horizontal
Round
Termination
Exterior Portion of Wall
Firestop
(Round
Termination Only)
INSTRUCTIONS
Continued
Horizontal Termination Configuration
Figures 19 through 25 show different configurations and alternatives for venting with horizontal terminations. Each figure includes
a chart with critical minimum and maximum dimensions which
MUST be met.
venting must have a 1/4” rise for every 12” of run toward the termination.
Recommended Applications for Top Vent Model (V)CD36T:
• Installation using cabinet surrounds
• Through the wall using round or square termination
(up to a maximum of 24” of horizontal pipe)
• Corner installation
(Using one 90° elbow and a maximum of 24” of horizontal pipe).
Required Vertical (V) Allowable
Vertical (V) Vertical Pipe Horizontal (H)
45 ½” None 26” Max.
57 ¼” Min. 1 ft. 30” Max.
69 ¼” Min. 2 ft. 74” Max.
81 ½” Min. 3 ft. 98” Max.
94” Min. 4 ft. 122” Max.
106” Min. 5 ft. 146” Max.
159” Min. 9 ft. 20’ Max.
Figure 21 - Horizontal Termination Configuration for Corner
Installation using One 90° Elbow (Model (V)CD36T)
SNORKEL TERMINATION INSTALLATION
Recommended Applications Models (V)CD36R and (V)CD36T:
• Installations requiring vertical rise on building exterior. • Installation using snorkel termination to achieve 1 ft. above grade.
Snorkel terminati
you must provide proper drainage to prevent water from entering snorkel (see Figure 23). Do not back fill around snorkel termination.
Figure 23 - Snorkel Termination Configurations for Below Ground Installation
Figure 22 - Horizontal Termination Configuration with
Vertical Rise and One 90° Elbow (Model (V)CD36T)
www.desatech.com
116035-01B
90° Elbow
Venting with Two 90° Elbows
Vertical (V)
Horizontal (H
2
)
Horizontal (H
1
) +
8' min.
9' max.
9' min.
11' max.
10' min.
13' max.
12' min.
17' max.
14' min.
20' max.
HORIZONTAL SYSTEM INSTALLATION USING TWO 90°
90° Elbow
Venting with Three 90° Elbows
Vertical (V)
Horizontal (H
2
)
Horizontal (H
1
) +
5' min.
6' max.
6' min.
8' max.
7' min.
10' max.
8' min.
12' max.
12' min.
20' max.
Horizontal (H
1
)
2' max.
3' max.
4' max.
5' max.
8' max.
20' max.20' max.
8' max.
TOH
ELBOWS
The following configurations show the minimum vertical rise
requirements for a horizontal system using two 90° elbows.
VENTING INSTALLATION INSTRUCTIONS
Installation Planning (Cont.)
13
Figure 24 - Horizontal Termination Configuration for Venting using Two 90° Elbows (Model (V)CD36T)
Figure 25 - Horizontal Termination Configuration for Venting using Three 90° Elbows (Model (V)CD36T)
116035-01B
www.desatech.com
45° Elbow
Wall Strap
Roof
Flashing
Ceiling
Firestop
VENTING INSTALLATION INSTRUCTIONS
14
Installation for Vertical Terminations
VENTING INSTALLATION
INSTRUCTIONS
Continued
Note:
Vertical restrictor must be installed in all vertical installations.
1. Determine the route your vertical venting will take. If ceiling
Joists, roof rafters, or other framing will obstruct the venting
system, consider an offset (see Figure 26) to avoid cutting loadbearing members.
lation instructions for required clearances (air space) to com bustibles when passing through ceilings, walls roofs, enclo sures, attic rafters, etc. Do not pack air spaces with insulation.
Also note maximum horizontal offset limitations.
2. Set fireplace in desired location. Drop a plumb line down
from the ceiling to the position of the fireplace exit flue. Mark
the center point where the vent will penetrate the ceiling. Drill
a small locating hole at this point.
Drop a plumb line from the inside of the roof to the locating
hole in the ceiling. Mark the center point where the vent will
penetrate the roof. Drill a small locating hole at this point.
NOTE:
Pay special attention to these instal-
2. Assemble the desired lengths of pipe and elbows necessary to
reach from the fireplace flue up through the firestop. Be sure
all pipe and elbow connections are fully twist-locked (see Fig-ure 11, page 9).
3. Cut a hole in the roof using the locating hole as a center point.
(Cover any exposed open vent pipes before cutting hole in roof.)
The 10 ¾” x 10 ¾” hole must be measured on the horizontal;
actual length may be larger dependiong on the pitch of the roof.
There must be a 1” clearance from the vent pipe to combustible
materials. Frame the opening as shown in Figure 12, page 9.
4. Connect a section of pipe and extend up through the hole.
Note:
If an offset is needed to avoid obstructions, you must
support the vent pipe every 3 feet. Use wall straps for this
purpose (see Figure 26). Whenever possible, use 45º elbows
instead of 90º elbows. The 45º elbow offers less restriction to
the flow of the flue gases and intake air.
5. Place the flashing over the pipe section(s) extending through
the roof. Secure the base of the flashing to the roof and fram ing with roofing nails. Be sure roofing material overlaps the
top edge of the flashing as shown in Figure 26. There must be
a 1” clearnace from the vent pipe to combustible materials
6. Continue to add pipe section until the height of the vent cap
meets the minimum building code requirements described in
Figure 10 on page 7.
steep roof pitches. Nearby trees, adjoining rooflines, steep
pitched roofs, and other similar factors may cause poor draft
or down-drafting in high winds. Increasing the vent height may
solve this problem.
7. Twist-lock the vent cap onto the kast section of vent pipe.
Note:
If the vent pipe passes through any occupied areas above the
first floor, including storage spaces and closets, you must enclose
pipe. You may frame and sheetrock the enclosure with standard
construction material. Make sure and meet the minimum allowable
clearances to combustibles. Do not fill any of the required air spaces
with insulation.
Note:
You must increase vent height for
Figure 26 - Offset with Wall Strap and 45° Elbows
Flat Ceiling Installation
1. Cut a 10 ¾” square hole in the ceiling using the locating hole as
a center point. The opening should be framed to 10 ¾” x 10 ¾”
(273 mm x 273 mm) inside dimensions, as shown in Figure 12on page 9 using framing lumber the same size as the ceiling
joists. If the area above the ceiling is an insulated ceiling or a
room, nail firestop from the top side. This prevents loose insula tion from falling into the required clearance space. Otherwise,
install firestop below the framed hole. The firestop should be
installed with no less than three nails per side (see Figure 27).
www.desatech.com
If area above is a room, install If the area above is not a room, install
firestop above framed hole. firestop below framed hole.
Figure 27 - Installing Firestop
116035-01B
VENTING INSTALLATION
Venting with Three 90° Elbows
Vertical (V)
Horizontal (H
2
)
Horizontal (H
1
) +
8' min.5' max.
10' min.
8' max.
12' min.
11' max.
14' min.
14' max.
16' min.
17' max.
90° Elbow
Note:
Install
restrictor ring
into inner pipe
section prior to
attaching vent
termination cap.
18' min.
20' max.
40' max.
20' max.
90° Elbow
Note:
Install
restrictor ring
into inner pipe
section prior to
attaching vent
termination cap.