MODELS S42, S42H, S42R, S42RH, VS42(1) AND VS42H(1)
SAVE THIS BOOK
This book is valuable. In addition to instructing you
on how to install and maintain your appliance, it also
contains information that will enable you to obtain replacement parts or accessory items when needed. Keep
it with your other important papers.
This fireplace is approved for use as a wood burning
fireplace or for use with a vented gas log approved to
ANS Z21.60, Z21.84 or RGA 2-72 standards or for use
with a vent-free gas log heater approved to ANS Z21.11.2
standard. A DESA hood must be installed when using a
vent-free log heater (see Accessories, page 16).
This wood burning fireplace complies with UL127CAN/ULS-S610-M87 standard as a FACTORY BUILT
APPLIANCE.
FOR CANADA: The authority having jurisdiction (such
as the municipal building department, fire department,
etc.) should be contacted before installation to determine the need to obtain a permit.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury, property
damage or loss of life. Refer to this manual for assis
tance or additional information. Consult a qualified
installer or local distributor.
TABLE OF CONTENTS
Safety Information ............................................... 2
IMPORTANT: Check local codes
before installing this fireplace.
Before beginning the installation of the fireplace,
read these instructions through completely.
• This DESA fireplace and its components are
safe when installed according to this installation
manual. Unless you use DESA components,
which have been designed and tested for the
fireplace system, you may cause a fire hazard.
• The DESA warranty will be voided by and
DESA disclaims any responsibility for the
following actions.
a. Modification of the fireplace, components,
doors, air inlet system and damper control.
b. Use of any component part not manufac
tured or approved by DESA in combination
with a DESA fireplace system.
Proper installation is the most important step in
ensuring safe and continuous operation of the
fireplace. Consult the local building codes as to
the particular requirements concerned with the
installation of all factory built fireplaces.
WARNING: Do not install a
fireplace insert in this box unless
the manufacturer's instructions
with the insert specifically state
this fireplace has been tested for
use with this insert.
FOR YOUR SAFETY
• Do not store or use gasoline
or any other flammable vapors
or liquids in the vicinity of this
or any other appliance.
• Due to high temperatures, the
appliance should be located
out of traffic and away from
furniture and draperies.
• Do not place clothing or other
flammable materials on or near
the appliance.
• Never leave children unat
tended when a fire is burning
in the fireplace.
-
WARNING: Use solid wood
or processed solid fuel firelogs
only. When processed wood fuel
fire logs are used, do not poke or
stir the logs while they are burning. Use only fire logs that have
been evaluated for the application
in fireplace and refer to fire log
warnings and caution markings
on packaging prior to use.
This fireplace is not intended to be
used as a substitute for a furnace
to heat an entire home. Use for
supplemental heat only.
-
2
www.desatech.com
111099-01C
SPECIFICATIONS
0" TO
BOTTOM
(LEFT SIDE ONLY)
OUTSIDE AIR
TOP
SPACERS
BACK AND SIDES
3/4" AIR SPACE
HEARTH EXTENSION
66" X 20"
TO
PERPENDICULAR
12"
EACH SIDE
NOT LESS
THAN 12"
1" AIRSPACE
TO
COMBUSTIBLE
COMBUSTIBLE
WALL BOARD
0" TO
MATERIAL
NO COMBUSTIBLE
MATERIAL ON FACE
SIDEWALL
TERMINATION
SQUARE CHASE-TOP
GAS LINE
KNOCK OUT
AIR KIT
KNOCK OUTS
ROUND TOP TERMINATION
GAS LINE
KNOCK OUTS
ELECTRICAL
OUTLET
LEFT SIDE
RIGHT SIDE
8.125"
12.625"
14.25"
45.25"
41"
48"
42"
24"
8"
39"
16.25"
29.5"
2.5"
10.625"
1"
12"
2.5"
8.125"
6.75"
10.625"
12.25"
48"
0.625"
36"
22.5"
111099-01C3
www.desatech.com
23.50”
43.375”
48.25”
59.264"
19.466"
27.527"
83.830"
MAINTAIN 3/4"
CLEARANCE AT
SIDES AND BACK
OF FIREPLACE
3
/4" CLEARANCE
NOT REQUIRED AT
NAILING FLANGES
FIREPLACE INSTALLATION
SELECTING LOCATION
To determine the safest and most efficient location
for the fireplace, you must take into consideration
the following guidelines:
1. The location must allow for proper clearances
(see Figures 1 and 2).
2. Consider a location where the fireplace will
not be affected by drafts, air conditioning
ducts, windows or doors.
3. A location that avoids the cutting of joists or
roof rafters will make installation easier.
4. An outside air kit is available with this fireplace
(see Optional Outside Air Kit on page 6).
MINIMUM CLEARANCE TO
COMBUSTIBLES
Back and sides of fireplace 3/4" minimum*
Floor** 0" minimum
Perpendicular wall to opening 12" minimum
Top spacers 0" minimum
Mantel clearances
Chimney outer pipe surface 1" minimum
* Not required at nailing flanges
** See step 2 of Framing
WARNING: Do not pack required air spaces with insulation
or other materials.
Minimum/Maximum Chimney Height for
Residential Installation
The minimum height of the chimney, measured
from the base of the fireplace to the flue gas outlet
of the termination, is 14.5 feet for straight flue or
a flue with one elbow set. The maximum distance
between elbows is 6 feet. For systems with two
elbow sets, the minimum height is 22 feet. The
maximum height of any system is 50 feet. This
measurement includes the fireplace, chimney sec
tions and the height of the termination assembly
at the level of the flue gas outlet (see Figure 18,
page 11).
Minimum/Maximum Chimney Height for
Outdoor Installation
The minimum height of the chimney, measured
from the base of the fireplace to the flue gas outlet
of the termination, is 8 feet (minimum of 4 feet
of chimney pipe sections required for outdoor
installation).
see Mantels, page 5
FRAMING
1. Frame the opening for the fireplace using the
dimensions shown in Figures 1 and 2.
2. If the fireplace is to be installed directly on
carpeting, tile (other than ceramic) or any
combustible material other than wood floor
ing, the fireplace must be installed upon a
metal or wood panel extending the full width
and depth of the fireplace.
3. Set the fireplace directly in front of this open
ing and slide the unit back until the nailing
flanges touch the side framing.
4. Check the level of the fireplace and shim with
sheet metal if necessary.
5. Before securing fireplace to prepared fram
ing, the ember protector (provided) must
be placed between the hearth extension (not
supplied) and under the bottom front edge
of the fireplace to protect against glowing
embers falling through. If the fireplace is to be
installed on a raised platform, a Z-type ember
protector (not supplied) must be fabricated to
fit your required platform height. The ember
protector should extend under the fireplace a
minimum of 1 1/2". The ember protector should
be made of galvanized sheet metal (28 gauge
minimum) to prevent corrosion.
6. Using screws or nails, secure the fireplace to
the framing through flanges located on the
sides of the fireplace.
-
Figure 1 - Framing Dimensions
Figure 2 - Corner Installation
-
-
-
4
www.desatech.com
111099-01C
FIREPLACE INSTALLATION
FIREBOX
SAFE ZONE
Continued
Note: For outdoor installations, the fireplace enclosure must allow for adequate drainage and fresh
air ventilation. It is recommended that a sealed,
corrosion resistant catch pan with provision for
drainage be installed under the fireplace within
the fireplace enclosure.
HEARTH EXTENSION
A hearth extension projecting a minimum of 16"
in front of and a minimum of 8" beyond each
side of the fireplace opening is required to protect
combustible floor construction in front of the fire
place. Fabricate a hearth extension using a material
MANTELS
A mantel may be installed if desired (see Figure
4). Woodwork such as wood trims, mantels or
any other combustible material projecting from
the front face must not be placed within 12" of
the fireplace opening. Combustible materials
above 12" and projecting more than 1
the fireplace must not be placed less than 15"
from the top opening of the fireplace (NFPA STD
211, Sec. 7-3.3.3).
Mantels or any other combustible material also
may come up to the side edge of the black metal
face of the fireplace just as long as the projection
from the front face fall within the limit shown in
-
Figure 4.
1
/
" from
2
which meets the following specifications: a layer
of noncombustible, inorganic material having a
thermal conductivity of K=0.84 BTU IN/FT, HR.
F (or less) at 1" thick. For example, if the material
selected has a K factor of 0.25, such as glass fiber,
the following formula would apply:
0.25 x 1.0" = 0.30" thickness required
0.84
Thermal conductivity "K" of materials can be
obtained from the manufacturer or supplier of the
noncombustible material. If the hearth extension
is to be covered, use noncombustible material such
as tile, slate, brick, concrete, metal, glass, marble,
6"
Ref.
15" Min.
1
12
/
" Ref.
4
33°
3" Nom.
1
1
/
" Max.
2
Combustible
Material
Safe
Zone for
Projection of
Combustible
Materials
stone, etc. Provide a means to prevent the hearth
extension from shifting and seal gap between the
fireplace frame and hearth extension with a non
combustible material (see Figure 3).
WARNING: Hearth extension
is to be installed only as shown
-
12" Min.
Fireplace
Opening
Upper
Section of
Fireplace
in Figure 3.
Fireplace Front
Seal Gap
Ember Protector
Fireplace Front
Raised Hearth
Ember Protector
Hearth
Extension
Fireplace Front
Elevated
Seal Gap
Ember Protector
Figure 3 - Hearth Extension
111099-01C5
www.desatech.com
Top View of Fireplace
8.0"
33°
Min. to
Perpendicular
Side Wall
12"
Figure 4 - Mantel Clearances to
Combustible Material
2" Max.
3.0"
Combustible
Material Must
Not Overlap
Front Face
VENTING INSTALLATION
OPTIONAL OUTSIDE AIR KIT
(MODEL AK4/AK4F)
The installation of an outside air kit should be performed during the rough framing of the fireplace
due to the nature of it's location. Outside combus
tion air is accessed through a vented crawl space
(AK4F) or through a sidewall (AK4).
CAUTION: Combustion air
inlet ducts shall not terminate
in attic space.
Secure to Collars with Metal Tape,
Screws or Straps (Min. of 1/4" x 20"
in size)
Air Inlet
Location
Must Allow
For Bushes
or Snow
Air Inlet
Eyebrow
Vented Crawl Space
(Check Local Codes
Before Installing in a
Vented Crawl Space)
Figure 5 - Outside Air Kit
CHIMNEY PIPE
The DESA chimney system consists of 12", 18",
24", 36" and 48" snap-lock, double-wall pipe
segments, planned for maximum adaptability
to individual site requirements. Actual lengths
gained after fitting overlaps must be taken into
consideration (lineal gain) and are given in the
lineal gain chart (see Figure 6). Lineal gain is the
actual measurable length of a part after two or more
parts are connected. For Canada, use chimney parts
designated "HT".
WARNING: The opening in the
collar around the chimney at the
top of the fireplace must not be
obstructed. Never use blown insulation to fill the chimney enclosure.
Vent Hood
Required for
Wall Installation
LINEAL GAIN
PART NO.
42"Fireplace44
12-8DM
12-8HT
18-8DM
-
18-8HT
24-8DM
24-8HT
36-8DM
36-8HT
48-8DM
48-8HT
RT-8DM Round Termination6 7/8"
RTL-8DM Round Termination
RTT-8DM
RTTL-8DM
ET-8DM Square Chase-Top12
ETO-8DM
ETL-8DM
ETLO-8DM
* The lineal gain for the terminations is measured to the flue gas outlet height.
12" Galvanized
Outer Pipe
3
/
12
8
Stainless
Inner Pipe
DESCRIPTIONGAIN
Pipe Section10 5/8"
Pipe Section16 5/8"
Pipe Section23 5/8"
Pipe Section34 5/8"
Pipe Section46 5/8"
Round Termination
with Slip Section
Round Termination
with Slip Section
Square Chase-Top
with Mesh
Square Chase-Top
with Slip Section
Square Chase-Top
with Mesh & Slip
Section
"
Figure 6 - Lineal Gain
7" to 15"*
Hemmed
End
ASSEMBLY AND INSTALLATION OF
DOUBLE WALL CHIMNEY SYSTEM
Each double wall chimney section consists of a
galvanized outer pipe, a stainless steel inner flue
pipe and a wire spacer. The pipe sections must be assembled independently as the chimney is installed.
When connecting chimney directly to the fireplace,
the inner flue pipe section must be installed first
with the lanced side up. The outer pipe section can
then be installed over the flue pipe section with the
hemmed end up. Press down on each pipe section
until the lances securely engage the hem on the fire
place starter. The wire will assure the proper spacing
between the inner and outer pipe sections.
"
*
*
7 3/4"
6 7/8" to
23 1/8"*
8 1/2" to
21 1/2"*
*
"
*
12
"
12" to
25 1/2"
*
-
6
www.desatech.com
111099-01C
VENTING INSTALLATION
Continued
Continue to assemble chimney sections as outlined,
making sure that both the inner and outer pipe sec
tions are locked together. When installing double
wall snap-lock chimney together, it is important
to assure the joint between the chimney sections
is locked. Check by pulling chimney upward after
locking. The chimney will not come apart if properly locked. It is not necessary to add screws to
keep the chimney together (exception - see Figure
9, page 8).
USING ELBOW OFFSETS (30E-8DM)
1. To achieve desired offset, you may install
combinations of 12", 18", 24", 36" and 48"
length of double wall pipe (see offset chart
and Figure 7).
2.
Chimney weight above offset rests on return
elbow. Straps must be securely nailed to rafters
or joists (see Figure 8, details a & b on page 8).
3. Maximum length of pipe between supports
(return elbow or 12S-8DM) is 6' of angle run.
Maximum of two 6' angle run sections per
chimney system (see Figure 7).
4. All pipe connections between the offset and
return must be secured with two screws on the
outer pipe only (see Figure 9, page 8). Do not
penetrate the inner stainless.
Firestop spacers are required at each point where
the chimney penetrates a floor space. Their purpose
is to establish and maintain the required clearance
between the chimney and the combustible materials.
When the pipe passes through a framed opening into
a living space above, the firestop must be placed onto
the ceiling from below as shown in Figure 10.
They also provide complete separation from one floor
space to another or attic space as required by most
codes. When the double wall pipe passes through a
framed opening into an attic space, the firestop must
be placed into an attic floor as shown in Figure 11.
Straps
Detail B
Straps
12S-8DM
A
Figure 9 - Elbow Offset
See Detail B
B
Existing
Ceiling
Frame
Firestop
Spacer
Screws or
Staples
(Min. of 8)
Figure 10 - Firestop Spacer with Living
Firestop
Spacer
Figure 11 - Firestop Spacer with Attic
Space Above Ceiling
Screws or Staples
(Min. of 8)
Existing
Ceiling
Frame
Space Above Ceiling
PENETRATING THE ROOF
To maintain a 1" clearance to the pipe on a roof
with a pitch, a rectangular opening must be cut.
1. Determine the center point through which the
pipe will penetrate the roof.
2. Determine the center point of the roof. Pitch
is the distance the roof drops over a given
span, usually 12". A 6/12 pitch means that
the roof drops 6" for each 12" one measure
horizontally down from the roof rafters.
3. Use the roof opening chart (Figure 12, page
9) to determine the correct opening length and
flashing required.
4. Remove the shingles around the opening
measured. Cut out this section.
5. Add the next sections of the pipe until the
end penetrates the roof line. Check to see that
the proper clearances are maintained. Extend
chimney by adding sections of double wall
pipe until pipe is minimum of 30" above the
highest point of the roof cutout. Termination
and chimney must extend a minimum of
36" above the highest point where it passes
through the roof.
8
www.desatech.com
111099-01C
VENTING INSTALLATION
14 3/8" Min.
(365 mm)
30" Min.
(762 mm)
1" Min.
(25 mm)
1" Min.
(25 mm)
1" Min.
(25 mm)
Opening "A"
Continued
Storm Collar Installation (SC1 or SC2)
Place storm collar over pipe and slide down until
it is snug against the open edge of the flashing (see
Figure 14). Use SC1 for all round terminations and
SC2 for all terminations with slip sections. Apply
waterproof caulk around the perimeter of the collar
to provide a proper seal.
Chimney
Pipe
Waterproof
Caulk
Storm
Collar
Flashing
PitchSlope Opening "A"
Flat0°15"V6F-8DM
0-6/1226.6°16 1/8"V6F-8DM
6/12-
45.0°20 3/8"V12F-8DM
12/12
Max.
Figure 12 - Roof Opening Measurements
FLASHING INSTALLATION (V6F-8DM
OR V12F-8DM)
Determine the flashing to be used with the roof
opening chart. Slide flashing over pipe until base
is flat against roof. Replace as many shingles as
needed to cover exposed area and flashing base.
Used Flashing
Model No.
Figure 14 - Storm Collar
Terminations/Spark Arrestor
The fireplace system must be terminated with the
listed round top or chase terminations. In any case,
refer to the installation instructions supplied with
the termination. The termination approved for this
fireplace are the RT-8DM and RTL-8DM that can
be used for flashing or chase and ET-8DM, ETO8DM, ETL-8DM and ETLO-8DM for chase style
termination only. Figure 15 shows an RTL-8DM
round top termination.
Secure in position by nailing through shingles
(see Figure 13). DO NOT NAIL THROUGH
FLASHING CONE.
Installing Flashing on a Metal Roof
When installing the flashing on a metal roof, it is
required that putty tape be used between the flashing
and the roof. The flashing must be secured to the roof
using #8 x 3/4" screws and then sealed with roof coat
ing to prevent leakage through the screw holes. A roof
coating must also be applied around the perimeter of
the flashing to provide a proper seal.
Storm Collar
Flashing
Cone
Overlap
Shingles Top
and Sides Only
Nail Only
-
CAUTION: Do not seal openings on the rooftop flashing. Fol
low the installation instructions
provided with the termination
being used.
Attach Bracket
Tabs to
Outer Pipe
(3 Places)
Secure with
Screws
Overlap
Shingles Top
and Sides
Outer
Perimeter
of Flashing
Underlap Shingles
at Bottom
Figure 13 - Flashing Installation
111099-01C9
Figure 15 - Termination
www.desatech.com
-
RTL-8D
Level of
Flue Gas
Outlet
Caulk
Collar
Flashing
Underlap
Shingles
Bottom Only
VENTING INSTALLATION
Continued
Terminations with 16" slip pipe sections are available. The RTT-8DM and RTTL-8DM are approved
for flashing installations. When needed, these
adjustable terminations may be used in combination with the pipe assembly to achieve the correct
chimney height.
Note: In the rare instance there is a problem with
the side driven rain or wind or the chimney is
not drafting properly, an ADS-8DM (Anti-Draft
Shield) can be used with round terminations.
CHASE INSTALLATIONS
Instructions for chase installations are included
with the chase style termination chosen. In a
multiple chase installation, be sure to provide
adequate distance between terminations to prevent
smoke spillage from one termination to another.
We suggest that terminations be separated at least
24", center to center and stacked at a vertical height
difference of 18" (see Figure 16).
Note: If a decorative shroud is to be installed,
contact the manufacturer for specifications.
18"
Min.
Typ.
10 FOOT RULE
All flue gas outlet chimney terminations must
extend a minimum of 3 feet in height above the
highest point where it passes through the roof and
must be at least 2 feet above the highest point of
the roof that is within a horizontal distance of 10
feet (see Figure 17).
3' Min.
Level of
Flue Gas
Outlet
10'
2' Min.
3' Min.
10'
2' Min.
Figure 17 - 10 Foot Rule
FINISHING THE FIREPLACE
Combustible materials, such as wallboard, gypsum
board, sheet rock, drywall, plywood, etc. may make
direct contact with sides and top around the fireplace
face. It is important that combustible materials do
not overlap the face itself. Brick, glass, tile or other
noncombustible materials may overlap the front
face provided they do not obstruct essential open
ings like louvered slots or any other opening. When
overlapping with a noncombustible facing material,
use only noncombustible mortar or adhesive.
-
24" Min.
24" Min.
Figure 16 - Multiple Chase Installation
10
www.desatech.com
111099-01C
VENTING INSTALLATION
EFFECTIVE HEIGHT OF
TERMINATION CA
P
30E-8DM
EFFECTIVE HEIGHT OF
TERMINATION CAP
EFFECTIVE HEIGHT OF
TERMINATION CAP
MINIMUM
HEIGHT
14.5 FT.
MINIMUM
UP TO 6FT.
HEIGHT
MAXIMUM
14.5 FT.
(WITH TWO ELBOW SETS
)
MINIMUM HEIGHT OF 22 FT
.
EFFECTIVE HEIGHT OF
MAXIMUM HEIGHT OF 50 FT
.
MAXIMUM
UP
TO 6 FT.
(ANY SYSTEM)
50 FT
.
HEIGH
T
MAXIMUM
30E-8DM
TERMINATION CAP
Continued
Figure 18 - Typical Residential Installations
OPTIONAL GAS LINE
INSTALLATION
Gas line hook up should be done by your supplier
or a qualified service person.
4. Repack insulation around gas line and into
sleeve opening. Seal any gaps between gas line
and refractory knockout hole with refractory cement or commercial furnace cement, Install the
gas appliance or cap-off gas line if desired.
Note: Before you proceed, make sure your gas
supply is turned off.
Use only a 1/2" black iron pipe and appropriate
fittings.
1. Remove knockout indentation on refractory or
firebrick wall located above the refractory hearth
floor. The knockout indentation must be firmly
tapped with any solid object such as a 1/2" dowel
until it is released. Remove fragmented portions
of refractory (see Figure 19).
2. Remove gas line cover plate located on either
side of fireplace and pull out insulation from
gas line conduit sleeve. Save insulation for
reuse. Replace screws.
3. Run a 1/2" black iron gas line into the fireplace
through the rear at gas line conduit sleeve (if
Outside of
Fireplace
Gas Line
Conduit
Insulation
Gas
Conduit
Cover
Figure 19 - Gas Line Knockout
using a raised platform, add height). Provide
sufficient gas line into fireplace chamber for
fitting connection (see Figure 20, page 12).
Note : Secure incoming gas line to wood
framing to provide rigidity for threaded end.
111099-01C11
www.desatech.com
Side
Firebrick
Finished
Side
1/2" Dowel
Refractory
Knockout
Plug
OPTIONAL GAS LINE
INSTALLATION
Continued
CAUTION: All gas piping
and connections must be tested
for leaks after the installation
is completed. After ensuring
that the gas valve is on, apply
soap and water solution to all
connections and joints. Bubbles
forming show a leak. Correct
all leaks at once. DO NOT USE
AN OPEN FLAME FOR LEAK
TESTING AND DO NOT OPERATE ANY APPLIANCE IF A LEAK
IS DETECTED. LEAK TESTING
SHOULD BE DONE BY A QUALIFIED SERVICE PERSON.
Note : A DESA hood must be installed when
using an unvented gas log set (see Accessories
on page 16).
WARNING: Do not operate an unvented gas log set in
this fireplace with the chimney
removed.
If you install a decorative gas appliance (vented
gas log), the decorative gas appliance must comply
with the Standard for Decorative Gas Appliance
for Installation in Solid Fuel Burning Fireplaces,
ANS Z21.60, Z21.84 or RG 2-72 and shall also be installed in accordance with the National Fuel Gas
Code, ANSI 7223NFPA 54 latest edition
Outside of
Fireplace
Gas
Line
Conduit
Incoming
1/2" Black
Iron Pipe
.
Side
Firebrick
Finished
Side
WARNING: To avoid the risk of
damaging the fireplace materials
and increasing the risk of spreading a fire, do not use the fireplace
to cook or warm food.
WARNING: If the fireplace
has been used for wood burning,
the firebox and chimney must be
cleaned of soot, creosote and
ashes be a qualified chimney
cleaner. Creosote will ignite if
heavily heated.
WARNING: When using a
decorative vented gas log, the
damper must be removed or per
manently locked in the fully open
position and the glass doors must
be in the fully open position.
OPERATION AND
MAINTENANCE
GUIDELINES
GLASS DOORS
Glass doors are optional with the fireplace. When
the fireplace is in operation, doors must be fully
opened or fully closed position only or a fire hazard
may be created (see Figure 21).
Doors Fully Closed
Fireplace Front
-
Seal
Repack
Insulation
Figure 20 - Gas Line Installation
12
Opening
with
Refractory
Cement
Provide Enough Threaded
End for Fitting Connection
www.desatech.com
Doors
Fully Opened
Fireplace Front
Figure 21 - Glass Doors
111099-01C
OPERATION AND
OPE
N
CLOS
E
MAINTENANCE
GUIDELINES
Continued
A fireplace equipped with glass doors operates
mush differently than a fireplace with an open
front. A fireplace with glass doors has a limited
amount of air for combustion. Excessive heat
within the fireplace can result if too large a fire
is built or if the combustion air gate is not completely open.
The following tips should be followed to assure
that both the fireplace and the glass door retain
their beauty and function properly. Both the flue
damper and the glass doors must be fully opened
before starting the fire. This will provide sufficient
combustion air and maintain safe temperatures in
the firebox.
IMPO RTANT: The glass must be allowed to
warm slowly and evenly. The tempered glass will
withstand a gradual temperature rise to 550° F,
which is more than a normal fire will generate.
Such materials as pitch/wax laden logs, very dry
mill end lumber and large amounts of paper or
cardboard boxes can create an excessively hot fire
and should not be burned in this fireplace. Always
keep the fire well back from the doors and never
allow flames to contact the glass.
WARNING: Fireplaces
equi pped with gla ss doors
should be operated only with
doors fully opened or doors fully
closed. Doors, if left partly open,
may draw gas and flame out of
the fireplace opening creating
risks of both fire and smoke.
If you wish to install an unvented (vent-free) gas
log set, only unvented gas log sets which have been
found to comply with the standard for unvented
room heaters, ANSI Z21.11.2 are to be installed
in this fireplace.
OUTSIDE AIR AND DAMPER
HANDLE OPERATION
The damper handle, which opens and closes the
damper blade, is located in the upper front face of
the fireplace. Pushing the handle into the left of the
keyway slot will free the damper blade to automatically open. Pushing the handle in to the right will
lock the damper blade closed (see Figure 22).
The outside air kit handle is located at the left hand
side of the fireplace (see Figure 22). Pulling the
handle out will free the outside air door to open.
Pushing the handle in will lock the door closed.
WARNING: Risk of fire! Replace
grate with DESA model 111100-01
only. This grate has been designed
to keep the operation of your fireplace safe and efficient.
For further operating guidelines, instructions and
warranty information, please refer to your home
owner's guide or contact your authorized dealer.
Damper
Handle
Keyway
Slot
-
Cleaning the Glass
Clean the glass with any commercial glass cleaner
or soap and water. Do not use any abrasive material to clean the glass. Do not clean the glass with
any cool water is the glass is still hot from the
fire and smoke.
A gas line or gas log lighter may be installed for the
purpose of installing a vented or vent-free decorative
gas appliance incorporating an automatic shutoff device and complying with the Standard for Decorative
Gas Appliances for Installation in Vented Fireplaces,
ANSI Z21.60 or American Gas Association draft re-
quirements for Gas Fired Log Lighters for Wood Burn
ing Fireplaces, Draft NO. 4 dated August, 1993.
111099-01C13
www.desatech.com
Outside Air
Kit Handle
Figure 22 - Damper and Air Kit Handle
Handle
Retainer
TECHNICAL SERVICE
You may have further questions about installation,
operation, or troubleshooting. If so, contact DESAʼs
Technical Service Department at 1-866-672-6040.
When calling please have your model and serial
numbers of your heater ready.
You can also visit DESAʼs technical services web
-
site at www.desatech.com.
ILLUSTRATED PARTS BREAKDOWN
9
26
16
33
27
16
27
4
32
34
19
12
25
20
30
17
8
1
5
21
2
35
18
11
14
3
13
22
10
6
31
7
37/38
36
28
29
24
23
15
WOODBURNING FIREPLACE MODELS
S42, S42H, S42R, S42RH, VS42(1) AND VS42H(1)
14
www.desatech.com
111099-01C
PARTS LIST
WOODBURNING FIREPLACE MODELS S42, S42H, S42R, S42RH, VS42(1)
AND VS42H(1)
This list contains replaceable parts used in your fireplace. When ordering parts,see Replacement Parts
on page 16 of this manual.
KEY
NO. PART NO. DESCRIPTIONQTY.
1107797-01 Insulation Pan1
2107798-01 Fireplace Top1
3107800-01 Fireplace Surround1
4106642-01 Air Rod Retainer1
5106643-01 Damper Rod Retainer1
6107809-01 Firebox Bottom1
7107810-01 Firebox Surround1
8**Air Separator1
9See Below Left Refractory1
10 See Below Right Refractory1
11
See Below Rear Refractory1
12 See Below Bottom Rear Refractory1
13 See Below Bottom Front Refractory1
14 106683-01 Firebox Support Leg4
15 106687-01 Damper Can Collar1
16 107839-01 Screen Rod2
17**Firebox Top Assembly1
18 106703-01 Air Kit Door Assembly1
19**Face Weldment1
20 110892-02 Air Deflector1
21 107824-01 Fireplace Top Insulation1
REFRACTORY BRICK
KEY
NO. PART NO. DESCRIPTIONQTY.
9107812-03 Left Refractory, Textured White Brick•1
108169-03 Left Refractory, Textured White Herringbone Brick•1
107812-02 Left Refractory, Textured Red Brick•1
108169-02 Left Refractory, Textured Red Herringbone Brick•1
107812-01 Left Refractory, Smooth White Brick•1
108169-01 Left Refractory, Smooth White Herringbone Brick•1
10 107814-03 Right Refractory, Textured White Brick•1
108170-03 Right Refractory, Textured White Herringbone Brick•1
107814-03 Right Refractory, Textured Red Brick•1
108170-02 Right Refractory, Textured Red Herringbone Brick•1
107814-01 Right Refractory, Smooth White Brick•1
108170-01 Right Refractory, Smooth White Herringbone Brick•1
11
107816-03 Rear Refractory, Textured White Brick•1
108171-03 Rear Refractory, Textured White Herringbone Brick•1
107816-02 Rear Refractory, Textured Red Brick•1
108171-02 Rear Refractory, Textured Red Herringbone Brick•1
107816-01 Rear Refractory, Smooth White Brick•1
108171-01 Rear Refractory, Smooth White Herringbone Brick•1
12 111091-01 Bottom Rear Refractory, White Brick• •• •1
111092-02 Bottom Rear Refractory, Red Brick
13 111092-01 Bottom Front Refractory, White Brick• •• •1