WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury, or loss of life.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
FOR YOUR SAFETY
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
WARNING: Improper installation,
adjustment, alteration, service,
or maintenance can cause injury
or property damage. Refer to this
manual for correct installation
and operational procedures. For
assistance or additional information consult a qualified installer, service agency, or the
gas supplier.
Installation and service must
be performed bay a qualified
installer, service agency, or the
gas supplier.
This appliance may be installed in an aftermarket*, permanently located, manufactured
(mobile) home, where not prohibited by state or local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance
is not convertible for use with other gases, unless a certified kit is used.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer.
Save this manual for future reference.
Save this manual for future reference.
TABLE OF CONTENTS
2
SAFETY INFORMATION
TABLE OF CONTENTS
SAFETY INFORMATION ............................................................ 2
WARNING: This product contains and/or generates
chemicals known to the State of California to cause
cancer or birth defects, or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully
and completely before trying to assemble, operate, or
service this fireplace. Improper use of this fireplace
can cause serious injury or death from burns, fire,
explosions, electrical shock, and carbon monoxide
poisoning.
DANGER: Carbon monoxide poisoning may lead
to death!
This fireplace must be installed by a qualified (certified or licensed)
service person. It has a sealed gas combustion chamber that uses a
coaxial pipe (pipe within a pipe and having the same center) venting
system. It brings in fresh air for combustion through the outer pipe and
combustion gases are exhausted through the inner pipe. If the glass
door assembly and venting pipe are not properly seated, connected,
and sealed, carbon monoxide leakage (spillage) can occur.
Carbon Monoxide Poisoning: Early signs of carbon monoxide
poisoning resemble the flu, with headaches, dizziness, or nausea. If
you have these signs, the fireplace may not have been installed
properly. Get fresh air at once! Have fireplace inspected and
serviced by a qualified service person. Some people are more
affected by carbon monoxide than others. These include pregnant
women, people with heart or lung disease or anemia, those under the
influence of alcohol, and those at high altitudes.
Propane/LP and Natural Gas: Propane/LP and natural gases are
odorless. An odor-making agent is added to the gas. The odor helps
you detect a gas leak. However, the odor added to the gas can fade.
Gas may be present even though no odor exists.
CLEANING AND MAINTENANCE ............................................ 26
OWERNER’S REGISTRATION FORM ..................................... 35
WARRANTY INFORMATION ....................................... Back Page
Make certain you read and understand all warnings. Keep this
manual for reference. It is your guide to safe and proper operation
of this fireplace.
WARNING: Any change to this fireplace or its
controls can be dangerous.
1.This appliance is only for use with the type of gas indicated on
the rating plate. This appliance is not convertible for use with
other gases unless a certified kit is used.
2.For propane/LP fireplace, do not place propane/LP supply
tank(s) inside any structure. Locate propane/LP supply tank(s)
outdoors. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
3.If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in
your building
• immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier's instructions
• if you cannot reach you gas supplier, call the fire department.
4.Never install the fireplace
• in a recreational vehicle
• in windy or drafty areas where curtains or other combustible
(flammable) objects can make contact with the fireplace front
• in high traffic areas
5.This fireplace reaches high temperatures. Keep children and
adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
6.Carefully supervise young children when they are in the room
with fireplace.
7.Do not modify this fireplace under any circumstances. Any
parts removed for servicing must be replaced prior to operating fireplace.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
SAFETY INFORMATION
PRODUCT IDENTIFICATION
LOCAL CODES
3
3
SAFETY INFORMATION
Continued
8.Turn fireplace off and let cool before servicing, installing, or
repairing. Only a qualified service person should install, service, or repair this fireplace. Have fireplace inspected annually by a qualified service person.
9.You must keep control compartments, burners, and circulating air passages clean. More frequent cleaning may be needed
due to excessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before cleaning
fireplace.
10. Have venting system inspected annually by a qualified service
person. If needed, have venting system cleaned or repaired.
See Cleaning and Maintenance, page 26.
11. Keep the area around your fireplace clear of combustible materials, gasoline, and other flammable vapor and liquids. Do
not run fireplace where these are used or stored. Do not place
items such as clothing or decorations on or around fireplace.
12. Do not use this fireplace to cook food or burn paper or other
objects.
13. Do not use any solid fuels (wood, coal, paper, cardboard, etc.)
in this fireplace. Use only the gas type indicated on fireplace
nameplate.
14. This appliance, when installed, must be electrically grounded
in accordance with local codes or, in the absence of local codes,
with the National Electrical Code, ANSI/NFPA 70, or the Ca-
nadian Electrical Code, CSA C22.1.
15. Do not use fireplace if any part has been exposed to or under
water. Immediately call a qualified service person to arrange
for replacement of the unit.
16. Do not operate fireplace if any log is broken.
17. Do not use a blower insert, heat exchanger insert, or other accessory not approved for use with this fireplace.
18. Do not operate fireplace with glass door removed, cracked, or
broken.
19. Provide adequate clearances around air openings.
PRODUCT IDENTIFICATION
Upper Louver
Panel
Nailing
Flange
Glass
Door
Assembly
Lower
Louver
Panel
Control
Valve
Figure 1 - Direct-Vent Fireplace with Electronic Ignition
Glowing
Embers
Flue Collar
Log Set
Burner
Assembly
Lava Rock
Switch Bracket for
Optional Remote
and Blower
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the
absence to local codes, use the current National Fuel Gas Code
ANSI Z223.1/NFPA 54* (USA) or the current CSA-B149.1 Installation Code (Canada).
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
111922-01C
For more information, visit www.desatech.com
For more information, visit www.desatech.com
PRODUCT FEATURES
4
PRE-INSTALLATION PREPARATION
Location and Space Requirements
PRODUCT FEATURES
These are a few facts that can help you understand and enjoy your
direct-vent fireplace:
• The venting system may be routed to the outside of your home
in several ways. It may vent through the roof (vertical) or it may
vent to an outside/exterior wall (horizontal). The vent pipe installation is very important to allow for proper operation. You
must follow the venting instructions very carefully for either
vertical or horizontal applications.
• This fireplace may be installed in any room of your house provided
all local codes and these installation instructions are followed.
• This fireplace does not require electricity to operate.
• Only the blower requires electricity if installed and if you plan
to install the blower at a later date, do not forget to wire the
outlet at the bottom of the fireplace when framing.
• A piezo ignitor and ceramic electrode create spark to ignite the
pilot light. It does not require any matches, batteries or any other
sources of ignition to light the pilot.
• Each time you turn on your fireplace, you may notice some
amount of condensation on the inside of the fireplace glass. This
is normal and will disappear after 10-20 minutes of operation.
• Your direct-vent gas fireplace system (fireplace and venting) is a
balanced and sealed gas operating unit. It requires approximately
10-20 minutes of operating time before the flame pattern stabilizes.
PRE-INSTALLATION
• Your fireplace is designed to be used in zero clearance installations. Wall or framing material can be placed directly against
any exterior surface on the back, sides, or top of your fireplace,
except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be
placed directly against wall or framing material. See framing
details on page 5.
• If you plan on installing a television or entertainment center recessed above your fireplace, it is recommended that you maintain a minimum 18" above top of louver opening.
• When locating termination cap, it is important to observe the
minimum clearances shown in Figure 7, page 6.
• If recessing into a wall, you can avoid extra framing by positioning your fireplace against an already existing framing member.
• Do not recess termination cap into a wall or siding.
• You may paint the termination cap with 450ºF (232ºC) heatresistant paint to coordinate with the exterior finish.
• There must not be any obstruction such as bushes, garden sheds,
fences, decks, or utility buildings within 24" from the front of
the termination cap.
• Do not locate termination cap where excessive snow or ice build
up may occur. Be sure to clear vent termination area after snow
falls to prevent accidental blockage of venting system. When
using snow blowers, do not direct snow towards vent termination area.
PREPARATION
LOCATION AND SPACE REQUIREMENTS
Determine the safest and most efficient location for your DESA
direct-vent fireplace. Make sure that rafters and wall studs are not
in the way of the venting system. Choose a location where the heat
output is not affected by drafts, air conditioning ducts, windows or
doors. Figure 2 shows some common locations. Be aware of all
restrictions and precautions before deciding the exact location for
your fireplace and termination cap.
When deciding the location of your fireplace, follow these rules:
• Do not connect this fireplace venting to a chimney flue serving
a separate solid-fuel burning fireplace or appliance.
• Due to high temperatures, do not locate this fireplace in high traffic areas, windy or drafty areas, or near furniture or draperies.
• Proper clearances must be maintained.
• If your fireplace is to be installed directly on carpeting, vinyl
tile, or any combustible material other than wood, it must be
installed on a metal or wood panel extending the full width and
depth of the fireplace. See Figure 3.
Flush with a wall
Through exterior wall
enclosed in a chase
Figure 2 - Common Fireplace Locations
36 1/4"
RW
23 1/4"
D
48"
FW
Figure 3 - Fireplace Bottom Dimensions
Corner
installation
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
PRE-INSTALLATION
PREPARATION
Continued
CLEARANCES
Minimum clearances to combustibles for the fireplace are as follows:
Back, and sides0"/mm
Perpendicular walls6" (152mm)
Floor0"/mm
Ceiling to louver opening42" (1067mm)
Front36" (914mm)
Top0"/mm
Vent(See venting instructions for
specific venting clearances.)
Combustible material with a maximum thickness of 5/8" may be
flush with the top front of fireplace .
NOTICE: This fireplace is intended for use as supplemental heat. Use this fireplace along with your primary heating system. Do not install this fireplace as
your primary heat source. If you have a central heating system, you may run system’s circulating blower
while using fireplace. This will help circulate the heat
throughout the house. In the event of a power outage,
you can use this fireplace as a heat source.
FRAMING AND FINISHING
Figure 4 shows typical framing of this fireplace. Figure 5 shows
framing for corner installation. All minimum clearances must be met.
For available accessories for this fireplace, see Accessories on page
34. If you are using a separate combustible mantel piece, refer to
Figure 6 for proper installation height. You can install noncombustible mantels at any height above the fireplace.
tible mantels may discolor!
Note:
Noncombus-
PRE-INSTALLATION PREPARATION
Clearances
C
/4"
41 5/8"
A
Framing and Finishing
3
/4"
D
13 1/2"
F
48"
1
G
48
81 1/2"
H
5
B
/8"58 1/2"
21
E
16
Figure 5 - Framing Clearances for Corner Installation
Figure 4 - Framing Clearances for Installation Against an Exterior
Wall
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
Figure 6 - Clearances for Combustible Mantels
LOCATION OF TERMINATION CAP
6
LOCATION OF TERMINATION CAP
D
E
V
B
L
V
A = clearance above grade, veranda, porch, deck, or balcony
[*12 inches (30.5mc) minimum]
B = clearance to window or door that may be opened
[12 inches (30.5cm) minimum]
C = clearance to permanently closed window [minimum 12 inches
(30.5cm) recommended to prevent condensation on window]
D = vertical clearance to ventilated soffit located above the terminal
within a horizontal distance of 24 inches (61cm) from the
center-line of the terminal [18 inches (45.7cm) minimum]
E = clearance to unventilated soffit [12 inches (30.5cm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly within
36 inches (91.4cm) horizontally from the center-line of the regulator
vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
*as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note
: Local codes or regulations may require different clearances
C
Fixed
Closed
V
Openable
B
F
TERMINATION CAP
V
Openable
B
AIR SUPPLY INLET
X
B
Fixed
Closed
J
V
A
I = clearance to service regulator vent outlet [*72 inches (182.9cm)
J = clearance to non-mechanical air supply inlet to building or the
K = clearance to a mechanical air supply inlet [*72 inches (182.9cm)
L = clearance above paved side-walk or a paved driveway located on
M = clearance under veranda, porch, deck [*12 inches (30.5cm) minimum ]
N = clearance above a roof shall extend a minimum of 24 inches (61cm)
N
H
V
B
X
G
minimum]
combustion air inlet to any other fireplace [*12 inches (30.5cm)
minimum]
minimum]
public property [*84 inches (213.3cm) minimum]
above the highest point when it passes through the roof surface and
any other obstruction within a horizontal distance of 18 inches (45.7cm)
G
GAS METERRESTRICTED AREA
I
M
V
(TERMINATION PROHIBITED)
N
G
G
X
K
V
V
A
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
NOTICE: Read these instructions completely before attempting installation.
These models are tested and approved for use with DESA (directvent) pipe components and terminations.
The venting system must terminate on the outside of the structure and
can not be attached to a chimney or flue system serving a separate
solid fuel or gas burning appliance. A direct-vent appliance must have
its own venting system. DO NOT common vent this appliance.
These models are approved to be vented either horizontally through
an outside wall or vertically through a roof or chase enclosure using
the following guidelines:
• When venting system terminates horizontally on an outside wall,
you may install a standoff if the termination cap is to be installed directly on a combustible finish such as vinyl, wood,
stucco, etc.
• Never run the vent downward as this may cause excessive temperatures which could cause a fire.
• Vent pipe air space clearances to combustibles are 1" on all sides
except on the horizontal sections, which requires 2" clearance
from the top of the pipe. Where the termination cap penetrates a
combustible wall, 1" air space clearance is required.
• Snorkel terminations are required when minimum clearance to grade
cannot be met (see Figure 16 on page 11).
• Have fireplace and selected vent components on hand to help
determine the exact measurements when elbowing or offsetting.
Always use wall firestops when penetrating walls and firestops
when penetrating ceilings or attic spaces.
• Install horizontal venting with a 1/4" rise for every 12" of run
toward the termination.
NOTICE: Failure to follow these instructions will void
the warranty.
INSTALLATION PRECAUTIONS
• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the warranty on your venting
system:
• Installation of any damaged venting component
• Unauthorized modification of the venting system (Do not cut
or alter vent components)
• Installation of any component part not manufactured or approved by DESA
• Installation other than as instructed by these instructions
WARNING: This gas fireplace and vent assembly
must be vented directly to the outside. The venting
system must NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each
direct-vent gas appliance must use a separate vent
system. Do not use common vent systems.
WARNING: Vent pipe air space clearances to combustibles are 1" on all sides except on the horizontal
sections, which require 2" clearances from the top of
the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
WARNING: Read all instructions completely and
thoroughly before attempting installation. Failure to
do so could result in serious injury, property damage
or loss of life.
IMPORTANT:
for service.
111922-01C
Do not seal vent cap to pipe. Cap must be removable
For more information, visit www.desatech.com
For more information, visit www.desatech.com
VENTING INSTALLATION INSTRUCTIONS
8
Installation Planning
VENTING INSTALLATION
INSTRUCTIONS
Continued
INSTALLATION PLANNING
There are two basic types of direct-vent installation:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
IMPORTANT:
portion of wall firestop. Horizontal installations using round termination require exterior portion of wall firestop.
1.Set the fireplace in its desired location and determine the route
your horizontal venting will take. Do not secure the fireplace
until all venting has been installed. Some installations require
sliding the fireplace in and out of position to make final venting
connections. Figures 14 through 18 on pages 10 through 12 show
different configurations for venting with horizontal termination
that will help you decide which application best suits your installation. Check to see if wall studs or roof rafters are in the
path of your desired venting route. If they are, you may want to
adjust the location of the fireplace.
2.Direct vent pipe sections and components are designed with
special twist-lock connections.
Twist-Lock Procedure: The female ends of the pipes have
locking lugs (indentations). These lugs will slide straight into
matching slots on the male ends of adjacent pipes. Push pipe
sections together and twist one section clockwise approximately
one-quarter turn until the sections are fully locked (see Figure
8).
Note:
feet. Use wall straps for this purpose.
3.Use a 45° elbow to connect venting system to fireplace flue collar. The elbow is designed to be twist-locked onto the flue collar
as described in step 2.
configuration of the elbow by cutting, twisting, bending, etc.
4.Assemble the desired combination of pipe and elbows to the
fireplace flue collar. If there are long portions of venting run,
pre-assembled pipe sections may be installed as subassemblies
for convenience.
5.Carefully determine the location where the vent pipe assembly
will penetrate the outside wall. The center of the hole should line
up with the center-line of the horizontal vent pipe. Mark the wall
for a 10 3/4" x 10 3/4" square hole. Cut and frame the square hole in
the exterior wall where the vent will be terminated. If the wall
being penetrated is constructed of noncombustible material, such
as masonry block or concrete, a 8 1/2" hole with zero clearance is
acceptable (see Figure 9).
Horizontal square terminations require only inner
Horizontal runs of vent must be supported every three
IMPORTANT:
Do not attempt to alter the
Female
Locking Lugs
Male
Slots
Figure 8 - Vent Pipe Connections
Vent Opening
Combustible Wall
3
/4"
10
(273mm)
3
10
/4"
(273mm)
Vent Opening
Noncombustible Wall
8 1/2"
(216mm)
Figure 9 - Vent Opening Requirements
10
(Framing
Detail)
3
/4" Inside Framing
(273mm)
Center
of Hole
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
VENTING INSTALLATION
INSTRUCTIONS
Continued
WARNING: Do not recess vent termination into
any wall. This will cause a fire hazard.
6.Noncombustible Exterior Wall: Position the horizontal vent
cap in the center of the 8 1/2" round hole and attach to the exterior wall with four wood screws provided. Before attaching
the vent cap to exterior wall, run a bead of non-hardening mastic
(pliable sealant) around the outside edges to make a seal between it and the outside wall.
provided should be replaced with appropriate fasteners for
stucco, brick, concrete, or other types of sidings.
Combustible Exterior Wall: For vinyl siding, stucco, or wood
exteriors, a siding standoff may be installed between the vent
cap and exterior wall. The siding standoff prevents excessive
heat from damaging the siding materials. Siding material must
be cut to accommodate standoff. Bolt the vent cap to the standoff. Apply non-hardening mastic around outside edge of standoff. Position the standoff/cap assembly in the center of the
10 3/4" square hole and attach to exterior wall with wood
screws provided (see Figure 11). The siding standoff must sit
flush against the exterior fascia material.
7.Combustible Exterior Wall Only: Slide the wall firestop over
the vent pipe before connecting horizontal run to vent cap (see
Figure 12).
8.Carefully move fireplace, with vent assembly attached, toward
wall and insert vent pipe into horizontal termination. The pipe
overlap should be a minimum of 11/4".
9.Combustible Exterior Wall Only: Slide wall firestop against
interior wall surface and attach with screws provided (see
Figure 12). See Figure 13, page 10, for horizontal termination details.
Figure 10 - Installing Horizontal Vent Cap (Noncombustible
Exterior)
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
Screw
Figure 12 - Connecting Vent Cap with Horizontal Vent Pipe
VENTING INSTALLATION INSTRUCTIONS
10
Installation Planning (Cont.)
VENTING INSTALLATION
INSTRUCTIONS
Continued
10. Place fireplace into position and shim with noncombustible material if needed. Nail or screw side flanges to framing to secure
unit in place.
securing. If fireplace is not level it will not work properly.
IMPORTANT:
Make sure fireplace is level before
WARNING: Never run vent downward as this may
cause excessive temperatures which could cause a
fire. Operation of improperly installed and maintained venting system could result in serious injury,
property damage or loss of life.
Minimum Pipe
Overlap 1
Direct Vent
Pipe
Wall
Firestop
Maintain 1"
Minimum Air
Space Around
Outer Pipe When
Penetrating a Wall
Figure 13 - Typical Horizontal Termination Cap Mounting with
Additional Siding Standoff Installed
3
/4" x 10 3/4"
10
Framed
Opening
1
/4"
Siding Standoff
Screws
High Wind
Termination
Apply Mastic to
Outside Edge of
Standoff
Exterior Wall
with Vinyl Siding
GROUND FLOOR INSTALLATION
Recommended Applications:
• Installation using cabinet surrounds
• Through the wall using round or square termination
(up to 12" horizontal pipe)
• NOT FOR CORNER INSTALLATION
45° Elbow
Horizontal High
Wind Square
Termination
Adjustable
Pipe 12" Max.
Wall
Firestop
Square Termination
Vertical (V)Horizontal (H)
36 3/4"17" max.
45° Elbow
Wall
Firestop
Exterior Portion of Wall
Firestop (Round
Termination Only)
Horizontal Termination Configurations
Figures 14 through 18 show different configurations and alternatives
for venting with horizontal termination. Each figure includes a chart
with critical minimum and maximum dimensions which MUST be
met.
IMPORTANT:
have a 1/4" rise for every 12" of run toward the termination.
Remember that a horizontal run of venting must
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Horizontal
Round
Termination
Figure 14 - Horizontal Termination Configuration for Square or
Round Termination
111922-01C
VENTING INSTALLATION
INSTRUCTIONS
Continued
CORNER INSTALLATION
Recommended Applications:
• Corner ground floor installation
• Ground floor installation where pipe vents horizontally through wall
(over 12" horizontal pipe)
• Basement installation where one foot clearance from ground to
termination is possible
Not to Exceed
(H) Limits
Square
Termination
90° Elbow
As Required for (V)
See Chart for Pipe
Section Required
VENTING INSTALLATION INSTRUCTIONS
Vertical (V)Vertical PipeHorizontal (H)
1
/4" min.None30" max.
*46
57 1/4" min.1 ft.48" max.
1
/4" min.2 ft.60" max.
69
1
/4" min.3 ft.84" max.
81
93 1/4" min.4 ft.20' max.
* Ground Floor Corner Venting
Installation Planning (Cont.)
Required
Not to Exceed
(H) Limits
90° Elbow
Square
Termination
11
11
Wall
Firestop
Figure 15 - Horizontal Termination Configuration for Corner Installation Using One 90° Elbow
45°
Elbow
Wall
Firestop
45° Elbow
SNORKEL TERMINATION INSTALLATION
Recommended Applications:
• Installations requiring a vertical rise on building exterior
• Any installation using snorkel termination to achieve one foot above ground
Snorkel terminations are available for installations requiring a vertical rise on the exterior of the building. If
installing snorkel termination below grade, you must provide proper drainage to prevent water from entering snorkel
termination (see Figure 16). Do not back fill around snorkel termination.
Snorkel
Termination
12"
Minimum
Snorkel
Termination
12"
Minimum
Adequate
Drainage
90° Elbow
45°
Elbow
Wall
Firestop
12" Minimum
Snorkel
Termination
12"
Minimum
Figure 16 - Snorkel Termination Configurations for Below Ground Installation
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
VENTING INSTALLATION INSTRUCTIONS
12
Installation Planning (Cont.)
VENTING INSTALLATION
INSTRUCTIONS
Continued
HORIZONTAL SYSTEM INSTALLATION USING TWO 90°
ELBOWS
The following configurations show the minimum vertical rise
requirements for a horizontal system using two 90° elbows.
Figure 18 - Horizontal Termination Configuration for Venting Using Two 90° Elbows with Termination at 90° with Fireplace
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
VENTING INSTALLATION
INSTRUCTIONS
Continued
VENTING INSTALLATION INSTRUCTIONS
Installation for Vertical Termination
13
13
INSTALLATION FOR VERTICAL TERMINATION
Note:
Vertical restrictor must be installed in all vertical installations.
1.Determine the route your vertical venting will take. If ceiling
joists, roof rafters, or other framing will obstruct the venting
system, consider an offset (see Figure 19) to avoid cutting load
bearing members.
lation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with insulation.
Also note maximum vertical rise of the venting system and
any maximum horizontal offset limitations.
2.Set the fireplace in desired location. Drop a plumb line down
from the ceiling to the position of the fireplace exit flue. Mark
the center point where the vent will penetrate the ceiling. Drill
a small locating hole at this point.
Drop a plumb line from the inside of the roof to the locating
hole in the ceiling. Mark the center point where the vent will
penetrate the roof. Drill a small locating hole at this point.
Wall Strap
Figure 19 - Offset with Wall Strap and 45° Elbows
Note:
Pay special attention to these instal-
Roof Flashing
45° Elbow
Ceiling Firestop
2.Assemble the desired lengths of pipe and elbows necessary to
reach from the fireplace flue up through the firestop. Be sure
all pipe and elbow connections are fully twist-locked (see Figure 8, page 8).
3.Cut a hole in the roof using the locating hole as a center point.
(Cover any exposed open vent pipes before cutting hole in roof.)
The 10
actual length may be larger depending on the pitch of the roof.
There must be a 1" clearance from the vent pipe to combustible
materials. Frame the opening as shown in Figure 9, page 8.
4.Connect a section of pipe and extend up through the hole.
Note:
support the vent pipe every 3 feet. Use wall straps for this
purpose (see Figure 19). Whenever possible, use 45° elbows
instead of 90° elbows. The 45° elbow offers less restriction to
the flow of the flue gases and intake air.
5.Place the flashing over the pipe section(s) extending through
the roof. Secure the base of the flashing to the roof and framing with roofing nails. Be sure roofing material overlaps the
top edge of the flashing as shown in Figure 19. There must be
a 1" clearance from the vent pipe to combustible materials.
6.Continue to add pipe sections until the height of the vent cap
meets the minimum building code requirements described in
Figure 7 on page 6.
steep roof pitches. Nearby trees, adjoining rooflines, steep
pitched roofs, and other similar factors may cause poor draft
or down-drafting in high winds. Increasing the vent height may
solve this problem.
7.Twist-lock the vent cap onto the last section of vent pipe.
Note:
first floor, including storage spaces and closets, you must enclose
pipe. You may frame and sheetrock the enclosure with standard
construction material. Make sure and meet the minimum allowable
clearances to combustibles. Do not fill any of the required air spaces
with insulation.
3
/4"x10 3/4" hole must be measured on the horizontal;
If an offset is needed to avoid obstructions, you must
Note:
You must increase vent height for
If the vent pipe passes through any occupied areas above the
Flat Ceiling Installation
1.Cut a 10 3/4" square hole in the ceiling using the locating hole as
a center point. The opening should be framed to 10 3/4"x10 3/4"
(273 mm x 273 mm) inside dimensions, as shown in Figure 9
on page 8 using framing lumber the same size as the ceiling
joists. If the area above the ceiling is an insulated ceiling or a
room, nail firestop from the top side. This prevents loose insulation from falling into the required clearance space. Otherwise,
install firestop below the framed hole. The firestop should be
installed with no less than three nails per side (see Figure 20).
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
If area above is a room, install
firestop above framed hole.
Figure 20 - Installing Firestop
If area above is not a room, install
firestop below framed hole.
14
VENTING INSTALLATION INSTRUCTIONS
Installation for Vertical Termination (Cont.)
VENTING INSTALLATION
INSTRUCTIONS
Continued
Vertical Termination Configurations
Figures 21 through 24 show four different configurations for vertical termination.
Install restrictor
into inner collar of
fireplace as shown.
45° Elbow
Note:
Vertical (V1) + Vertical (V2) = 40' max.
Figure 23 - Vertical Venting Configuration Using Two 90° Elbows
(Vertical Round High Wind Termination Shown)
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
VENTING INSTALLATION
INSTRUCTIONS
Continued
Vertical Venting
V = 40' max.
Note:
Install restrictor
into inner collar of
fireplace as shown.
45° Elbow
Figure 24 - Vertical Venting Configuration With No Horizontal
Run (Vertical Round High Wind Termination Shown)
HIGH ALTITUDE INSTALLATION
Your DESA direct-vent fireplace has been tested and approved for
elevations from 0-2000 feet (USA) and elevations from 0-4500 feet
(Canada).
When installing this fireplace at an elevation above 2000 feet (in the
USA), you may need to decrease the input rating by changing the
existing burner orifice to a smaller size. Reduce input 4% for each
1000 feet above sea level. Check with your local gas company for
proper orifice size identification.
VENTING INSTALLATION INSTRUCTIONS
Installation for Vertical Termination (Cont.)
High Altitude Installation
Parts Lists for Venting Kits and Components
15
15
When installing this fireplace at an elevation above 4500 feet (in
Canada), check with local authorities.
Consult your local gas company to help determine the proper orifice
for your location.
For assistance with any high altitude installation contact DESA’s
Customer Service Department at 1-866-672-6040.
PARTS LISTS FOR VENTING KITS AND COMPONENTS
DESA (5/8") Pipe & Vent Kits
Check Gas Type
Installing Optional Blower Accessory
FIREPLACE INSTALLATION
CHECK GAS TYPE
Use proper gas type for the fireplace unit you are installing. If your
gas supply is not correct, do not install fireplace. See retailer where
you purchased the fireplace for proper fireplace according to your
gas type or to purchase gas conversion kit (see Accessories, page 34).
INSTALLING OPTIONAL BLOWER
ACCESSORY
NOTICE: If installing blower in an existing fireplace
with gas connections, shut off gas supply and disconnect heater from gas supply. Contact a qualified
service person to do this.
WARNING: If there is a duplex electrical outlet
installed in the right side of the bottom of the fireplace
base area, be sure that the electrical power to the outlet
is turned off before proceeding with blower installation.
Failure to do this may result in serious injury.
Model BK Installation
Follow all instructions provided in the blower accessory kit.
1.Attach the power cord to the blower motor by firmly pushing the
two female terminals at the end of the power cord onto the two
spade terminals on the blower motor (see Figure 25).
2.Attach green ground wire from power cord to blower housing
using screw provided (see Figure 25). Tighten screws securely.
3.Place the blower against the lower rear wall of the firebox outer
wrapper with the exhaust port directed upward. The blower
will fit inside the back opening and be held in position against
the back wall by the magnets (see Figure 25).
4.Be certain that all wire terminals are securely attached to terminals on blower motor and that the screw retaining the green
ground wire is tight.
5.Mount speed control box to switch bracket by placing the plastic
control shaft forward through the opening in the switch bracket
(see Figure 26).
6.While supporting speed control, secure control shaft with lock
nut by pushing and turning lock nut with pliers clockwise until it
is tight against front panel. Place control knob provided on shaft.
7.Turn on power to duplex outlet if previously turned off per the
warning in column 1.
8.Plug in blower power cord.
a. If your firebox is installed as a freestanding unit with an
accessory mantel, determine whether the power cord will
exit the left side or the right side of the firebox. Route power
cord through exit hole and plug the power cord into a wall
receptacle near the firebox.
b. If your firebox installation is recessed and/or pre-wired,
plug the power cord into the duplex outlet provided. Refer
to your firebox owner’s manual for instructions on wiring
the duplex outlet.
CAUTION: Never touch the blower wheel while in
operation.
9.Check to make sure that the power cord is completely clear of the
blower wheel and that there are no other foreign objects in blower
wheel. Turn blower on and check for operation. Turn blower off
by turning knob fully counterclockwise before continuing.
Switch
Bracket
Speed Control
Blower
Plug-In
Lower Firebox
Cavity
Side View
Spade Terminals
Green
Ground Wire
Figure 25 - Blower Model BK
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Screw
Blower
Location
Magnetic Strips
Exhaust
Port
Control
Knob
Locknut
Figure 26 - Attaching Speed Control to Firebox
Control
Shaft
Duplex Outlet
(Located underneath
firebox floor against
lower right outside wall)
111922-01C
FIREPLACE INSTALLATION
Continued
Installing Optional Blower Accessory (Cont.)
FIREPLACE INSTALLATION
17
17
10. Peel off the backing paper and stick the supplied wiring diagram decal on the firebox bottom approximately 12" in front
of the blower (see Figure 27).
le
h
b
itc
ria
w
a
V
Blower
n S
Motor
a
F
n
O
ck
la
f
B
ite
k
f
h
O
lac
W
k
B
c
la
B
k
ac
5
l
B
ite
.
11
h
/
n
C
0
.
e
W
1
.A
re
1
V
G
Wiring Diagram Decal
12" in Front of Blower
Figure 27 - Location of Wiring Diagram Decal (Model May Vary
From Illustration)
Model BKT Installation
Note:
When installing the BKT thermostatically-controlled blower,
you must first secure the thermal switch bracket to the blower if it
has not already been factory installed.
1.Place the green ground wire with ring terminal between the
bottom hole on the thermal switch bracket and the top ear hole
on the blower assembly. Insert the phillips screw into all three
pieces and tighten securely (see Figure 28).
2.Connect wire harness and power cord terminals. Connect the
blue jumper wire to the blower motor terminal and the right
side terminal of the thermal switch. Connect the black wire to
the left side of the thermal switch and the white wire to the
other remaining blower motor terminal.
Note:
The power cord outer insulation sleeve may have to be
stripped slightly to allow enough wire length to reach and make all
connections. DO NOT trim excessive length away. Just enable
enough to make all connections securely.
3.Place the blower against the lower rear wall of the firebox outer
wrapper with the exhaust port directed upward and the thermodisc
positioned up near the fireplace bottom. The thermodisc must be
oriented near the fireplace bottom as shown in Figure 28 in order
to sense temperature and properly operate. The blower will be
held in position against the back wall by the magnets incorporated onto the blower housing (see Figure 28).
4.Be certain that all wire terminals are securely attached to ter-
minals on blower motor and thermal switch, and that the screw
for the thermodisc bracket and green ground wire is tight.
5.Mount the speed control box against the mounting plate pro-
vided in the lower fireplace cavity by placing the plastic control
shaft forward through the round hole (see Figure 26, page 16).
6.While supporting speed control, secure control shaft with lock
nut by pushing and turning lock nut with pliers clockwise until it is tight against mounting plate. Place control knob provided on shaft (see Figure 26, page 16).
7.Check to make sure that the power cord is completely clear of the
blower wheel and that there are no other foreign objects in blower
wheel. Also double check all wire leads and make sure wire routing is not pinched or in a precarious position. Correct accordingly.
8.Turn on power to duplex outlet if previously turned off per the
warning in column 1, page 16.
9.Plug in blower power cord to duplex outlet.
10. The blower will only run when the speed control knob is in the
ON position and the thermal switch senses temperature after
the fireplace begins to heat up. The blower speed can be adjusted by rotating the control knob. To turn off, turn knob fully
counterclockwise until it clicks off. If the blower is ON and
has been running with the fireplace operating, the blower will
continue to run for a short time after the fireplace has been
turned off. As the thermal switch cools down, the blower shuts
down automatically.
11. Peel off the backing paper and stick the supplied wiring diagram decal on the firebox bottom approximately 12" in front
of the blower (see Figure 27).
.
Power Cord
Thermal
Switch
Bracket
Black
Wire
Phillips
Screw
Thermal Switch
Route BKT
Blower Through
This Area
Side View Firebox Bottom
Figure 28 - Blower Model BKT
White Wire
Ring Terminal
on Green Wire
Thermodisc
Blue Wire
Air Flow
Direction
Air Flow Direction
Magnetic
Strips
Magnets
Blower
Location
111922-01C
For more information, visit www.desatech.com
For more information, visit www.desatech.com
FIREPLACE INSTALLATION
18
Installing Optional Blower Accessory (Cont.)
Installing Gas Piping to Fireplace Location
FIREPLACE INSTALLATION
Continued
Blower Wiring Diagram
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation. Verify proper
operation after servicing.
Variable
Fan Switch
1
Off
110/115
V.A.C.
Black
White
Green
Figure 29 - Blower Wiring Diagram for Thermostat-Controlled
Models
2
On
Black
Fan Switch
(N.O.)
Blue
Blower
Motor
INSTALLING GAS PIPING TO FIREPLACE
LOCATION
WARNING: A qualified service person must connect fireplace to gas supply. Follow all local codes.
For propane/LP connection only, the installer must supply an
external regulator. The external regulator will reduce incoming gas
pressure. You must reduce incoming gas pressure to between 11 and
14 inches of water. If you do not reduce incoming gas pressure,
fireplace regulator damage could occur. Install external regulator
with the vent pointing down as shown in Figure 30. Pointing the vent
down protects it from freezing rain or sleet.
CAUTION: Use only new, black iron or steel pipe.
Internally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2"
inside diameter or greater to allow proper gas volume
to fireplace. If pipe is too small, undue loss of volume
will occur.
Installation must include an equipment shutoff valve, union, and
plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge
hook up. NPT tap must be upstream from fireplace (see Figure 31,
page 19).
IMPORTANT:
Install main gas valve (equipment shutoff valve) in
an accessible location. The main gas valve is for turning on or
shutting off the gas to the appliance.
Check your building codes for any special requirements for locating
equipment shutoff valve to fireplaces.
Apply pipe joint sealant lightly to male NPT threads. This will
prevent excess sealant from going into pipe. Excess sealant in pipe
could result in clogged fireplace valves.
CAUTION: For propane/LP units, never connect
fireplace directly to the propane/LP supply. This
heater requires an external regulator (not supplied).
Install the external regulator between the fireplace
and propane/LP supply.
Installation Items Needed
Before installing fireplace, make sure you have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved flexible gas line with gas connector (if allowed by local codes)
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap
is an acceptable alternative to test gauge connection. Purchase the
CSA design-certified equipment shutoff valve from your retailer.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
External
Regulator
Vent
Pointing
Down
Figure 30 - External Regulator with Vent Pointing Down
(Propane/LP Only)
Propane/LP
Supply Tank
111922-01C
FIREPLACE INSTALLATION
Continued
FIREPLACE INSTALLATION
Installing Gas Piping to Fireplace Location (Cont.)
Connecting Fireplace to Gas Supply
Checking Gas Connections
19
19
WARNING: Use pipe joint sealant that is resistant
to liquid petroleum (LP) gas.
We recommend that you install a sediment trap/drip leg in supply
line as shown in Figure 31. Locate sediment trap/drip leg where it
is within reach for cleaning. Install in piping system between fuel
supply and fireplace. Locate sediment trap/drip leg where trapped
matter is not likely to freeze. A sediment trap traps moisture and
contaminants. This keeps them from going into fireplace gas controls. If sediment trap/drip leg is not installed or is installed wrong,
fireplace may not run properly.
CSA Design-Certified
Equipment Shutoff Valve
with 1/8" NPT Tap*
Natural - From
Gas Meter (5.5"
W.C. to 10.5"
Approved Flexible
Gas Line
3" Minimum
Figure 31 - Gas Connection
Cap Pipe Nipple Tee Joint
Sediment Trap/Drip Leg
W.C. Pressure)
Propane/LP
From External
Regulator (11"
W.C. to 14"
W.C. Pressure)
* The CSA design-certified equipment shutoff valve may be supplied with the appliance or you can purchase it from your retailer.
CONNECTING FIREPLACE TO GAS SUPPLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not provided)
1.Open lower louver door panel by gently pulling forward.
2.Route flexible gas line (provided by installer) from equipment
shutoff valve to fireplace. Route flexible gas supply line through
one of the access holes on side of fireplace.
3.Attach flexible gas line from gas supply to control valve (see
Figure 32).
4.Check all gas connections for leaks. See Checking Gas Con-
nections.
Red Surface Indicates
Equipment
Shutoff Valve
1/2" NPT Incoming
Gas Line
Note:
Wire Connections Not Shown for Clarity
Figure 32 - Connecting Flexible Gas Line to Electronic Valve
Flexible Gas Line
Do NOT Kink
Inlet Pressure Tap
For Propane/LP Use Only
Outlet Pressure Tap
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping and connections,
internal and external to unit, for leaks after installing
or servicing. Correct all leaks at once.
WARNING: Never use an open flame to check for a
leak. Apply noncorrosive leak detection fluid to all joints.
Bubbles forming show a leak. Correct all leaks at once.
Pressure Testing Gas Supply Piping System
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1.Disconnect fireplace and its individual equipment shutoff valve
from gas supply piping system. Pressures in excess of 1/2 psig
(3.5 kPa) will damage fireplace gas regulator.
2.Cap off open end of gas pipe where equipment shutoff valve
was connected.
3.Pressurize supply piping system by either opening propane/LP
supply tank valve for propane/LP gas fireplace or opening main
gas valve located on or near gas meter for natural gas fireplace, or using compressed air.
4.Check all joints of gas supply piping system. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a
leak. Correct all leaks at once.
5.Reconnect fireplace and equipment shutoff valve to gas supply. Check reconnected fittings for leaks.
111922-01C
For more information, visit www.desatech.com
For more information, visit www.desatech.com
FIREPLACE INSTALLATION
20
Checking Gas Connections (Cont.)
Removing/Replacing Glass Door
FIREPLACE INSTALLATION
Continued
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1.Close equipment shutoff valve (see Figure 33).
2.Pressurize supply piping system by either opening propane/LP
supply tank valve for propane/LP gas fireplace or opening main
gas valve located on or near gas meter for natural gas fireplace, or using compressed air.
3.Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 34 for propane/LP or Figure 35 for
natural gas). Apply noncorrosive leak detection fluid to all joints.
Bubbles forming show a leak. Correct all leaks at once.
Equipment
Shutoff
Valve
Figure 33 - Equipment Shutoff Valve
Equipment Shutoff Valve
Propane/LP
Supply Tank
Open
Closed
Pressure Testing Fireplace Gas Connections
1.Open equipment shutoff valve (see Figure 33).
2.Open propane/LP supply tank valve for propane/LP fireplace
or main gas valve located on or near gas meter for natural
gas fireplace.
3.Make sure control knob of fireplace is in the OFF position.
4.Check all joints from equipment shutoff valve to gas valve
(see Figure 34 for propane/LP or Figure 35 for natural gas).
Apply noncorrosive leak detection fluid to all joints. Bubbles
forming show a leak. Correct all leaks at once.
5.Light fireplace (see Operating Fireplace, pages 24 and 25).
Check all other internal joints for leaks.
6.Turn off fireplace (see To Turn Off Gas to Appliance, page 24).
REMOVING/REPLACING GLASS DOOR
CAUTION: Do not operate this fireplace with a
broken glass door panel or without the glass door
panel securely in place. For replacement part information see
CAUTION: Wear gloves and safety glasses while
handling or removing broken glass. Do not remove if
glass is hot. Keep children and pets away from glass.
Replacement Parts
, page 29.
Gas Valve
Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace
Equipment Shutoff Valve
Gas
Meter
Gas Valve
Figure 35 - Checking Gas Joints for Natural Gas Fireplace
For more information, visit www.desatech.com
For more information, visit www.desatech.com
WARNING: If fireplace has been running, turn
off and unplug fireplace. Let cool before removing
glass door or louvers.
Removing Louver Panels
Remove the top and bottom louver panels by simultaneously pulling
both top end spring latches towards the center of the appliance until
they are disengaged from the locating holes (see Figure 36). Repeat
for bottom spring latches and pull the louvers outward. To install or
replace items removed, simply reverse the procedures above.
If replacement of glass is necessary, the entire assembly, glass and
frame, must be replaced. If glass is broken, wear gloves and tape the
remaining fragments onto the frame.
1.Remove screen assembly by pushing the rod either left or right
and then down and forward to remove screen/rod assembly
from the firebox. Set assembly aside.
2.Lift up on latches to unlock. There are two on top of firebox and
two below firebox that hold glass door in place (see Figure 37).
3.While holding glass door to prevent it from falling and causing injury, remove the five screws from the hinge located on
the left side of door frame assembly (see Figure 37).
4.Remount the new frame at the hinge with five new screws
before closing door. This will ensure seating of the gasket.
5.Close glass door frame. Lock latches by placing the bar under the
tab on door and pushing down and back on latch (see Figure 37).
6.Replace screen/rod assembly by reversing step 1.
7.Replace louvers by reversing procedure under Removing Lou-ver Panels, page 20.
WARNING: If fireplace has been running, turn
off and unplug fireplace. Let cool before installing
brick liner.
You may purchase brick liner from your local retailer or see
Accessories, page 34.
CAUTION: Always handle brick panels with two
hands. Do not force brick panels into place. Excessive force will break brick panels.
1.Remove top and bottom louvers to allow access to door latches.
2.Remove screen, unlock door latches and open glass door. See
Removing/Replacing Glass Door, steps 1 and 2.
3.If installing brick liner in new fireplace, go to step 4. If installing brick liner in an existing fireplace, carefully remove logs,
lava rock, and ember material.
4.Remove three screws from deflector shield on the inside top
of firebox. Set shield and screws aside.
5.Install rear brick panel first. Rest bottom edge of panel on back
edge of grate (see Figure 38).
6.Install left side brick panel by sliding it between the grate and
the side of the firebox (see Figure 38).
7.Install the right brick panel using the same method described
in step 6 for left brick panel.
8.Replace deflector shield using screws removed in step 4.
9.Install logs, lava rock and glowing embers. See Installing Logs,Lava Rock and Glowing Embers, page 22.
10. Close glass door and lock latches on top and bottom of door
and replace screen. See Removing/Replacing Glass Door, steps
5 and 6.
11. Close top and bottom louvers.
Left Brick
Panel
111922-01C
Rear Brick
Panel
Figure 38 - Installing Rear, Left and Right Brick Panels
For more information, visit www.desatech.com
For more information, visit www.desatech.com
FIREPLACE INSTALLATION
22
Installing Logs, Lava Rock and Glowing Embers
Wall Switch Installation
FIREPLACE INSTALLATION
Continued
INSTALLING LOGS, LAVA ROCK AND
GLOWING EMBERS
Each log is marked with a number. These numbers will help you
identify the log when installing. It is very important to install these
logs exactly as instructed. Do not modify logs. Only use logs
supplied with fireplace.
Open louvers, remove screen, unlock door latches, and open glass
door. See Removing/Replacing Glass Door, steps 1 and 2 on page 21.
Install logs according to instructions for fireplace model numbers.
1.Place log #1 (left base log) onto pin on left side of burner as
shown in Figure 39.
2.Place log #2 (right base log) onto pin on right side of burner as
shown in Figure 39.
3.Place logs #3 (left front log) and log #4 (right front log) onto
pins as shown in Figure 40.
4.Place log #5 (right rear log) onto pins on right rear of burner
(see Figure 41). Rest log #6 (middle crossover log) on top of
log number 2 as shown in Figure 41.
5.Place back end of log #7 (left rear log) onto pin on left rear
burner and rest front onto log #1 as shown in Figure 42.
2
1
3
4
6.Rest log #8 (left crossover log) onto log #3 and rest log #9 (right
crossover log) onto logs #4 and #5 as shown in Figure 42.
7.Pull ember material apart into pieces no larger than a dime. Place
these pieces loosely and sparingly directly onto the exposed front
section of the burner (see Figure 44). This will create the glowing
ember appearance as the flame touches the ember material. Do
not block air slots by using too much ember material in one area.
It is not necessary to use all of the ember material provided.
NOTICE: Do not put lava rock on burner or under
burner. Placing lava rock on burner will cause performance problems.
8.Close glass door, lock door latches, replace screen, and close
louvers (see Removing/Replacing Glass Door, steps 5 through
7 on page 21).
WARNING: The glass door must be securely in
place before running this fireplace. Do not run this
fireplace if glass is missing or broken.
Figure 39 - Installing Logs
No. 1 and No. 2
5
Figure 40 - Installing Logs
No. 3 and No. 4
7
6
Figure 41 - Installing Logs
No. 5 and No. 6
Figure 42 - Installing Log No. 7
9
8
Figure 43 - Installing Logs No. 8 and No. 9
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Ember Material
Figure 44 - Placing Ember Material on Burner
WALL SWITCH INSTALLATION
The installation of a wall switch allows you to activate the gas
control valve and turn the fireplace on and off. The wall switch is
to be connected to the incoming 120 volt regular household wiring
that supplies the electricity to the fireplace. Refer to wiring
diagram below.
111922-01C
FIREPLACE INSTALLATION
Continued
FIREPLACE INSTALLATION
Optional Remote Control Installation
WIRING DIAGRAM
23
23
OPTIONAL REMOTE CONTROL
INSTALLATION (Model WRC)
Note:
If using optional wireless hand-held remote control, the wall
switch must be in the ON position to be operational. The remote control
then becomes the switching mechanism for fireplace operation.
1.Open lower louver panel.
2.The WRC model receiver does not require a battery. The re-
ceiver can be installed by first plugging the short extension
cord into the fireplace receptacle. Then plug the receiver unit
into the extension cord. Finally plug the ignition module plug
into the receiver unit (see Figure 45).
3.Activate the remote handset battery by removing the insulat-
ing tab on the back of the handset (see Figure 46). The battery
is included pre-installed.
4.Once the battery is activated the unit is ready to use.
5.Close lower louver panel.
WIRING DIAGRAM
Pilot
INCOMING MAIN
GASSUPPLY
EV1
EV2
GAS LINE TO
BURNER
Burner
Pilot Gas
Line
MV
TH
PV/MV
TR
GND
PV
IGN
24V AC
TRANSFORMER
120V AC
STEP DOWN
WALL SWITCH
(NOT SUPPLIED)
ON
WHITE
GREEN
BLACK
OPTIONAL
REMOTE
CONTROL
Fireplace
Receptacle
Remote Control
Receiver
Ignition
Extension Cord
Module Plug
Figure 45 - Installing the WRC Remote Receiver
Battery Cover
12 Volt Battery
Back of
Handset
Figure 46 - Installing Battery into Back of Handset
OFF
BLACK
WHITE
GREEN
ELECTRICAL RATING:
120v, 60Hz, 0.7A
INCOMING
120V AC
(FUSE BOX
OR BREAKER)
Pull to Remove
Insulation Tab
111922-01C
For more information, visit www.desatech.com
For more information, visit www.desatech.com
OPERATING FIREPLACE
24
For Your Safety Read Before Lighting
Lighting Instructions
To Turn Off Gas To Appliance
Optional Remote Operation
OPERATING FIREPLACE
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance is equipped with an ignition device which
automatically lights the pilot. Do not try to light the pilot
by hand.
B. BEFORE LIGHTING smell all around the appliance area
for gas. Be sure to smell next to the floor because some gas
is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch.
• Do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
C. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect
the appliance and to replace any part of the control system
and any gas control which has been under water.
LIGHTING
INSTRUCTIONS
NOTICE: During initial operation of new heater, burning logs will give off a paper-burning smell. Orange
flame will also be present. Open damper or window to
vent smell. This will only last a few hours.
1.STOP! Read the safety information, above.
2.Turn off all electric power to the appliance.
3.Turn wall switch to the OFF position.
4.Open lower louver panel.
5.Turn equipment shutoff valve clockwise
position (see Figure 47). Do not force.
6.Wait five (5) minutes to clear out any gas. Then smell for
gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information above. If you don’t smell
gas, go to the next step.
7.Turn equipment shutoff valve counterclockwise
the ON position. Do not force.
8.Close lower louver panel.
9.Turn on all electric power to the appliance.
10. Turn the wall switch to the ON position.
Clockwise
to the OFF
C-clockwise
to
11. Visually locate the pilot. The ignitor should begin to spark and
the main burner should ignite once flame appears at pilot.
• If lighting the appliance for the first time each season, it
may take several attempts before the supply gas can reach
the pilot and main burners.
• If the appliance will not stay lit after several attempts,
follow the instructions To Turn Off Gas To Appliance,
below, and call your service technician or gas supplier.
Equipment Shutoff Valve
Figure 47 - Turning Equipment Shutoff Valve to the OFF Position
Adjustment
Screw
TO TURN OFF GAS
TO APPLIANCE
1.Turn off the wall switch.
2.Turn off all electric power to the appliance if service is to
be performed.
3.Open lower louver panel.
4.Remove front hearth brick and control access panel.
5.Turn equipment shutoff valve clockwise
Clockwise
to OFF. Do
not force.
6.Close lower louver panel.
Pilot Burner
Figure 48 - Pilot
Sensing Rod
Ignitor
OPTIONAL REMOTE
OPERATION
Note:
The WRC receiver and hand-held remote control kit
must be purchased separately (see Accessories, page 34). Follow
installation instructions on page 23.
1.Turn equipment shutoff valve to ON position. You can now
turn the burner on and off with the hand-held remote control unit.
IMPORTANT:
hand-held remote control unit for up to 3 seconds to assure
proper operation.
2.Press the ON/OFF button to turn the burner on and off.
Be sure to press the ON/OFF buttons on the
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
Operating Optional Blower Accessory
OPERATING FIREPLACE
INSPECTING BURNERS
Pilot Assembly
Burner Flame Pattern
25
25
OPERATING FIREPLACE
Continued
OPERATING OPTIONAL
BLOWER ACCESSORY
Locate the blower controls by opening the lower louver panel on
the fireplace. Blower controls are located on the left side of the
switch bracket to the left just inside the louver panel.
The BK manual blower and the BKT thermostatically-controlled blower have an ON setting and an OFF setting. The
blower will only run when the switch is in the ON position. In the
OFF position, the blower will not operate.
Note for BKT Only:
thermostat (wall mounted or remote control) for the fireplace,
your fireplace and blower will not turn on and off at the same
time. The fireplace may run for several minutes before the
blower turns on. After the heater modulates to the pilot position,
the blower will continue to run. The blower will shut off after the
firebox temperature decreases.
The blower helps distribute heated air from the fireplace.
Periodically check the louvers of the firebox and remove any
dust, dirt, or other obstructions that will hinder the flow of air.
If you are using BKT blower with optional
INSPECTING BURNERS
Check pilot flame pattern and burner flame patterns often.
PILOT ASSEMBLY
The pilot assembly is factory preset for the proper flame. Alterations
may have occurred during shipping and handling. The pilot is
located on the back right hand side of the burner.
The flame must envelope 1/4" of top of the ignitor/sensor and
grounding stem.
If your pilot assembly does not meet these requirements:
• Turn the adjustment screw marked PILOT clockwise to decrease
or counterclockwise to increase the flame to proper size (see
Figure 47, page 24). Do not remove the adjustment screw.
• see Troubleshooting, pages 27 and 28
Pilot Burner
Sensing Rod
Ignitor/Sensor
Figure 49 - Correct Pilot Flame Pattern
BURNER FLAME PATTERN
Burner flames will be steady; not lifting or floating. Flame patterns
will be different from unit to unit and will vary depending on
installation type and weather conditions.
If the vent configuration is installed incorrectly, the flames will lift
or "ghost". This can be dangerous. Inspect the flames after installation to ensure proper installation and performance.
Figure 50 shows a typical flame pattern.
If burner flame pattern differs from that described:
• turn fireplace off (see To Turn Off Gas to Appliance, page 24)
• see Troubleshooting, pages 27 and 28
111922-01C
Figure 50 - Typical Flame Pattern
For more information, visit www.desatech.com
For more information, visit www.desatech.com
CLEANING AND MAINTENANCE
26
Glass Door
Pilot and Burners
Logs
Venting System
CLEANING AND
MAINTENANCE
WARNING: Turn off fireplace and let cool before
cleaning.
CAUTION: You must keep control areas, burners,
and circulating air passageways of fireplace clean.
Inspect these areas of fireplace before each use.
Have fireplace inspected yearly by a qualified service
person. Fireplace may need more frequent cleaning
due to excessive lint from carpeting, bedding material, pet hair, etc.
GLASS DOOR
WARNING: Handle glass door panel with care. Do
not strike, slam, or otherwise abuse glass. Do not
operate fireplace with the glass door removed,
cracked, or broken.
WARNING: Do not use abrasive cleaners as this
may damage glass. Use a nonabrasive household glass
cleaner to clean glass. Do not clean glass when hot.
Glass must be cleaned periodically. During start-up it is normal for
condensation to form on the inside of the glass causing lint, dust, and
other airborne particles to cling to the glass surface. During initial
start-up a slight film may form on the glass due to paint curing. The
glass should be cleaned several times with a non-ammonia, nonabrasive household cleaner and warm water after the first two weeks
of operation. Thereafter, clean the glass two or three times during
each heating season, depending on the usage and circumstances
present. Refer to Removing/Replacing Glass Door on page 21 of this
manual when removing glass door for cleaning.
WARNING: Only parts supplied by the manufacturer should be used when replacing broken or damaged glass door panel (see
29). This glass door panel is a complete unit. No
substitute materials may be used.
CAUTION: Wear gloves and safety glasses while
handling or removing broken glass. Do not remove if
glass is hot. Keep children and pets away from glass.
If glass has been broken, carefully remove glass door (see Removing/Replacing Glass Door, page 21). Vacuum all glass pieces with
a shop vac.
Replacement Parts
, page
CAUTION: Do not vacuum if pieces are hot.
Use only the tempered glass door replacement intended for this
fireplace (see Replacement Parts, page 29 for detail on ordering).
No substitutions may be made. See Removing/Replacing GlassDoor, page 21 for instructions for replacing glass door.
WARNING: Do not operate fireplace with the glass
door removed, cracked, or broken.
PILOT AND BURNERS
• Remove ember material before cleaning burners and replace
when cleaning is complete.
• Burner and controls should be cleaned with compressed air to
remove dust, dirt, or lint.
• Use a vacuum cleaner or small, soft bristled brush to remove
excess dust, dirt, or lint.
LOGS
• If you remove logs for cleaning, refer to Installing Logs, Lava
Rock, and Glowing Embers, page 22, to properly replace logs.
• Use a vacuum cleaner to remove any carbon buildup on logs.
• Replace log(s) if broken. See Replacement Parts on page 29.
• Replace ember material periodically as needed. See Replace-ment Parts on page 29.
VENTING SYSTEM
Conduct annual inspection of the venting system following these
guidelines:
1.Check areas of venting system that are exposed to the weather
for corrosion (rust spots or streaks and, in extreme cases, holes).
Have these items replaced immediately by a qualified service
person.
2.Remove the vent cap and shine a flashlight into the vent. Re-
move any foreign material.
3.Check for evidence of excessive condensation. Continuous
condensation can cause corrosion of caps, pipes, and fittings
and can be caused by having excessive lateral runs, too many
elbows, or exterior portions of the system being exposed to
cold weather.
4.Inspect joints to verify that no pipe section or fitting has been
disturbed and loosened. Check mechanical supports such as
wall straps for rigidity.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
TROUBLESHOOTING
27
27
TROUBLESHOOTING
Note:
For additional help, visit DESA’s
technical service web site at
www.desatech.com.
Note:
Before troubleshooting the system, make
sure the gas shutoff valve is ON.
OBSERVED PROBLEM
Ignitor will not spark or pilot will not light
WARNING: Turn off heater
and let cool before servicing. Only
a qualified service person should
service and repair heater.
The two most common causes of a malfunctioning gas appliance are:
1. Loose wiring connections
2. Construction debris clogging the pilot and/or gas control valve filter
POSSIBLE CAUSE
1. No gas supply, or shutoff valve is OFF
2. Air in gas line
3. Construction debris clogging pilot orifice
4. Low gas pressure
5. Kinked pilot line
6. Control valve knob is not opening
7. No power to unit or the ignition module
or power transformer is bad
8. Vent damper not fully open
REMEDY
1. Check to see if you have gas supply and
2. Repeat lighting procedure several times
3. Remove debris and dirt, inspect and
4. Contact your gas supplier to check
5. Have a qualified technician replace pi-
6. Replace control valve (Refer to Replace-
7. Check that main power is on and that all
8. Open vent damper until fully locked in
CAUTION: Never use a wire,
needle, or similar object to
clean pilot. This can damage
pilot unit.
that equipment shutoff valve is opened
to purge all air out of lines. If after repeated attempts appliance does not light,
call for qualified service and repair.
clean any other possible obstructions
pressure
lot line
ment Parts, page 29)
wire connections are made correctly to
the ignition model (see Wiring Diagram,
page 23). Check for 24 VAC at the secondary side of the transformer. If 24
VAC is present, and the module does not
oporate, have the module replaced otherwise have the transformer replaced.
OPEN position
Pilot will not stay lit
No gas to burner, although wall switch and
valve are set to the ON position
Frequent pilot outage
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
1. Loose wiring on ignitor wire to ignition
module and/or poor ground to ignition
module
2. Pilot flame too low to sense
1. Wall switch wires defective or too long
1. Pilot flame may be too low, causing
safety pilot to “drop out”
2. Improper venting or excessive blockage
1. Check wiring connection. Refer to wiring diagram (see Wiring Diagram,
page 23) and/or check ground wire to
ignition module
2. Clean and adjust pilot burner and check
gas supply and inlet pressure to unit
Note:
Have a qualified technician replace
pilot assembly if broken or corroded
1. Check electrical connections
1. Clean and adjust pilot flame for maximum
flame impingement on thermopile
2. Have the vent system inspected, including the termination cap. Remove any
restriction or obstruction
28
TROUBLESHOOTING
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the
gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
OBSERVED PROBLEM
Fireplace produces a clicking/ticking noise
just after burner is lit or shut off
Slight smoke or odor during initial operation
Gas odor even when control knob is in OFF
position
Gas odor during combustion
Glass soots
Dark residue on logs or inside of fireplace
POSSIBLE CAUSE
1. Metal expanding while heating or contracting while cooling
1. Residues from manufacturing processes
and logs curing
1. Gas leak. See Warning statement at
top of page
2. Control valve defective
1. Foreign matter between control valve
and burner
2. Gas leak. See Warning statement at
top of page
1. Flame impingement on logs
2. Debris around burner air mixer
1. Improper log placement
2. Air holes at burner inlet blocked
3. Burner flame holes blocked
4. Improper venting or excessive blockage
5. Excessive amounts of embers and pan
material
REMEDY
1. This is common with most fireplaces. If
noise is excessive, contact qualified service person
1. Problem will stop after a few hours of
operation
1. Locate and correct all leaks (see Check-ing Gas Connections, pages 19 and 20)
2. Replace control valve
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks (see Check-ing Gas Connections, pages 19 and 20)
1. Adjust the log set so that the flame does
not excessively impinge on it
2. Inspect the opening at the base of the
burner to see that it is NOT packed with
any type of material
1. Properly locate logs (see log placement
sections on page 22)
2. Clean out air holes at burner inlets. Periodically repeat as needed
3. Remove blockage
4. Have the vent system inspected, including the termination cap. Remove any
restrictions or obstruction
5. Clear excess embers until a minimum
gap of 1/2" remains under the grate
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
REPLACEMENT PARTS
SPECIFICATIONS
SERVICE HINTS
TECHNICAL SERVICE
29
29
REPLACEMENT PARTS
Note:
Use only original replacement parts. This will protect your
warranty coverage for parts replaced under warranty.
PARTS UNDER WARRANTY
Contact authorized retailers of this product. If they can not supply
original replacement part(s), call DESA’s Customer Service Department at 1-866-672-6040.
When calling DESA, have ready
• your name
• your address
• model and serial numbers of your fireplace
• how fireplace was malfunctioning
• type of gas used (propane/LP or natural gas)
• purchase date
Usually, we will ask you to return the part to the factory.
PARTS NOT UNDER WARRANTY
Contact authorized retailers of this product. If they can not supply
original replacement part(s), call DESA at 1-866-672-6040 for
referral information.
When calling DESA, have ready
• model number of your fireplace
• the replacement part number
SERVICE HINTS
When Gas Pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• fireplace will not produce specified heat
• propane/LP gas supply might be low (propane/LP units only)
You may feel your gas pressure is too low. If so, contact your local
gas supplier.
TECHNICAL SERVICE
You may have further questions about installation, operation, or
troubleshooting. If so, contact DESA’s Customer Service Department at 1-866-672-6040. When calling, please have your model and
serial numbers of your heater ready.
You can also visit DESA’s technical service web site at
www.desatech.com.
SPECIFICATIONS
(V)K42EN Series(V)K42EP Series
Btu28,000/40,000 Btu/hr24,000/34,000 Btu/hr
Gas TypeNaturalPropane/LP
IgnitionElectronicElectronic
Manifold Pressure3.5" w.c.10.0" w.c.
Minimum Inlet Supply Pressure5.5" w.c.11.0" w.c.
Dimension, Inches/mm (HxWxD)
Fireplace (Actual size of
firebox. Measurements do not40" x 48" x 23 1/2"40" x 48" x 23 1/2"
include nailing flanges or1016 x 1219 x 599 mm1016 x 1219 x 599 mm
standoffs).
Carton41" x 51" x 24"41" x 51" x 24"
1041 x 1295 x 610 mm1041 x 1295 x 610 mm
Weight, lbs/kg*
Fireplace197 lbs/89 kg197 lbs/89 kg
Shipping200 lbs/91 kg200 lbs/91 kg
111922-01C
For more information, visit www.desatech.com
For more information, visit www.desatech.com
30
ILLUSTRATED PARTS BREAKDOWN
Models (V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH
ILLUSTRATED PARTS
BREAKDOWN
MODELS
(V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH
10-8
10-6
10-4
10-1
10-7
10-2
10-5
15
14
10-3
16
10-9
11
6
7
8
1
4
9
3
20
18
17
12
21
13
19
5
For more information, visit www.desatech.com
For more information, visit www.desatech.com
2
111922-01C
PARTS LIST
MODELS
(V)K42N, (V)K42NH, (V)K42P, (V)K42PH
This list contains replaceable parts used in your fireplace. When
ordering parts, follow the instructions listed under ReplacementParts on page 29 of this manual.
BURNER ASSEMBLY FOR MODELS
(V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH
18
19
10
12
7
12
8
9
4
5
6
1
2
3
12
22
23
24
20
17
5
21
12
30
29
14
15
13
16
25
27
26
For more information, visit www.desatech.com
For more information, visit www.desatech.com
28
11
111922-01C
PARTS LIST
BURNER ASSEMBLY FOR MODELS
(V)K42N, (V)K42NH, (V)K42P, (V)K42PH
This list contains replaceable parts used in your fireplace. When
ordering parts, follow the instructions listed under ReplacementParts on page 29 of this manual.
KEYPART
NO.NUMBERDESCRIPTIONQTY.
1111920-01 Pan Assembly Burner1
2111311-02 Grate Base1
3111312-02 Burner Base Bottom1
426808Valve Bracket1
511107Screw, #10-32 x 1/4 PPH Zinc4
6104506-27 Burner Orifice (Natural Gas)1
104506-26 Burner Orifice (Propane/LP Gas)1
711102Screw, #8-32 x 3/8 PPH Zinc2
8108866-01 Pilot (Natural Gas)1
108866-02 Pilot (Propane/LP Gas)1
9111316-01 Pilot Bracket1
10111913-02 Burner Base Gasket1
11111310-02 Firebox Bottom1
1211165Screw, #10 x 5/8 HWH Zinc12
1326827Switch Bracket1
1414500Brass Fitting1
15111912-01 Tubing Assembly1
1614569Electronic Elec. Valve (Natural Gas)1
14570Electronic Elec. Valve (Propane/LP Gas)1
1714253Flex Gas Line1
1811186Screw, #8-32 x 1 Zinc2
19110286-01 Ignition Module, Synetek1
2011147Screw, #10-24 x 1/2 PPH MS Blk2
2114129Transformer, 24V Class 21
2217223Magnet2
2311201Nut, 8-32 Hex Zinc4
2423416Elect. Components Board1
2514120Spade 1/4 Female Connector4
2614134Wire, 18 GA Black5
2714126Wire, 16 GA TFFN/MTW Green1
2814115Spade Tongue Connector1
2914149Spade 1/4 F R/Angle Connector4
30108863-01 24" Supply Connect Plug1
Models (V)K42EN, (V)K42ENH, (V)K42EP, (V)K42EPH
PARTS LIST
33
33
111922-01C
For more information, visit www.desatech.com
For more information, visit www.desatech.com
34
ACCESSORIES
ACCESSORIES
NOTICE: All accessories may not be available for all
fireplace models.
Purchase these fireplace accessories from your local retailer. If they
can not supply these accessories, call DESA’s Sales Department at
1-866-672-6040. for information. You can also write to the address
listed on the back page of this manual.
LT42B - Rolled Louver Trim Kit - Brushed Brass
LT42P - Rolled Louver Trim Kit - Platinum
LT42PB - Rolled Louver Trim Kit - Polished Brass
DEFLECTION HOODS
(Not Shown)
HD42 - Hood - Black (2" Brow)
MANUAL BLOWER KIT - BK
Manual variable control blower accessory provides better heat distribution. Complete installation and operation instructions included in
this manual.
THERMOSTATICALLY- CONTROLLED
BLOWER KIT - BKT
Provides better heat distribution. Blower turns off and on automatically, as needed. Complete installation and operation instructions
included in this manual.
REMOTE CONTROL KIT - WRC SERIES
(Not Shown)
Standard ON/OFF electronic remote control kit.
WALL MOUNTED THERMOSTAT CONTROL
KIT - GWMT1 (Not Shown)
Allows easy wall access for thermostatic operation of your fireplace.
WALL MOUNTED ON/OFF SWITCH - GWMS2
(Not Shown)
Allows burner system to be turned on and off with a wall switch.
PERIMETER TRIM KIT
(Not Shown)
PT42 - Perimeter Trim Kit - Black
PT42B - Perimeter Trim Kit - Brushed Brass
PT42P - Perimeter Trim Kit - Platinum
PT42PB - Perimeter Trim Kit - Polished Brass
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01C
OWNER'S REGISTRATION FORM
In order to provide better customer service for this and future purchases, we recommend that you register your product with us.
You can register online at www.desatech.com. If access to our website is not available to you, please complete this Owner’s
Registration Form and mail to the address on the back of this owner’s manual. Please provide the following product information:
Brand:
Model:
Date Purchased:
Serial Number:
First Name: Last Name:
Address:
City:State:Zip: Country:
Home Phone: ( ) -
E-Mail:
Please answer the following questions to register your product with DESA:
2. If you bought this product yourself, did you plan to purchase this type of product before going into the store? ❍ Yes ❍ No
3. Who selected the product? ❍ Male ❍ Female ❍ Both
4. What is the population of your area? ❍ Under 10,000 ❍ 10,000 to 25,000 ❍ 25,000 to 50,000 ❍ 50,000 to 100,000
❍ 100,000 to 250,000 ❍ Over 250,000
5. What is your primary source of heat? ❍ Propane (LP Gas) ❍ Fuel Oil ❍ Wood ❍ Natural Gas ❍ Electric ❍ Other
6. How was the product installed? ❍ Professional Installer ❍ Self ❍ Other
7. Cost of product excluding sales tax? $___________________
8. Cost to install product? $____________________
9. Type of store where product was purchased? ❍ Hardware ❍ Propane Dealer ❍ Natural Gas/Utility Co. ❍ Home Center/Builder’s Supply
❍ Fireplace or Hearth Shop ❍ Farm Store ❍ Other
10. What motivated you to buy this product? ❍ Sudden Cold Weather ❍ Replace Older Model ❍ D.I.Y. Home Project
❍ Emergency Back-Up Heat ❍ Heater was on Sale ❍ Energy Savings/High Efficiency ❍ Construction Project ❍ Other
11. How did you learn about this product brand? ❍ Advertising ❍ Relative or Friend
12. Level of Education of Purchaser: ❍ Some High School ❍ Completed High School ❍ Completed College ❍ Completed Graduate School
13. Age of Purchaser: ❍ Under 20 ❍ 20 - 29 ❍ 30 - 39 ❍ 40 - 49 ❍ 50 - 59 ❍ 60 or Over
14. Buyer’s total annual household income: ❍ Under $15,000 ❍ $15,000 to $19,999 ❍ $20,000 to $34,999 ❍ $35,000 to $49,999
❍ $50,000 to $74,999 ❍ $75,000 to $99,999 ❍ $100,000 and Over
15. Store where product was purchased:
Name: ______________________________________
City: _______________________ State: __________
16. In choosing this product, how important were the following:
Availability
Price
Brand Name
Overall Quality
Heat Output
Made in USA
Warranty
Local Service
Value for Price
Prior Brand Experience
Controls Location
Thermostat, Remote, or Manual Operation
Ease of Operation
Special Features
Salesperson’s Recommendation
Friend/Relative’s Recommendation
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Portability
111922-01C
Quiet Operation
Not ImportantSomewhat ImportantVery Important
(Comfort Glow, Vanguard, etc.)
(EFP33PR, VTGH33NR, etc.)
Note:
Keep receipt for warranty verification.
7 or 9 digit number located on product or identification tag.
❍ Store Display ❍ Other ________________________
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
❍
35
35
36
TAPE
2701 Industrial Drive
P.O. Box 90004
Bowling Green, KY 42102-9004
Always specify model and serial numbers when communicating with the factory.
We reserve the right to amend these specifications at any time without notice. The only warranty applicable is our standard written warranty. We
make no other warranty, expressed or implied.
LIMITED WARRANTY
DIRECT-VENT FIREPLACE
DESA warrants this product to be free from defects in materials and components for two (2) years from the date of first purchase, provided that the
product has been properly installed, operated and maintained in accordance with all applicable instructions. To make a claim under this warranty
the Bill of Sale or cancelled check must be presented.
This warranty is extended only to the original retail purchaser. This warranty covers the cost of part(s) required to restore this heater to proper operating
condition and an allowance for labor when provided by a DESA Authorized Service Center. Warranty part(s) MUST be obtained through authorized
retailers of this product and/or DESA who will provide original factory replacement parts. Failure to use original factory replacement parts voids this
warranty. The heater MUST be installed by a qualified installer in accordance with all local codes and instructions furnished with the unit.
This warranty does not apply to parts that are not in original condition because of normal wear and tear, or parts that fail or become damaged as a
result of misuse, accidents, lack of proper maintenance or defects caused by improper installation. Travel, diagnostic cost, labor, transportation and
any and all such other costs related to repairing a defective heater will be the responsibility of the owner.
TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT; THIS
EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIES AND LIMITS THE DURATION OF ANY AND
ALL IMPLIED WARRANTIES, INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE
TO TWO (2) YEARS ON ALL COMPONENTS FROM THE DATE OF FIRST PURCHASE; AND DESA’S LIABILITY IS HEREBY LIMITED
TO THE PURCHASE PRICE OF THE PRODUCT AND DESA SHALL NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER
INCLUDING INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow a limitation on how long an implied warranty lasts or an exclusion or limitation of incidental or consequential damages,
so the above limitation on implied warranties, or exclusion or limitation on damages may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights that vary from state to state.
For information about this warranty write:
2701 Industrial Drive
P.O. Box 90004
Bowling Green, KY 42102-9004
www.desatech.com
111922 01
NOT A UPC
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111922-01
Rev. C
04/04
111922-01C