Desa CGD3924NT, CGD3930NT, CGD3018NT, CGB3924NT, CGB3930NT User Manual

BILTMORE SPLIT OAK, MOUNTAIN OAK,
PREMIUM AGED SPLIT OAK, AND
SMOKY MOUNTAIN OAK UNVENTED (VENT-FREE)
NATURAL GAS LOG HEATERS
VARIABLE MANUALLY-CONTROLLED MODELS ALSO DESIGNED CERTIFIED
AS VENTED DECORATIVE APPLIANCE
OWNER’S OPERATION AND INSTALLATION MANUAL
18", 24", and 30" Variable
Manually-Controlled Models
CGD3018N CY2718N CGD3924N CY3124N CGD3930N
Patent Pending
(Smoky Mountain Oak Model Shown)
CGD3924NT CGD3930NT CGD3018NT CGB3924NT CGB3930NT CCL3018NT CCL3924NT CCL3930NTA
18", 24" and 30"
Thermostatically-
Controlled Models
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury, or loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this or any other appliance.
WARNING: Improper installation, adjust­ment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installa­tion and operational procedures. For as­sistance or additional information con­sult a qualified installer, service agency, or the gas supplier.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas sup­plier, call the fire department.
— Installation and service must be per-
formed by a qualified installer, service agency, or the gas supplier.
WARNING: This appliance is for installa­tion only in a solid-fuel burning masonry or UL127 factory-built fireplace, or in an approved ventless firebox. It is design­certified for these installations in accor­dance with ANS Z21.11.2. Exception: Do not install this appliance in a factory-built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs.
WARNING: This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must be provided. Refer to
Air for Combustion and Ventilation
section on page 4 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufac­tured (mobile) home, where not prohibited by local codes.
This appliance is only for use with type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
VENT-FREE NATURAL GAS LOG HEATER
SAFETY INFORMATION
WARNINGS
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, oper­ate, or service this heater. Im­proper use of this heater can cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influence of alcohol, and those at high altitudes.
Natural Gas: Natural gas is odorless. An
odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this heater.
WARNING: Any change to this heater or its controls can be dangerous.
WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
WARNING: Do not use a blower insert, heat exchanger insert or other accessory not ap­proved for use with this heater.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects on the heater.
Heater base assembly becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater will remain hot for a time after shut­down. Allow surface to cool be­fore touching.
Carefully supervise young chil­dren when they are in the room with heater.
You must operate this heater with a fireplace screen in place. Make sure fireplace screen is closed before running heater.
Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do
not use any phone in your building
• immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier ,
call the fire department
3. This heater shall not be installed in a bedroom or bathroom, unless installed as a vented appliance (Variable Manu­ally-Controlled Models Only). See In-
stalling Damper Clamp Accessory for Vented Operation, page 10.
4. Before installing in a solid fuel burn­ing fireplace, the chimney flue and fire­box must be cleaned of soot, creosote, ashes, and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. Inspect chimney flue for damage. If damaged, operate heater with flue damper closed.
5. If fireplace has glass doors, never op­erate this heater with glass doors closed. If you operate heater with doors closed, heat buildup inside fireplace will cause glass to burst. Also if fireplace open­ing has vents at the bottom, you must open the vents before operating heater.
6. This log heater is designed to be smoke­less. If logs ever appear to smoke, turn off heater and call a qualified service person.
Note:
During initial operation, slight smoking could occur due to log curing and heater burning manufacturing residues.
7. T o prevent the creation of soot, follow the instructions in Cleaning and Main- tenance, page 21.
8. Before using furniture polish, wax, car­pet cleaner, or similar products, turn heater off. If heated, the vapors from these products may create a white pow­der residue within burner box or on adjacent walls or furniture.
9. This heater needs fresh, outside air ven­tilation to run properly . This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if not enough fresh air is available. See Air for Combustion and Ventilation, pages 4 through 6. If heater keeps shutting off, see T rouble- shooting, pages 22 through 24.
10. Do not run heater
• where flammable liquids or vapors
are used or stored
• under dusty conditions
11. Do not use this heater to cook food or burn paper or other objects.
12. Do not use heater if any part has been exposed to or under water. Immediately call a qualified service technician to in­spect the room heater and to replace any part of the control system and any gas control which has been under water.
13. Do not operate heater if any log is bro­ken. Do not operate heater if a log is chipped (dime-sized or larger).
For more information, visit www.desatech.com
2
107123
OWNER’S MANUAL
SAFETY INFORMATION
Continued
14. T urn heater of f and let cool before ser­vicing. Only a qualified service person should service and repair heater.
15. Operating heater above elevations of 4,500 feet could cause pilot outage.
PRODUCT IDENTIFICATION
Crossover Log
Front Log
Piezo Ignitor
Control Knob
Figure 1 - Vent-Free Gas Log Heater - Duel Burner (Logs May Vary by Model ­Smoky Mountain Oak Logs Shown)
Back Log
Burner
Middle Log
Base Grate
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code, ANS Z223.1, also known as NFPA 54*.
*Available from: American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Note:
Where listed vented decorative logs are required, thermostat models are not permitted.
UNPACKING
CAUTION: Do not remove the metal data plates from the grate assembly. The data plates contain important product information.
1. Remove logs and heater base assem­bly from carton. heater base assembly by burners. This could damage heater. Always handle base assembly by grate.
2. Remove all protective packaging ap­plied to logs and heater for shipment.
3. Check all items for any shipping dam­age. If damaged, promptly inform dealer where you bought heater.
Note:
Do not pick up
Back Log
Crossover Log
Front Log
Burner
Piezo Ignitor
Control Knob
Figure 2 - Vent-Free Gas Log Heater - Single Burner (Mountain Oak Logs Shown)
107123
3
For more information, visit www.desatech.com
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by realistic, dancing yellow flames. This heater is designed for vent-free operation with flue damper closed. It has been tested and ap­proved to ANS Z21.11.2 standard for unvented heaters. State and local codes in some areas prohibit the use of vent-free heaters. Non-thermostat models may also be operated as a vented decorative (ANS Z21.60) product by opening flue damper.
VENT-FREE NATURAL GAS LOG HEATER
PRODUCT FEATURES
Continued
SAFETY PILOT
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This heater has a piezo ignitor. This system requires no matches, batteries, or other sources to light heater.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ven­tilation air. Read the following in­structions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy effi­cient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper com­bustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide ad­equate fresh air for these appliances. This will insure proper venting of vented fuel­burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, NFPA 54/ANS Z223.1, Sec­tion 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 4 through 6 will
help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and win­dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is de­fined as construction where:
a. walls and ceilings exposed to the
outside atmosphere have a con­tinuous water vapor retarder with a rating of one perm (6 x 10 per pa-sec-m2) or less with open­ings gasketed or sealed
b. weather stripping has been
added on openable windows and doors
c. caulking or sealants are applied
to areas such as joints around window and door frames, be­tween sole plates and floors, be­tween wall-ceiling joints, be­tween wall panels, at penetra­tions for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide ad­ditional fresh air. See
From Outdoors
If your home does not meet all of the three criteria above, proceed to
termining Fresh-Air Flow for Heater Location
and
Ventilation Air
, page 6.
, page 5.
and
-11
kg
De-
Confined and Unconfined Space
The National Fuel Gas Code, ANS Z223.1 defines a confined space as a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggre­gate input rating of all appliances installed in that space and an unconfined space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed*, through openings not furnished with doors, are con­sidered a part of the unconfined space.
This heater shall not be installed in a con­fined space or unusually tight construction unless provisions are provided for adequate combustion and ventilation air.
* Adjoining rooms are communicating only if there are doorless passageways or ventila­tion grills between them.
For more information, visit www.desatech.com
4
107123
OWNER’S MANUAL
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height = _________________ cu. ft. (volume of space)
Example:
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.
____________(volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)
Example:
3. Add the Btu/Hr of all fuel burning appliances in the space. Vent-free heater ______________ Btu/Hr Gas water heater* ______________ Btu/Hr Gas furnace ______________ Btu/Hr Vented gas heater ______________ Btu/Hr Gas fireplace logs ______________ Btu/Hr Other gas appliances* + ______________ Btu/Hr Total = ______________ Btu/Hr * Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
_________________ Btu/Hr (maximum the space can support) _________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-
ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6. C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
2560 cu. ft. (volume of space) ÷ 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)
Example:
Gas water heater 40,000 Btu/Hr Vent-free heater + 39,000 Btu/Hr Total = 79,000 Btu/Hr
51,200 Btu/Hr (maximum the space can support) 79,000 Btu/Hr (actual amount of Btu/Hr used)
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the
107123
National Fuel Gas Code, ANS Z223.1, Section 5.3
5
For more information, visit www.desatech.com
or applicable local codes.
Continued
VENT-FREE NATURAL GAS LOG HEATER
AIR FOR COMBUSTION AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro­vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 3). You can also remove door into adjoining room (see op­tion 3, Figure 3). Follow the National Fuel
Gas Code, NFPA 54/ANS Z223.1, Section
5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
WARNING: Rework work­sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two per­manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
IMPORTANT:
inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Do not provide openings for
Ventilation
Grills
Into Adjoining
Room,
Option 1
Figure 3 - Ventilation Air from Inside Building
Outlet Air
Inlet Air
Figure 4 - Ventilation Air from Outdoors
Or
Remove Door into Adjoining
Room, Option
3
12"
Outlet Air
Inlet Air
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilated Attic
Ventilated
Crawl Space
12"
To Attic
To
Crawl
Space
For more information, visit www.desatech.com
6
107123
OWNER’S MANUAL
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your pri­mary heating system. Do not in­stall this heater as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circu­late the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualified ser­vice person must install heater. Follow all local codes.
NOTICE: State or local codes may only allow operation of this appli­ance in a vented configuration. Check your state or local codes.
WARNING: Before installing in a solid fuel burning fireplace, the chimney flue and firebox must be cleaned of soot, creosote, ashes, and loose paint by a quali­fied chimney cleaner. Creosote will ignite if highly heated. A dirty chimney flue may create and dis­tribute soot within the house. In­spect chimney flue for damage. If damaged, operate heater with flue damper closed.
WARNING: Never install the
heater
• in a bedroom or bathroom un­less installed as a vented ap­pliance (Variable Manually­Controlled Models Only) (see page 10)
• in a recreational vehicle
• where curtains, furniture, clothing, or other flammable objects are less than 42 inches from the front, top, or sides of the heater
• in high traffic areas
• in windy or drafty areas
CAUTION: This heater cre­ates warm air currents. These currents move heat to wall sur­faces next to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as to­bacco smoke, aromatic candles, cleaning fluids, oil or kerosene lamps, etc) in the air exist, may discolor walls.
IMPORTANT:
ture to the air. Although this is beneficial, installing heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Com- bustion and Ventilation, pages 4 through 6.
Vent-free heaters add mois-
CHECK GAS TYPE
Use only natural gas. If your gas supply is not natural gas, do not install heater. Call dealer where you bought heater for proper type heater.
INSTALLATION AND CLEARANCES (Vent-Free Operation Only)
WARNING: Maintain the mini­mum clearances. If you can, pro­vide greater clearances from floor, ceiling, and adjoining wall.
MINIMUM FIREPLACE CLEARANCE
TO COMBUSTIBLE MATERIALS
Log Size Side Wall Ceiling
18", 24", 30" 16" 42"
LOG SIZING REQUIREMENTS
Minimum Firebox Size Log Front Rear* Size Height Depth Width Width
18" 17" 14" 24" 20" 24" 17" 14" 28" 21" 30" 17" 14" 34" 24"
*Measured at 14" Depth
Carefully follow the instructions below. This will ensure safe installation into a masonry, UL127-listed manufactured fireplace, or cer­tified vent-free firebox.
WARNING: Seal any fresh air vents or ash clean-out doors lo­cated on floor or wall of fireplace. If not, drafting may cause pilot outage or sooting. Use a heat­resistant sealant. Do not seal chimney flue damper.
107123
Continued
7
For more information, visit www.desatech.com
VENT-FREE NATURAL GAS LOG HEATER
INSTALLATION
Continued
Minimum Clearances For Side Combustible Material, Side Wall, and Ceiling
A. Clearances from the side of the fire-
place cabinet to any combustible ma­terial and wall should follow diagram in Figure 5.
Example:
shelf, etc. is made of combustible ma­terial and protrudes 3 1/2" from the wall. This combustible material must be 4" from the side of the fireplace opening (see Figure 5).
Note:
into a manufactured firebox, follow firebox manufacturer’s instructions for minimum clearances to combustible materials.
B. Clearances from the top of the fireplace
opening to the ceiling should not be less than 42 inches.
The face of a mantel, book-
When installing your gas logs
Minimum Noncombustible Material Clearances
If Not Using Mantel
Note:
If using a mantel, proceed to If Using
Mantel. If not using a mantel, follow the
information below. You must have noncombustible material(s)
above the fireplace opening. Noncombus­tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" and 30" models only). See Figure 6 for minimum clearances.
IMPORTANT:
minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 10.
If you cannot meet these
If Using Mantel
You must have noncombustible material(s) above the fireplace opening. Noncombus­tible materials (such as slate, marble, tile, etc.) must be at least 1/2 inch thick. With sheet metal, you must have noncombustible material behind it. Noncombustible mate­rial must extend at least 8 inches up (for all models). If noncombustible material is less than 12", you must install the fireplace hood accessory (24" and 30" models only). Even if noncombustible material is more than 12", you may need the hood accessory to deflect heat away from your mantel shelf. See Figure 6 and Figures 7 and 8 on page 9 for minimum clearances.
IMPORTANT:
minimum clearances, you must operate heater with chimney flue damper open. Go to Installing Damper Clamp Accessory for Vented Operation, page 10.
If you cannot meet these
Example
*
*Minimum 16 inches from Side Wall
Figure 5 - Minimum Clearance for Com­bustible to Wall
NOTICE: Manual control heaters may be used as a vented product. If so, you must always run heater with chimney flue damper open. If running heater with damper open, noncombustible material above fireplace opening is not needed. Go to
Installing Damper Clamp Accessory for Vented Operation
, page 10.
Noncombustible Requirements for Material Distance (A) Safe Installation
12" or more Noncombustible material okay. Between 8" and 12" 24" or 30" Models: Install fireplace hood acces-
sory (GA6050, GA6052, or GA6053 see
ries,
page 27).
18" Model: Noncombustible material okay.
Less than 8" Noncombustible material must be extended to at
least 8". See cannot extend material, you must operate heater with flue damper open.
Heat Resistant Material
(A)
Between 8" and 12",
Accesso-
above. If you
Figure 6 - Heat Resistant Material (Slate, Marble, Tile, etc.) Above Fireplace
For more information, visit www.desatech.com
8
107123
OWNER’S MANUAL
Hearth
5" Min.
Combustible Material
INSTALLATION
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible mate­rial clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clear­ances listed in Figure 7, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 7).
Determining Minimum Mantel Clearance When Using a Hood
If minimum clearances in Figure 7 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clear­ances shown in Figure 8 when using hood.
NOTICE: Surface temperatures of adjacent walls and mantels be­come hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these tempera­tures meet the requirement of the national product standard. Fol­low all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the minimum clear­ances shown, you must do one of the following:
• operate the logs only with the
flue damper open
• raise the mantel to an accept-
able height
• remove the mantel
Mantel Shelf
"
/2
(A)
18" 20" 22" 24"
12" 8" 8" 14" 16
Distances to Underside of Mantel
3
/4" 20"
Underside of Mantel Shelf
Top of Fireplace Opening
Minimum Non­Combustible Material
10" 8" 6"
1
2
Minimum Non­Combustible Material Height
Figure 7 - Minimum Mantel Clearances Without Using Hood
8" Min.
Mantel Shelf
12" 15" 18"
Distances to Underside of Mantel
20"
Minimum Non­Combustible Material
12" 10" 8" 6"
1
"
/2
2
Hood
(GA6050, GA6052,
(GA6050, GA6052)
and GA6053)
Figure 8 - Minimum Mantel Clearances When Using Hood
All minimum distances are in inches
Log Set
24"/30" Models 18" Model
Underside of Mantel Shelf
All minimum distances are in inches
Log Set
18", 24", 30"
All Models
Models
Top of Fireplace Opening
FLOOR CLEARANCES
A. If installing appliance on the floor level,
you must maintain the minimum distance of 14" to combustibles (see Figure 9).
B. If combustible materials are less than
14" to the fireplace, you must install appliance at least 5" above the combus­tible flooring (see Figure 10).
107123
Combustible
14" Min.
Noncombustible Material
Material
Figure 9 - Minimum Fireplace Clearances If Installed at Floor Level
9
For more information, visit www.desatech.com
Figure 10 - Minimum Fireplace Clearances Above Combustible Flooring
Continued
VENT-FREE NATURAL GAS LOG HEATER
INSTALLATION
Continued
INSTALLING DAMPER CLAMP ACCESSORY FOR VENTED OPERATION
Note:
When used as a vented heater, appli­ance must be installed only in a solid-fuel burning fireplace with a working flue and constructed of noncombustible material.
If your heater is a manually-controlled model, you may use this heater as a vented product. There are three reasons for operat­ing your heater in the vented mode.
1. The fireplace does not meet the clear-
ance to combustibles requirements for vent-free operation.
2. State or local codes do not permit vent-
free operation.
3. You prefer vented operation. If reasons number 1 or 2 above apply to you,
you must permanently open chimney flue damper. You must install the damper clamp accessory (to order, see Accessories, page
27). This will insure vented operation (see Figure 11). The damper clamp will keep damper open. Installation instructions are included with clamp accessory.
See chart below for minimum permanent flue opening you must provide. Attach damper clamp so the minimum permanent flue opening will be maintained at all times.
Figure 11 - Attaching Damper Clamp
Damper Clamp
Damper
Masonry Fireplace
Damper
Damper Clamp
Damper
Manufactured Fireplace
Area of Various Standard
Round Flues
Diameter (ins.) Area (sq. ins.)
5" 20 sq. inches 6" 29 sq. inches 7" 39 sq. inches 8" 51 sq. inches
Chimney Minimum Permanent
Height (ft.) Flue Opening (sq. ins.)
6' to 15' 39 sq. inches
15' to 30' 29 sq. inches
For more information, visit www.desatech.com
10
107123
OWNER’S MANUAL
INSTALLATION
Continued
INSTALLING HEATER BASE ASSEMBLY
CAUTION: Do not remove the
metal data plates attached to the heater base assembly. The data plates contain important warranty information.
WARNING: You must secure
this heater to fireplace floor. If not, heater will move when you adjust controls. Moving heater may cause a gas leak or log mis­placement.
WARNING: If installing in a
sunken fireplace, special care is needed. You must raise the fire­place floor to allow access to heater control panel. This will in­sure adequate air flow and guard against sooting. Raise fireplace floor with noncombustible mate­rial. Make sure material is secure.
CAUTION: Do not pick up
heater base assembly by the burner. This could damage heater. Only handle base assem­bly by grates.
IMPORTANT:
ers are level. If heater is not level, heater will not work properly. For thermostat models, avoid damage to thermostat bulb. Avoid nicks or sharp bends in thermostat bulb wire. Keep thermostat bulb in mounting bracket.
Make sure the heater burn-
Installation Items Needed
• hardware package (provided with heater)
• approved flexible gas hose (not provided) (if allowed by local codes)
• sealant resistant to propane (propane/LP) gas, not provided
• electric drill with 3/16" drill bit
• flathead screwdriver
1. Apply pipe joint sealant lightly to male
threads of the fitting to be threaded into gas regulator. Connect approved flex­ible gas hose to gas regulator of heater (see Figure 12).
IMPORTANT:
wrench when connecting flexible gas hose.
2. Locate masonry screws in hardware
package.
3. Position heater base assembly in fire-
place.
4. Place logs in their proper position on heater
base, see Installing Logs on pages 14 through 17.
5. Center heater base and logs front-to-
back and side-to-side in fireplace.
6. Carefully remove logs without moving
heater base.
7. Mark screw locations through holes in
mounting brackets (see Figure 13 or
14). If installing in a brick-bottom fire­place, mark screw locations in mortar joint of bricks.
8. Remove heater base from fireplace.
9. Drill holes at marked locations using
3/16" drill bit.
10. Attach base assembly to fireplace floor
using two masonry screws (in hardware package) (see Figures 13 or 14).
Hold gas regulator with
Flexible Gas Hose (if allowed by local codes)
Fitting
Figure 12 - Attaching Flexible Gas Hose to Heater Gas Regulator
Figure 13 - Attaching Base Assembly to Fireplace Floor - Dual Burner Model
Figure 14 - Attaching Base Assembly to Fireplace Floor - Single Burner Model
Heater Gas Regulator
Masonry Screw
Mounting Bracket
Masonry Screw
Mounting Bracket
107123
11
Continued
For more information, visit www.desatech.com
VENT-FREE NATURAL GAS LOG HEATER
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 1/2" NPT (National Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualified ser­vice person must connect heater to gas supply. Follow all local codes.
Installation Items Needed
Before installing heater, make sure you have the items listed below.
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench * An CSA/AGA design-certified equip-
ment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connec­tion. Purchase the optional CSA/AGA de­sign-certified equipment shutoff valve from your dealer. See Accessories, page 27.
WARNING: Never connect heater to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
CAUTION: Use only new, black iron or steel pipe. Inter­nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.
Installation must include an equipment shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 15).
IMPORTANT:
Install equipment shutoff valve in an accessible location. The equip­ment valve is for turning on or shutting off the gas to the appliance.
Apply pipe joint sealant lightly to male
We recommend that you install a sediment trap in supply line as shown in Figure 15. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sedi­ment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater
may not run properly. threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas
CAUTION: Use pipe joint seal-
piping and/or fittings.
ant that is resistant to liquid pe­troleum (LP) gas.
CSA/AGA Design­Certified Equipment
From Gas Meter (5" W.C.** to
10.5" W.C. Pressure)
Tee Joint Pipe
Nipple Cap
Sediment Trap
Figure 15 - Gas Connection
Shutoff Valve With 1/8" NPT Tap*
3" Minimum
Approved Flexible Gas Hose (if allowed by local codes)
Gas Regulator
* Purchase the optional CSA/AGA design-certified equipment shutoff valve from your dealer. See Accessories, page 27.
** Minimum inlet pressure for purpose of input adjustment.
For more information, visit www.desatech.com
12
107123
OWNER’S MANUAL
ON
POSITION
OFF
POSITION
INSTALLATION
Continued
CHECKING GAS CONNECTIONS
WARNING: Test all gas pip­ing and connections for leaks after installing or servicing. Cor­rect all leaks at once.
WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.
Pressure Testing Gas Supply Piping system
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect appliance with its appliance main gas valve (control valve) and equip­ment shutoff valve from gas supply pip­ing system. Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was con­nected.
3. Pressurize supply piping system by ei­ther using compressed air or opening main gas valve located on or near gas meter.
4. Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles form­ing show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve to gas supply. Check re­connected fittings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig­ure 16).
2. Pressurize supply piping system by ei­ther using compressed air or opening main gas valve located on or near gas meter.
3. Check all joints from gas meter to equipment shutoff valve (see Figure
17). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Equipment Shutoff Valve
Figure 16 - Equipment Shutoff Valve
Gas Meter
Figure 17 - Checking Gas Joints
Open
Closed
Pressure Testing Heater Gas Connections
1. Open equipment shutoff valve (see Fig­ure 16).
2. Open main gas valve located on or near gas meter.
3. Make sure control knob of heater is in the OFF position.
4. Check all joints from equipment shutoff valve to control valve (see Figure 17). Apply mixture of liquid soap and wa­ter to gas joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Light heater (see Operating Heater, pages 18 and 19 [manually-controlled models] or pages 19 and 20 [thermo­statically-controlled models]). Check all other internal joints for leaks.
7. Turn off heater (see To Turn Off Gas to Appliance, page 19 [manually-con­trolled models] or page 20 [thermostati­cally-controlled models]).
Equipment Shutoff Valve
Thermostat Gas Valve or Control Valve Location
107123
13
Continued
For more information, visit www.desatech.com