WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing
property damage, personal injury, or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire
department.
— Installation and service must be performed by a quali-
fied installer, service agency, or the gas supplier.
Save this manual for future reference.
For more information, visit www.desatech.com
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installation
and operational procedures. For assistance or additional information consult a qualified installer, service
agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses
air (oxygen) from the room in which it is installed. Provisions for adequate combustion and ventilation air must
be provided. Refer to Air for Combustion and Ventilation
section on page 5 of this manual.
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where
not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
TABLE OF CONTENTS
Safety Information ............................................... 3
Local Codes ........................................................ 4
Warranty Information ...........................Back Cover
6-01A
11389
23
27
SAFETY INFORMATION
WARNING: This product contains and/or generates chemicals
known to the state of California
to cause cancer or birth defects,
or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate, or service this fireplace.
Improper use of this fireplace
can cause serious injury or death
from burns, fire, explosion,
electrical shock, and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning:
monoxide poisoning resemble the flu, with head
aches, dizziness, or nausea. If you have these signs,
the heater may not be working properly. Get fresh air at once! Have heater serviced. Some people
are more affected by carbon monoxide than others.
These include pregnant women, people with heart
or lung disease or anemia, those under the influence
of alcohol, and those at high altitudes.
Natural and Propane/LP Gas: Natural and pro-
pane/LP gases are odorless. An odor-making agent
is added to the gas. The odor helps you detect a gas
leak. However, the odor added to the gas can fade.
Gas may be present even though no odor exists.
Make certain you read and understand all warn
ings. Keep this manual for reference. It is your
guide to safe and proper operation of this heater.
Early signs of carbon
WARNING: Do not allow fans
to blow directly into the fireplace.
Avoid any drafts that alter burner
flame patterns. Ceiling fans can
create drafts that alter burner
flame patterns. Altered burner
patterns can cause sooting.
Due to high temperatures, the
appliance should be located out
of traffic and away from furniture
and draperies.
Do not place clothing or other
flammable material on or near the
appliance. Never place any objects in the fireplace or on logs.
Fireplace front and screen become very hot when running fire
place. Keep children and adults
-
away from hot surfaces to avoid
burns or clothing ignition. Fire
place will remain hot for a time
after shutdown. Allow surfaces
to cool before touching.
Carefully supervise young children when they are in the room
with fireplace.
You must operate this fireplace
with a fireplace screen in place.
-
Make sure fireplace screen is
closed before running heater.
-
-
WARNING: Any change to
this heater or its controls can
be dangerous.
Keep the appliance area clear
and free from combustible materials, gasoline, and other flam
mable vapors and liquids.
WARNING: Do not use a
blower insert, heat exchanger
insert, or other accessory not approved for use with this heater.
6-01A3
11389
www.desatech.com
-
SAFETY INFORMATION
Continued
1. This appliance is only for use with the type
of gas indicated on the rating plate. This ap
pliance is not convertible for use with other
gases.
2. Do not place propane/LP supply tank(s) in
side any structure. Locate propane/LP supply
tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use
any phone in your building
• immediately call your gas supplier from a
neighborʼs phone. Follow the gas supplierʼs
instructions
• if you cannot reach your gas supplier, call
the fire department
4. This fireplace shall not be installed in a bed
room or bathroom.
5. Do not use this fireplace as a wood-burning
fireplace. Use only the logs provided with the
fireplace.
6. Do not add extra logs or ornaments such as
pine cones, vermiculite, or rock wool. Using
these added items can cause sooting. Do not
add lava rock around base. Rock and debris
could fall into the control area of fireplace.
7. This fireplace is designed to be smokeless.
If logs ever appear to smoke, turn off fire
place and call a qualified service person.
Note: During initial operation, slight smoking
could occur due to log curing and fireplace
burning manufacturing residues.
8. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance
page 21.
9. Before using furniture polish, wax, carpet
cleaner, or similar products, turn heater off.
If heated, the vapors from these products may
create a white powder residue within burner
box or on adjacent walls or furniture.
10. This fireplace needs fresh air ventilation to run
properly. This fireplace has an Oxygen Deple
tion Sensing (ODS) safety shutoff system. The
ODS shuts down the fireplace if not enough
fresh air is available. See Air for Combustion and Ventilation, page 5. If fireplace keeps
shutting off, see Troubleshooting, page 23.
11. Do not run fireplace
• where flammable liquids or vapors are used
or stored.
• under dusty conditions.
-
12. Do not use this fireplace to cook food or to
burn paper or other solid fuels.
13. Do not use fireplace if any part has been under
water. Immediately call a qualified service
technician to inspect the room fireplace and
to replace any part of the control system and
any gas control which has been under water.
14. Turn off and unplug fireplace and let cool
before servicing. Only a qualified service
person should service and repair fireplace.
15. Operating fireplace above elevations of 4,500
feet could cause pilot outage.
16. Do not operate fireplace if any log is broken.
Do not operate fireplace if a log is chipped
(dime-sized or larger).
17. To prevent performance problems, do not use
propane/LP fuel tank of less than 100 lbs.
capacity (propane/LP units only).
18. Prov id e adequate clearances aro un d air
openings.
LOCAL CODES
Install and use fireplace with care. Follow all local
codes. In the absence of local codes, use the lat
est edition of The National Fuel Gas Code, ANSI
Z223.1/NFPA 54
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
,
*.
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
UNPACKING
1. Remove and fireplace from carton.
2. Remove all protective packaging applied to
fireplace for shipment.
3. Make sure your fireplace includes one hard
ware packet.
4. Check fireplace for any shipping damage. If
fireplace is damaged, promptly inform dealer
where you bought fireplace.
-
-
4
www.desatech.com
11389
6-01A
PRODUCT
IDENTIFICATION
Fireplace
Cabinet
Brick
Liner
Logs
Heater Controls
(Inside Door)
Figure 1 - Vent-Free Propane/LP Gas
Screen
Compact Fireplace
PRODUCT FEATURES
SAFETY PILOT
This fireplace has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free room
fireplaces. The ODS/pilot shuts off the fireplace if
there is not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system
requires no matches, batteries, or other sources
to light fireplace.
AIR FOR COMBUSTION
AND VENTILATION
WARNING: This heater shall
not be installed in a confined
space or unusually tight con
struction unless provisions are
provided for adequate combus
tion and ventilation air. Read the
following instructions to insure
proper fresh air for this and
other fuel-burning appliances
in your home.
Todayʼs homes are built more energy efficient than
ever. New materials, increased insulation, and
new construction methods help reduce heat loss
in homes. Home owners weather strip and caulk
around windows and doors to keep the cold air out
and the warm air in. During heating months, home
owners want their homes as airtight as possible.
While it is good to make your home energy effi
cient, your home needs to breathe. Fresh air must
enter your home. All fuel-burning appliances need
fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel
burning appliances draw air from the house to
operate. You must provide adequate fresh air for
these appliances. This will insure proper venting
of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54 Section 5.3, Air
for Combustion and Ventilation.
All spaces in homes fall into one of the three fol
lowing ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
The information on pages 5 through 7 will help
you classify your space and provide adequate
ventilation.
-
-
-
-
6-01A5
11389
www.desatech.com
AIR FOR COMBUSTION
AND VENTILATION
Continued
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion and
ventilation. However, in buildings of unusually
tight construction, you must provide additional
fresh air.
Unusually tight construction is defined as
construction where:
a. walls and ceilings exposed to the out
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and floors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical, and gas lines,
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh
air. See Ventilation Air From Outdoors,
page 7.
If your home does not meet all of the three
criteria above, proceed to Determining
Fresh-Air Flow For Fireplace Location
below.
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1 defines
a confined space as a space whose volume is less
than 50 cubic feet per 1,000 Btu per hour (4.8 m
per kw) of the aggregate input rating of all appliances installed in that space and an unconfining
space as a space whose volume is not less than
50 cubic feet per 1,000 Btu per hour (4.8 m3 per
kw) of the aggregate input rating of all appliances
installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if
there are doorless
-11
kg per pa-sec-m2) or
DETERMINING FRESH-AIR FLOW
FOR FIREPLACE LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a
confined or unconfined space.
Space: Includes the room in which you will
install heater plus any adjoining rooms with door
less passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length x
width x height).
-
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft.
(volume of space)
If additional ventilation to adjoining room is
supplied with grills or openings, add the volume
of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
__________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2560 cu. ft. (volume of space) x 20 =
51,200 (maximum Btu/Hr the space can support)
3. Add the Btu/Hr of all fuel burning appliances in
the space.
Vent-free fireplace ___________
Gas water heater* ___________
Gas furnace ___________
Vented gas heater ___________
Gas fireplace logs ___________
,
Other gas appliances* + ___________
Total = ___________
* Do not include direct-vent gas appliances. Di
rect-vent draws combustion air from the outdoors
and vents to the outdoors.
3
Example:
Gas water heater
Vent-free fireplace + ________
Total = ________
4. Compare the maximum Btu/Hr the space can
support with the actual amount of Btu/Hr used.
_________
_________
Example: 51,200 Btu/Hr (maximum the space
56,000 Btu/Hr (actual amount of
Btu/Hr (maximum the space can support)
Btu/Hr (actual amount of Btu/Hr used)
can support)
Btu/Hr used)
30,000
__________ Btu/Hr
26,000
56,000
-
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
Btu/Hr
-
Btu/Hr
Btu/Hr
6
www.desatech.com
11389
6-01A
AIR FOR COMBUSTION
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills
into Adjoining
Room,
Option 1
Outlet
Air
Ventilated
Attic
Outlet
A
ir
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To Attic
To
Crawl
Space
AND VENTILATION
Continued
The space in the above example is a confined space
because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide
additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoin-
ing room. If the extra space provides an unconfined
space, remove door to adjoining room or add
ventilation grills between rooms. See Ventilation
Air From Inside Building.
B. Vent room directly to the outdoors. See Ventila
tion Air From Outdoors.
C. Install a lower Btu/Hr fireplace, if lower Btu/Hr
size makes room unconfined.
If the actual Btu/Hr used is less than the maximum
Btu/Hr the space can support,
confined space. You will need no additional fresh
air ventilation.
WARNING: If the area in
which the heater may be operated is smaller than that defined
as an unconfined space or if the
building is of unusually tight
construction, provide adequate
combustion and ventilation air
by one of the methods described
in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes.
the space is an un-
-
Figure 2 - Ventilation Air from Inside
Building Shown with Optional Mantel
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or
ducts. You must provide two permanent openings:
one within 12” of the ceiling and one within 12”
of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These
spaces include attics and crawl spaces. Follow the
National Fuel Gas Code ANSI Z223.1/NFPA 54,
Section 5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
IMPORTANT:
Do not provide openings for inlet
or outlet air into attic if attic has a thermostatcontrolled power vent. Heated air entering the attic
will activate the power vent.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining un
confined space. When ventilating to an adjoining
unconfined space, you must provide two perma
nent openings: one within 12” of the ceiling and
one within 12” of the floor on the wall connecting
the two spaces (see options 1 and 2, Figure 2). You
can also remove door into adjoining room (see
option 3, Figure 2). Follow the National Fuel Gas
Code ANSI Z223.1/NFPA 54, Section 5.3, Air for
Combustion and Ventilation for required size of
ventilation grills or ducts.
11389
6-01A7
-
-
Figure 3 - Ventilation Air from Outdoors
Shown with Optional Mantel
www.desatech.com
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your pri
mary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
WARNING: A qualified service person must install fire
place. Follow all local codes.
Note: Your Comfort Glow fireplace is designed
to be used in zero clearance installations. Wall or
framing material can be placed directly against
any exterior surface of your fireplace, except
where standoff spacers are integrally attached.
If standoff spacers are attached to your fireplace,
these spacers can be placed directly against wall
or framing materials.
Use the dimensions shown for rough openings to
create the easiest installation (see Built-In Fireplace Installation, page 9).
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP)
for your unit. If your gas supply is not correct, do
not install fireplace. Call dealer where you bought
fireplace for proper type fireplace.
WARNING: This appliance
is equipped for (natural or pro
pane/LP) gas. Field conversion
is not permitted.
LOCATING FIREPLACE
WARNING: Maintain the
minimum clearances shown in
Figure 4 and 5, page 9. If you can,
provide greater clearances from
floor, ceiling, and joining wall.
-
-
-
You can recess firebox into the wall. You can also
position fireplace in the optional cabinet mantels.
IMPORTANT: Only use optional cabinet mantels
specified in this manual. Purchase the optional mantel from your dealer (see Accessories, page 32).
WARNING: Never install the
fireplace
• in a bedroom or a bathroom
• in a recreational vehicle
• where curtains, furniture,
clothing, or other flammable
objects are less than 42 inches
from the front, top, or sides of
the fireplace
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
CAUTION: This fireplace creates warm air currents. These
currents move heat to wall surfaces next to fireplace. Installing
fireplace next to vinyl or cloth
wall coverings or operating
fireplace where impurities (such
as, but not limited to, tobacco
smoke, aromatic candles, clean-
-
ing fluids, oil or kerosene lamps,
etc.) in the air exist, may discolor
walls or cause odors.
IMPORTANT: Vent-free fireplaces add moisture
to the air. Although this is beneficial, installing fire
place in rooms without enough ventilation air may
cause mildew to form from too much moisture. See
Air for Combustion and Ventilation
, page 5.
CAUTION: If you install the
fireplace in a home garage
•
fireplace pilot and burner must be
at least 18 inches above floor.
• locate fireplace where moving
vehicle will not hit it.
For convenience and efficiency, install fireplace
• where there is easy access for operation, inspec
tion, and service.
• in coldest part of room.
-
-
8
www.desatech.com
11389
6-01A
INSTALLATION
36
5
/8
"
25
7
/8
"
51
3
/
4
"
26
7
/8
"
26
7
/
8
"
26
7
/
8
"
3/4" Off
The Floor
Minimum
10
1
/
2
"
6"
Minimum
From
Sides Of
Fireplace
Left
Side
CEILING
42" Minimum
FLOOR
Right
Side
Top Of
Mantel Can
Be Flush
With Wall
Left
Side
CEILING
Right
Side
42"
Minimum
Continued
An optional blower kit is available from your
dealer. See Accessories, page 32. If planning to use
blower, locate fireplace near an electrical outlet.
Note: When installing fireplace directly on carpet
ing, tile or other combustible material, other than
wood flooring, the fireplace shall be installed on a
metal or wood panel extending the full width and
depth of the fireplace.
0" Minimum Clearance To Top Surface Of
Carpeting, Tile Or Other Combustible Material
Figure 4 - Mounting Clearances As
Viewed From Front of Fireplace Shown
Built In The Wall
BUILT-IN FIREPLACE
INSTALLATION
Built-in installation of this fireplace involves installing fireplace into a framed-in enclosure. This
makes the front of fireplace flush with wall. Follow
the instructions below to install the fireplace in this
manner. If installing a built-in mantel above the
fireplace, you must follow the clearances shown
in Figure 9, page 11. If using for built-in installation off of the floor, follow clearances shown
in Figure 4.
Actual Framing
Height 26" 26
Front Width 26
Depth 9 1/2" 10 1/2"
Bottom 3/4" 3/4"
1. Frame in rough opening. Use dimensions shown
in Figure 6 for the rough opening.
If installing in a corner, use dimensions shown
in Figure 7 for the rough opening. The height
1
/8" which is the same as the wall opening
is 26
above.
2. An optional blower accessory is available (see
Accessories, page 32). There are two options
for connecting blower to electrical source.
Option one: Have a licensed electrician install
a properly grounded, three-prong 120-volt
electrical outlet at fireplace location. Locate
outlet inside the framed enclosure. Blower
power cord will plug into this outlet.
3
/4" 26 7/8"
7
/8"
0" Minimum Clearance To Top Surface Of
Carpeting, Tile Or Other Combustible Material
Figure 5 - Mounting Clearances As
Viewed From Front of Fireplace Shown
11389
with Optional Mantel
6-01A9
Figure 6 - Rough Opening for Installing
in Wall
Figure 7 - Rough Opening for Installing
in Corner
www.desatech.com
INSTALLATION
Continued
Option two: Have a licensed electrician con-
nect blower to electrical source at junction box
inside fireplace.
If using option one, have electrical outlet in
stalled at this time. If using option two, do not
connect blower to electrical source at junction
box until step 6.
3. Install gas piping to fireplace location. This
installation includes an approved flexible gas
line (if allowed by local codes) after the equip
ment shutoff valve. The flexible gas line must
be the last item installed on the gas piping.
4. Carefully set fireplace in front of rough opening
with back of fireplace inside wall opening.
5. Attach flexible gas line to fireplace gas regula
tor. See Connecting Fireplace to Gas Supply,
page 16.
6. If the optional blower has been installed con
nect blower to electrical source.
Option one: Route blower electrical cord
through side or rear access door of fireplace.
Plug electrical cord into electrical outlet.
Option two: Have a licensed electrician con-
nect blower to electrical source at junction box
inside fireplace.
7. Bend four nailing flanges on outer casing with
pliers (see Figure 8).
8. Attach fireplace to wall studs using nails
or wood screws through holes in nailing
flange.
9. Check all gas connections for leaks. See
Checking Gas Connections, page 17.
IMPORTANT: When finishing your firebox,
combustible materials such as wall board, gyp
sum board, sheet rock, drywall, plywood, etc.
may be butted up next to the sides and top of
the firebox. Combustible materials should never
overlap the firebox front facing. Firebox should
not be placed on top of carpet or other kinds of
fibrous material.
WARNING: Do not allow any
combustible materials to overlap
the firebox front facing.
IMPORTANT: Noncombustible materials such as
brick, tile, etc. may overlap the front facing, but
should never cover any necessary openings like
louvered slots.
WARNING: Do not allow noncombustible materials to cover
any necessary openings like
louvered slots.
-
WARNING: Never modify or
cover the louvered slots on the
front of the firebox.
-
WARNING: Use only noncombustible mortar or adhe
sives when overlapping the front
facing with noncombustible
facing material.
-
Nails or
-
Wood
Screws
Figure 8 - Attaching Fireplace to Wall
Mantel Clearances for Built-In Installation
NOTICE: Surface temperatures
-
Studs
of adjacent walls and mantels
become hot during operation.
Walls and mantels above the
firebox may become hot to
the touch. If installed properly,
these temperatures meet the
requirement of the national
product standard. Follow all
minimum clearances shown in
this manual.
If placing mantel above built-in fireplace, you must
meet minimum clearance between mantel shelf and
top of fireplace opening.
-
Nailing
Flanges
10
www.desatech.com
11389
6-01A
INSTALLATION
13"
16"
19"
21"
2 1/2"
6"
8"
10"
Minimum NonCombustible
Material
Continued
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• raise the mantel to an acceptable height
• remove the mantel
Note: All vertical
measurements
are from top
of fireplace
opening to
bottom of
mantel shelf.
Mantel Shelf
6. While firmly holding edges of trim together,
tighten both set screws on the adjusting plate
with slotted screwdriver.
7. Repeat steps 1 through 6 for other corner.
8. Set trim assembly aside for later installation.
Slot
Slot
Shim
Top
Trim
Mitered
Edge
Side
Trim
Set Screws
Adjusting
Plate
Figure 10 - Assembling Trim
OPTIONAL MANTEL INSTALLATION
Note: Refer to instructions provided with the mantel for assembly instructions. Refer to instructions
below for system installation. If using blower accessory (see Accessories, page 32), see installation
instructions on pages 12 through 15.
1. Choose location for fireplace and install gas
supply line.
2. Remove screen from fireplace by removing
screws in each end of screen rod (see Figure
11). Hold screen rod cover while removing
five hex head screws underneath hood (see
Figure 12). Carefully lift and pull out hood
(see Figure 13, page 12).
REMOVING BRICK LINER
RETAINER
1. Using Phillips screw driver, remove 2 screws
2. Remove brick liner retainers and discard.
ASSEMBLING TRIM
(Trim shipped with mantel)
1. Remove packaging from three pieces of trim.
2. Locate two adjusting plates with set screws,
3. Align shim under adjusting plate as shown in
4. Slide one end of adjusting plate/shim in slot
5. Slide other end of adjusting plate/shim in slot
11389
Figure 9 - Minimum Mantel Clearances
for Built-In Installation
attaching brick liner retainers to vertical
sides.
Replace 2 screws into vertical sides.
and two shims in the hardware packet.
Figure 10.
on mitered edge of top trim (see Figure 10).
on mitered edge of side trim (see Figure 10).
6-01A11
www.desatech.com
Figure 11 - Removing Screen
Hood
Screen Rod
Cover
Screw
Figure 12 - Removing Hood Screws
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.