Desa CF26PT User Manual

VENT-FREE PROPANE/LP GAS
BAY FRONT FIREPLACE
OWNER’S OPERATION AND INSTALLATION MANUAL
CF26PT
15,000 to 26,000 Btu/Hr
with Thermostat
A U T O
O F F
O N
Patent Pending
Fireplace Shown
With Optional
Bay Front Mantel
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result caus­ing property damage, personal injury, or loss of life.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by
a qualified installer, service agency, or the gas supplier.
WARNING: Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for correct installation and operational procedures. For assistance or additional infor­mation consult a qualified in­staller, service agency, or the gas supplier.
WARNING: This is an unvented gas-fired heater. It uses air (oxy­gen) from the room in which it is installed. Provisions for ad­equate combustion and ventila­tion air must be provided. Refer to
Air for Combustion and Ven-
tilation
section on page 4 of this
manual.
This appliance may be installed in an aftermarket*, permanently located, manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
*Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
CF26PT
VENT-FREE PROPANE/LP BAY FRONT FIREPLACE
SAFETY INFORMATION
WARNINGS
WARNING ICON G 001
IMPORTANT: Read this Owner’s Manual carefully and completely before trying to assemble, operate, or service this fireplace. Improper use of this fireplace can cause se­rious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the flu, with headaches, dizziness, or nausea. If you have these signs, the fireplace may not be working properly. Get fresh air at once! Have fireplace serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease or anemia, those under the influ­ence of alcohol, and those at high altitudes.
Propane/LP Gas: Propane/LP gas is odor-
less. An odor-making agent is added to pro­pane/LP gas. The odor helps you detect a propane/LP gas leak. However, the odor added to propane/LP gas can fade. Propane/LP gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this fireplace.
WARNING: Any change to this fireplace or its controls can be dangerous.
WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. Ceiling fans can create drafts that alter burner flame patterns. Altered burner patterns can cause sooting.
WARNING: Do not use a blower insert, heat exchanger insert, or other accessory not ap­proved for use with this fireplace.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Do not place clothing or other flammable material on or near the appliance. Never place any objects in the fireplace.
Fireplace front and screen becomes very hot when running fireplace. Keep children and adults away from hot surfaces to avoid burns or cloth­ing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young chil­dren when they are in the room with fireplace.
You must operate this fireplace with a fireplace screen in place. Make sure fireplace screen is in place before running fireplace.
Keep the appliance area clear and free from combustible materials, gasoline, and other flammable va­pors and liquids.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/ LP supply tank(s) outdoors.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do
not use any phone in your building
• immediately call your gas supplier
from a neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier,
call the fire department
4. This fireplace shall not be installed in a bedroom or bathroom.
5. Do not use this fireplace as a wood­burning fireplace. Use only the logs provided with the fireplace.
6. Do not add extra logs or ornaments such as pine cones, vermiculite, or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could fall into the control area of fireplace.
7. This fireplace is designed to be smoke­less. If logs ever appear to smoke, turn off fireplace and call a qualified service per-
Note:
son. smoking could occur due to log curing and fireplace burning manufacturing residues.
8. T o prevent the creation of soot, follow the instructions in Cleaning and Main- tenance, page 17.
9. Before using furniture polish, wax, car­pet cleaner, or similar products, turn heater off. If heated, the vapors from these products may create a white pow­der residue within burner box or on adjacent walls or furniture.
10. This fireplace needs fresh air ventila­tion to run properly . This fireplace has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the fireplace if not enough fresh air is available. See Air for Combus- tion and Ventilation, pages 4 through
6. If fireplace keeps shutting off, see Troubleshooting, pages 18 through 20.
11. Do not run fireplace
• where flammable liquids or vapors
are used or stored.
• under dusty conditions.
12. Do not use this fireplace to cook food or burn paper or other objects.
13. Do not use fireplace if any part has been under water. Immediately call a quali­fied service technician to inspect the room fireplace and to replace any part of the control system and any gas con­trol which has been under water.
14. Turn off and unplug fireplace and let cool before servicing. Only a qualified service person should service and re­pair fireplace.
During initial operation, slight
For more information, visit www.desatech.com
2
107187
OWNER’S MANUAL
SAFETY INFORMATION
Continued
15. Operating fireplace above elevations of 4,500 feet could cause pilot outage.
16. Do not operate fireplace if any log is broken. Do not operate fireplace if a log is chipped (dime-sized or larger).
17. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lbs. capacity.
18. Provide adequate clearances around air openings.
PRODUCT IDENTIFICATION
Fireplace Cabinet
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI Z223.1/NFPA 54*.
*Available from: American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
UNPACKING
1. Remove and fireplace from carton.
2. Remove all protective packaging ap­plied to fireplace for shipment.
3. Make sure your fireplace includes one hardware packet.
4. Check fireplace for any shipping damage. If fireplace is damaged, promptly inform dealer where you bought fireplace.
Brick Liner
Logs
A U T
O
O F F
ON
Heater Controls (Inside Door)
Figure 1 - Vent-Free Propane/LP Gas Compact Fireplace
PRODUCT FEATURES
Screen
SAFETY PILOT
This fireplace has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff sys­tem. The ODS/pilot is a required feature for vent-free room fireplaces. The ODS/pilot shuts off the fireplace if there is not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This sys­tem requires no matches, batteries, or other sources to light fireplace.
107187
3
For more information, visit www.desatech.com
CF26PT
VENT-FREE PROPANE/LP BAY FRONT FIREPLACE
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall not be installed in a confined space or unusually tight construction unless provisions are provided for adequate combustion and ven­tilation air. Read the following in­structions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy effi­cient than ever. New materials, increased insulation, and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. During heating months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs to breathe. Fresh air must enter your home. All fuel-burning appliances need fresh air for proper com­bustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Sec­tion 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space The information on pages 4 through 6 will
help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and win­dows may provide enough fresh air for combustion and ventilation. However, in buildings of unusually tight construction, you must provide additional fresh air.
Unusually tight construction is de­fined as construction where:
a. walls and ceilings exposed to the
outside atmosphere have a con­tinuous water vapor retarder with a rating of one perm (6 x 10 per pa-sec-m2) or less with open­ings gasketed or sealed
b. weather stripping has been
added on openable windows and doors
c. caulking or sealants are applied
to areas such as joints around window and door frames, be­tween sole plates and floors, be­tween wall-ceiling joints, be­tween wall panels, at penetra­tions for plumbing, electrical, and gas lines, and at other openings.
If your home meets all of the three criteria above, you must provide ad­ditional fresh air. See
From Outdoors
If your home does not meet all of the three criteria above, proceed to
mining Fresh-Air Flow For Fireplace Location,
and
page 5
, page 6
.
Ventilation Air
.
-11
and
Deter-
kg
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/ NFPA 54 defines a confined space as a
space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appli­ances installed in that space and an unconfining space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are in­stalled*, through openings not furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless passageways or ventila­tion grills between them.
For more information, visit www.desatech.com
4
107187
OWNER’S MANUAL
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or unconfined space. Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length x width x height). Length x Width x Height = ____________________ cu. ft. (volume of space)
Example:
If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
_________________ (volume of space) x 20 = (Maximum Btu/Hr the space can support)
Example:
3. Add the Btu/Hr of all fuel burning appliances in the space. Vent-free fireplace _________________Btu/Hr Gas water heater* _________________Btu/Hr Gas furnace _________________Btu/Hr Vented gas heater _________________Btu/Hr Gas fireplace logs _________________Btu/Hr Other gas appliances* + _________________Btu/Hr Total = _________________Btu/Hr * Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.
___________ Btu/Hr (maximum the space can support) ___________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A.
Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.
B.
Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.
C. Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined. If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
2560 cu. ft. (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)
Example:
Gas water heater 30,000 Btu/Hr Vent-free fireplace + 26,000 Btu/Hr Total = 56,000 Btu/Hr
51,200 Btu/Hr (maximum the space can support)
56,000 Btu/Hr (actual amount of Btu/Hr used)
WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the
107187
National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3
5
For more information, visit www.desatech.com
or applicable local codes.
Continued
CF26PT
VENT-FREE PROPANE/LP BAY FRONT FIREPLACE
AIR FOR COMBUSTION AND VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro­vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op­tion 3, Figure 2). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section
5.3, Air for Combustion and Ventilation for
required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two per­manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the
National Fuel Gas Code, ANSI Z223.1/ NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventila-
tion grills or ducts.
IMPORTANT:
inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.
Do not provide openings for
Ventilation
Grills
into Adjoining
Room,
Option 1
Figure 2 - Ventilation Air from Inside Building Shown with Optional Mantel
Outlet Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors Shown with Optional Mantel
Or
Remove Door into Adjoining
Room,
Option 3
Outlet Air
Inlet Air
Into Adjoining Room,
12"
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your pri­mary heati n g system. Do not in­stall this heater as your primary heat source. If you have a central heating system, you may run systems circulating blower while using heater. This will help circu­late the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
12"
Ventilation Grills
Option 2
Ventilated Attic
To Attic
To
Crawl
Space
Ventilated
Crawl Space
WARNING: A qualified ser­vice person must install fireplace. Follow all local codes.
Note:
Your Comfort Glow fireplace is de­signed to be used in zero clearance installa­tions. Wall or framing material can be placed directly against any exterior surface of your fireplace, except where standoff spacers are integrally attached. If standoff spacers are attached to your fireplace, these spacers can be placed directly against wall or framing materials.
Use the dimensions shown for rough open­ings to create the easiest installation (see Built-In Fireplace Installation, page 8).
For more information, visit www.desatech.com
6
107187
INSTALLATION
Continued
CHECK GAS TYPE
Use only propane/LP gas. If your gas supply is not propane/LP, do not install fireplace. Call dealer where you bought fireplace for proper type fireplace.
INSTALLATION ITEMS
Before installing fireplace, make sure you have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• sediment trap
• tee joint
• pipe wrench
• test gauge connection* * A CSA design-certified equipment shutoff
valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Pur­chase the optional CSA design-certified equipment shutoff valve from your dealer. See Accessories, page 26.
Note:
If desired, purchase a four-sided brass trim kit for built-in installations. See Acces- sories, page 26.
LOCATING FIREPLACE
WARNING: Maintain the mini-
mum clearances shown in Fig­ures 4 and 5. If you can, provide greater clearances from floor, ceiling, and joining wall.
You can recess firebox into the wall. You can also position fireplace in the optional cabinet mantels. optional cabinet mantels specified in this manual. Purchase the optional mantel from your dealer (see Accessories, page 26).
IMPORTANT:
Only use
OWNER’S MANUAL
WARNING: Never install the
fireplace
in a bedroom or a bathroom
in a recreational vehicle
where curtains, furniture,
clothing, or other flammable objects are less than 42 inches from the front, top, or sides of the fireplace
as a fireplace insert
in high traffic areas
in windy or drafty areas
CAUTION: This fireplace cre­ates warm air currents. These cur­rents move heat to wall surfaces next to fireplace. Installing fire­place next to vinyl or cloth wall coverings or operating fireplace where impurities (such as, but not limited to, tobacco smoke, aromatic candles, cleaning flu­ids, oil or kerosene lamps, etc.) in the air exist, may discolor walls.
I
MPORTANT:
ture to the air. Although this is beneficial, installing fireplace in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combus- tion and Ventilation, pages 4 through 6.
CAUTION: If you install the fireplace in a home garage
fireplace pilot and burner must
be at least 18 inches above floor.
locate fireplace where moving
vehicle will not hit it.
For convenience and efficiency, install fire­place
• where there is easy access for operation, inspection, and service.
• in coldest part of room.
An optional blower kit is available from your dealer. See Accessories, page 26. If planning to use blower, locate fireplace near an electrical outlet.
Vent-free fireplaces add mois-
Note:
When installing fireplace directly on carpeting, tile or other combustible mate­rial, other than wood flooring, the fireplace shall be installed on a metal or wood panel extending the full width and depth of th fireplace.
CEILING
42" Minimum
6" Minimum From Sides Of Fireplace
Left Side
FLOOR
Figure 4 - Mounting Clearances As Viewed From Front of Fireplace Shown Built In The Wall
Top Of Mantel Can Be Flush With Wall
Left Side
Figure 5- Mounting Clearances As Viewed From Front of Fireplace Shown with Optional Mantel
0" Minimum Clearance To Top Surface Of Carpeting, Tile Or Other Combustible Material
CEILING
0" Minimum Clearance To Top Surface Of Carpeting, Tile Or Other Combustible Material
42"
Minimum
Right Side
Right Side
107187
Continued
7
For more information, visit www.desatech.com
CF26PT
VENT-FREE PROPANE/LP BAY FRONT FIREPLACE
INSTALLATION
Continued
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves installing fireplace into a framed-in enclo­sure. This makes the front of fireplace flush with wall. Follow the instructions below to install the fireplace in this manner. If install­ing a built-in mantel above the fireplace, you must follow the clearances shown in Figure 9, page 9. If using for built-in instal­lation off of the floor, follow clearances shown in Figure 4, page 7.
Actual Framing
Height 26" 26
Front Width 26
Depth 9
Bottom
3
/4" 26 7/8"
1
/2" 10 1/2"
3/4" 3/4"
1. Frame in rough opening. Use dimen­sions shown in Figure 6 for the rough opening.
If installing in a corner, use dimensions shown in Figure 7 for the rough open­ing. The height is 26 1/8" which is the same as the wall opening above.
1
10
/
2
"
7
/
8
"
26
7
26
/
8
"
Figure 6 - Rough Opening for Installing in Wall
7
/8"
3/4" Off The Floor Minimum
2. An optional blower accessory is avail­able (see Accessories, page 26). There are two options for connecting blower to electrical source.
Option one: Have a licensed electri-
cian install a properly grounded, three­prong 120-volt electrical outlet at fire­place location. Locate outlet inside the framed enclosure. Blower power cord will plug into this outlet.
Option two: Have a licensed electri-
cian connect blower to electrical source at junction box inside fireplace.
If using option one, have electrical out­let installed at this time. If using option two, do not connect blower to electrical source at junction box until step 6.
3. Install gas piping to fireplace location. This installation includes an approved flexible gas line (if allowed by local codes) after the equipment shutoff valve. The flexible gas line must be the last item installed on the gas piping.
4. Carefully set fireplace in front of rough opening with back of fireplace inside wall opening.
5. Attach flexible gas line to fireplace gas regulator. See Connecting Fir eplace to Gas Supply, page 13.
6. If the optional blower has been installed connect blower to electrical source.
Option one: Route blower electrical
cord through side or rear access door of fireplace. Plug electrical cord into electrical outlet.
Option two: Have a licensed electrician
connect blower to electrical source at junction box inside fireplace.
7. Bend four nailing flanges on outer cas­ing with pliers (see Figure 8).
8. Attach fireplace to wall studs using nails or wood screws through holes in nailing flange.
9. Check all gas connections for leaks. See Checking Gas Connections, page 14.
IMPORTANT:
When finishing your fire­box, combustible materials such as wall board, gypsum board, sheet rock, drywall, plywood, etc. may be butted up next to the sides and top of the firebox. Combustible materials should never overlap the firebox front facing. Firebox should not be placed on top of carpet or other kinds of fibrous material.
WARNING: Do not allow any combustible materials to overlap the firebox front facing.
IMPORTANT:
Noncombustible materials such as brick, tile, etc. may overlap the front facing, but should never cover any neces­sary openings like louvered slots.
WARNING: Do not allow non­combustible materials to cover any necessary openings like lou­vered slots.
WARNING: Never modify or cover the louvered slots on the front of the firebox.
WARNING: Use only noncom­bustible mortar or adhesives when overlapping the front fac­ing with noncombustible facing material.
5
36
/
8
"
25
7
/
8
"
26
3
/
4
"
51
7
/
8
"
Nails or Wood Screws
Figure 7 - Rough Opening for Installing in Corner
Figure 8 - Attaching Fireplace to Wall Studs
For more information, visit www.desatech.com
N
8
Flanges
107187
A
Nailing
U T O
O F F
O
OWNER’S MANUAL
INSTALLATION
Continued
Mantel Clearances for Built-In Installation
If placing mantel above built-in fireplace, you must meet minimum clearance between mantel shelf and top of fireplace opening.
NOTICE: Surface temperatures of adjacent walls and mantels be­come hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these tempera­tures meet the requirement of the national product standard. Fol­low all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the minimum clearances shown, you must do one of the following:
raise the mantel to an accept­able height
remove the mantel
Note:
All vertical measurements are from top of fireplace opening to bottom of mantel shelf.
Minimum Non­Combustible Material
Figure 9 - Minimum Mantel Clearances for Built-In Installation
10" 8" 6" 2 1/2"
Mantel Shelf
13"
16"
19"
21"
REMOVING BRICK LINER RETAINER
1. Using Phillips screw driver, remove 2 screws attaching brick liner retainers to vertical sides.
2. Remove brick liner retainers and discard. Replace 2 screws into vertical sides.
ASSEMBLING BRASS TRIM
(Brass trim shipped with mantel)
1. Remove packaging from three pieces of brass trim.
2. Locate two adjusting plates with set screws, and two shims in the hardware packet.
3. Align shim under adjusting plate as shown in Figure 10.
4. Slide one end of adjusting plate/shim in slot on mitered edge of top brass trim (see Figure 10).
5. Slide other end of adjusting plate/shim in slot on mitered edge of side brass trim (see Figure 10).
6. While firmly holding edges of brass trim together, tighten both set screws on the adjusting plate with slotted screwdriver.
7. Repeat steps 1 through 6 for other corner.
8. Set brass assembly aside for later in­stallation.
Top Brass Trim
Side Brass Trim
Slot
Slot
Shim
Mitered Edge
Set Screws
Adjusting Plate
Figure 10 - Assembling Brass Trim
OPTIONAL MANTEL INSTALLATION
Note:
Refer to instructions provided with the mantel for assembly instructions. Refer to instructions below for system installa­tion. If using blower accessory (see Acces- sories, page 26), see installation instruc­tions on pages 10 and 11.
1.Choose location for fireplace and in-
stall gas supply line.
2. Remove screen from fireplace by remov­ing screws in each end of screen rod (see Figure 11). Hold screen rod cover while removing five hex head screws under­neath hood (see Figure 12). Carefully lift and pull out hood (see Figure 13).
3. Assemble brass trim kit. See Assem- bling Brass Trim, column 2.
4. Place brass trim on the shoulder screws located on the side and top of the fireplace. Firmly snap the brass trim over the shoul­der screws on fireplace (see Figure 14, page 10).
5. Place mantel base close to wall in de­sired fireplace location.
6. Install gas line. See Connecting T o Gas Supply, page 12
7. Carefully place fireplace on mantel base and center left to right. Check for gas leaks. See Checking Gas Connections, page 14.
8. Refer to instructions provided with the mantel for permanent attachment to wall.
9. Slide mantel around fireplace. Be care­ful not to damage wall or mantel.
Figure 11 - Removing Screen
Hood
Screen Rod Cover
Screw
Figure 12 - Removing Hood Screws
Mantel Screw Location
107187
Figure 13 - Removing Hood
Continued
9
For more information, visit www.desatech.com
Loading...
+ 21 hidden pages