WARNING: If the information in this manual is not
followed exactly, a fire or explosion may result
causing property damage, personal injury, or
loss of life.
— Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of
this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call
the fire department.
— Installation and service must be performed by
a qualified installer, service agency, or the gas
AUTO
OFF
ON
Fireplace Shown With Optional
Bay Front Mantel
WARNING: Improper installation, adjustment, alteration, service, or maintenance
can cause injury or property damage.
Refer to this manual for correct installation and operational procedures. For assistance or additional information consult a qualified installer, service agency,
or the gas supplier.
WARNING: This is an unvented gasfired heater. It uses air (oxygen) from the
room in which it is installed. Provisions
for adequate combustion and ventilation air must be provided. Refer to
Combustion and Ventilation
section on
page 4 of this manual.
Air for
This appliance may be installed in an aftermarket,* permanently located, manufactured
(mobile) home, where not prohibited by local codes.
This appliance is only for use with type of gas indicated on the rating plate. This appliance
is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Save this manual for future reference.
Save this manual for future reference.
TABLE OF CONTENTS
SAFETY INFORMATION
2
TABLE OF CONTENTS
SAFETY INFORMATION ............................................................ 2
WARNING: This product contains and/or generates
chemicals known to the State of California to cause
cancer or birth defects, or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and
completely before trying to assemble, operate, or service this fireplace. Improper use of this fireplace can
cause serious injury or death from burns, fire, explosion, electrical shock, and carbon monoxide poisoning.
DANGER: Carbon monoxide poisoning may lead
to death!
Carbon Monoxide Poisoning: Early signs of carbon monoxide
poisoning resemble the flu, with headaches, dizziness, or nausea. If
you have these signs, the fireplace may not be working properly.
Get fresh air at once! Have fireplace serviced. Some people are
more affected by carbon monoxide than others. These include
pregnant women, people with heart or lung disease or anemia, those
under the influence of alcohol, and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/LP gases are
odorless. An odor-making agent is added to the gas. The odor helps
you detect a gas leak. However, the odor added to the gas can fade. Gas
may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this
manual for reference. It is your guide to safe and proper operation
of this fireplace.
WARNING: Any change to this fireplace or its
controls can be dangerous.
WARNING: Do not allow fans to blow directly into
the fireplace. Avoid any drafts that alter burner flame
patterns. Ceiling fans can create drafts that alter
burner flame patterns. Altered burner patterns can
cause sooting.
WARNING: Do not use a blower insert, heat
exchanger insert, or other accessory not approved
for use with this fireplace.
Due to high temperatures, the appliance should be
located out of traffic and away from furniture and
draperies.
Do not place clothing or other flammable material on
or near the appliance. Never place any objects in the
fireplace.
Fireplace front and screen becomes very hot when
running fireplace. Keep children and adults away
from hot surfaces to avoid burns or clothing ignition.
Fireplace will remain hot for a time after shutdown.
Allow surfaces to cool before touching.
Carefully supervise young children when they are in
the room with fireplace.
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111410-01C
AUT
O
OFF
ON
SAFETY INFORMATION
Continued
SAFETY INFORMATION
PRODUCT IDENTIFICATION
3
3
You must operate this fireplace with a fireplace screen
in place. Make sure fireplace screen is in place before
running fireplace.
Keep the appliance area clear and free from combustible materials, gasoline, and other flammable vapors
and liquids.
1.This appliance is only for use with the type of gas indicated on
the rating plate. This appliance is not convertible for use with
other gases.
2.Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3.If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not use any phone in
your building
• immediately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions
• if you cannot reach your gas supplier, call the fire department
4.This fireplace shall not be installed in a bedroom or bathroom.
5.Do not use this fireplace as a wood-burning fireplace. Use only
the logs provided with the fireplace.
6.Do not add extra logs or ornaments such as pine cones, vermiculite, or rock wool. Using these added items can cause sooting. Do not add lava rock around base. Rock and debris could
fall into the control area of fireplace.
7.This fireplace is designed to be smokeless. If logs ever appear
to smoke, turn off fireplace and call a qualified service person.
Note:
During initial operation, slight smoking could occur due
to log curing and fireplace burning manufacturing residues.
8.To prevent the creation of soot, follow the instructions in Clean-ing and Maintenance, pages 17 and 18.
9.Before using furniture polish, wax, carpet cleaner, or similar
products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or
on adjacent walls or furniture.
10. This fireplace needs fresh air ventilation to run properly . This
fireplace has an Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the fireplace if not enough
fresh air is available. See Air for Combustion and Ventilation,
pages 4 through 6. If fireplace keeps shutting off, see Trouble-shooting, pages 19 through 21.
11. Do not run fireplace
• where flammable liquids or vapors are used or stored.
• under dusty conditions.
12. Do not use this fireplace to cook food or burn paper or other
objects.
13. Do not use fireplace if any part has been under water. Immediately call a qualified service technician to inspect the room
fireplace and to replace any part of the control system and any
gas control which has been under water.
14. Turn off and unplug fireplace and let cool before servicing. Only
a qualified service person should service and repair fireplace.
15. Operating fireplace above elevations of 4,500 feet could cause
pilot outage.
16. Do not operate fireplace if any log is broken. Do not operate
fireplace if a log is chipped (dime-sized or larger).
17. To prevent performance problems, do not use propane/LP fuel
tank of less than 100 lbs. capacity (propane/LP units only).
18. Provide adequate clearances around air openings.
PRODUCT IDENTIFICATION
Fireplace
Cabinet
Brick Liner
Logs
Screen
Heater Controls
(Inside Door)
Figure 1 - Vent-Free Bay Front Compact Fireplace
111410-01C
For more information, visit www.desatech.com
For more information, visit www.desatech.com
LOCAL CODES
UNPACKING
4
PRODUCT FEATURES
AIR FOR COMBUSTION AND VENTILATION
Providing Adequate Ventilation
LOCAL CODES
Install and use fireplace with care. Follow all local codes. In the absence
of local codes, use the latest edition of The National Fuel Gas CodeANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
UNPACKING
1.Remove and fireplace from carton.
2.Remove all protective packaging applied to fireplace for
shipment.
3.Make sure your fireplace includes one hardware packet.
4.Check fireplace for any shipping damage. If fireplace is damaged, promptly inform dealer where you bought fireplace.
PRODUCT FEATURES
SAFETY PILOT
This fireplace has a pilot with an Oxygen Depletion Sensing (ODS)
safety shutoff system. The ODS/pilot is a required feature for ventfree room fireplaces. The ODS/pilot shuts off the fireplace if there is
not enough fresh air.
PIEZO IGNITION SYSTEM
This fireplace has a piezo ignitor. This system requires no matches,
batteries, or other sources to light fireplace.
AIR FOR COMBUSTION AND
VENTILATION
WARNING: This heater shall not be installed in a
confined space or unusually tight construction unless
provisions are provided for adequate combustion and
ventilation air. Read the following instructions to insure proper fresh air for this and other fuel-burning
appliances in your home.
Today’s homes are built more energy efficient than ever. New
materials, increased insulation, and new construction methods help
reduce heat loss in homes. Home owners weather strip and caulk
around windows and doors to keep the cold air out and the warm air
in. During heating months, home owners want their homes as airtight
as possible.
While it is good to make your home energy efficient, your home
needs to breathe. Fresh air must enter your home. All fuel-burning
appliances need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers, and fuel burning appliances
draw air from the house to operate. You must provide adequate fresh
air for these appliances. This will insure proper venting of vented
fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation
classifications:
1.Unusually Tight Construction
2.Unconfined Space
3.Confined Space
The information on pages 4 through 6 will help you classify your
space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings of
unusually tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction
where:
a.walls and ceilings e xposed to the outside atmosphere
have a continuous water vapor retarder with a rating
of one perm (6x10
openings gasketed or sealed
b. weather stripping has been added on openable win-
dows and doors
For more information, visit www.desatech.com
For more information, visit www.desatech.com
-11
kg per pa-sec-m2) or less with
and
and
111410-01C
AIR FOR COMBUSTION AND
VENTILATION
Continued
AIR FOR COMBUSTION AND VENTILATION
Providing Adequate Ventilation (Cont.)
Determining Fresh-Air Flow for Heater Location
5
5
c. caulking or sealants are applied to areas such as
joints around window and door frames, between sole
plates and floors, between wall-ceiling joints, between
wall panels, at penetrations f or plumbing, electrical,
and gas lines, and at other openings.
If your home meets all of the three criteria above, you
must provide additional fresh air. See
From Outdoors
, page 6
.
Ventilation Air
If your home does not meet all of the three criteria above,
proceed to
tion
, below.
Determining Fresh-Air Flow for Heater Loca-
Confined and Unconfined Space
National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined
space as a space whose volume is less than 50 cubic feet per 1,000
Btu per hour (4.8 m3 per kw) of the aggregate input rating of all
appliances installed in that space and an unconfined space as a space
whose volume is not less than 50 cubic feet per 1,000 Btu per hour
(4.8 m3 per kw) of the aggregate input rating of all appliances
installed in that space. Rooms communicating directly with the
space in which the appliances are installed*, through openings not
furnished with doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless
passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR
HEATER LOCATION
Determining if You Have a Confined or
Unconfined Space
Use this work sheet to determine if you have a confined or unconfined space.
Space: Includes the room in which you will install heater plus any adjoining
rooms with doorless passageways or ventilation grills between the rooms.
1.Determine the volume of the space (length x width x height).
Length x Width x Height =___________ cu. ft. (volume of space)
Example:
height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or open-
ings, add the volume of these rooms to the total volume of the space.
2.Multiply the space volume by 20 to determine the maximum Btu/Hr
the space can support.
__________ (volume of space) x 20 = (Maximum Btu/Hr the space
Example:
Btu/Hr the space can support)
Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling
can support)
2560 cu. ft. (volume of space) x 20 = 51,200 (maximum
3.Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free heater_____________ Btu/Hr
Gas water heater*_____________ Btu/Hr
Gas furnace_____________ Btu/Hr
Vented gas heater_____________ Btu/Hr
Gas fireplace logs_____________ Btu/Hr
Other gas appliances* + _____________ Btu/Hr
Total = _____________ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater_____________ Btu/Hr
Vent-free heater+ _____________ Btu/Hr
Total= _____________ Btu/Hr
4.Compare the maximum Btu/Hr the space can support with the actual
amount of Btu/Hr used.
__________________ Btu/Hr (maximum the space can support)
__________________ Btu/Hr (actual amount of Btu/Hr used)
Example:
The space in the above example is a confined space because the actual Btu/
Hr used is more than the maximum Btu/Hr the space can support. You must
provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an adjoining room. If the
extra space provides an unconfined space, remove door to adjoining
room or add ventilation grills between rooms. See V entilation Air Fr omInside Building, page 6.
B. Vent room directly to the outdoors. See Ventilation Air From Out-
doors, page 6.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room
unconfined.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can
support, the space is an unconfined space. You will need no additional fresh
air ventilation.
51,200 Btu/Hr (maximum the space can support)
56,000 Btu/Hr (actual amount of Btu/Hr used)
30,000
26,000
56,000
WARNING: If the area in which the heater may be
operated is smaller than that defined as an unconfined space or if the building is of unusually tight
construction, provide adequate combustion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54 Section 5.3
or applicable local codes
.
111410-01C
For more information, visit www.desatech.com
For more information, visit www.desatech.com
AIR FOR COMBUSTION AND VENTILATION
6
Ventilation Air
INSTALLATION
Check Gas Type
AIR FOR COMBUSTION AND
VENTILATION
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space.
When ventilating to an adjoining unconfined space, you must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor on the wall connecting the two spaces
(see options 1 and 2, Figure 2). You can also remove door into
adjoining room (see option 3, Figure 2). Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion
and Ventilation for required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one within 12" of the floor. Connect these items directly to the
outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
IMPORTANT:
attic if attic has a thermostat-controlled power vent. Heated air
entering the attic will activate the power vent.
Do not provide openings for inlet or outlet air into
12"
Outlet
Air
Outlet
Air
Inlet
Air
Inlet Air
Figure 3 - Ventilation Air from Outdoors Shown with Optional
Mantel
Ventilated
Attic
To Attic
To
Crawl
Space
Ventilated
Crawl Space
INSTALLATION
NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary
heating system. Do not install this heater as your
primary heat source. If you have a central heating
system, you may run system’s circulating blower
while using heater. This will help circulate the heat
throughout the house. In the event of a power outage,
you can use this heater as your primary heat source.
Ventilation Grills
Ventilation
Grills
into Adjoining
Room,
Option 1
Figure 2 - Ventilation Air from Inside Building Shown with
Optional Mantel
Or
Remove
Door into
Adjoining
Room,
Option 3
Into Adjoining Room,
Option 2
12"
For more information, visit www.desatech.com
For more information, visit www.desatech.com
WARNING: A qualified service person must in-
stall fireplace. Follow all local codes.
Note:
Your Comfort Glow fireplace is designed to be used in zero
clearance installations. Wall or framing material can be placed
directly against any exterior surface of your fireplace, except where
standoff spacers are integrally attached. If standoff spacers are
attached to your fireplace, these spacers can be placed directly
against wall or framing materials.
Use the dimensions shown for rough openings to create the easiest
installation (see Built-In Fireplace Installation, page 8).
CHECK GAS TYPE
Use the correct gas type (natural or propane/LP) for your unit. If
your gas supply is not correct, do not install fireplace. Call dealer
where you bought fireplace for proper type fireplace.
111410-01C
INSTALLATION
Continued
LOCATING FIREPLACE
WARNING: Maintain the minimum clearances
shown in Figures 4 and 5. If you can, provide greater
clearances from floor, ceiling, and joining wall.
You can recess firebox into the wall. You can also position fireplace
in the optional cabinet mantels.
cabinet mantels specified in this manual. Purchase the optional
mantel from your dealer (see Accessories, page 29).
WARNING: Never install the fireplace
• in a bedroom or a bathroom
• in a recreational vehicle
• where curtains, furniture, clothing, or other flam-
mable objects are less than 42 inches from the
front, top, or sides of the fireplace
• as a fireplace insert
• in high traffic areas
• in windy or drafty areas
IMPORTANT:
Only use optional
INSTALLATION
Locating Fireplace
Note:
When installing fireplace directly on carpeting, tile or other
7
7
combustible material, other than wood flooring, the fireplace shall
be installed on a metal or wood panel extending the full width and
depth of the fireplace.
CEILING
42" Minimum
6"
Minimum
From
Sides Of
Fireplace
Left
Side
Right
Side
CAUTION: This fireplace creates warm air currents. These currents move heat to wall surfaces next
to fireplace. Installing fireplace next to vinyl or cloth
wall coverings or operating fireplace where impurities
(such as, but not limited to, tobacco smoke, aromatic
candles, cleaning fluids, oil or kerosene lamps, etc.) in
the air exist, may discolor walls or cause odors.
I
MPORTANT:
Vent-free fireplaces add moisture to the air. Although
this is beneficial, installing fireplace in rooms without enough ventilation air may cause mildew to form from too much moisture. See Airfor Combustion and Ventilation, pages 4 through 6.
CAUTION: If you install the fireplace in a home
garage
• fireplace pilot and burner must be at least 18
inches above floor.
• locate fireplace where moving vehicle will not hit it.
For convenience and efficiency, install fireplace
• where there is easy access for operation, inspection, and service.
• in coldest part of room.
An optional blower kit is available from your dealer. See Accesso-
ries, page 29. If planning to use blower, locate fireplace near an
electrical outlet.
FLOOR
0" Minimum Clearance To Top Surface Of Carpeting,
Tile Or Other Combustible Material
Figure 4 - Mounting Clearances As Viewed From Front of
Fireplace Shown Built In The Wall
CEILING
Top Of
Mantel Can
Be Flush
With Wall
Left
Side
0" Minimum Clearance To Top Surface Of
Carpeting, Tile Or Other Combustible Material
42"
Minimum
Right
Side
111410-01C
Figure 5 - Mounting Clearances As Viewed From Front of
Fireplace Shown with Optional Mantel
For more information, visit www.desatech.com
For more information, visit www.desatech.com
36
5
/
8
"
25
7
/
8
"
51
3
/
4
"
26
7
/
8
"
INSTALLATION
8
Built-In Fireplace Installation (Cont.)
INSTALLATION
Continued
BUILT-IN FIREPLACE INSTALLATION
Built-in installation of this fireplace involves installing fireplace
into a framed-in enclosure. This makes the front of fireplace flush
with wall. Follow the instructions below to install the fireplace in
this manner. If installing a built-in mantel above the fireplace, you
must follow the clearances shown in Figure 9, page 9. If using for
built-in installation off of the floor, follow clearances shown in
Figure 4, page 7.
1.Frame in rough opening. Use dimensions shown in Figure 6
for the rough opening.
If installing in a corner, use dimensions shown in Figure 7 for
the rough opening. The height is 26 1/8" which is the same as
the wall opening above.
2.An optional blower accessory is available (see Accessories,
page 29). There are two options for connecting blower to electrical source.
Option one: Have a licensed electrician install a properly
grounded, three-prong 120-volt electrical outlet at fireplace
location. Locate outlet inside the framed enclosure. Blower
power cord will plug into this outlet.
Option two: Have a licensed electrician connect blower to elec-
trical source at junction box inside fireplace.
If using option one, have electrical outlet installed at this time.
If using option two, do not connect blower to electrical source
at junction box until step 6.
3.Install gas piping to fireplace location. This installation includes
an approved flexible gas line (if allowed by local codes) after
the equipment shutoff valve. The flexible gas line must be the
last item installed on the gas piping.
4.Carefully set fireplace in front of rough opening with back of
fireplace inside wall opening.
5.Attach flexible gas line to fireplace gas regulator. See Con-necting Fireplace to Gas Supply, pages 13 and 14.
6.If the optional blower has been installed connect blower to
electrical source.
Option one: Route blower electrical cord through side or rear
access door of fireplace. Plug electrical cord into electrical outlet.
Option two:Have a licensed electrician connect blower to elec-
trical source at junction box inside fireplace.
7.Bend four nailing flanges on outer casing with pliers (see
Figure 8, page 9).
3
/49 1/2"3/4"
8.Attach fireplace to wall studs using nails or wood screws
through holes in nailing flange.
9.Check all gas connections for leaks. See Checking Gas Con-nections, pages 14 and 15.
IMPORTANT:
When finishing your firebox, combustible materials such as wall board, gypsum board, sheet rock, drywall, plywood,
etc. may be butted up next to the sides and top of the firebox.
Combustible materials should never overlap the firebox front facing. Firebox should not be placed on top of carpet or other kinds of
fibrous material.
WARNING: Do not allow any combustible materi-
als to overlap the firebox front facing.
1
10
/
2
"
7
26
/
8
"
3/4" Off
7
26
/
8
"
Figure 6 - Rough Opening for Installing in Wall
Figure 7 - Rough Opening for Installing in Corner
Nails or Wood
Screws
AUTO
OFF
ON
Figure 8 - Attaching Fireplace to Wall Studs
The Floor
Minimum
Nailing
Flanges
For more information, visit www.desatech.com
For more information, visit www.desatech.com
111410-01C
INSTALLATION
Continued
Built-In Fireplace Installation (Cont.)
INSTALLATION
Removing Brick Liner Retainer
Assembling Trim
Optional Mantel Installation
9
9
IMPORTANT:
Noncombustible materials such as brick, tile, etc.
may overlap the front facing, but should never cover any necessary
openings like louvered slots.
WARNING: Do not allow noncombustible materials
to cover any necessary openings like louvered slots.
WARNING: Never modify or cover the louvered
slots on the front of the firebox.
WARNING: Use only noncombustible mortar or
adhesives when overlapping the front facing with
noncombustible facing material.
Mantel Clearances for Built-In Installation
If placing mantel above built-in fireplace, you must meet minimum
clearance between mantel shelf and top of fireplace opening.
NOTICE: Surface temperatures of adjacent walls and
mantels become hot during operation. Walls and
mantels above the firebox may become hot to the
touch. If installed properly, these temperatures meet
the requirement of the national product standard.
Follow all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the minimum
clearances shown, you must do one of the following:
• raise the mantel to an acceptable height
• remove the mantel
Mantel Shelf
Note:
All vertical
measurements are from
top of fireplace opening
to bottom of mantel shelf.
Minimum NonCombustible
Material
Figure 9 - Minimum Mantel Clearances for Built-In Installation
2.Remove brick liner retainers and discard. Replace 2 screws into
vertical sides.
ASSEMBLING TRIM
(Trim shipped with mantel)
1.Remove packaging from three pieces of trim.
2.Locate two adjusting plates with set screws, and two shims in
the hardware packet.
3.Align shim under adjusting plate as shown in Figure 10.
4.Slide one end of adjusting plate/shim in slot on mitered edge
of top trim (see Figure 10).
5.Slide other end of adjusting plate/shim in slot on mitered edge
of side trim (see Figure 10).
6.While firmly holding edges of trim together, tighten both set
screws on the adjusting plate with slotted screwdriver.
7.Repeat steps 1 through 6 for other corner.
8.Set brass assembly aside for later installation.
Set Screws
Adjusting
Plate
Shim
Figure 10 - Assembling Trim
Slot
Top Trim
Mitered Edge
Side Trim
Slot
OPTIONAL MANTEL INSTALLATION
Note:
Refer to instructions provided with the mantel for assembly
instructions. Refer to instructions below for system installation. If
using blower accessory (see Accessories, page 29), see installation
instructions on pages 11 and 12.
1.Choose location for fireplace and install gas supply line.
2.Remove screen from fireplace by removing screws in each
end of screen rod (see Figure 11, page 10). Hold screen rod
cover while removing five hex head screws underneath hood
(see Figure 12, page 10). Carefully lift and pull out hood (see
Figure 13, page 10).
3.Assemble trim kit. See Assembling Trim, above.
4.Place trim on the shoulder screws located on the side and top
of the fireplace. Firmly snap the trim over the shoulder screws
on fireplace (see Figure 14, page 10).
5.Place mantel base close to wall in desired fireplace location.
6.Install gas line. See Connecting To Gas Supply, pages 12 and 13.
111410-01C
For more information, visit www.desatech.com
For more information, visit www.desatech.com
Loading...
+ 21 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.