Deltatherm LT 5 Series, LT 5 VV PGD 50 Hz, LT 5 VV PGD 60 Hz Assembly Instructions Manual

Hirmer GmbH * 53804 Much * Gewerbegebiet Bövinge n 122
* Telefon 02245/6107-0 FAX: 02245/6107-10
* e-mail : info@deltatherm.de
* http://www.deltatherm.de
Assembly instructions
Machinetype / Maschinentype : LT 5 Machine No. / Maschinennummer : 2-*****
Date of build / Baujahr : **/20**
Duties for operators of refrigerating systems
From 2006-12-01
Apply for systems with more than 3kg refrigerant agent
Leak-tightness check2) minimum once a year;
Duty of recording with duty of storage ab out type and quantity of used and
2)
recycled refrigerant agents
for 5 years;
Continuous inspection and maintenance according to the manufacturer information with duty of storage about all adopted measures in the operating manual
2)
for 5 years.
From 2007-07-04: Apply for systems with more than 3kg refrigerant agent
Leak-tightness check by accredited staff at a filling quantity
3 kg – 30 kg in periodic intervals of 12 months 30 kg – 300 kg in periodic intervals of 6 months
over 300 kg in periodic intervals of 3 months
*
Periodic intervals double, if a leakage recognition system exists.
Installation of leakage recognition systems for systems with over 300 kg refrigerant agent with a duty of inspection in periodic intervals of 12 months;
Duty of recording with duty of storage ab out type and quantity of used and recycled refrigerant agents and all adopted measures of maintenance / inspection for 5 years and duty of presentation at the authorities in charge upon their request;
Recycling of F gases by accredited staff.
1)
3)
*
*
Please contact our in-house service for
maintenance and a leak-tightness check.
DELTATHERM Hirmer GmbH
Industrial cooling and heating
Gewerbegebiet Bövingen 122
DE – 53804 Much / Germany
Tel: +49 (0)2245 6107 0
Fax: +49 (0)2245 6107 10
Mail:
Web: www.deltatherm.de
1) Perfluorocarbons (PFC), partial halogenated fluorocarbons (H-PFC) according to regulation (EG) 2037/2000 e.g. R22
2) Chemicals ozone layer regulation – „ChemOzonSchichtV“ 2006-11-13
3) Regulation (EG) 842/2006 (F gases regulation) e.g. R134a, R404a, R407c, R 410a, R417a
Only the passages important for operators of DELTATHERM – refrigerating systems have been communicated correspondingly. We refer to the full wording of the regulations and the treatment of regulatory offences and criminal offences. DELTATHERM- refrigerating systems contain in general up to approx. refrigerant agent. Further information amongst others www.deltatherm.de
, www.bmu.de, www.gesetze-im-internet.de
info@deltatherm.de
Operating manual for LT series cooling water heat exchanger
Special design DMG with reflow-admixture
and optional reference control
Contents Page
1.) Technical data 2
2.) General safety information 3 - 4
3.) Description 5
4.) Application domain 5
5.) Transport 6
6.) Function description 7 - 8
7.) Setup 9
8.) Cooling circuit connection 10 - 11
9.) Electrical connection 12
10.) Commissioning 13
11.) Care and maintenance 14
12.) Repair 14
13.) Faults and causes 15
14.) Pump data sheets 16 - 17
15.) in case of emergency 18
16.) Disposal 19
17.) Reference values for evaporation losses 20
- Temperature control operating manual
- Circuit diagrams
- Parts list
- Dimensional drawing
- Flow diagram
Version: 11/2013
1
Operating manual for LT series cooling water heat exchanger
V
28
1
2,86
3
07C
1,6
6
10+ 2
10
0
1
3,8
02
CuC
S
1203
1
0,1350,1851450
1690
0
0,39
2250
1
CM 3-6
23
4
0
0
1,28
3,0
Multi
2PE31
830
1200
19
16
3
0/60
6%/-10%
24V DC
3
91
8
8,49
1. Technical data
Implementation
Cooling fluid Cooling fluid filling quantity kg Cooling performance at tw +20°C kW Max. operating pressure bar
Temperature ranges **
Min. water feed °C Max. w ater feed °C Min. environment temperature °C Max. environment temperature °C
Compressor for tc/to=55/7°C
Amount Piece I mplementation Nominal power kW Nominal current A Max. nominal current A
Evaporator
I mplementation Material
Condense r
I mplementation Material
entilator
Amount Piece I mplementation Nominal power kW Nominal current A Air power m³/h Nominal rotation speed n
Pum p
Amount Piece Type set transport pow er l/min set transport pressure bar Nominal power kW Nominal current /max. A I mplementation
Temperature regulator
I mplementation Temperature display Sw itching pow er AC / A
Container
Material Contents Liter
Dim ens ions
Width approx. mm Depth approx. mm Height approx. mm
Weight
Weight approx. kg
Electrical conn ection
Connection voltage Control voltage Nominal connection power kW Nominal current draw A Max. insulation A
Type
LT 5 VV PGD 50 Hz LT 5 VV PGD 60 Hz
R 4
+ +
+ 4
completely sealed
7 4,
5,
Tube coils
air-cooled, axial
u-tube/ Alu-blades
4D400AP
Axial ventilator w ith impeller
,44
A-R-A-E-AQQE OAAN
,7
,74
-stage block pump electronic
Digital
47
x 400V 5
,74 4, ,54
5
,44
5 Hz +
2
Operating manual for LT series cooling water heat exchanger
2. General safety information
Information marks in the operating manual
Safety information whose non-observance may cause danger to persons is marked with the general danger symbol "Safety symbols according to DIN 4844­W9".
When warning against electrical voltage, the marking occurs in accordance with "Safety symbols according to DIN 4844-W 8".
General information that should be observed by the person performing the setup or the operator is marked with the following symbol.
This operating manual does not contain any general safety rules for cooling and electrical installations.
In accordance with EG machine directive 2006/42/EG from May 17th, 2006, appendix II A, we declare that the designated machine complies with the basic safety and health regulations of the EG directive 2004/42/EG from appendix I, articles 1.1.2, 1.1.3, 1.1.5, 1.3.2, 1.5.1 in its design and construction. This declaration becomes invalid in case of modifications without our prior agreement.
Furthermore, compliance with the following regulations/directives applying to the product is declared:
-EG Pressurized device directive (97/23/EG) from May 27th, 1997
-EMC Directive (2004/108/EG) from December 15th, 2004
-EG Low voltage directive (2006/95/EG) from December 12th, 2006
In particular the following harmonized standards:
-EN 60204-1:2006 Safety of machines; Electrical equipment of machines; Part 1: General regulations
-EN ISO 12100:2003 Safety of machines; General requirements
-DIN EN 378-1 b. 4:1/2008 Cooling installations and heat pumps; Safety-relevant and environmentally relevant requirements; Parts 1 to 4
3
Operating manual for LT series cooling water heat exchanger
Along with the general safety information listed in the following, you will find further safety information in this operating manual under the main points as well as in the section "In case of emergency". The directives and standards not named here also retain their validity.
This operating manual contains basic information to be followed during setup, operation and maintenance. Therefore, the operating manual is to be read by the assembler and operator before the assembly and commissioning and should be constantly available on the site of operation of the machine/installation.
Persons who are not familiar with this operating manual as well as children and adolescents below age 16 may not use the device and should be kept away from the connected device.
The working area is to be locked off in accordance with the task and should correspond to the local directives on work protection.
Use personal safety equipment such as safety shoes, rubber gloves, protective goggles and a helmet.
Ensure that all evacuation routes from the work area are unobstructed. In order to prevent asphyxiation and poisoning, a sufficient oxygen supply to the
workplace is to be ensured and the absence of poisonous gases should be verified. If work is to be performed with welding equipment or electrical tools, ensure that there
is no danger of explosion. All safety and protective installations are to be mounted and started up immediately
after the end of works. The operator is responsible for third parties in the working area. We draw your attention to the fact that according to product liability regulations, we are
not responsible for damages caused by our device in the case where information and directives from this operating manual are not respected. The same regulations apply for accessories.
4
Operating manual for LT series cooling water heat exchanger
3. Description
The LT series air-cooled cooling water heat exchangers are compact devices and are intended for cooling liquid fluids (Drinking water, all other fluids and additives are to be released by the device manufacturer). The operating domain of the devices was determined to be a fluid temperature between +10°C and +25°C. The stated cooling performance relates to a fluid temperature of +20°C and an environment temperature of +40°C (+50°C for tropical design). For physical reasons, the cooling performance declines for sinking fluid temperatures and rising environment temperatures. In case of rising fluid temperature and sinking environment temperature, the cooling performance increases as defined by the laws of physics. A special equipment is necessary for the use with demineralized water.
No flammable or explosive substances may be used.
In case of cooling fluid temperatures below +8°C, the cooling fluid should be combined with adequate antifreeze in sufficient concentrations ( in accordance with manufacturer information ).
Release for mixing ration water/antifrogen 70/30%. Provided the cooling fluid is not mixed with antifreeze, the cooling fluid should be
completely drained in case of longer stoppage or during transportation with environment temperatures below +4°C in order to avoid any frost damage.
4. Application domain
The cooling water heat exchangers are intended for cooling
- Molds and baths for the plastic industry
- hydraulic presses and dies
- Drilling and cutting emulsions
- Machine tools
- Welding machines, transformers and grippers
- Compressors and pipe coils
- Tri and Per cleaning installations
- Laboratory and experimental installations
- galvanic and chemical baths
- chemical and cosmetic emulsions
- Laser and X-ray installations
- Cooling walls and air-conditioning
- other systems
5
Operating manual for LT series cooling water heat exchanger
5. Transport
The heat exchanger may only be transported upright and with a completely empties cooling fluid vat. The warning signs on the packaging should imperatively be observed.
Only use adequate transportation aids such as lifting equipment or forklifts during transportation.
The delivery of the device is made with filled cooling fluid. When employing a transporter, they should be informed of this. The type and quantity of cooling fluid are provided in section 1.
The respectively applicable safety regulations are to be followed when transporting in different countries or by boat or airplane. The safety data sheet for the used cooling fluid may be obtained on demand from the manufacturer.
Before unpacking the heat exchanger, check the packaging or the device for any visible transportation damage. In case of transportation damage, notify the transporter and the manufacturer immediately.
If lifting brackets are available, always use all available lifting brackets during transportation as non-compliance may cause damages to the housing and components.
When using lifting brackets, a lifting crossbeam should imperatively be used.
NO
STEP
6
Operating manual for LT series cooling water heat exchanger
6. Function
The heat exchanger is mainly composed of a cooling circuit and a cold fluid circuit. The cooling circuit serves the purpose of collecting the heat to be extracted from the user or at the tool. The heat gathered by the cooling fluid is dissipated in the environing air via thecoldfluidcircuit.
Cooling fluid circuit:
The cooling fluid transportation in the cooling circuit occurs via a built-in cooling centrifugal pump and constantly circulates between the cooling fluid vat and the user. The cooling fluid releases the heat to be evacuated via an evaporator in the cooling fluid vat.
The cooling fluid vat is composed of high-resistance PE plastic as serves the purpose of collecting the cooling fluid required for the cooling circuit. (See section "Technical data" for contents of the container)
The filling level of the cooling fluid vat can be measured from outside using the integrated filling level display.
Cooling fluid pump:
A robust, multi-stage block pump is used for the recirculation of the cooling fluid required for cooling.
The pump must be deaerated at the pump head before commissioning. A deaeration tube which is closed with a red lid is attached to the pump head for this purpose. The lid is to be removed before filling. Filling is done via the filling nozzle on the casing lid. If the water level reaches the upper mark on the water level display, filling of the device is complete.
Avoid dry running of the pump
Cold fluid circuit:
The cold fluid circuit functions with safety cooling fluid R407C (R134a for tropical design). This cold fluid is not poisonous, non-flammable and non-explosive.
The cold fluid is propelled by the compressor and circulates in a closed circuit between the evaporator and condenser. If collects the heat from the liquid to be cooled in the evaporator and thereby changes its state from liquid to gaseous. The gaseous overheated cold fluid is sucked up by the compressor and compressed. The compression of the cold fluid increases the pressure and temperature in the cold circuit. The collected heat including the compression heat is dissipated in the environing air in the condenser, and the cold fluid condenses at constant pressure. The condensing pressure is brutally dropped at the thermostatic expansion valve mounted between condenser and evaporator, allowing liquid cold fluid to be injected to the evaporator. The injecting cold fluid evaporates again in the evaporator by obtaining the necessary evaporation energy through heat collected from the cooling fluid. This circular process repeats as long as the compressor is switched on, or as long as the desired target temperature set on the temperature controller is not reached.
7
Operating manual for LT series cooling water heat exchanger
Evaporator:
The evaporator is designed as a pipe coil heat exchanger and is located in the cooling fluid vat. The used material is exclusively copper. The cooling fluid runs through the heat exchanger tubes during the heat exchange and the fluid to be cooled flows around the tubes. The evaporator pipe coils should always be surrounded by sufficient fluid to be cooling fluid, as the cooling performance diminished otherwise.
Condenser:
An air-cooled blade condenser is used for heat evacuation. The condenser retrieves approx. 1,3 times the heat quantity of the cooling performance.
Collector:
The collector is used to collect the cooling fluid necessary for the sage operation of the unit.
Inspection glass:
The inspection glass is used to check the cold circuit in case of faults. Permanent bubbling in the inspection glass during operation indicates a lack of
cooling fluid.
High pressure control:
The high pressure control acts as a safety organ in the cold circuit and switches off the compressor in case of excessive pressure in the system.
Low pressure control:
The low pressure control acts as a safety organ and switches off the compressor in case of too low pressure in the system.
Floater switch for too low water level
The pre-warning "Water level too low" indicates that too little water is present in the container. The missing water should be filled in.
Protection against dry running
The protection against dry running serves the purpose of protection the recirculation pump and the compressor from damage. If the min. water level is reached, it switches off the device. The device only switches back on once the min. filling level is exceeded.
No further description of the cold circuit will be given here, since further manipulation of the circuit should only be performed by trained cooling technicians.
8
Operating manual for LT series cooling water heat exchanger
7. Setup
The corresponding local regulations should be observed when setting up the heat exchanger.
In accordance with accident prevention directive BGR500, it should be ensured that the place of setup has a large enough ventilation area and is sufficiently ventilated in the case of a cooling fluid leak.
The setup of the heat exchanger should preferably be performed in a frost-safe room. The minimum distances provided in the dimensions sheet should be respected. It should be ensured that the room air does not become excessively warm because of the heat to be evacuated. If heating of the room is unavoidable due to the available room dimensions, the generated heat should be evacuated using adequate additional installations (for examples windows or ventilators) and cooler air should be transported into the room. High room temperatures lead to high pressure switch-offs in the cooling circuit and thereby reduce the cooling performance of the device. The air in- and outlet grills should not be blocked.
In order to prevent unnecessary pressure losses in the pipes connecting to the user, the heat exchanger should be set up as close as possible to the tool to be cooled. The connection tubes are to be insulated against unnecessary heat uptake and condensation water formation using adequate insulation materials (for example Armaflex).
A special base is not necessary for the setup of the heat exchanger, a level installation on a floor capable of supporting its mass is sufficient.
9
Operating manual for LT series cooling water heat exchanger
8. Cooling circuit connection
The heat exchanger is a compact device and contains all the parts necessary for cooling the fluid. Only the connection tubes between the heat exchanger and the user to be cooled or the tool are to be provided on-site. The fluid in- and outlets are to be connected using flexible pressure tubes. No rigid pipe connections are to be created. The flow direction is marked by arrows on the connections. The filling of the container is done via a filling connection on the device lid.
When filling the device, observe the following:
a) Before the feed and reflux pipes are connected, the container in the device is to be pre-filled to the
maximum filling level (see upper marking on the filling level display). The air contained in the system can thereby escape in an optimal fashion.
b) During first filling, the pump and pump head are to be deaerated. For this, a deaeration tube is attached to the top of the pump head and is closed off by a red
plug. The lid is to be removed before filling. Filling is done via the filling nozzle on the casing lid. If the water level reaches the upper mark on the water level display, filling of the device is complete. The de­aeration tube is to be closed with the red plug.
Avoid dry running of the pump
c) At the end of the filling process, the device is to be connected to the feed and
reflux tubes as described above.
In order to pull out the plug press the side ring of the plug connection towards the back.
10
Operating manual for LT series cooling water heat exchanger
n
n
A
6
1 Container 2Pump 2 Shut-off valve
7
1
4
5
2
3
3 Shut-off slider for setting the 5User
6 Deaerator 7 Filling connection
Behälter
1
Pumpe
2
Absperrventil
3 4
Absperrschieber für Druck- u
pressure and flow rate
Durchflußmengen Einstellung Verbraucher
5
Entlüfter6 Füllanschluß
7
B
6
6
6
9
1
2
47
338
5
3
3
1 Container 2Pump 2 Shut-off valve 3 Shut-off slider for setting the
5User 6 Deaerator 7 Magnetic valve 8 Holding valve 9 Filling connection
Behälter1
2
Pumpe
3
Absperrventil
4
Absperrschieber für Druck- u
pressure and flow rate
Durchflußmengen Einstellung
5
Verbraucher Entlüfter
6 7
Magnetventil
8
Rückschlagventil
9
Füllanschluß
If the user is mounted higher than the heat exchanger, the container may overflow due to water reflux once the recirculation pump is switched off. In this case, a holding valve should be installed in the feed and a magnetic valve in the reflux tube.
11
Operating manual for LT series cooling water heat exchanger
9. Electrical connection
The electrical connection of the device should be performed in accordance with VDE 0/100 and the TAB of the responsible EVU.
The expert verification before commissioning should determine that the required protective measures are available.
The power connection is done using a Harting plug. If the device is connected to a three-phase mains, the rotating field and the rotation
direction of the pump and ventilator motors should be checked. If necessary, the rotation direction should be corrected by exchanging two outside wires.
The device connection should occur with a right hand rotation field.
ONLY FOR SPECIAL VOLTAGES
If a power transformer is built into the device, the mains connection is directly made on the connections of the transformer. The protective sheet over the terminal block has to be removed first.
MAINS VOLTAGE see identification plate
12
Operating manual for LT series heat exchanger
10. Commissioning
If the cooling circuit is filled as described in point 8 and the device is electrically connected as described in point 9, the heat exchanger may be started / stopped using the button, see controller description in the appendix.
The error notifications are to be requested as aggregate error notifications with potential free queries to the Harting connector. See circuit diagram.
In case of deviations of the set value, a warning signal is output to the display of the controller.
Information on hydraulic device adaptation
A hydraulic adaptation to the local conditions is to be performed on-site for each device. For this, DMG co. need to install baffle plates in order to regulate the corresponding flow rates. It should be ensured that the set water pressure and the flow rates are in the application domain of the pump characteristic. Operating conditions deviating from this may cause damages to the pump.
13
Operating manual for LT series cooling water heat exchanger
11. Care and maintenance
The heat exchanger requires no special care as the device is constructed in a manner that ensures maximum operating safety and the lowest possible requirements toward s maintenance, inspection and monitoring.
However, in order to avoid faults and damages, it is necessary to observe the following
points.
1.) The condenser blades and protective grills must be free of dust and dirt. If necessary, these are to be cleaned using compressed air.
2.) The pipe coil evaporator should be cleaned in accordance with the state of the fluid.
Dirty fluid should thereby be drained.
3.) The air filter mat should be regularly changed.
If pollution occurs after a short time when using water as cooling fluid, the cooling water should be prepared (see water preparation).
12. Repair
The following paragraphs should imperatively be observed when repairs are to be performed.
Only remove the metal cover sheets with the device turned off. All maintenance and repair work should be performed with the device disconnected
from all power sources. Work on the electrical installation may only be performed by expert electricians. The applicable VDE directives and annex regulations of the responsible EVU are to be
observed. Safety installations should never be bridged. Work on the cold circuit may only be performed by trained cooling technicians. For
environmental protection reasons, the cooling fluid may not be released into the atmosphere. The cooling fluid should be suctioned off and disposed of in the adequate manner.
In case of a defect on the machine within the warranty period, all repairs may only be performed by the manufacturer or an authorized expert workshop.
Modifications to the device are only admissible with prior consent of the manufacturer. Only original spare parts should be used.
We draw your attention to the fact that according to product liability regulations, we are not responsible for damages caused by our device in the case where unauthorized repair attempts are performed neither by the manufacturer or by an authorized workshop, or when parts are exchanged for non-original replacement parts.
The same regulations apply for accessories.
14
Operating manual for LT series cooling water heat exchanger
13. Faults and causes
Work on the cooling circuit and work on the electrical wiring may only be performed by trained expert personnel or the DELTATHERM service.
Verifications and repairs may only be performed if the device is disconnected from all power supplies.
Fault Cause Solution
Too low cooling performance
Pump runs, compressor does not switch on
“Fault” Temperature regulator temperature excess
“Fault” Pump does not switch on
Condenser or evaporator are polluted
Lack of cooling fluid
Environment temperature too high
Device is overloaded
Filter mat is blocked
Check settings on temperature control Fluid temperature is too high Motor winding protection in motor winding is open
Limit values are exceeded or underrun
“Pump” motor protection switch triggers
Clean parts
Have an expert remedy the leak Fill in cooling fluid Reduce room temperature through adequate measures (i.e. additional ventilators) Check whether additional users were connected or the production conditions changed Change the filter mat
If necessary, exchange temperature control
Have expert check
Check temperature control and device Check sensor
Check fuses Pump works outside its characteristic
“Fault” Motor protection switch “Compressor”
“Fault” High pressure switch
“Fault” low pressure switch
Filling level fault
“Compressor” motor protection switch triggers Compressor does not switch on
Environment temperature too high Condenser polluted Ventilator defective
Fluid temperature too low Condenser polluted Lack of cooling fluid Cold circuit component defective
Filling level in the container too low Leak in the fluid circuit
15
Check fuses
Have expert check
Raise temperature Clean condenser
Have expert check Check filling level
Refill fluid Look for leak
Operating manual for LT series cooling water heat exchanger
TypeCM 3-6 A-R-A-E AQQE O-A-A-N
120
55 °C Maxi
ibl
10 bar
Y
P
G
EN-JL1030 AISI 30 B
Stainl
l
DIN W.-N
4301, AISI 304
Stainl
l
1.4301 (AISI 304)
l
AQQE
2
r
50/60 H
C
3~400V
I
F Protecti
IP 55
Pump characteristic at 50Hz
Implementation
Horizont al , m ul t i -s tage high pres sure centrifugal pump in bl ock design
Application domai n
For pure, non -explosi ve trans port li qui ds wi t h out abras i ve or solid c omponent s, without suspensions, and that do not corrode the pump materials. For increasing the pressure of the water network (observe local regulations).
Opera ting conditions
Fluid temperature -20 - + Environment temperature max .
mum admiss
Constant operation
ump housing / Valve y oke
e pump pressure
es
ray iron Impeller Axis Axis sea
Motor Frequency
onnection voltage
nsulation class
on type
60 50 40
H
30
m
20 10
0
l/min
m³/h
13,28 19,92 26,56 33,2 39,84 46,48
0,8 1,2 1,6 2,0 2,4 2,8
ess stee
r. 1.
ess stee
pol. induction moto
z
Characteristic data
Typ e
CM 3-6 IE2 0,74
3~ 400V 50 Hz P2 HP
AkWHP
3,00
Q
n =
Q
m³/h
l/min
16
2900
1/min
0,8 1,2 1,6 2,0 2,4 2,8
13,28 19,92 26,56 33,2 39,84 46,48
56 54 52 50 47 43
Operating manual for LT series cooling water heat exchanger
g
y
r
A
Pump characteristic at 60Hz
Implementation
Horizont al , m ul t i -s tage high pres s ure centri fugal pump i n block design
Application domai n
For pure, non-expl os i ve transport l i quids wit hout abrasive or sol i d c om ponent s, with out s uspensi ons, a nd that do no t corrode the pum p m aterial s. For increasing the pressure of the water network (observe local regulations).
Operatin T
conditions
pe CM 3-6 A-R-A-E AQQE O-A-A-N
Fluid temperature -20 - +120 Environment tempe rat ure max. 55 °C Max i mum adm i ssibl e pum p pressure 10 ba Const ant operat ion Y es Pump housing / V al ve yoke Gray iron
EN-JL1030 AISI 30 B
Impeller St ai nless st eel
DIN W. -Nr. 1. 4301 A IS I 304
Axis Stainless steel
DIN W. -Nr. 1. 4301 A IS I 304
Sli di ng ring s eal
QQE
Motor 2 pol. induction motor Frequency 50/60 Hz Connecti on voltage 3~400V Insulation class F Protection type IP 55 Design according to
90 80 70 60
H
50 40
m
30 20 10
0
l/min m³/h
16,6 25 33,3 41,6 50 58,3
1,0 1,5 2,0 2,5 3,0 3,5
Q
Characteristic data
Typ e
CM 3-6 IE2 1,28
3~ 400V 60 Hz P2 HP
AkWHP
3,0
n =
Q
m³/h
l/min
3480
1/min
1,0 1,5 2,0 2,5 3,0 3,5
16,6 25 33,3 41,6 50 58,3
80 77 74 71 66 62
17
Water quality
Requirements and water-care for heat-exchangers (chillers) and heat-balancing plant (temperature control units)
Subject to the equipment to be cooled or heat-balanced, certain requirements have to be met by the cooling water regarding cleanliness and purity. The degree of the water`s contamination, as well as the size and construction of the heat-exchanging­or –balancing plant determine the process most suitable for the application of additives and/or care of the water-supply in question.
In the interest of achieving the optimum layout for operating an appropriate heat­exchanger unit or heating-cooling plant, the consistency of the water used schould not deviate too significantly from the following list of hydrological data:
Hydrological Data max. unit
PH-value 7,5 – 8,5 ­Carbonate hardness 3 - 5 °dH Free carbonic acid 0 mg/l Carbonic acid 0 mg/l Aggesiv carbonic acid 0 mg/l Chlorid Cl <50 mg/l Sulphate So4 10 mg/l Nitrate and nitrite <50 mg/l Ammonia 0 mg/l Iron Fe 0,1 mg/l Manganese 0,05 mg/l Free from solids 0 mg/l Conductivity 600-1000 µS/cm
With deviating water-quality, we recommend using the services of consultants, or to have a water analysis or water sample sent to us. Deltatherm is not liable for any malfunctions or damages arising from deviating water qualities.
When employing chillers at temperatures below + 8°C, an anti-freeze medium must be added (Release by DELTATHERM).
Operating manual for LT series cooling water heat exchanger
15. In case of emergency
Immediately cut off power supply to the installation
-switch off main switch
-Pull out power plug
-Unscrew fuses or switch them off (Automata) Filling in cooling fluid:
Only the prescribed R134a or R407c cooling fluids should be used - observe max. filling level! The R134a and 407c cooling fluids are CFC-free. Before maintenance work on the cold circuit of the unit, it should be drained and the cooling fluid disposed of adequately. Cooling fluids, oils, etc. and parts may only be disposed of and filled in/installed by expert and certified companies.
Personal protection equipment In case of larger cooling fluid leaks, enter the machine room with a gas-mask or breathing protection if necessary. Protect the face and hands from direct contact with cooling fluid. EN 378 Parts 2 and 3 are to be observed! The accident prevention directive BGR 500 chap. 2.35 "Protective equipment against cooling fluids" should be observed.
First aid In case of injury, accidents, poisoning or burns, please immediately contact the following telephonic contacts:
Management Tel.: Mustermann co. Emergency doctor Tel.: 112 Firebrigade Fire brigade Tel.: 112 Firebrigade Hospital Tel.: Hospital xy Burns Tel.: Hospital xy
18
Operating manual for LT series cooling water heat exchanger
16. Disposal
The cold circuit of the cooling water heat exchanger contains R407C cooling fluid (R134a for tropical design). Before maintenance work on the cold circuit of the unit, it should be drained and the cooling fluid disposed of adequately. Retrofitting on the cold circuit of the installation may therefore only be performed by an expert company.
19
Reference value for evaporation losses
The evaporation quantity depends on the environment tempera ture and the air humidity. The evaporation quantity may reach up to 30% per week. When refilling, make sure that the water 70% / glycol 30% ratio does not get exceeded, as this can lead to damage to the pump and a weakened performance. This should be checked with the corresponding measurement devices. An incorrect mixing ration voids the liability of Detatherm
20
Cancel Switches to the previous menu item
Display
Operation keys
Operation The device is switched on
Operating Instructions for Temperature Regulator FX 06
Operation keys
OK Opens the input field Confirms entry
UP Switches to the next menu item or input field Increases the numerical input value Alarm reset by simultaneous pressing of the UP and DOWN key
DOWN Switches to the next menu point or input field Decreases the numerical input value Deletes alarm indicator
Display
Pump The pump is switched on. The pump has a follow-up time of 5 sec. (only
appears with active pumps)
ALARM General alarm L Minimum limit temperature undercut
H Maximum limit temperature exceeded Cooling Control valve in operation
PROP-BAND
I-ANTEIL
D-ANTEIL 20 sec
T HIGH DIFF 3,0 °C
T ALARM DLY
T HYST 0,5 °C
CONTRAST
BACKLIGHT ON
DEF-COLOR
ALARM COLO
HOUR
MINUTE
DAY
MONAT
YEAR
SERVICE
04
TEMP
ZONE
01
A1-F
A1-H
A1-L
05 DISPLAY
NO EVENTS
D-SP 0,0 °C
A1 OFFSET
DIFF
A2-F
MS
FS
A2 OFFSET
COOL 100
02
03
USER
T LOW DIFF
T HIGH MIN 15,0 °C
T LOW MIN 0,0 °C
T HIGH MAX 35,0 °C
T LOW MAX 25,0 °C
PUMP ENAB
DIFF-SP
-2,5 °C
D-SP 25,0 °C
MIN-SP
06
07
UT-MIN
UT-MAX
FL-START-DLY
FL-RUN-DLY
VALVE-DLY
PUMP OF DLY
5 sec
PUMP FS DLY
20,0 °C
20,0 °C
0,0 °C
USER
SERVICE
ALARME
ACITV
HIGH
10.0 °C
10 sec
10.0 °C
100 sec
0,0 °C
25 °C
SETP
5,0°C
BLUE
0,0 °C
10 sec
RTC
RED
OFF
1 sec
3 sec
PASSWORD
# # # #
# # # #
-3,0 °C
60 sec
The water temperature is shown in the main view
Shows the active set point. Subject to the zone sensor, it is
is shown in the display.
TEMP
SETP
COOL
Shows the degree of opening of the control valve in %.
Shows the temperature of the difference sensor
ZONE
Display of temperature difference between the zone sensor and
DIFF
Display menu
The device can be sw itched on and off from an external position. When the device is switched on, a wavy line appears in the display. The pump switches off after a follow-up time of 5 sec.
17.5 °C
20.0 °C
-2.5 °C
the flow sensor
2.5 °C
switched over from difference to fixed value regu lation when a temperature value is undercut or exceeded. The active set point
100
0 % Valve closed 100 % Valve c ompletely open
- 01-
In the ALARMS level, the upcoming alarms are shown. By
NO EVENT
01 ALARMS
ALARMS
AVAILABLE
pressing the OK key, the display window can be reached. If many alarms are set, the status messages can be shown individually with the UP or DOWN keys.
Is shown when no alarm is set.
Alarm signals
A1-F Temperature sensor A1 failure (defective or not connected, limit temperature undercut or
exceeded).
A1-H The set temperature (TEMP MAX) has been exceeded.
A1-L The set temperature (TEMP MIN) has been undercut.
A2-F Temperature sensor A2 failure (defective or not connected, limit temperature undercut or
exceeded).
FS Flow monitor has switched off. Recirculated quantity in circuit too low, air in system MS Motor overload switch of the pump has tripped.
- 02-
DIFF-SP
DIFF-SP
After pressing the OK key, the set point can be changed. When
MIN-SP
MIN-SP
MAX-SP
MAX-SP
02 SETP
In the SETUP level, the set points for the different temperature ranges are entered. The temperature for the transfer is determined by the zone sensor.
SETP
the entry field is blinking, the value can be adjusted by pressing the UP or DOWN keys. The adjusted value has to be confirmed with a press of the OK key.
-2,5 °C
Entry of the desired difference set point
5,0 °C
Set point at low temperatures
45,0 °C
Set point at high temperatures
03 RTC
In this level, the time and date are set. Hour, minute, day, month, year
- 05-
By pressing the OK key, the selection level can be reached. In
USER
SERVICE
05 PASSWORD
PASSWORD
1 # # #
1 # # #
this menu item, the desired parameter level can be opened when the correct password is entered.
The password for the USER level is 1 1 1 1 and can be entered with the UP and DOWN key and confirmed by pressing the OK key.
The service level is password protected.
05 DISPLAY
In this level, the contrast and color for the displays and the alarm signals can be changed. 01 LCD CONTRAST = HIGH (MED/LOW) 02 BACKLIGHT TIME MIN = 2 Min . Illumination of the display goes out after 2 minutes. Factory
s setting ON
03 DEFAULT COLOR = BLUE (RED) 04 ALARM COLOR = RED (BLUE)
06 USER
By pressing the OK key, the submenu can be reached and the
PROP-BAND
Proportional range
T HIGH DIFF
T LOW DIFF
Maximum temperatur e deviation of difference regul ation. If the
I-ANTEIL
D-ANTEIL
Integral proportion factor
Setting parameter for the differential proportion
Minim um temperature deviation of difference regulation. If the
T HIGH MIN
T LOW MIN
Minimum limit temperature at low temperatures.
display.
T HIGH MAX
Maximum limit temperature at high temperatures.
display.
Minimum limit temperature at high temperatures.
display.
06 USER
parameter value shown can be changed. Please note: The changed values must be confirmed after
entering by a press of the OK key.
10,0 °C
Setting the proprotional range of the PID conroller. The proportion funct ions in a way that the cor rec ti ng vari ab l e is linearly reduced from +/-100% to 0% when the actual value nears the set point.
100 sec
Setting the I and D proportions of the PID regulator. When the setting is 0, the values are invalid
20 sec
see integral proportion
3 °C
temperature deviation of the flow temperature from the zone temperature is larger t han the set value, the alarm output D06 is activated and the symbol H appears in the display.
-3 °C
temperature deviation of the flow temperature from the zone temperature is larger t han the set value, the alarm output D06 is activated and the symbol L appears in the display.
25,0 °C
If the flow temperature is colder than the set value, the alarm output D06 is activated and the symbol L appears in the
45,0 °C
If the flow temper ature is warmer than the set value, the alarm output D06 is activated and the symbol H appears in the
0,0 °C
If the flow temperature is colder than the set value, the alarm
output D06 is activated and the symbol L appears in the
T HYST
Temperature difference for switching the max/min limit
A1 O FFSET
Alignment for temperature sensor for adjusting to the existing
A2 O FFSET
Alignment for temperature sensor for adjusting to the existing
Maximum limit temperature at low temperatures.
display.
T LOW MAX
T ALARM DLY
Delay time for the temperature alarm.
PUMP ENAB
If a circulation pump is present, this can be switched on here.
15,0 °C
If the flow temper ature is warmer than the set value, the alarm output D06 is activated and the symbol H appears in the
0,5 °C
temperature on and off.
1 sec
0,0 °C
temperature values.
0,0 °C
temperature values.
OFF
OFF = Exit pump DO1 not activated ON = Exit pump DO1 activated
When the pump is activated, a pump symbol appears in the display.
Adjustment value:
Hydraulic circuit KK1, KK2 and KK5
Change over temperature UT-MAX 40 °C Set point SP-MAX 40 °C Category temperature min. T LOW MAX 15 °C Category temperature max. T HIGH MAX 45 °C
Different set point DIFF-SP -2,5 K Deviation temperature min. T HIGH DIFF 3,0 °C Deviation temperature max. T LOW DIFF -3,0 °C
Change over temperature UT-MIN 10 °C Set point SP-MIN SP-MIN 5 °C Category temperature min. T LOW MIN 0 °C Category temperature max. T HIGH MIN 25 °C
Hydraulic circuit KK3
Change over temperature UT-MAX 40 °C
Set point SP-MAX 40 °C
Category temperature min. T LOW MAX 15 °C Category temperature max. T HIGH MAX 45 °C
Different set point DIFF-SP -2,5 K Deviation temperature min. T HIGH DIFF 3,0 °C Deviation temperature max. T LOW DIFF -3,0 °C
Change over temperature UT-MIN 20 °C Set point SP-MIN SP-MIN 15 °C Category temperature min. T LOW MIN 0 °C Category temperature max. T HIGH MIN 25 °C
Water circuit KK6 (main spindle motor)
Change over temperature UT-MAX 40 °C Set point SP-MAX 40 °C
Category temperature min. T LOW MAX 15 °C Category temperature max. T HIGH MAX 45 °C
Different set point DIFF-SP -2,5 K Deviation temperature min. T HIGH DIFF 3,0 °C Deviation temperature max. T LOW DIFF -3,0 °C
Change over temperature UT-MIN 10 °C Set point SP-MIN SP-MIN 10 °C Category temperature T LOW MIN 0 °C Category temperature max. T HIGH MIN 25 °C
Water circuit KK4 (control box)
Change over temperature UT-MAX 25 °C Set point SP-MAX 30 °C Category temperature min. T LOW MAX 20 °C Category temperature max. T HIGH MAX 45 °C
Different set point DIFF-SP 2,5 K Deviation temperature min. T HIGH DIFF 3,0 °C Deviation temperature max. T LOW DIFF -3,0 °C
Change over temperature UT-MIN 10 °C Set point SP-MIN SP-MIN 12 °C Category temperature min. T LOW MIN 0 °C Category temperature max. T HIGH MIN 17 °C
Channel Name Pin Number Type
AI1
AI2
DI1
DI2
DI3
DO1
DO6
AO1
Flow
Zone
Start_Stop
Motor protection
Flow
Pump
Alarm
Valve
0
0
0
0
0
0
0
0
NTC 10 kOhms
NTC 10 kOhms
Binary
Binary
Binary
Binary
Binary
Linear0 10V
Matthias Schürmann
User
1/8
08.09.2014
Page
Printdate
Mandant
Deltatherm | Gewerbegebiet Bövingen 122 | 53804 Much |
parts list
MaschinenNr:
002-222334
Artikelnr.
Beschreibung
002-222334
Chiller LT 5 VV
50/60 Hz
DMG Nr: 2762868
_______________________________________________________________________________________________________________________________________________________
050-1367
case LT 5 DMG
_______________________________________________________________________________________________________________________________________________________
050-5018
primer
47.99.001.2
a 10kg
_______________________________________________________________________________________________________________________________________________________
050-1408
colour
D PUR PLUS texture paint 2K
titangrey KM 8491
_______________________________________________________________________________________________________________________________________________________
050-1287
rubber buffer
D=40mm,H=25mm
M8, C
_______________________________________________________________________________________________________________________________________________________
050-1401
inlet filter
DMG LT5
_______________________________________________________________________________________________________________________________________________________
020-4463
condenser aircooled
LH 44 OPTI 5 (zinc coated/without paint)
_______________________________________________________________________________________________________________________________________________________
020-1461
scroll compressor
ZR 28K3E-TFD 522
with tab connection
_______________________________________________________________________________________________________________________________________________________
020-1788
liquid drum
FM 1.6
_______________________________________________________________________________________________________________________________________________________
020-4180
expansion valve
TEZ 2, flange, without MOP
_______________________________________________________________________________________________________________________________________________________
020-4243
valve core for
TEN/TN, TEz/TZ size 03
_______________________________________________________________________________________________________________________________________________________
040-5431
tab connector
7/16" UNFx6/8/10mm
_______________________________________________________________________________________________________________________________________________________
040-5432
Schrader valve
48 bar
_______________________________________________________________________________________________________________________________________________________
040-5408
hard tab connector
6mm x 7/16" UNF DIN 8906"
_______________________________________________________________________________________________________________________________________________________
020-4831
valve cap with seal
Typ 34998-00
_______________________________________________________________________________________________________________________________________________________
020-4317
screwcap KM 3/4"
UNF 12mm sw24 DIN 8912
_______________________________________________________________________________________________________________________________________________________
Matthias Schürmann
User
2/8
08.09.2014
Page
Printdate
Mandant
Deltatherm | Gewerbegebiet Bövingen 122 | 53804 Much |
Artikelnr.
Beschreibung
020-4174
screwcap KM 5/8"
UNF 10 mm SW22 DIN 8912
_______________________________________________________________________________________________________________________________________________________
020-4308
screwcap KM 7/16"
UNF 6mm x 1/4" sw17 DIN 8912
_______________________________________________________________________________________________________________________________________________________
041-0558
copper nipple 28o x 22mm
_______________________________________________________________________________________________________________________________________________________
040-0591
tab nipple 16x10
NR. 5243
_______________________________________________________________________________________________________________________________________________________
020-4820
dryer
FF 083MMS
10mm ODF
_______________________________________________________________________________________________________________________________________________________
020-4346
sight glass
SLI 10 10X10ODF
_______________________________________________________________________________________________________________________________________________________
020-4491
evaporator
LT5 3CU12
special design
_______________________________________________________________________________________________________________________________________________________
020-4798
venturi dispenser
12-6-3
_______________________________________________________________________________________________________________________________________________________
041-0035
copper tube 12 x 1
_______________________________________________________________________________________________________________________________________________________
041-0033
copper tube 6 x 1
CU-DHP EN 12735-1 und EN 13348
_______________________________________________________________________________________________________________________________________________________
020-4467
fan with protective grid
S4D400 AP1203
_______________________________________________________________________________________________________________________________________________________
020-4813
pressostat low pressure, auto-reset, fixed
P100-AP-32D
_______________________________________________________________________________________________________________________________________________________
030-2388
hp pressostat auto reset
P100-CP-100D
_______________________________________________________________________________________________________________________________________________________
050-4722
insulation
endlessplate
_______________________________________________________________________________________________________________________________________________________
050-4724
insulation
hose 6 x 16mm
AERO
_______________________________________________________________________________________________________________________________________________________
050-4725
Insulation
tube 6 x 22MM
_______________________________________________________________________________________________________________________________________________________
030-2580
thermowell G1/4"
brass chromed
_______________________________________________________________________________________________________________________________________________________
Matthias Schürmann
User
3/8
08.09.2014
Page
Printdate
Mandant
Deltatherm | Gewerbegebiet Bövingen 122 | 53804 Much |
Artikelnr.
Beschreibung
040-5434
cap screw
GN 747-G1-A-1
with DIN-Symbol
_______________________________________________________________________________________________________________________________________________________
040-2200
IE2 pump
CM 3-6 A-R-A-E-AQQE OAAN
50/60Hz,0,74/1,28KW,IP 55
_______________________________________________________________________________________________________________________________________________________
050-0019
rubber buffer
40/40 M8x23 / M8i
_______________________________________________________________________________________________________________________________________________________
040-0137
tank
LTK 60l white
_______________________________________________________________________________________________________________________________________________________
040-0138
tank cover
for 60l tank
_______________________________________________________________________________________________________________________________________________________
040-5445
level switch
HK 1008/1-E, IP65, 240V/0,5A
_______________________________________________________________________________________________________________________________________________________
040-4760
three way valve DN15
BUN015F300
kvs 4,0 PN 16
_______________________________________________________________________________________________________________________________________________________
040-5772
valve drive
AVM105SF921 24VAC, 2,5m wire
_______________________________________________________________________________________________________________________________________________________
041-0364
angle red brass i/o 90° 3/4"
3092
_______________________________________________________________________________________________________________________________________________________
041-0365
elbow red brass i/a 90° 1"
_______________________________________________________________________________________________________________________________________________________
041-0359
elbow red brass i/i 90° 3/4"
_______________________________________________________________________________________________________________________________________________________
041-0453
ellbow red brass 28mm x 1" outside thread
4092g
_______________________________________________________________________________________________________________________________________________________
041-0265
hose barb 3/4" brass
_______________________________________________________________________________________________________________________________________________________
041-0266
hose barb 1" brass
_______________________________________________________________________________________________________________________________________________________
041-0470
crossover fitting red brass
10mm x 1/4" 4270g
_______________________________________________________________________________________________________________________________________________________
041-0370
hex nut 3/4"
brass viega
_______________________________________________________________________________________________________________________________________________________
041-0369
hexagonal nut 1/2"
brass
_______________________________________________________________________________________________________________________________________________________
Matthias Schürmann
User
4/8
08.09.2014
Page
Printdate
Mandant
Deltatherm | Gewerbegebiet Bövingen 122 | 53804 Much |
Artikelnr.
Beschreibung
041-0474
crossover fitting red brass
22mm x 3/4" 4092g
_______________________________________________________________________________________________________________________________________________________
041-0530
T-piece copper
5130
_______________________________________________________________________________________________________________________________________________________
041-0382
t-piece red brass 1"
_______________________________________________________________________________________________________________________________________________________
041-0416
reduction fitting 3/4"outside x 1"inside
round 3242
_______________________________________________________________________________________________________________________________________________________
041-0427
muffle red brass 1"
3270
_______________________________________________________________________________________________________________________________________________________
041-0392
reductoin muffle red brass 1" x 3/4"
3240
_______________________________________________________________________________________________________________________________________________________
041-0457
shift nipples
22mm x 3/4 outside thread 4243g
_______________________________________________________________________________________________________________________________________________________
041-0422
double nipples red brass 1" x 3/4"
_______________________________________________________________________________________________________________________________________________________
041-0434
double nipples red brass 1"
_______________________________________________________________________________________________________________________________________________________
041-0404
reduction piece red brass 1" x 3/8"
3241
_______________________________________________________________________________________________________________________________________________________
041-0399
restricted fitting 3/8" x 1/4" red brass
3241
_______________________________________________________________________________________________________________________________________________________
041-0400
reduction piece red brass 1/2" x 3/8"
3241
_______________________________________________________________________________________________________________________________________________________
041-0028
compression fitting 12mm x 1/2"
_______________________________________________________________________________________________________________________________________________________
041-0029
compression fitting 15mm x 1/2" AG
with cylindrical thread brass
_______________________________________________________________________________________________________________________________________________________
041-0432
double nibble red brass 1/2"
3280
_______________________________________________________________________________________________________________________________________________________
041-0379
t-piece red brass, 1/2"
_______________________________________________________________________________________________________________________________________________________
040-2300
Manometer
case 63mm, connection backside 1/4", 0-10 bar
_______________________________________________________________________________________________________________________________________________________
Matthias Schürmann
User
5/8
08.09.2014
Page
Printdate
Mandant
Deltatherm | Gewerbegebiet Bövingen 122 | 53804 Much |
Artikelnr.
Beschreibung
040-4138
sealing plug
8mm
_______________________________________________________________________________________________________________________________________________________
040-4132
straight connector
8mm
_______________________________________________________________________________________________________________________________________________________
040-4104
screw in connector
3/8"a x 8i
_______________________________________________________________________________________________________________________________________________________
040-4105
screw-in connector
1/2"a x 10i
_______________________________________________________________________________________________________________________________________________________
040-4139
screw-in connector
3/8"a x 10i
_______________________________________________________________________________________________________________________________________________________
040-4112
elbow connector
10 mm
_______________________________________________________________________________________________________________________________________________________
040-4136
plug-in elbow connector
10 mm
_______________________________________________________________________________________________________________________________________________________
040-4245
pipe
8mm
_______________________________________________________________________________________________________________________________________________________
090-2226
plexiglass XT-tube
10/7 mm D, 170mm long, colourless, seamless, polished
_______________________________________________________________________________________________________________________________________________________
040-5750
rubber hose oil resistant
25 x 5 mm
_______________________________________________________________________________________________________________________________________________________
030-2224
temperatuire controller
LP-FX06P00-900C
24 V AC/DC IP 54
_______________________________________________________________________________________________________________________________________________________
030-3080
cable set
for LP-FX06
_______________________________________________________________________________________________________________________________________________________
030-3121
temperature sensor NTC
TE-9100-8502
_______________________________________________________________________________________________________________________________________________________
030-2763
cabinet with mounting plate
200x500x120
_______________________________________________________________________________________________________________________________________________________
030-5750
DIN Rail
TS35x7.5
_______________________________________________________________________________________________________________________________________________________
030-0232
contactor S00
4KW-400V/50Hz 24VAC-50/60Hz 1S
3RT20 16-2AB01
_______________________________________________________________________________________________________________________________________________________
030-0469
motor circuit breaker S00
In=6,3A; 4,5-6,3A; 3RV20 11-1GA10
_______________________________________________________________________________________________________________________________________________________
Matthias Schürmann
User
6/8
08.09.2014
Page
Printdate
Mandant
Deltatherm | Gewerbegebiet Bövingen 122 | 53804 Much |
Artikelnr.
Beschreibung
030-0465
motor circuit breaker SOO
In=3,2A; 2,2-3,2; 3RV20 11-1DA10
_______________________________________________________________________________________________________________________________________________________
030-0340
aux switch transverse for circuit breaker
S00 and S0
3RV29 01-2E
_______________________________________________________________________________________________________________________________________________________
030-0442
circuit breaker
2A 1Ph, AC 230/400V, C Charkteristic
5SY4 102-7
_______________________________________________________________________________________________________________________________________________________
030-0449
circuit breaker
1A 2Ph, AC 400V, C Charkteristic
5SY4 201-7
_______________________________________________________________________________________________________________________________________________________
031-0011
transformer for DIN rail mounting
UST 0.05 D; 0,05 KVA; Prim. 230V/400V +-15V (A=0,23/
Sek. 24V (A=2,1); 50/60 Hz
_______________________________________________________________________________________________________________________________________________________
030-1074
EMV module, 7,5kW
575V, 50/60 Hz
_______________________________________________________________________________________________________________________________________________________
030-2830
DIN Rail adapter
20900
_______________________________________________________________________________________________________________________________________________________
030-4613
terminal strip
PDU 2,5/4
_______________________________________________________________________________________________________________________________________________________
030-4674
serial terminal
PDK 2,5/4
_______________________________________________________________________________________________________________________________________________________
030-4610
terminal strip for ground
PPE 2,5/4
_______________________________________________________________________________________________________________________________________________________
030-5381
serial terminal
PDK 2,5/4 PE
_______________________________________________________________________________________________________________________________________________________
030-5382
terminal strip
PDU 2,5/4/3 AN
_______________________________________________________________________________________________________________________________________________________
030-5383
terminal strip for ground
PPE 2,5/4/3 AN
_______________________________________________________________________________________________________________________________________________________
030-4611
split clamp
PTR 2,5/4
_______________________________________________________________________________________________________________________________________________________
030-5749
finish plate, spacer for PDK2.5/4
PAP PDK2.5/4
_______________________________________________________________________________________________________________________________________________________
030-5747
spacer plate for PTR2.5/4
PAP PTR2.5/4
_______________________________________________________________________________________________________________________________________________________
030-5748
spacer plate for PDU2.5/4/3
PAP PDU 2.5/4/3AN
_______________________________________________________________________________________________________________________________________________________
Matthias Schürmann
User
7/8
08.09.2014
Page
Printdate
Mandant
Deltatherm | Gewerbegebiet Bövingen 122 | 53804 Much |
Artikelnr.
Beschreibung
030-5752
jumper
ZQV2.5/3 3pole
_______________________________________________________________________________________________________________________________________________________
030-5751
jumper
ZQV2.5/2 2pole
_______________________________________________________________________________________________________________________________________________________
030-5743
bracket
ZEW35
_______________________________________________________________________________________________________________________________________________________
030-3234
accessory case
HAN10B 09300100305
_______________________________________________________________________________________________________________________________________________________
030-2765
pin insert part
HAN 10B 09330102601
_______________________________________________________________________________________________________________________________________________________
030-1256
relais with socket, 1 changer, 24V UC (AC/DC)
MRZ 24Vuc 1CO spring balancer connector
rated power 154mW, AC/DC=11mA/6,4mA
_______________________________________________________________________________________________________________________________________________________
030-5767
clamp marker
DEK 5 FWZ 1-10
_______________________________________________________________________________________________________________________________________________________
030-5769
clamp marker
DEK 5 GW PE
_______________________________________________________________________________________________________________________________________________________
030-5773
Multicard
ESG 7/20 SIRIUS/WS
_______________________________________________________________________________________________________________________________________________________
030-5777
Multicard
DEK 5/5 Plus neutral WS
_______________________________________________________________________________________________________________________________________________________
030-5774
multicard
SFC 1/12 neutral WS
_______________________________________________________________________________________________________________________________________________________
090-2228
plexiglass XT-slice
190x160x2mm(LT4/5Re)
_______________________________________________________________________________________________________________________________________________________
090-2229
plexiglass XT-slice
150x50x2mm(LT4/5Wa)
_______________________________________________________________________________________________________________________________________________________
030-1242
reduction
M20x1,5/M16x1,5PA Polyamid
RAL 7035
_______________________________________________________________________________________________________________________________________________________
030-1225
cable gland
12x1,5PA Polyamid
RAL 7035
_______________________________________________________________________________________________________________________________________________________
030-1226
cable gland
16x1,5PA Polyamid
RAL 7035
_______________________________________________________________________________________________________________________________________________________
030-1227
cable gland
20x1,5PA Polyamid
RAL 7035
_______________________________________________________________________________________________________________________________________________________
Matthias Schürmann
User
8/8
08.09.2014
Page
Printdate
Mandant
Deltatherm | Gewerbegebiet Bövingen 122 | 53804 Much |
Artikelnr.
Beschreibung
030-1228
screw connection
25x1,5PA Polyamid
RAL 7035
_______________________________________________________________________________________________________________________________________________________
030-1233
locknut
12x1,5PA Polyamid
RAL 7035
_______________________________________________________________________________________________________________________________________________________
030-1234
locknut
16x1,5PA Polyamid
RAL 7035
_______________________________________________________________________________________________________________________________________________________
030-1235
locknut
20x1,5PA Polyamid
RAL 7035
_______________________________________________________________________________________________________________________________________________________
030-1236
conter nut
25x1,5PA Polyamid
RAL 7035
_______________________________________________________________________________________________________________________________________________________
050-1434
clip hinge SYS.1
Snap-Line 130°
_______________________________________________________________________________________________________________________________________________________
0 1
3x400V 50/60Hz
2
43
5
6 7
8 9
1X12 3 PE
X4
1
+24V DC Fehlermeldungen
+24V DC Störmeldungen
2 3 4 5 97 86 10 PE
Extern Ein/Aus
0V DC Priorität 2 Priorität 1 Priorität 3
1 3 5
Q1
2 4 6
12345
K1
2.5 2.4
2.0
2.9
2.9
2.0
2.9
2.9
2.9
4X15 6 PE PE PE
U V W PE
M
M1
3
13 14
6
Z1
400V AC 4 KW 4 kW 50/60Hz
U V W PE
M2
3
M
1 3 5
Q2
2 4 6
K2
7X18 9
U V W PE
M3
12345
M
3
13 14
6
400V AC 4 KW
Z2
4 kW 50/60Hz
1.8
F1
T1
L1 L2
1.8
0 24
400V/24V 50 VA
F2
24V
0V
2.0
2.0
Hartingstecker
Geräteanschluß Pow e r in p ut unit 3 x 40 0V P E 50/60Hz
Datum Bearb.
Gepr.
NormÄnderung Datum Name
11.06.07 J.H.
DELTATHERM Hirmer GmbH
Maschinen der Kälte-, Wärme-
und Klima t e c hn ik
Kompressor compressor
Deckel Maho
DIN 34Für d iese Zei c hnun g beh a lten wir u ns al le R e c ht e v or, gemä ß
Ventilator fan
Hauptstromkreis
LT 4+5 Ausf. DMG
Pumpe pump
Urspr. Ers.f Ers.d
Cabinet / Case
Schaltschrank / Gehäuse
Rücklaufbeimischung
Blatt 1
Bl.
3
1.9
1.9
0 1
24V
0V
2
43
5
6 7
8 9
Extern Ein/Aus
1.3
0V DC
1.3
2.3
K3
11 14
A1
A2
2.7
K4
11 14
A1
A2
9X210X211
bl
1 2a 3u
MM 01 03
Motorventil
Y1
X2
Q1
13
14
P
B1
X2
11
K3 *
14
2.1
X2
br
rd
X2
7
P
B2 B3
X2
8
5
Q2
6
N1
1.6
X21X2
13
14
X22X2
AO Com
AO2
AO1
DI Com
DO1.DO2.DO3.DO4.DO5.DO6
.
A1
K2
A2
5 6 3 4 1 2
3
4
DI5
DI4
DI3
DI2
DI1
AI Com
A1
K1
A2
5 6 3 4
1.3 1 2
X3
1
R3 R1 R2B4
X3
X3
4
AI4
AI3
AI2
AI1
X3
3
2
+5VDC
+15VDC
LL-
LL+
24VCom
24VACD
24VCom
24VACD
B1 Hochdruckschalter, high pressure B2 Niederdruckschalter, low pressure R1 Tankfühler, tank sensor R2 Vorlauffühler, outlet sensor R3 Zonenfühler, zone sensor B3 Füllstand, level control B4 Trockenlaufschutz, dry protection
*Fühler R3 nur bei Referenzgeführter Regelung *Sensor R3 for reference controller
11
K4
14
2.1
1
X4 X4 X4 X4 X4
2 3 4 5
+24V DC Fehlermeldungen +24V DC error message
+24V DC Störmeldungen +24V DC trouble message
Priorität 2
Priority 2
Priorität 1
Priority 1
Priorität 3
Priority 3
1.3
1.3
1.3
1.3
1.3
Extern Ein/Aus external on/off
Diff.Reg. 09.10.07 GK ext. Ans. 21.01.08 JH K4 29.10.08 GK
Datum Bearb.
Gepr.
NormÄnderung Datum Name
11.06.07 J.H.
3-Wegeventil 3-way valve
DELTATHERM Hirmer GmbH
Maschinen der Kälte-, Wärme-
und Klima t e c hn ik
Pumpe pump
Deckel Maho
DIN 34Für d iese Zei c hnun g beh a lten wir u ns al le R e c ht e v or, gemä ß
Kompressor compressor
Steuerung
LT 4+5 Ausf. DMG
Urspr. Ers.f Ers.d
Rücklaufbeimischung
Blatt 2 3
Bl.
0 1
2
43
5
6 7
8 9
Zuleitung power input
3x400V 50/60Hz Kompressor
compressor
Pumpe pump M3
Trockenlaufschutz Running dry switch
Füllstand tank level switch
ND-Schalter LP press. switch
HD-Schalter HP press. switch
3-Weg-Ventil 3-way valve
Temperaturfühler (Vorl)
temp. sensor
Temperaturfühler (Tank)
temp. sensor Temperaturfühler (Zone)
zone temp. sensor
Temperaturregler temperature control N1
Relais Ein/Aus extern on/out external
M1
B4
B3
B2
B1
B1
R2
R1
R3
X1
1
X1
2
X1
3
PE
X1 X1
4
X1
5
X1
6
PE
X1 X1
7
X1
8
X1
9
PE
X1
X2
1
X2
2
X2
PE 3
X2 X2
4
X2
PE
5
X2
6
X2 X2 PE X2X27
8
X2
9
X2
10
X2
11
X3
1
X3 2 X3
1
X3
3
X3
1
X3
4
1
X4
2
X4
3
X4
4
X4
5
X4
X4 6
2.1 3.2
Priorität, Priority 2 Priorität, Priority 1 Priorität, Priority 3
0V DC
error message+24V DC Fehlermeldungen,
trouble message+24V DC Störmeldungen,
Datum Bearb.
Gepr.
NormÄnderung Datum Name
11.06.07 J.H.
DELTATHERM Hirmer GmbH
Maschinen der Kälte-, Wärme-
und Klima t e c hn ik
Deckel Maho
Klemmenplan
LT 4+5 Ausf. DMG
DIN 34Für d iese Zei c hnun g beh a lten wir u ns al le R e c ht e v or, gemä ß
Urspr. Ers.f Ers.d
Rücklaufbeimischung
Blatt 3 3
Bl.
IMPRESSUM
User manual
Don't forget:
• Original DELTATHERM spare parts
• DELTATHERM service
DELTATHERM Hirmer GmbH
Maschinen der Kälte-, Wärme- u. Klimatechnik
Gewerbegebiet Bövingen 122
D — 53804 Much / Germany
Tel.: +49 2245 / 6107 0
Fax: +49 2245 / 6107 10
Internet: www.deltatherm.de
e-mail: info@deltatherm.de