Delta Products HEX260PA Data Sheet

Internal door mount
HEX260PA-A series
Dimension drawing
Features Unit
◆ IP55 waterproof at external side
◆ "One touch" dry run test and dust cleaning W/K (W/
◆ Standalone temperature control
◆ Clear LED status indicator
◆ Dry contact alarm output
Design °C
◆ Air to air heat exchange
◆ Rated voltage at 48V
◆ Reduntant fan quantity design
◆ High efficiency and reliable fan
◆ Easy installation and maintenance
Operating temperature range -10 ~ +65
* Note : The cooling capacity (W/K , W/°C or W/℉) is defined as Q/ (TI-TA) Q : Heat dissipation (W) from inside of cabinet TI : Return temperature of internal air circuit (K , °C or ℉) TA : Ambient temperature of external air circuit (K , °C or * Specifications are subject to change without notice.
Main feature
Dimension (H x W x D)
Cooling capacity
Rated voltage 48
Operating current
Opearting power
Operating voltage range 40 ~ 60
Noise (1.5 meter) 65.0 75.0
Weight 37 (82)
*Note
mm
(in)
VDC
A
W
VDC
dB-A
Kg (Lb)
Specification
1400 x 650 x 260
(55 x 26 x 10)
175 (97) 230 (128)
)
3.1 10.0
149 480
)
HEX260PA-A Heat Exchanger
Instruction Manual
Table of contents
1. Version ......................................................................................................... 1
2. Description ................................................................................................... 1
2-1. General ................................................................................................ 1
2-2. Specification ....................................................................................... 1
2-3. Environmental condition .................................................................... 2
3. Installation ................................................................................................... 2
3-1. Outline drawing .................................................................................. 2
3-2. Mounting panel cutout and waterproof foam sticking .................... 3
4. Electrical specification ................................................................................ 3
4-1. Connection and LED indicator (on HEX panel) ................................ 3
4-2. Standalone control mode ................................................................... 5
5. Mechanical feature ...................................................................................... 6
5-1. Thermal path and Airflow baffle ....................................................... 6
5-2. Configuration ..................................................................................... 6
6. Maintenance and Replacement .................................................................. 7
6-1. Maintenance ....................................................................................... 7
6-2. Replacement ...................................................................................... 8
7. MTBF and Reliability ................................................................................... 8
7-1. MTBF................................................................................................... 8
7-2. Relibability ......................................................................................... 8
8. Safety ............................................................................................................ 9
9. Accessory .................................................................................................... 9
9-1. Power cable ........................................................................................ 9
9-2. Function cable ................................................................................... 9
10. General Safety and Warnings ................................................................... 9
HEX260PA-A Heat Exchanger Instruction Manual
1. Version
Rev. Description Drawn Approved Issue date
00 Issue spec. Nick Wang Adam Chen 2016/6/10
2. Description
2-1 . General
Delta Heat Exchanger (HEX) is designed for direct air to air heat
exchange to remove heat from the cabinet.
The internal and the external air circulation loops of the HEX are separated to prevent the introduction of dust, humidity and dirt. The fan on the external air loop conforms to IP55 protection rating.
2-2 . Specification
Outline Dimension (H x W x D)
Cooling Capacity (*Note 1) Rated Voltage VDC 48 Rated Current (*Note 2) A 12.0 Operating Voltage Range VDC 40 - 60 Operating Current A 3.1 10.0 Operating Power Consumption W 149 480 Acoustic Noise at 1.5M (SPL) dB-A 65.0 74.0
Main feature Unit
mm
(in)
W/K (W/)
Model Number
HEX260PA-A
1400 x 650 x 265
(55 x 26 x 10)
175 (97) 230 (128)
Weight Kg (Lb) 37 (82)
* Note1 : The cooling capacity (W/K , W/°C or W/) is defined as Q/ (TI-TA)
Q : Heat dissipation (W) from inside of cabinet TI : Return temperature of internal air circuit (K , °C or ) TA : Ambient temperature of external air circuit (K , °C or )
*Note 2 : Rated current is announcement of safety
Page 1
2-3 . Environmental condition
Description Specification
HEX260PA-A Heat Exchanger Instruction Manual
Operating Storage
Humidity Ingress protection
(on external side)l
3. Installation
3-1 . Outline drawing
-10°C ~ +65°C (-14°F ~ 149°F)
-40°C ~ +70°C (-40°F ~ 158°F) External air circuit: 0 ~ 100% RH
IEC60529 IP55 (NEMA 3) GR-487 720hrs salt spray
(1) Material : Aluminum sheet t=1.5mm (2) Finish : Power paint , Color RAL7032 (3) Dimensional tolerance : ± 1mm [0.04”]
Page 2
HEX260PA-A Heat Exchanger Instruction Manual
3-2 . Mounting panel cutout and waterproof foam sticking
4. Electrical specification
4-1. Connection and LED indicator (on HEX panel)
Power Connection
on panel plate : CVILUX 3W3CS0000100000
mate with : CVILUX 3W3CP0000100000
COMM connection
on panel plate : CVILUX CD5115PA100
mate with : CVILUX CD5115SA100
Page 3
HEX260PA-A Heat Exchanger Instruction Manual
User can follow dry contact definition that is Normal Close (N.C.) to detect abnormal status from pin 10 & pin 11
Definition N. C
Connection Pin 10 & Pin 11 Control board, NTC and fan are in
normal status NTC resistance is over range such as
“open circuit” or “short circuit” Fan speed is lower than 50% of
definition or fan is locked
Dry contact max. rating : 75VDC/50mA
LED indicator
INNER FAN / OUTER FAN / STATUS LEDs indicate fan and NTC
CLOSE
OPEN
OPEN
sensor status .
Depress "TEST" button to start auto-test of outer and inner fans
running from low to high speed. Turn off by depressing the “TEST” button
again .
INNER FAN Normal GREEN Failed* RED Normal
Blinking
OUTER FAN STATUS
GREEN
RED
GREEN
RED
Blinking
N/A
(touch TEST / CLEAN) Failed*
GREEN Blinking
GREEN
Blanking
N/A
(touch TEST / CLEAN)
RED
RED
* FAN failed : Fan speed is lower than 50% of definition or fan is locked * STATUS Failed : NTC resistance is over range such as “open circuit” or “short circuit”
Page 4
NTC temperature sensor
User can switch inner sensor (on control panel) or external sensor (COMM port Pin7 & Pin8 ) via J13 connector on controller as shown below to change sensor location .
4-2. Standalone control mode
HEX can detect ambient temperature to control cooling capacity .
Internal fan and external fan speed default settings are shown below
HEX260PA-A Heat Exchanger Instruction Manual
Cooling capacity (W/K) vs, Temperature
Inner fan speed vs. Temperature Outer fan speed vs. Temperature
Page 5
5. Mechanical feature
5-1 . Thermal path and Airflow baffle
With forced convection using the centrifugal fan, warm air generated by the equipment will be blown into the internal return opening and pass though the HEX, then flow out from internal supply opening. The air supply of the cold air will be used to cool down the system; On the opposite side, cooler air from the surrounding environment will be drawn in from the external air inlet side , and push the heat of the HEX out from the external air exhaust side. The thermal exchange path is shown in the figure below .
HEX260PA-A Heat Exchanger Instruction Manual
5-2 . Configuration
Item Q'ty
Description 1 1 Chassis assy 2 4 Fan guard 3 1 Controller 4 2 Internal fan
5 2 External fan 6 1 Heat exchange CORE
7 1 Internal plate assy 8 2 External plate assy
Page 6
6. Maintenance and Replacement
Be sure to SHUT DOWN the power before proceeding with any
maintenance or component replacement .
6-1. Maintenance
Monthly
Use brush and low pressure air to remove the dust or any debris on
both internal/external air inlet and air outlet opening .
Quarterly
Internal loop maintenance :
* The maintenance is from internal side . * Use screw driver to remove secured screw on upper
HEX260PA-A Heat Exchanger Instruction Manual
portion of chassis assy (Item 1) . * Disassemble the internal plate assy (Item 7) and disconnect fan from controller (Item 3) , Note the connection location . * Use brush and low pressure air to remove dust on internal
plate assy (Item 7) , internal fan (item 4) & core opening . * Connect internal fan to controller (Item 3) . * Re-attach internal plate assy (Item 7) and use screw driver to secure screw with chassis assy (Item 1) .
External loop maintenance :
* The maintenance is from internal side . * Use screw driver to remove secured screw on bottom portion of chassis assy (Item 1) . * Disassemble the external plate assy (Item 8) much carefully to avoid waterproof foam between around external plate assy (Item 8) and chassis assy (Item 1) to be damaged . * Use brush and low pressure air tor emove dust on external plate assy (Item 8) , external fan (Item 5) & heat exchange CORE opening . * Please check waterproof foam whether had damaged
before secure external plate assy plate (Item 8) back , if
yes , please remove damaged and stick new waterproof
foam first .
Page 7
HEX260PA-A Heat Exchanger Instruction Manual
Test
Please power on and follow LED status to check that HEX has
resumed to normal function after maintenance .
6-2. Replacement
Delta HEX is designed with dry contact alarm output and LED
indicator on panel shown below to describe abnormal situation .
Refer to Section 4-1 for checking abnormal part is internal fan ,
external fan or controller for abnormalities .
In cases of parts abnormality , Delta will follow the reading and submit
spare part(s) below for replacement .
Internal fan P/N : KFB2348HHUBDB
External fan P/N : KFB2348HHUA6T
Controller P/N : HEX260PA-A000C
User can then refer to maintaince sequence on previous page , or
request Delta authorized support for assistance .
7. MTBF and Reliability
7-1. MTBF
L10 Fan life is expected to be a minimum 80,000 hours continuous
operation at 40°C with 15 ~ 65%RH .@ label rated vo ltage
7-2. Relibability
Test item Condition
High temperature IEC 60068-2-2 Low temperature IEC 60068-2-1 High temp. / High humidity IEC 60068-2-14 TEST Nb Temperature cycle IEC 60068-2-3 Vibration ETSI 300 019-1-4 CLASS 4.1 Ingress protection
(External side)
IEC 60529 IP55 (NEMA 3) GR-487 720hrs salt spray
Package bump IEC 60068-2-29
Page 8
8. Safety
9. Accessory
9-1. Power cable
HEX260PA-A Heat Exchanger Instruction Manual
9-2. Function cable
10. General Safety and Warnings
* Some electronic parts have a high operating temperature .
Use caution at all times. * Incorrect installation may cause damage and/or injury. * Installation and maintenance should be performed only by qualified
personnel . Use caution at all times. * Ensure the grounding wire is connected before powering on the system. * Ensure the cover and the mounting hardware are secure upon installation. * All the cables connected to the unit must confirm to UL standards.