* Note : The cooling capacity (W/K , W/°C or W/℉) is defined as Q/ (T
Q : Heat dissipation (W) from inside of cabinet
T
T
* Specifications are subject to change without notice.
Main featureSpecification
Dimension (H x W x D)
Cooling capacity
Rated voltage48
Operating current4.1
Opearting power197
Operating voltage range40 ~ 60
Noise (1.5 meter)64.0
Weight33 (73)
: Return temperature of internal air circuit (K , °C or ℉)
I
: Ambient temperature of external air circuit (K , °C or ℉)
A
*Note
mm
(in)
VDC
A
W
VDC
dB-A
Kg (Lb)
1151 x 471 x 193
)
(45 x 19 x 8)
120 (67)
I-TA
)
HEX120PA Heat Exchanger
Instruction Manual
Table of contents
1. Version ......................................................................................................... 1
9. General Safety and Warnings ..................................................................... 9
HEX120PA Heat Exchanger Instruction Manual
1. Version
Rev. Description Drawn Approved Issue date
00 Issue spec. Nick Wang Adam Chen 2016/1/25
01 Add section 9 Nick Wang Adam Chen 2016/6/10
2. Description
2-1 . General
Delta Heat Exchanger (HEX) is designed for direct air to air heat
exchange to remove heat from the cabinet.
The internal and the external air circulation loops of the HEX are
separated to prevent the introduction of dust, humidity and dirt. The fan on
the external air loop conforms to IP55 protection rating.
2-2 . Specification
Outline Dimension (H x W x D)
Cooling Capacity (*Note 1)
Rated Voltage VDC 48
Rated Current (*Note 2) A 6.0
Operating Voltage Range VDC 40 - 60
Operating Current A 4.1
Operating Power Consumption W 197
Acoustic Noise at 1.5M (SPL) dB-A 64.0 dB-A
Weight Kg (Lb) 33 (73)
Main feature Unit
mm
(in)
W/K (W/℉)
Model Number
HEX120PA
1151 x 471 x 192
(45 x 19 x 8)
120 (67)
* Note1 : The cooling capacity (W/K , W/°C or W/℉) is defined as Q/ (TI-TA)
Q : Heat dissipation (W) from inside of cabinet
TI : Return temperature of internal air circuit (K , °C or ℉)
TA : Ambient temperature of external air circuit (K , °C or ℉)
With forced convection using the centrifugal fan, warm air generated
by the equipment will be blown into the internal return opening and pass
though the HEX, then flow out from internal supply opening. The air supply
of the cold air will be used to cool down the system; On the opposite side,
cooler air from the surrounding environment will be drawn in from the
external air inlet side , and push the heat of the HEX out from the external
air exhaust side. The thermal exchange path is shown in the figure on next
page .
Be sure to SHUT DOWN the power before proceeding with any
maintenance or component replacement .
Page 6
6-1. Maintenance
Monthly
both internal/external air inlet and air outlet opening .
Quarterly
HEX120PA Heat Exchanger Instruction Manual
Use brush and low pressure air to remove the dust or any debris on
Follow below maintenance sequence
Internal loop maintenance :
* The maintenance is from internal side .
* Use screw driver to remove secured screw on upper
portion of chassis assy (Item 1) .
* Disassemble the internal plate assy (Item 7) and disconnect
fan from controller (Item 3) , Note the connection location .
* Use brush and low pressure air to remove dust on internal
* Hold internal plate assy (Item 7) and connect fan to controller
(Item 3) .
* Re-attach internal plate assy (Item 7) and use screw driver to
secure screw with chassis assy (Item 1) .
External loop maintenance :
* The maintenance is from internal side .
* Use screw driver to remove secured screw on bottom
portion of chassis assy (Item 1) .
* Disassemble the external plate assy (Item 8) much
carefully to avoid waterproof foam between around external
plate assy (Item 8) and chassis assy (Item 1) to be damaged .
* Use brush and low pressure air tor emove dust on
external plate assy (Item 8) , external fan (Item 5) & heat
exchange CORE opening .
* Please check waterproof foam whether had damaged
before secure external plate assy plate (Item 8) back , if
yes , please remove damaged and stick new waterproof
foam first .
Page 7
HEX120PA Heat Exchanger Instruction Manual
Test
Please power on and follow LED status to check that HEX has
resumed to normal function after maintenance .
6-2. Replacement
Delta HEX is designed with dry contact alarm output and LED
indicator on panel shown below to describe abnormal situation .
Refer to Section 4-1 for checking abnormal part is internal fan ,
external fan or controller for abnormalities .
In cases of parts abnormality , Delta will follow the reading and submit
spare part(s) below for replacement .
Internal fan P/N : KFB2348HHUBDB
External fan P/N : KFB2348HHUA6T
Controller P/N : HEX120PA-000C
User can then refer to maintaince sequence on previous page , or
request Delta authorized support for assistance .
7. MTBF and Reliability
7-1. MTBF
L10 Fan life is expected to be a minimum 80,000 hours continuous
operation at 40°C with 15 ~ 65%RH .@ label rated voltage
7-2. Relibability
Test item Condition
High temperature IEC 60068-2-2 Low temperature IEC 60068-2-1 High temp. / High humidity IEC 60068-2-14 TEST Nb Temperature cycle IEC 60068-2-3 Vibration ETSI 300 019-1-4 CLASS 4.1 Ingress protection
(External side)
IEC 60529 IP55 (NEMA 3)
GR-487 720hrs salt spray
Package bump IEC 60068-2-29
Page 8
8. Safety
HEX120PA Heat Exchanger Instruction Manual
9. General Safety and Warnings
* Some electronic parts have a high operating temperature .
Use caution at all times.
* Incorrect installation may cause damage and/or injury.
* Installation and maintenance should be performed only by qualified
personnel . Use caution at all times.
* Ensure the grounding wire is connected before powering on the system.
* Ensure the cover and the mounting hardware are secure upon installation.
* All the cables connected to the unit must confirm to UL standards.
Page 9