Delta Products HEX100PC Data Sheet

External door mount
HEX100PC series
Dimension drawing
Features Unit
IP55 waterproof at external side
"One touch" dry run t est and dust cleaning
Standalone temperat ure control W/K (W/
Clear LED status i ndicator
Dry contact alarm output
Design VDC
Air to air heat exchange
Rated voltage at 48V
Reduntant fan quantity design
High efficiency and reliable fan
Easy installation and maintenance
Operating temperature range -10 ~ +65
* Note : The cooling capacity (W/K , W/°C or W/) is defined as Q/ (TI-TA) Q : Heat dissipation (W) from inside of cabinet TI : Return temperature of internal air circuit (K , °C or ℉) TA : Ambient temperature of external air circuit (K , °C or ℉) * Specifications are subject to change without notice.
Main feature
Dimension (H x W x D)
Cooling capacity
Rated voltage
Operating current
Opearting power
Operating voltage range
Noise (1.5 meter) 65.0 70.0
Weight 13 (29)
*Note
mm
(inch)
A
W
°C
dB-A
Kg (Lb)
Specification
690 x 360 x 242
(27 x 14 x 10)
70 (39) 90 (50)
)
1.7 82 173
40 ~ 60
48
3.6
HEX100PC Heat Exchanger
Instruction Manual
Table of contents
1. Version ......................................................................................................... 1
2. Description ................................................................................................... 1
2-1. General ................................................................................................ 1
2-2. Specification ....................................................................................... 1
2-3. Environmental condition ................................................................... 2
3. Installation ................................................................................................... 2
3-1. Outline drawing .................................................................................. 2
3-2. Mounting panel cutout and waterproof foam sticking .................... 3
4. Electrical specification ................................................................................ 3
4-1. Connection and LED indicator (on HEX panel) ................................ 3
4-2. Standalone control mode ................................................................... 5
5. Mechanical feature ...................................................................................... 6
5-1. Thermal path and Airflow baffle ....................................................... 6
5-2. Configuration ..................................................................................... 6
6. Maintenance and Replacement .................................................................. 7
6-1. Maintenance ....................................................................................... 7
6-2. Replacement ...................................................................................... 8
7. MTBF and Reliability ................................................................................... 8
7-1. MTBF................................................................................................... 8
7-2. Relibability ......................................................................................... 8
8. Safety ............................................................................................................ 9
9. Accessory .................................................................................................... 9
9-1. Power cable ........................................................................................ 9
9-2. Function cable ................................................................................... 9
10. General Safety and Warnings ................................................................... 9
HEX100PC Heat Exchanger Instruction Manual
1. Version
Rev. Description Drawn Approved Issue date
00 Issue spec. Nick Wang Adam Chen 2016/1/25 01 Add section 10 Nick Wang Adam Chen 2016/6/10
2. Description
2-1 . General
Delta Heat Exchanger (HEX) is designed for direct air to air heat
exchange to remove heat from the cabinet.
The internal and the external air circulation loops of the HEX are separated to prevent the introduction of dust, humidity and dirt. The fan on the external air loop conforms to IP55 protection rating.
2-2 . Specification
Outline Dimension (H x W x D)
Cooling Capacity (*Note 1) Rated Voltage VDC 48 Rated Current (*Note 2) A 4.2 Operating Voltage Range VDC 40 - 60 Operating Current A 1.7 3.6 Operating Power Consumption W 82 173 Acoustic Noise at 1.5M (SPL) dB-A 65.0 70.0
Main feature Unit
mm
(in)
W/K (W/)
Model Number
HEX100PC
690 x 360 x 242
(27 x 14 x 10)
70 (39) 90 (50)
Weight Kg (Lb) 13 (29)
* Note1 : The cooling capacity (W/K , W/°C or W/) is defined as Q/ (TI-TA)
Q : Heat dissipation (W) from inside of cabinet TI : Return temperature of internal air circuit (K , °C or ) TA : Ambient temperature of external air circuit (K , °C or )
*Note 2 : Rated current is announcement of safety
Page 1