Delta Products HEX060PA Instruction Manual

HEX060PA Heat Exchanger
Instruction Manual
USA 46101 Fremont Blvd, Fremont, CA 94538, U.S.A. TEL : 1-510-668-5100 FAX : 1-510-668-0680 Cabinet-Thermal-Solutions@deltaww.com Taiwan Delta Electronics, Inc. 252, Shang Ying Road, Kuei San District TEL : 886-(0)3-3591968 Taoyuan City 33341, Taiwan, R. O. C. FAX : 886-(0)3-3591991
Table of contents
1. Version ......................................................................................................... 1
2. Description ................................................................................................... 1
2-1. General ................................................................................................ 1
2-2. Specification ....................................................................................... 1
2-3. Environmental condition ................................................................... 2
3. Installation ................................................................................................... 2
3-1. Outline drawing .................................................................................. 2
3-2. Mounting panel cutout and waterproof foam sticking .................... 3
4. Electrical specification ................................................................................ 3
4-1. Connection and LED indicator (on HEX panel) ................................ 3
4-2. Standalone control mode ................................................................... 4
5. Mechanical feature ...................................................................................... 5
5-1. Thermal path and Airflow baffle ....................................................... 5
5-2. Configuration ..................................................................................... 6
6. Maintenance and Replacement .................................................................. 6
6-1. Maintenance ....................................................................................... 6
6-2. Replacement ...................................................................................... 8
7. MTBF and Reliability ................................................................................... 8
7-1. MTBF................................................................................................... 8
7-2. Relibability ......................................................................................... 8
8. Safety ............................................................................................................ 9
9. General Safety and Warnings ..................................................................... 9
HEX060PA Heat Exchanger Instruction Manual
1. Version
Rev. Description Drawn Approved Issue date
00 Issue spec. Nick Wang Adam Chen 2016/1/25 01 Add section 9 Nick Wang Adam Chen 2016/6/10
2. Description
2-1 . General
Delta Heat Exchanger (HEX) is designed for direct air to air heat
exchange to remove the heat from the cabinet.
The internal and the external air circulation loops of the HEX are separated to prevent the introduction of dust, humidity and dirt. The fan on the external air loop conforms to IP55 protection rating.
2-2 . Specification
Outline Dimension (H x W x D)
Cooling Capacity (*Note 1) Rated Voltage VDC 48 Rated Current (*Note 2) A 2.9 Operating Voltage Range VDC 40 - 60 Operating Current A 0.55 Operating Power Consumption W 27 Acoustic Noise at 1.5M (SPL) dB-A 62.0 dB-A Weight Kg (Lb) 17 (37)
Main feature Unit
mm
(in)
W/K (W/)
Model Number
HEX060PA
850 x 500 x 148
(33 x 20 x 6)
60 (33)
* Note1 : The cooling capacity (W/K , W/°C or W/) is defined as Q/ (TI-TA)
Q : Heat dissipation (W) from inside of cabinet TI : Return temperature of internal air circuit (K , °C or ) TA : Ambient temperature of external air circuit (K , °C or )
*Note 2 : Rated current is announcement of safety
Page 1
2-3 . Environmental condition
Description Specification
HEX060PA Heat Exchanger Instruction Manual
Operating
Storage
Humidity
Ingress protection
(on external side)l
3. Installation
3-1 . Outline drawing
-10°C ~ +65°C (-14°F ~ 149°F)
-40°C ~ +70°C (-40°F ~ 158°F) External air circuit: 0 ~ 100% RH
IEC60529 IP55 (NEMA 3) GR-487 720hrs salt spray
(1) Material : SGCC sheet t=1.0mm (2) Finish : Power paint , Color RAL7032 (3) Dimensional tolerance : ± 1mm [0.04”]
Page 2