Delta Products HEX020VA Data Sheet

Internal door mount
HEX020VA series
Dimension drawing
UNIT : MM
XXXXXXXXXXXXXXXX YYWW-SSSS
Dust filter
Features Unit
◆ IP55 waterproof at external side
◆ Dry contact alarm output
Design VDC
◆ Air to air heat exchange
◆ Rated voltage at 24V
◆ Reduntant fan quantity design
◆ High efficiency and reliable fan
◆ Easy installation and maintenance
Operating temperature range -10 ~ +65
* Note : The cooling capacity (W/K , W/°C or W/℉) is defined as Q/ (TI-TA) Q : Heat dissipation (W) from inside of cabinet T TA : Ambient temperature of external air circuit (K , °C or ℉)
Main feature Specification
Dimension (H x W x D)
Cooling capacity
Rated voltage 24
Operating current 0.9
Opearting power 22
Operating voltage range 20 - 26
Noise (1.5 meter) 54.0
Weight 7 (15)
: Return temperature of internal air circuit (K , °C or ℉)
I
*Note
mm
(inch)
W/K (W/
A
W
VDC
°C
dB-A
Kg (Lb)
EXTERNALINTERNAL
590 x 283 x 99
(23 x 11 x 4)
20 (11)
* Specifications are subject to change without notice.
HEX020VA Heat Exchanger
Instruction Manual
Table of contents
1. Version ........................................................................................................ 1
2. Description . ................................................................................................. 1
2-1. General description ......................................................................... 1
2-2. Main feature ...................................................................................... 2
2-3. Dimension ........................................................................................ 3
2-3-1. Label ............................................................................................ 3
2-3-2. Dimension drawing .................................................................... 4
2-3-3. Mounting panel cutout and waterproof sticking ....................... 4
3. Configuration & Maintenance ................................................................... 5
3-1. Configuration ................................................................................... 5
3-2. Thermal path and airflow baffle ...................................................... 5
3-3. Dust filter maintenance ................................................................... 6
3-4. Heat exchanger maintenance . ......................................................... 6
3-5. Replacement part ............................................................................. 6
4. Electrical specification ............................................................................. 6
4-1. Connection ....................................................................................... 6
4-2. Connector ......................................................................................... 7
5. Environmental condition ........................................................................... 7
5-1. Operating temperature .................................................................... 7
5-2. Storage temperature ........................................................................ 7
5-3. Humidity ........................................................................................... 7
5-4. Ingress protection rating (external side) ....................................... 7
5-5. MTBF ................................................................................................. 7
6. Reliability .................................................................................................... 8
7. Safety certification ..................................................................................... 8
8. Packing list ................................................................................................... 8
9. General Safety and Warnings ..................................................................... 8
1...Version
HEX020VA Heat Exchanger Instruction manual
Rev.
Description Drawn Approved Issue date
00 Issue spec. 01 Correct 2-2 & 5-1 02 Correct section 9 Nick Wang Adam Chen 2016/6/10
2...Description
2-1...General description
XXXXXXXXXXXXXXXX YYWW-SSSS
李武奇
陳英琦 9/30’14
李武奇 陳英琦
12/3’14
INTERNAL EXTERNAL
- 1 -
heat exchange to remove heat from the cabinet.
are separated to prevent the introduction of dust, humidity and dirt.
The fan on the external air loop conforms to IP55 protection rating.
2-2...Main feature
HEX020VA Heat Exchanger Instruction manual
Delta Heat Exchanger (HEX) is designed for direct air to air
The internal and the external air circulation loops of the HEX
Model number HEX020VA
Mounting type Internal door mount
Dimension 590 H x 283 W x 99 D mm
Weight 7.0 ± 0.5 Kg
Cooling capacity
(*Note 1)
20 W/K
Rated voltage DC24 V
Operating voltage DC20~ 26 V
Current 0.9 A
Power 22.0 W
Noise (SPL 1m) 60.0 dB-A
Internal : 2pcs
Fan quantity
External : 2pcs
Fan protection
Polarity
Connection Socket
*Note 1 : The cooling capacity (W/K or W/°C) is defined as Q/ (TI-TA)
Q : Heat dissipation (W) from inside TI : Return temperature of internal air circuit (K OR °C) TA : Ambient temperature of external air circuit (K OR °C)
- 2 -
2-3...Dimension
2-3-1...Label
(3.5”)
HEX020VA Heat Exchanger Instruction manual
(2”)
(2”)
XXXXXXXXXXXXXXXX YYWW-SSSS
NAME PLATE LABEL BARCODE LABEL
(0.6”)
- 3 -
2-3-2...Dimension drawing
XXXXXXXXXXXXXXXX YYWW-SSSS
HEX020VA Heat Exchanger Instruction manual
NOTE :
(1) Material : SGLC T=0.8mm (2) Dimensional tolerance : ± 0.5mm[±0.02"]
Dust filter
INTERNAL
EXTERNAL
2-3-3...Mounting panel cutout and waterproof foam sticking
- 4 -
HEX020VA Heat Exchanger Instruction manual
3...Configuration & Maintenance
3-1...Configuration
The HEX is composed of the key components as the following : Chassis , Heat exchange Core , Controller Internal/External fan tray & dust filter .
3-2...Thermal path and airflow baffle
With forced convection using the axial fan , warmer return air will be blowing into the HEX ,the cooler supply air will be used to cool down the system ; On the opposite side , cooler air will be drawn into the lower inlet and push the heat out from the upper outlet .
The thermal exchange path is shown in the figure below.
Item
Q’ty
Description 1 1 Chassis 2 1 Heat exchange CORE 3 1 Internal fantray 4 1 External fantray 5 1 Controller 6 1 Dust filter
- 5 -
HEX020VA Heat Exchanger Instruction manual
3-3...Dust filter maintenance
Criterion: Monthly
1.Please kindly slide dust filter out upward from trail on external side
2.Use brush and low pressure air to blow out the dust or use water for cleaning
3.Slide dust filter into the rail back
3-4...Heat exchanger maintenance
Criterion: Quarterly
1.Please kindly slide out the dust filter first
2.Use screw driver to remove screw of both external / internal fan tray , be sure to disconnect the fan first , then take out the fan tray
3.Use brush and low pressure air to remove dust on both internal/external fan tray
4.Use brush and low pressure air to remove dust on HEX case and
heat exchange CORE
5.Assembly both internal/external fan tray back and slide dust filter into
the rai
l
3-5...Replaement part
Item Description Delta P/N
1 Dust filter 3242547300 2 Internal fan PFB0924GHEA02 3 External fan PFB0924GHEA01
Controller HEX020VA-000C
4...Electrical specification
4-1...Connection Example : The HEX have to connect with AC-DC output 24V power supply
AC
AC----DC
DC
ACAC
DCDC
PPPPower supply
ower supply
ower supplyower supply
Output
Output voltage
OutputOutput
Output power:
Output power:
Output power: Output power:
MMMMore than 24W
voltage:
voltagevoltage
DC24V
DC24V
DC24VDC24V
ore than 24W
ore than 24W ore than 24W
necessary
necessary
necessarynecessary
Heat exchanger
Heat exchanger
:
: :
Heat exchangerHeat exchanger
HEX
HEX000022220000VA
HEXHEX
Connector
Connector
ConnectorConnector
VA
VAVA
- 6 -
4-2...Connector
On panel 2EHDRM-06P Mate with 2ESDPLM-06P
XXXXXXXXXXXXXXXX YYWW-SSSS
HEX020VA Heat Exchanger Instruction manual
5...Environmental condition
5-1...Operating temperature
-10°C +65°C
5-2....Storage temperature
-40°C +75°C
5-3...Humidity
External air loop : 0 ~ 100% RH Internal air loop: 0 ~ 90% RH, non-condensing
5-4...Ingress protection rating (external side)
IP55(IEC06529)
5-5...MTBF
L10 Fan life is expected to be a minimum 70,000 hours continuous operation at 40°C with 15 ~ 65%RH .@ label rated vo ltage
- 7 -
6. Reliability
Test item Condition High temperature IEC 60068-2-2 Low temperature IEC 60068-2-1 High temp. / High humidity IEC 60068-2-14 TEST Nb Temperature cycle IEC 60068-2-3 Vibration ETSI 300 019-1-4 CLASS 4.1 Ingress protection (External side) IEC 60529 IP55 Salt fog test (External fan) IP55 (NEMA 3) Package bump IEC 60068-2-29
7. Safety certification
Description P/N Safety
HEX020VA Heat Exchanger Instruction manual
Heat exchanger HEX020VA UL , cUL, TUV, CE Fan unit PFB0924GHE series UL , CSA , VDE , CE
8. Packing list
Description Unit Quantity Heat excahnger SET 1 Dust filter PCS 1 Waterproof foam (1M) PCS 3 User manual (English) PCS 1 User manual (Japanese) PCS 1
9. General safety and Warnings
* Some electronic parts have a high operating temperature .
Use caution at all times. * Incorrect installation may cause damage and/or injury. * Installation and maintenance should be performed only by qualified
personnel . Use caution at all times. * Ensure the grounding wire is connected before powering on the system. * Ensure the cover and the mounting hardware are secure upon installation. * All the cables connected to the unit must confirm to UL standards.