Delta Products DTB Series Instruction Sheet

Series Temperature Controller
Instruction Sheet
Thank you very much for purchasing DELTA B Series. Please read this instruction sheet before using your B series to ensure proper operation and please keep this instruction sheet handy for quick reference.
DANGER! Caution! Electric Shock!
1. Do not touch the AC terminals while the power is supplied to the controller to prevent an electric shock.
2. Make sure power is disconnected while checking the unit inside.
3. The symbol REINFORCED INSULATION (equivalent to Class II of IEC 536).
WARNING!
This controller is an open-type temperature controller. Make sure to evaluate any dangerous application in which a serious human injury or serious property damage may occur.
1. Always use recommended solder-less terminals: Fork terminal with isolation (M3 screw, width is 7.0mm (6.0mm for DTB 4824), hole diameter 3.2mm). Screw size: M3 x 6.5 (With 6.8 x 6.8 square washer). Screw size for DTB4824: M3 x 4.5 (With 6.0 x 6.0 square washer). Recommended tightening torque: 0.4 N.m (4kgf.cm). Applicable wire: Solid/twisted wire of 2 mm tighten them properly.
2. Do not allow dust or foreign objects to fall inside the controller to prevent it from malfunctioning.
3. Never modify or disassemble the controller.
4. Do not connect anything to the “No used” terminals.
5. Make sure all wires are connected to the correct polarity of terminals.
6. Do not install and/or use the controller in places subject to:
Dust or corrosive gases and liquid High humidity and high radiation Vibration and shock High voltage and high frequency
7. Must turn power off when wiring and changing a temperature sensor.
8. Be sure to use compensating wires that match the thermocouple types when extending or connecting the thermocouple wires.
9. Please use wires with resistance when extending or connecting a platinum resistance thermometer (RTD).
10. Please keep the wire as short as possible when wiring a platinum resistance thermometer (RTD) to the controller and please route power wires as far as possible from load wires to prevent interference and induced noise.
11. This controller is an open-type unit and must be placed in an enclosure away from high temperature, humidity, dripping water, corrosive materials, airborne dust and electric shock or vibration.
12. Please make sure power cables and signals from instruments are all installed properly before energizing the controller, otherwise serious damage may occur.
13. Please do not touch the terminals in the controller or try to repair the controller when power is applied to prevent an electric shock.
14. Wait at least one minute after power is disconnected to allow capacitors to discharge, and please do not touch any internal circuit within this period.
15. Do not use acid or alkaline liquids for cleaning. Please use a soft, dry cloth to clean the controller.
16. This instrument is not furnished with a power switch or fuse. Therefore, if a fuse or power switch is required, install the protection close to the instrument. Recommended fuse rating: Rated voltage 250 V, Rated current 1 A. Fuse type: Time-lag fuse
17. This controller does not provide overcurrent protection. Use of this product requires that suitable overcurrent protection device(s) must be added to ensure compliance with all relevant electrical standards and codes. (Rated 250 V, 15 Amps max). A suitable disconnecting device should be provided near the controller in the end-use installation.
indicates that this Delta B Series Temperature Controller is protected throughout by DOUBLE INSULATION or
2
, 12AWG to 24AWG. Please be sure to
Display, LED & Pushbuttons
- 1 -
Ordering Information
DTB
DTB Series DTB: Delta B Series Temperature Controller
1 2 3 4
Panel size (W×H)
5
1st output group selection
6
2nd output group selection
7
EVENT inputs / CT function (optional)
8
Power supply
Note 1: DTB4824 series: no optional function provided and no extra alarm output supported, but user can set 2nd output as alarm mode. Note 2: DTB4848 series: only one alarm output when optional function supported, but user can set 2nd output as 2nd alarm output. Note 3: “Valve control” with feedback selection is only available for DTB4896RRV, DTB9696RRV.
4824: 1/32 DIN W48 × H24mm 4848: 1/16 DIN W48 × H48mm
R: Relay output, SPDT (SPST: 1/16 DIN and 1/32 DIN size), 250VAC, 5A V: Voltage pulse output, 14V +10% ~ -20% (Max. 40mA) C: DC current output , 4 ~ 20mA L: Linear voltage output, 0 ~ 5V, 0 ~ 10VDC
R: Relay output, SPDT (SPST: 1/16 DIN and 1/32 DIN size), 250VAC, 5A V: Voltage pulse output, 14V +10% ~ -20% (Max. 40mA)
None: No EVENT input , No CT (Current transformer) E: EVENT input is provided, No CT (Current
transformer) None: AC 100 ~ 240V; D: DC24V
1 2 3 4 5 6 7 8
4896: 1/8 DIN W48 × H96mm 9696: 1/4 DIN W96 × H96mm
T: CT (Current transformer) is provided, No EVENT input
V: Valve control
Specifications
Input voltage AC100 ~ 240V, 50/60Hz; DC24V±10% Operation voltage rrange Rated voltage: AC 85% ~ 110%; DC 90 ~ 110% Power consumption 5VA max. Memory Protection EEPROM 4K bit (non-volatile memory (number of writes: 100,000) Display method 2 line x 4 character 7-segment LED display Process value (PV): Red color, Set point (SV): Green color
Thermocouple: K, J, T, E, N, R, S, B, L, U, TXK
Sensor type
Control mode PID, ON/OFF, Manual or PID program control (Ramp/Soak control)
Control output
Display accuracy 0 or 1 digit to the right of the decimal point (selectable) Sampling rate Analog input: 150 msec/ per scan Thermocouple or Platinum RTD: 400 msec/per scan RS-485 communication MODBUS ASCII / RTU communication protocol Vibration resistance 10 to 55Hz, 10m/s2 for 10min, each in X, Y and Z directions Shock resistance Max. 300m/ s2, 3 times in each 3 axes, 6 directions Ambient temperature 0oC ~ +50oC Storage temperature -20oC ~ +65oC Altitude 2,000m or less Relative humidity 35% ~ 80% (non-condensing) Panel protection level IP65
3-wire Platinum RTD: Pt100, JPt100 Analog input: 0 ~ 5V, 0 ~ 10V, 0 ~ 20 m A, 4 ~ 20 m A, 0 ~ 50mV
Relay output: SPDT (SPST: 1/16 DIN and 1/32 DIN size), Max. load 250VAC, 5A resistive load Voltage pulse output: DC 14V, Max. output current 40mA Current output: DC 4 ~ 20m A output (Load resistance: Max. 600) Linear voltage output: 0 ~ 10V
Temperature Sensor Type & Temperature Range
Input Temperature Sensor Type Register Value LED Display Temperature Range
0 ~ 50mV Analog Input 17
- 2 -
-999 ~ 9,999
Input Temperature Sensor Type Register Value LED Display Temperature Range
4 ~ 20mA Analog Input 16 0 ~ 20mA Analog Input 15 0V ~ 10V Analog Input 14
0V ~ 5V Analog Input 13
Platinum Resistance (Pt100) 12
Platinum Resistance (JPt100) 11
Thermocouple TXK type 10
Thermocouple U type 9 Thermocouple L type 8 Thermocouple B type 7 Thermocouple S type 6 Thermocouple R type 5 Thermocouple N type 4 Thermocouple E type 3 Thermocouple T type 2 Thermocouple J type 1 Thermocouple K type 0
Note 1: An internal 249 precision resistor for the current input is built-in, please refer to the item “How To Set Up Current Input”. Note 2:
(Operation mode) must be set if user wishes to specify decimal point position. Except for the thermocouple B, S, R type, the
decimal point positions of all the other thermocouple type input sensors can be set. The default range of analog input is -999 ~ 9,999. For example, when a 0 ~ 20mA analog input is selected as the input temperature sensor
type, -999 indicates 0mA and 9,999 indicates 20mA. If change the input range to 0 ~ 2,000, then 0 indicates 0mA and 2,000 indicates 20mA. One display scale is equal to 0.01mA.
-999 ~ 9,999
-999 ~ 9,999
-999 ~ 9,999
-999 ~ 9,999
-200 ~ 600
-20 ~ 400
-200 ~ 800
-200 ~ 500
-200 ~ 850
100 ~ 1,800
0 ~ 1,700 0 ~ 1,700
-200 ~ 1,300 0 ~ 600
-200 ~ 400
-100 ~ 1,200
-200 ~ 1,300
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
o
C
Operation
There are three modes of operation: operation, regulation and initial setting. When power is applied, controller gets into the operation
mode. Press the initial setting mode. Pressing the
operation mode.
PV/SV: Sets the temperature set point and displays the temperature process value. Use keys to set the temperature set point. Setting method: While in any function mode, press the key to select the desired function and use the keys to change
settings.
Press key to save the changes. The next flow chart shows how to switch for settings and internal functions:
Regulation Mode Operation Mode Initial Setting Mode
Auto-tuning
(Set in PID control and RUN mode)
4 groups PID modes (n=0~3). When
n=4, PID control is auto regulated.
key to switch to regulation mode. If the key is pressed for more than 3 seconds, controller will switch to the
key while in the regulation mode or initial setting mode, forces the controller to return to the
Press
Press
Use key to set temperature set
point
Control setting RUN or STOP
Press
Press
Set input type
Press
Set temperature unit
(Not display when in analog input)
Press
- 3 -
Regulation Mode Operation Mode Initial Setting Mode
PD control offset setting
(When PID control is ON and Ti=0, set the value of PdoF.)
Heating hysteresis setting
(Set in ON/OFF control mode)
Cooling hysteresis setting
(Set in ON/OFF control mode)
or Heating/Cooling control
cycle setting (Set in PID control mode)
Control cycle setting of 2nd output
group (Set in PID control and Dual Loop output
control mode)
P value of 1st & 2nd output group
during dual loop output control P value of 2
output group x COEF
(Set in Dual Loop output control mode)
value (Displayed with valve control is ON)
Press
value (Displayed when valve control is ON)
to full open (Displayed when valve control is ON)
(Displayed when valve control is ON)
nd
output group=(P value of 1st
Deadband
Switch setting for feedback signal of
Automatically regulate feedback
Time setting for valve from full close
Valve Deadband setting
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Start pattern setting
(PID program control and
Time
setting.
Press
Decimal point position selection
(except for B, S, R type, all the other types can be set)
Press
Upper-limit alarm 1
(This parameter is available only when ALA1 function is enabled.)
Press
Lower-limit alarm 1 (This parameter is available only when ALA1 function is enabled.)
Press
Upper-limit alarm 2 (This parameter is available only when ALA2 function is enabled.)
Press
Lower-limit alarm 2 (This parameter is available only when ALA2 function is enabled.)
Press
Upper-limit alarm 3 (This parameter is available only when ALA3 function is enabled.)
Press
Lower-limit alarm 3 (This parameter is available only when ALA3 function is enabled.)
Press
Setting lock mode
Press
Display and adjust output value of 1st output group
(Display in PID control mode and manual RUN mode)
Press
Display and adjust output value of 2 output group
(Display in dual loop PID control mode and manual RUN mode)
Press
Set upper-limit of temperature range
Set lower-limit of temperature range
Select control mode (See “Pattern
and Set Editing Selection” for detail)
Select heating/cooling control or dual
loop output control
Alarm 1 mode setting
Alarm 2 mode setting
Alarm 3 mode setting
Set system alarm
Enable/disable communication write
function
ASCII, RTU communication formats
selection
nd
Communication address setting
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
Press
- 4 -