Delta Elektronika 240 s 24 schematic

P.O. BOX 27 4300 AA ZIERIKZEE NETH ER LANDS TEL. +31 111 413656
FAX +31 111 416919
www.DeltaPowerSupplies.com
240 W SWITCHED MODE DC POWER SUPPLY
240 S 24 24 V 10 A
AD JUST ABLE 12 - 30 V Max. cur rent:12 A at 12 - 15 V
10 A at 24 V 8 A at 30 V
Out put : Ad just able 12 - 30 V with a screw driver or
an a log pro gram ma ble by 2 - 5 V. Fac tory set at 24 V.
In put : AC 195 - 265 V 48 - 62 Hz 1.8 A rms
100 - 132 V 48 - 62 Hz 3.2 A rms
For DC or op er a tion at 400 Hz con tact factory Fuse 4 A T at 230 V, 6.3 A T at 110 V
SELV / PELV
EMC : EN 61204-3 Low Volt age DC Power Sup plies
EN 61000-6-3 (EN 55022B) Ge neric Emis sions EN 61000-6-2 Ge neric Immunity
Ef fi ciency : 87% at 240 W out put
(max. heat dis si pa tion 36W)
Reg u la tion
Load 0 - 100% : 50 mV (10 mV when us ing sense points) Line 198 - 265 V AC : 10 mV
Rip ple + noise : 5 mV rms, 15 mV p-p Temp. co ef fi cient : 5.10–5 per °C Sta bil ity dur ing 8 hrs : 3.10–4 (af ter 1 hr warm up) Out put im ped ance : 0.1 Ohm up to 100 kHz Re cov ery time : In su la tion
In put / out put : 3750 Vrms (1 min.) In put / case : 2500 Vrms (1 min.) Out put / case : 500 V DC
Hold-up time : 20 ms (24 V / 10 A, 230 V AC in put) Am bi ent tem per a ture : Op er ating: –10 to +50 °C. Above 50 °C de rate cur rent lin early to 20% at 80 °C.
Se ries op er a tion : Up to 500 V to tal volt age Par al lel op er a tion : At 90% of max. cur rent (In ter nal cur rent limit switch at low). The ex tra pos i tive out put
Alarm cir cuit : A re lay con tact changes over when the out put drops 10% be low the set value.
Cur rent limit : Con stant power limit from 30 to 22 V, con stant cur rent be low 22 V.
OVL : Limits the max i mum out put volt age at about 33 V. MTBF : 1 000 000 hrs Di men sions and weight: 240 x 71 x 156 mm (h x w x d) 14 TE 6 U 2.0 kg
200 µs af ter 50 - 100% load step
Eurocassette 6 HE high, 14 TE wide (front panel 16 TE). Is sup plied incl. H15 mat ing con nec tor (faston ver sion), CL15 and 2 pcs H155.
Stor age: –40 to +85 °C.
ter mi nal, via a built-in Schottky di ode, sep a rates the out put cir cuits when units are op er ated in par al lel.
Gold con tact, rat ing max. 100 mA / 30 V.
Cur rent limit pro tects against con tin u ous over load and short cir cuit.
CL15
Mount ing : The 240 S 24 should be mounted ver ti cally for op ti mal cool ing. When mounted hor i zon tally, put
in ter nal cur rent limit switch at low and keep the am bi ent temp. be low 40 °C.
Re mote sens ing : The sense points (pin 8 and 10) are in ter nally con nected to + and – out put (pin 6 and pin 12), but
these links can be re moved when re mote sens ing is re quired. The volt age drop across the leads plus the load can never ex ceed the sup ply max i mum out put rat ing. For ex am ple at 24 V 8 A it is pos si ble to com pen sate 6 V (3 V per lead) be cause the unit can sup ply max. 30 V 8 A.
Re mote progr. : 2 - 5 V be tween pin 14 and 10 gives 12 - 30 V out put (in ter nal switch in po si tion P). Pro gramming in -
put is not iso lated (con nected to – out put).
Volt age adj. with ex ter nal potmeter: Is pos si ble if an in ter nal link and a re sis tor are re moved.
H 15 con nec tor
Re dun dant par al lel op er a tion with un der volt age alarm. Out puts are sep a rated by the built-in Schottky se ries di odes.
240 S 24 with bench adapter BA 150
240 S 24
Front panel F 19/2 for hor i zon tal 19" rack mount ing of one unit
Front panel F 16-6
Two ways of ver ti cal wall moun t ing. Mating con nec tor (H15 with faston or screw con nec tions) can be fixed with sup plied clamp.