Delta Electronika SM3300 Series, SM66-AR-110, SM 18-220, SM 100-AR-75, SM 660-AR-11 Quick Start Manual

...
DELTA ELEKTRONIKA B.V.
DC POWER SUPPLIES
SM3300-se ries
SM 18-220
SM 66-AR-110
SM 100-AR-75
SM 330-AR-22
Vissersdijk 4, 4301 ND
Zierikzee, the Netherlands
www.DeltaPowerSupplies.com
Tel. +31 111 413656
SM 660-AR-11
Firm ware Up date
It is strongly rec om mended, first to per form a firm ware up date be fore fur ther op er a tion.
See chap ter Quick Start, para graph 2.
QUICK START GUIDE
SM3300 SAFETY INSTRUCTIONS
1 SAFETY INSTRUCTIONS SM3300
1 Caution
The following safety precautions must be observed during all phases of operation, service and repair of this equipment. Failure to comply with the safety precautions or warnings in this document violates safety standards of design, manufacture and intended use of this equipment and may impair the built-in protections within. Delta Elektronika shall not be liable for user’s failure to comply with these requirements.
2 Installation Category
The Delta Elektronika power supplies have been evaluated to installation category II (Over voltage category II).
3 Grounding of Mains Input
This product is a safety Class 1 instrument. To minimize shock hazard, the instrument chassis must be connected t o the AC Power Supply mains through a three or four conductor power cable for resp. a single or three phase unit, with the ground wire firmly connected to an electrical ground (safety ground) at the power outlet.
For instruments designed to be hard-wired to supply mains, the protective earth terminal must be connected to the safety electrical ground before another connection is made. Any interruption of the protective ground conductor, or disconnection of the protective earth terminal will cause a potential shock hazard that might cause personal injury.
4 Grounding of Power Output
If the output of a unit is specified to deliver maximum 60VDC, and either the negative or positive power output is grounded, the voltage on the power outputs and sense connections can be considered safe.
Warning:
When the positive power output can exceed 60VDC in respect to the negative outpu measures must be taken to ensure safety isolation of the power outputs and sense connections.
Warning:
When the negative power output of the unit can exceed 60VDC / 42.4Vpk in respect to ground, additional external measures must be taken to ensure safety isolation of the power outputs and sense connections.
The standard LAN and Interlock connectors and optional interfaces are at ground level and can be considered safe if the negative power output of the unit does not exceed 1000VDC / 707Vpk in respect to ground.
Caution 1: If a low voltage unit has both power outputs floating, or if the output is in series with an external high AC or DC voltage, the negative power output can exceed the safe value in respect to ground as specified in the above warning!
Caution 2: Although a high voltage unit is set to a safe voltage below 60VDC, for safety it must always be considered as high voltage unit! Wrong operation, a programming error or an external defect can result in an unsafe high output voltage.
For more information and schematics regards Grounding and Safety, see the special application note "Safe operation of a power supply" on the Delta Elektronika website.
t, additional external
5 Fuses
Fuses must be changed by authorized Delta Elektronika service personnel only, for continued protection against risk of fire.
6 Input Ratings
Do not use an AC Supply which exceeds the input voltage and frequency rating of this instrument. The input voltage and frequency rating of the Delta Elektronika power supply series ar e stated in de accompanying datasheet.
7 Live Circuits
Operating personnel must not remove the instrument cover. No internal adjustment or component replacement is allowed by non Delta Elektronika qualified personnel. Never replace components with the power cable connected. To avoid injuries, always disconnect power, discharge circuits and remove external voltage sources before touching components.
8 Parts Substitutions & Modifications
Parts substitutions and modifications are allowed by authorized Delta Elektronika service personnel only. For repairs or modifications the unit must be returned to a Delta Elektronika service facility.
rev. Dec.2017 DELTA ELEKTRONIKA B.V. Page 1 - 1
SAFETY INSTRUCTIONS SM3300
!
9 Removal of (safety) covers
Safety cover(s) are used to cover potentially hazardous v oltages. Observe the following when removing safety cover(s):
Switch off the unit.
Disconnect the unit from the mains supply.
Wait for 3 minutes to allow internal capacitors to discharge.
Unscrew the screws and remove the cover(s).
Always place the cover(s) back before connecting the unit to the mains supply again.
10 Environmental Conditions
The Delta Elektronika power supplies safety approval applies to the following operating conditions:
Indoor use
Ambient temperature : 20 to 50 °C
Maximum relative humidity : 95%, non condensing, up to 40 °C
: 75%, non condensing, up to 50 °C
Altitude : up to 2000 m
Pollution degree : 2
Cau tion risk of elec tri cal Shock
Instruction manual symbol. The instrument will be marked with this symbol when it is necessary for the user to refer to the instruction manual
Pro tec tive ground con duc tor ter mi nal
Off (sup ply)
o
On (sup ply)
I
11 Canada
This product has been tested to the requirements of CAN/CS A-C22.2 No. 61010-1, second edition, including Amendment 1, or a later version of the same standard incorporating the same level of testing requirements
12 cTUVus
WEEE (Waste Electrical & Electronic Equipment)
1 Correct Disposal of this Product
Applicable in the European Union.
This marking shown on the product, its packing or its literature indicates that it should not be disposed with other wastes at the end of its working life, but should be collected separately to recycle it responsibly to promote the sustainable reuse of material resources.
Page 1 - 2 DELTA ELEKTRONIKA B.V. rev. Dec.2017
SM3300 QUICK START
2 QUICK START GUIDE - SM3300
1 Con nect ing the unit
Mains switch
A-knobV-knob
LAN
CON B1 & CON B2
CON D
fig. 2 - 1
Warn ing! Never make con nec tions to the Power In puts and Out puts or the Sense Con nec tor when the unit is con nected to the mains sup ply or power out let! Safety cov ers are used to cover these in- and out puts. Care fully read the chap ter "Safety In struc tions" in t his man ual be fore con nect ing or op er at ing the unit!
Warn ing! Some com po nents in side the power sup ply are at AC volt age even when the On/Off switch is in the off po si tion. There fore a readily ac ces si ble, ap pro pri ately rated, dis con nect de vice shall be in cor po rated ex ter nal to the equip ment.
The power sup ply shall be con nected to the mains sup ply via a pro tec tion de vice with a rat ing of max i mum 16A. For ex am ple a cir cuit breaker or fuses etc.
AC POWER TER MI NALS (AC-MAINS)
This con nec tor is lo cated at the rear side, marked as CON D.
Use a ca ble with a di am e ter of 2.5 mm
Use the in cluded 4-pole header with the mark ings L1, L2, L3, PE for con nect ing the wire to the unit (see fig. 2 - 1).
The mount ing torque for the header ter mi nals is 0.6 Nm.
Al ways con nect the PE ter mi nal to the Pro tec tive Earth, no neu tral con nec tion is re quired.
The unit can op er ate both on a sin gle phase and a 3 phase grid, with a rated volt age of 200...480VAC.
Af ter in stal la tion, con nect the pull re lief and add the safety cover over the AC ter mi nals.
2
for each wire and a suf fi cient volt age rat ing for the AC in put volt age of the unit.
DC POWER TER MI NALS
These ter mi nals are lo cated at the rear side, marked as CON B1 (PLUS) and B2 (MI NUS).
Use ca bles with a suf fi cient volt age rat ing for the max i mum out put volt age of the unit.
The ca ble di am e ter de pends on the type of unit, see ta ble 2.1. For all units the ter mi nals are bolts size M8 and re quire a mount ing torque of 20Nm.
Use low re sis tive con nec tions be tween the power sup ply and the load:
- Mount the ca ble lugs di rectly on the DC ter mi nals followed by a washer, a split washer and a nut. Al ways in this or der!
- Never place wash ers be tween the lugs and the strips - this can re sult in ex ces sive heat!
- Only use nuts and wash ers sup plied with the unit.
The DC power ter mi nals are float ing in re la tion to Pro tec tive Earth.
Af ter in stal la tion mount the safety cover over the DC power ter mi nals.
Unit DC-ca bles
SM18-220 70 SM66-AR-110 35 SM100-AR-75 25 SM330-AR-22 4 SM660-AR-11 2.5
ta ble 2 - 1
Rec om mended
ca ble di am e ters
LAN-CONNECTOR
In sert a stan dard RJ45 net work ca ble to the LAN-con nec tor at the rear side, see fig. 2 - 1 and make con nec tion to a Lo cal
Area Net work (LAN) to per form a firm ware up date and use the units' web browser, see chap ter 2.
The LAN-connector is at Pro tec tive Earth level.
LOAD SENS ING, IN TER LOCK, USB, IN TER FACES, SE RIES-PAR AL LEL, MAS TER/SLAVE
Re fer to user man ual for con nect ing and us ing these fea tures and op tions.
2 Op er at ing the unit
FIRM WARE UP DATE
Switch the unit on by ro tat ing the mains switch on the front panel clock wise.
In the unit menu, check the firm ware re vi sion via Menu > Sys tem > info > Unit > Version.
On a com puter, check at www.DeltaPowerSupplies.com if there is new firm ware avail able via:
Prod ucts > SM3300 > Down loads.
If newer, download the firm ware pack age to the com puter and con nected this to the same LAN as the unit.
In the unit menu, check the IP-ad dress via Menu > In ter faces > LAN > Ad dress*.
On the com puter, open the SM3300 web in ter face us ing an internet browser by en ter ing the IP-ad dress of the unit in the
ad dress bar of the browser.
In the web in ter face, go to Ad min is tra tion > Firm ware.
Se lect "Choose File" and browse to the down loaded pack age, en ter pass word and "Start Up date".
[mm2]
*Note: when DHCP is en abled, the IP-ad dress can change, for ex am ple af ter a power cy cle.
rev. Dec.2017 DELTA ELEKTRONIKA B.V. Page 2 - 1
QUICK START SM3300
cv
9.2V 2.10A
front 9.2V front 10.00A
Menu Lock
on/OFF
Menu Lock
on/OFF
0.0V 0.00A
front 0.0V front 0.00A
Menu Lock
on/OFF
0.0V 0.00A
cv
cc
front 0.0V front 0.00A
FIRST OP ER A TION
The first line in the front dis play in di cates the ac tual out put volt age and cur rent.
The sec ond line shows the set tings of the con trols.
Check the text 'front' is in di cated - this means the unit is in lo cal-op er a tion and
can be con trolled by the V-knob and A-knob at the front panel.
Switch the out put on by press ing the on/OFF but ton.
Turn the V- and A-knob a half turn clock wise. De pend ing on the load, a volt age
should now be pres ent on the out put and a cur rent will run through the load.
De pend ing on the load and set tings, the unit will be ei ther in con stant volt age or
con stant current mode, re spec tively CV- or CC-mode.
Re spec tively the in di ca tion 'CV' will ap pear on the first line, next to the ac tual volt -
age value. The in di ca tion 'CC' will ap pear next to the ac tual cur rent value.
LIM I TA TION OF SET TINGS
By de fault, the set tings for CV and CC Limit are set to the max i mum.
Change the limit set tings via Menu > Pro tec tion > Lim its.
RE MOTE PRO GRAM MING
By de fault a unit is in lo cal op er a tion, see fig. 2 - 3.
In re mote op er a tion dif fer ent pro gram ming op tions are avail able such as 'eth',
'web', 'seq', 'slot1' etc.
Via the front menu the source can be set to the re quired pro gram ming in put via:
Menu > Con fig u ra tion > Source.
When con nected to LAN, en ter the unit's IP-ad dress in a web browser to open the
web in ter face.
With this in ter face all above de scribed pa ram e ters plus ad di tional pa ram e ters can be set and read.
For more in for ma tion, see the chap ter Re mote
Pro gram ming of the user man ual.
ac tual volt age ac tual cur rent
set volt age set cur rent
in di ca tor for CV-mode CC-mode
lo cal op er a tion
fig. 2 - 2, Start-up set tings.
lo cal op er a tion CV-mode
fig. 2 - 3, 19W out put power.
3 Down load User Man ual
FULL VER SION
Check at www.DeltaPowerSupplies.com for the full
ver sion of the user man ual via: Prod ucts > SM15K > Down loads.
It is strongly rec om mended to reg u larly check for new ver sions of the user man ual and firm ware for ad di tional func tion al ity
and im prove ments.
fig. 2 - 4, The front console of the web in ter face for set ting
of the in put and mon i tor ing var i ous pa ram e ters.
fig. 2 - 5, Reg u larly check for new ver sions of user manual
and firmware.
Page 2 - 2 DELTA ELEKTRONIKA B.V. rev. Dec.2017
SM3300 EC DECLARATION
DELTA ELEKTRONIKA B.V.
DC POWER SUPPLIES
EC Dec la ra tion of Con for mity - SM3300-series
We
Delta Elektronika Vissersdijk 4 4301 ND ZIERIKZEE The Neth er lands
De clare un der sole re spon si bil ity that the fol low ing Power Sup plies:
SM 18-220 SM 66-AR-110 SM 100-AR-75 SM 330-AR-22 SM 660-AR-11
Meet the in tent of Di rec tives
2014/30/EC for Elec tro mag netic Com pat i bil ity 2014/35/EC re gard ing Elec tri cal Safety. (Low Volt age Di rec tive) 2011/65/EC Re duc tion of Haz ard ous Sub stances (RoHS2)
Vissersdijk 4, 4301 ND
Zierikzee, the Netherlands
www.DeltaPowerSupplies.com
Tel. +31 111 413656
Com pli ance was dem on strated to the fol low ing spec i fi ca tion as listed in the of fi cial Jour nal of the Eu ro pean Com mu ni ties:
EN 61000-6-3 Ge neric Emis sions: (res i den tial, light in dus trial)
EN 55022 Ra di ated and con ducted, Class B EN 61000-3-2 Power Har mon ics EN 61000-3-3 Volt age fluc tu a tion and flicker
EN 61000-6-1 Ge neric Im mu nity: (res i den tial, light in dus trial) EN 61000-6-2 Ge neric Im mu nity: (in dus trial en vi ron ment)
EN 61000-4-2 Elec tro static Dis charge EN 61000-4-3 Ra di ated elec tro mag netic fields EN 61000-4-4 Elec tri cal Fast Tran sients / Bursts EN 61000-4-5 Surge on DC out put EN 61000-4-5 Surge on line in put EN 61000-4-5 Surge on Sig nal EN 61000-4-6 RF com mon mode, con ducted EN 61000-4-11 Volt age vari a tions and dips EN 61000-4-8 Power-fre quency mag netic field
EN 60950 Safety of IT equip ment EN 61010 Safety of elec tri cal equip ment for mea sure ment, con trol and lab o ra tory use
J. Koopman, Man ag ing di rec tor Zierikzee, De cem ber 2017
rev. Dec.2017 DELTA ELEKTRONIKA B.V. Page 3 - 1