Delta Electronics SSW 230V-6kVA, SSW 230 V - 20 kVA User Manual

The Static Switch Product Line
SSW 230V-6kVA
SSW 230 V – 20 kVA
Description:
The static switch product line is a micro-controller driven state-of-the-art switch between the AC mains and the inverter to provide uninterruptible AC power. After an extremely quick detection of a mains fault, the static switch transfers the load almost without cut off to the redundant AC line. A communication and synchronization bus is responsible for the system performance and the Delta inverters are synchronized to the public AC mains. Modular UPS configurations in ON LINE or OFF LINE mode can be realized in combination with Delta inverters and DC power systems with battery backup.
Features
Two static switch models 6 kVA and 20 kVA
230 Vrms / 50 Hz single phase
ON LINE or OFF LINE mode selection
High performance AC line quality monitoring
Quick detection of AC faults
Configurable switching criteria
Load transfer of up to 6 kVA or 20 kVA
Synchronization of the Delta inverter group
Convection cooled
Compact and light
Power connectors on the rear
Specification
General
Product name SSW 230 V – 6 kVA SSW 230 V – 20 kVA Safety EN 60 950, class I EMI, radiated compliant with EN 55 022, class B EN 300 386-2 Cooling Convection cooled
Public AC Input
Voltage range 184 ... 276 V Frequency range 45 - 55 Hz EMI, conducted compliant with EN 55022, class B
Inverter AC Input
Voltage range 230 V Frequency 50 Hz EMI, conducted compliant with EN 55022, class B
AC Output
Voltage, nominal 230 V Frequency, nominal 50 Hz Maximum power 6 kVA / 20 kVA cosφ, range 0 .. 1 ind. and cap.
EMI, conducted compliant with EN 55022, class B
Mechanics
Width, overall 2.8” / 70 mm ; 5.3” / 135 mm Depth, overall 13.8” / 350 mm ; 13.8” / 350 mm Height, overall 12.2” / 311 mm ; 12.2” / 7U / 311 mm Weight 7.7 lb / 3.5 kg ; 18.0 lb / 8.6 kg
Switching Criteria
According to ETS 300 132-1 Static rms deviation ± 10 % Dynamic rms deviation ± 15 % for max. 500 ms Static freq. deviation ± 2Hz Dynamic freq. deviation ± 2Hz for 5 s maximum
Environment
Operating temperature 0 ... + 50 °C Relative humidity 95 % max, non condensing
6kVA ; 20kVA
rms
rms
± 1%
rms
Loading...