Delta Electronics RTU-DNET User Manual

RTU-DNET
DeviceNet Remote I/O Communication Module
Application Manual
DeviceNet Remote I/O Communication Module R TU-DNET
Warning
3
Please read this instruction carefully before use and follow this instruction to operate the device in order to prevent
damages on the device or injuries to staff.
3
Switch off the power before wiring.
3
RTU-DNET is an OPEN TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required for operating the enclosure) in case danger and damage on the device may occur.
3
RTU-DNET is to be used for controlling the operating machine and equipment. In order not to damage it, only
qualified professional staff familiar with the structure and operation of RTU-DNET can install, operate, wire and maintain it.
3
DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check
all the wirings again before switching on the power and DO NOT touch any terminal when the power is switched on. Make sure the ground terminal
1 INTRODUCTION ....................................................................................................................................3
2 PRODUCT PROFILE & OUTLINE .........................................................................................................5
Table of Contents
1.1 Features......................................................................................................................................3
1.2 Functions.....................................................................................................................................3
1.3 Specifications..............................................................................................................................3
1.4 Extension Modules Connectable to RTU-DNET .........................................................................4
2.1 Dimension ...................................................................................................................................5
2.2 Product Profiles...........................................................................................................................5
2.3 DeviceNet Connection Port.........................................................................................................6
2.4 RUN/STOP Switch......................................................................................................................6
is correctly grounded in order to prevent electromagnetic interference.
2.5 Address Switch ...........................................................................................................................6
2.6 Function Switch...........................................................................................................................6
2.7 Extension Port.............................................................................................................................7
3 BASIC OPERATION...............................................................................................................................7
3.1 Connecting RTU-DNET to DVP Slim DI/DO Extension Unit....................................................... 7
3.2 Installing RTU-DNET and DVP Slim DI/DO on DIN Rail.............................................................7
3.3 Connecting to DeviceNet Connection Port..................................................................................8
4 HOW TO CONFIGURE RTU-DNET .......................................................................................................8
4.1 Terms ..........................................................................................................................................8
4.2 Format of Requet Message and Response Message.................................................................9
DVP-PLC Application Manual
1
DeviceNet Remote I/O Communication Module R TU-DNET
4.3 DeviceNet I/O Mapping Data.................................................................................................... 14
4.4 Example.................................................................................................................................... 17
5 HOW TO CONSTRUCT A DEVICENET NETWORK USING RTU-DNET...........................................22
5.1 How to Construct DeviceNet by RTU-DNET ............................................................................22
5.2 How to Configure Network by DeviceNet Network Configuration Tool..................................... 22
6 LED INDICATOR & TROUBLE-SHOOTING ....................................................................................... 31
6.1 POWER LED............................................................................................................................31
6.2 NS LED..................................................................................................................................... 31
6.3 MS LED.................................................................................................................................... 31
6.4 ALARM LED............................................................................................................................. 31
6.5 RUN LED.................................................................................................................................. 32
2
DVP-PLC Application Manual
DeviceNet Remote I/O Communication Module R TU-DNET
A
1 Introduction
1. To ensure correct installation and operation of RTU-DNET, please read this chapter carefully before using your RTU-DNET.
2. This chapter only provides introductory information on RTU-DNET. For more detailed information on DeviceNet protocol, please refer to relevant references or literatures.
3. RTU-DNET is a remote I/O communication module applicable to the connectio n between DeviceNet an d DVP Slim DIDO module and special modules. RTU-DNET offers functions such as status diagnosis, error treatment and so on.
1.1 Features
z Supports Group 2 only servers. z Supports explicit connection via predefined Master/Slave connection set. z Supports polling z Supports EDS file configuration in DeviceNet network configuration tools. z Max. 256 digital I/O points extendable. z Max. 8 special modules extendable.
1.2 Functions
Item Explanation
Graphic configuration interface
Data retention
uto extension module
identification
Diagnosis
Status inquiry Error inquiry The user can read the error through DeviceNet network configuration tool. Error treatment
Flexible configuration
RTU-DNET supports gra phic configuration interface in DeviceNet network configuration tools.
The user can choose either to retain or give up the data in the register when RTU-DNET is offline.
The user can automatically identify the special module or the enumber of points on the DVP Slim DI/DO extension unit connected to RTU-DNET through DeviceNet network configuration tool.
RTU-DNET is able to diagnose the status of the special module connected to it. When an error occurs, The ALARM LED on RTU-DNET will flash in red.
RTU-DNET is able to inquire the connection status bet ween itself and the extension module in DeviceNet network configuration tool.
The user can choose a method to correct the error through DeviceNet network configuration tool.
The user can configure the control register (CR) in the special module in any way as the I/O mapping data for DeviceNet.
1.3 Specifications
DeviceNet connection
Transmission method CAN Electrical isolation 500 VDC Interface Removable connector (5.08mm) Transmission cable 2-wire twister shielded cable with 2-wire bus power and drain
Communication
Message type I/O polling, explicit
DVP-PLC Application Manual
3
DeviceNet Remote I/O Communication Module R TU-DNET
Baud rates 125 kbps; 250 kbps; 500 kbps
Electrical specification
Voltage 11 ~ 25 VDC, supplied by internal bus from PLC MPU Current 28mA (typical), 125mA impulse current (24 VDC)
Environment
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV, Digital I/O: 1KV
Noise immunity
Operation 0ºC ~ 55ºC (temperature); 50 ~ 95% (humidity); pollution degree 2 Storage -25ºC ~ 70ºC (temperature); 5 ~ 95% (humidity)
Analog & Communication I/O: 1KV Damped-Oscillatory Wav e: Power Line: 1KV, Digital I/O: 1KV RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Vibration/shock resistance
Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea)
Certificates IEC 61131-2, UL508
1.4 Extension Modules Connectable to RTU-DNET
T E N D
­U T R
T S 8 0
­P V D
DVP Slim DI/DO extension units connectable to RTU-DNET
Slim DI/DO
(model name)
(DeviceNet RTU-DNET)
DVP-08SM11N N/A 8 bits
P S 6 1
­P V D
I/O mapping data
D A
4 0
­P V D
C T 4 0
­P V D
T P 4 0
­P V D
A D
2 0
­P V D
I/O mapping data
(RTU-DNET DeviceNet)
DVP-08SN11R/T 8 bits N/A DVP-08SP11R/T 8 bits 8 bits DVP-16SP11R/T 8 bits 8 bits
DVP-08ST N/A 8 bits
Special modules connectable to RTU-DNET
Default I/O mapping data
Special module
(DeviceNet RTU-DNET)
(model name)
Start CR Length (words) Start CR Length (words) DVP-02DA CR#10 2 N/A N/A DVP-04DA CR#6 4 N/A N/A DVP-04AD N/A N/A CR#12 4 DVP-06AD N/A N/A CR#12 6
4
I/O mapping data
(RTU-DNET DeviceNet)
DVP-PLC Application Manual
DeviceNet Remote I/O Communication Module R TU-DNET
Special module
Default I/O mapping data
(DeviceNet RTU-DNET)
I/O mapping data
(RTU-DNET DeviceNet)
(model name)
Start CR Length (words) Start CR Length (words) DVP-04TC N/A N/A CR#14 4 DVP-04PT N/A N/A CR#18 4 DVP-06XA CR#10 2 CR#12 4 DVP-01PU CR#42 4 CR#33 4
Note: While connected to a special module, the start CR and length of upload/download data of RTU-DNET can be set up in DeviceNet network configuration tool.
2 Product Profile & Outline
2.1 Dimension
POWER
MS
RUN
5
6
NS
4
ALARM
7
3
1
8
2
x10
9
1
0
5
6
4
RUN
7
3
0
8
2
x10
9
1
0
DR 1 DR 0
STOP
IN 1 IN 0
2.2 Product Profiles
1. Extension port 7. NS (Network Status) indicator
2. Address switch 8. RUN indicator
3. Function switch 9. ALARM indicator
RTU-DNET
5 6 7
4 3
POWER
MS
5
6
NS
4
3 2
9
1
0
5
6
4
RUN
3 2
9
1
0
STOP
RTU-DNET
8
RUN
ALARM
7
9
1
8
x10
2
7
0
8
x10
DR 1 DR 0 IN 1 IN 0
11
1
10
12
4. RUN/STOP switch 10. DeviceNet connection port
5. POWER indicator 11. DIN rail
6. MS (Module Status) indicator 12. DIN rail clip
DVP-PLC Application Manual
5
DeviceNet Remote I/O Communication Module R TU-DNET
2.3 DeviceNet Connection Port
The connector is used on the connection to DeviceNet. Wire by using the connector enclosed with RTU-DNET.
PIN Signal Color Content
1 V- Black 0 VDC 2 CAN_L Blue Signal-
5 4 3
3 SHIELD - Shielded 4 CAN_H White Signal+ 5 V+ Red 24 VDC
2 1
2.4 RUN/STOP Switch
RUN/STOP action Explanation
1. Re-detecting the extension module.
STOP RUN
2. Reading/writing the data in the extension module.
RUN STOP
Stop reading/ writing the data in the extension module.
RUN
STOP
2.5 Address Switch
The switch is used on setting up the node address of RTU-DNET on DeviceNet. Range: 00 ~ 63 (64 ~ 99 are
forbidden).
Switch setting Content
0 ~ 63 Valid DeviceNet node address
64 ~ 99 Invalid DeviceNet node address
5
6
4
7
3
8
2
9
1
0
5
6
4
7
3
8
2
9
1
0
Example: If you need to set the node address of RTU-DNET to 26, simply switch the corresponding swit ch of x101 to 2 and the corresponding switch of x10
0
to 6.
Note:
z Please set up the node address when the power is switched off. After the setup is completed, re-power
RTU-DNET.
z When RTU-DNET is operating, changing the setting of node address will be invalid. z Use slotted screwdriver to rotate the switch carefully in case you scratch the switch.
2.6 Function Switch
The function switches are for:
z Setting up data retention function (IN0) z Setting up the baud rate of DeviceNet (DR0 ~ DR1)
DR1 DR0 Baud rate OFF OFF 125 kbps OFF ON 250 kbps
ON OFF 500 kbps ON ON Incorrect setting
6
DVP-PLC Application Manual
DeviceNet Remote I/O Communication Module R TU-DNET
OFF
When DeviceNet is off, the I/O data in the buffer area will be cleared.
IN0
ON
When DeviceNet is off, the I/O data in the buffer area will be held.
IN1 Reserved
Note:
z Please set up the function switch when the power is switched off. After the setup is completed, re-power
RTU-DNET.
z When RTU-DNET is operating, changing the setting of the function switch will be invalid. z Use slotted screwdriver to adjust the DIP switch carefully in case you scratch the switch.
2.7 Extension Port
The extension port is used on connecting RTU-DNET to DVP Slim DI/DO extension units and special modules.
3 Basic Operation
3.1 Connecting RTU-DNET to DVP Slim DI/DO Extension Unit
z Open the fixing clips on top and bottom of RTU-DNET. Meet the extension port of Slim DI/DO with RTU-DNE T. z Press the fixing clips on top and bottm of Slim DI/DO and check if the connection is fine.
T
T E
E N
N D
D
-
­U
U T
T R
R
P
P S
S 6
6 1
1
-
­P
P V
V D
D
A
A D
D 2
2 0
0
-
­P
P V
V D
D
3.2 Installing RTU-DNET and DVP Slim DI/DO on DIN Rail
z Use 35mm DIN rail. z Open the DIN rail clip on RTU-DNET and Slim DI/DO. Insert RTU-DNET and Slim DI/DO onto the DIN rail. z Clip up the DIN rail clips on RTU-DNET and Slim DI/DO to fix them on the DIN rail, as shown below .
35mm DIN rail
T E N D
­U T R
P S 6
1
­P V D
A D
2 0
­P V D
DVP-PLC Application Manual
7
DeviceNet Remote I/O Communication Module R TU-DNET
3.3 Connecting to DeviceNet Connection Port
z The colors on the PINs on the DeviceNet connection port match the colors of the connection cables. Make
sure you connect the cable to the right PIN.
z We recommend you also apply Delta’s power module in the connection.
4 How to Configure RTU-DNET
In this section we will introduce how RTU-DNET as a DeviceNet slave realizes the data exchange between
DeviceNet master and DVP Slim DI/DO extension unit.
z DeviceNet master sends the data to Slim DI/DO. z RTU-DENT sends the input data from Slim DI/DO to DeviceNet master.
DVPDNET-SL DVP28SV
DVPDNET DVP28SV
RUN
STOP
Master
T
T
E N D
­U T R
P
S
S
8
6
0
1
-
-
P
P
V
V
D
D
C
D
T
A
4
4
0
0
-
­P
P
V
V
D
D
A
T
D
P
2
4
0
0
-
­P
P
V
V
D
D
DeviceN et
4.1 Terms
No. Item Unit Explanation
1 Control word Word 2 Status word Word Displaying the status of RTU-DNET. See 4.3 for more details.
3
4
8
Number of digital
input points
Number of digital
output points
Bit
Bit
For setting up the mode of RTU-DNET, e.g. “H8000” for STOP mode and “H8001” for RUN mode. See 4.3 for more details.
The digital input points shall be 8’s multiple. The number will be regarded as 8 when it is less than 8 and as 16 when it is bigger than 8 but less than 16.
The digital output points shall be 8’s multiple. The num ber will be regarded as 8 when it is less than 8 and as 16 when it is bigger than 8 but less than 16.
DVP-PLC Application Manual
DeviceNet Remote I/O Communication Module R TU-DNET
No. Item Unit Explanation
Length of input data
5
6
7
8
9
10
11
12
of special module
Length of output
data of special
module
Length of input I/O
Length of output I/O
Number of special
modules
Diagnostic interval
Special module
offline treatment
Special module erro
treatment
data
data
time
Word
Word
Byte
Byte
Unit
Sec
N/A
N/A
The length of input data of the special module connected to RTU-DNET
The length of output data of the special module connected to RTU-DNET
The sum of the length of the status word of RTU-DNET and the input data of the special module connected to it. One input channel of the special module occupies 2 bytes. 8 points of the digital input are counted as 1 byte.
The sum of the length of the control word of RTU-DNET and theoutput data of the special module connected to it. One output channel of the special module occupies 2 bytes. 8 points of the digital output are counted as 1 byte.
The number of special modules connected to RTU-DNET.
Range: 0 ~ 8
The interval when RTU-DNET executes diagnosis.
Range: 1 ~ 65, Default: 5 secs
How RTU-DNET will react when the special module connected to it is offline. You can choose “Ignored”, “Alarm” or “Stop DeviceNet IO”. Default: Alarm
How RTU-DNET will react when it detacts errors. You can
choose “Ignored”, “Alarm” or “S top DeviceNet IO”. Default:
Alarm
13 Reset RTU-DNET N/A Reset the configuration of RTU-DNET to default settings.
For you to decide whether to add control word and status word
Add control word
14
15 Work mode N/A
16
17
18 Length of input data Word
19
20 I/O mapping N/A
and status word to
I/O data
Number of input
data connected
Number of output
data connected
Length of output
data
N/A
---
---
Word
to I/O data. When you choose not to do it, the I/O data in
RTU-DNET and DeviceNet master will not include control word
and status word. If you choose to add them in, the I/O data in
RTU-DNET and DeviceNet master will include control word and
status word.
For you to set up the work mode of the special module
connected to RTU-DNET. When set to “auto mode”, RTU-DNET
will configure default CR of the special module as DeviceNet I/O
mapping data. When set to “custom mode”, you can configure
any CR in the special module as DeviceNet I/O mapping data.
The number of input data of the special module connected to
RTU-DNET
The number of output data of the special module connected to
RTU-DNET
The sum of the length of input data of the special modules
connected to RTU-DNET
The sum of the length of output data of the special modules
connected to RTU-DNET
The I/O mapping relation between RTU-DNET and the special
module connected to it
4.2 Format of Requet Message and Response Message
1. RTU-DNET supports using DeviceNet explicit messages to poll special modules. Format of request messages
Byte position Data written into special module Data read from special module
0 Frag[0]+XID+MAC ID Frag[0]+XID+MAC ID
DVP-PLC Application Manual
9
DeviceNet Remote I/O Communication Module R TU-DNET
Byte position Data written into special module Data read from special module
1 R/R[0]+Service Code[0x10] R/R[0]+Service Code[0x0E] 2 Class ID [0x9C] Class ID [0x9C] 3 Instance ID Instance ID 4 Attribute ID Attribute ID 5 Low byte of Service Data N/A 6 High byte of Service Data N/A 7 N/A N/A
Format of response messages
Byte position Data written into special module Data read from special module
0 Frag[0]+XID+MAC ID Frag[0]+XID+MAC ID 1 R/R[1]+Service Code[0x10] R/R[1]+Service Code[0x0E] 2 Low byte of response data 3 High byte of response data
2. Definitions of DeviceNet Objects for RTU-DNET Class 0x9A – RTU-DNET setup parameter object
Class attribute
Attribute ID Access rule Name Data type
1 Get Revision UINT
Instance 1
Attribute
ID
1 Get
2 Get
3 Get
4 Get
5 Get
6 Get
7 Get
Access
rule
Name Range Default Explanation
Length of
input I/O data
Length of output I/O
data
Number of digital input
points (X)
Number of
digital output
points (Y)
Number of
special
modules
Length of
analog input
Length of
analog output
N/A N/A
N/A N/A
0 ~ 128 N/A
0 ~ 128 N/A
0 ~ 8 N/A
N/A N/A
N/A N/A
The sum of the length of the status word of RTU-DNET and the input data of the module connected to it. (Unit: byte)
The sum of the length of the control word of RTU-DNET and the output data of the module connected to it. (Unit: byte)
The number will be regarded as 8 when it is less than 8 and as 16 when it is bigger than 8 but less than 16. (Unit: bit)
The number will be regarded as 8 when it is less than 8 and as 16 when it is bigger than 8 but less than 16. (Unit: bit)
The number of special modules connected to RTU-DNET .
The length of input data of the special module connected to RTU-DNET. (Unit: word)
The length of output data of the special module connected to RTU-DNET. (Unit: word)
10
DVP-PLC Application Manual
DeviceNet Remote I/O Communication Module R TU-DNET
Attribute
ID
8 Get Status word 0~255 N/A
9 Get/Set Control word N/A N/A
10 Get/Set
11 Get/Set
12 Get/Set
13 Get/Set
14 Get/Set
Access
rule
Name Range Default Explanation
Diagnostic
interval time
Special
module offline
treatment
Special
module error
treatment
RTU-DNET
configuration
validation
Reset
RTU-DNET
1 ~ 65
secs
0 ~ 2 1
0 ~ 2 1
N/A 0
N/A 0
5 secs
Displaying the status of RTU-DNET. See 4.3 for more details.
For setting up the mode of RTU-DNET, e.g. “H8000” for STOP mode and “H8001” for RUN mode. See 4.3 for more details.
The interval when RTU-DNET executes diagnosis.
How RTU-DNET will react when the special module connected to it is offline.
0: Ignored 1: Alarm 2: Stop DeviceNet IO
How RTU-DNET will react when it detects errors.
0: Ignored 1: Alarm 2: Stop DeviceNet IO
Validating the configuration of RTU-DNET when set to “11”.
Resetting RTU-DNET when set to”10”. After it, the parameter will change to “0” automatically.
Class 0x9B – Extension module setup parameter object
Class attribute
Attribute ID Access rule Name Data type
1 Get Revision UINT
Instance 1 ~ 8 (parameters for the 1st ~ 8th special module s )
Attribute
ID
1 Get Model name N/A N/A Model code for the special module
2 Get
3
4
Access
rule
Get
Get
Name Range Default Explanation
Length of input data
Length of output data
Status 0 ~ 63 N/A
N/A N/A
N/A N/A
The sum of the input data length of special modules connected.
Unit: word The sum of the output data length of
special modules connected. Unit: word
b0
b1
b2
0 Special module online 1 Special module offline 0 Special module normal 1 Special module in error
Special module and
0
configuration consistent
DVP-PLC Application Manual
11
Loading...
+ 28 hidden pages