Delta Electronics RPI M30A, RPI M50A Operation And Installation Manual

RPI M30A/M50A Operation and Installation Manual
Grid-tie Transfomerless Solar Inverter
The power behind competitiveness
www.deltaww.com
English 1
77
简体中文
繁體中文
1. General Information
1.1. About this Manual
1.2. Product Description
1.3. Additional Information
2. Product Overview
2.1. Unpack the Inverter
2.2. Checking Unit and Accessories
2.3. Product Label
2.4. Exterior Objects
3. Installation
4. Wiring
4.1 Preparation Before Wiring (Models with Fuses)
4.2. Preparation Before Wiring (Models without Fuse)
4.3. AC Grid Connection: 3-Phase+PE or 3-Phase+N+PE
4.3.1. Required Protective Devices and Cable Cross-sections
4.4. DC Connection from PV Array
4.5. Communication Module Connections
4.5.1. RS-485 Connection
4.5.2. EPO Functions & Digital Input
4.5.3. Dry Contact Connection
5. Turn On PV Inverter
5.1. LCD Flow Chart
5.2. First startup
5.2.1. Home Page
5.2.2. Power Meter
5.2.3. Energy Log
5.2.4. Event Log
5.2.5. Inverter Information
5.2.6. General Settings
5.2.7. Install Settings
5.2.7.1. Inverter ID
5.2.7.2. Insulation
5.2.7.3. Country
5.2.7.4. Grid Settings
5.2.7.5. Dry Contact
5.2.7.6. EPO
5.2.7.7. AC connection
5.2.7.8. Max. Power
5.2.8. Active/Reactive power
5.2.8.1. Power Limit
5.2.8.2. Power vs. Frequency
5.2.8.3. P(V)
5.2.8.4. Constant cosphi
5.2.8.5. Cosphi (P)
5.2.8.6. Constant Q
5.2.8.7. Q(V)
5.2.9. FRT (Fault ride through)
6.Maintenance
6.1. Replace Surge Protection Device (SPD)
6.2. Replace Internal String Fuse
6.3. Clean Fan
6.4. Replace Fan
6.5. Clean Air Inlets
7.Error message and Trouble Shooting
8.De-Commissioning
9.Technical Data
5
5 5 5
6
6 6 9
10
12 16
16 21 31 31 35 36 37 38 39
40
40 41 41 42 42 43 44 44 45 45 46 46 47 48 49 49 49 50 50 50 51 52 52 53 53 54
55
56 58 59 60 60
61 67 68
Contents
03
Safety Instructions
This manual uses the following instructions for conveying important safety related information.
CAUTION !
Machine and equipment damage may occur if this hazardous situation is not avoided.
WARNING !
Death and serious injury may occur if this hazardous situation is not avoided.
Repair work on the device should ONLY be carried out by the manufacturer. No user serviceable parts inside.
In Australia, installation and maintenance work shall be conducted by qualified electrician and shall comply with Australian Regulations.
DANGER !
To avoid risk of electrical shock, do not open the solar inverter. Death and serious injury will occur if this hazardous situation is not avoided.
WARNING ! BURN HAZARD
The unit may reach high temperatures and the device surface can become hot. Sufficient cooling time is necessary for optimal yield.
04
1.General Information
1.1. About this Manual
This manual is to provide the explanation and procedures for installing, operating, maintaining, and troubleshooting of RPI M30A/ RPI M50A solar
inverters.
1.2. Product Description
This device is a 3-phase grid-tied solar inverter which does not support off­grid functionality.
The operation of solar inverter is shown as the Figure 1-1. Inverters convert
the
DC input power supplied from the PV Array into 3-phase AC output power
to Grid.
Figure 1-1 Solar system operation illustration
1.3. Additional Information
For more detailed or other related product information, please visit http://www.deltaww.com
PV Array Electrical GridSolar Inverter
3PH
AC Distribution
box
Surge arrestor
AC breaker
3 phase, N, PE
05
General Information
Figure 2-1 Unpack the inverter
The unpacking procedure of RPI M30A/ M50A is shown as Figure 2-1.
2.Product Overview
2.1 Unpack the Inverter
2.2 Checking Unit and Accessories
Unforeseeable events causing damage or movement may occur during shipment. Please check following items upon receiving your inverter.
• Check the damage on the packaging.
• Check if all the accessories are in the package.
The standard accessories are shown in following tables and figures: For RPI M30A, Please refer to Figure 2-2 and Table 2-1. For RPI M50A, Please refer to Figure 2-3 and Table 2-2.
Check the model number and the serial number on the packaging is identical with the model number and serial number on the unit itself. If there is any visible damage to the inverter/accesories or any damage to the packaging, please contact your inverter supplier.
06
Product Overview
Figure 2-2 Packing list of M30A
RPI M30A
Object Qty Description
1 PV Inverter 1 pcs
1 pcs
1 pcs
1 pcs
RPI series solar inverter
2 User Manual
The Instruction to provide the information of safety, Installation, specification, etc.
3 AC Plug
Mounting Bracket
Connector for AC connection
Wall mounting bracket to mount the solar inverter on the wall.
4
5
DC Plug 6 sets Connector for DC connection
Table 2-1 Packing list of M30A
These products does not provide grounding fuse. Users can choose 1000V/ 1A Midget size grounding fuse if needed.
07
Product Overview
Figure 2-3 Packing list of M50A
RPI M50A
Object Qty Description
1 PV Inverter 1 pcs
1 pcs
1 pcs
1 pcs
RPI series solar inverter
6 Holder 1 pcs Holder for Grounding Fuse
7 Bus-bar 2 pcs Bus-bar for DC+ or DC- Parallel Connection.
2 User Manual
The Instruction to provide the information of safety, Installation, specification, etc.
3 AC Plug
Mounting Bracket
Connector for AC connection
Wall mounting bracket to mount the solar inverter on the wall.
4
5
DC Plug 10 sets Connector for DC connection
Table 2-2 Packing list of M50A
These products does not provide grounding fuse. Users can choose 1000V/ 1A Midget size grounding fuse if needed.
⑥
08
Product Overview
2.3 Product Label
RPI M50A RPI M30A
Please refer to Figure 2-4 for the location of product label. You can identify the model number and the specifications by the information on the label. RPI M30A and M50A series have 3 models. The differences between them are having surge protection devices (SPD) and internal strings fuse or not. For more detail information, please see the table 2-3.
Figure 2-4 Product label
Model Name Part Number
RPI303FA0E1100
RPI503FA0E0000
RPI503FA0E0200
SPD
X
V
X
Internal Fuse
X
V
V
RPI M30A_121
RPI M50A_120
RPI M50A_122
Table 2-3 Model name
09
Product Overview
2.4 Exterior Objects
Display
Air inlet
Label
RPI M50A
Display
Air inlet
Label
RPI M30A
Input / Output
Interfaces
Input / Output
Interfaces
The Inverter’s exterior objects are shown in Figure 2-5. The detailed input/ output interfaces illustration is shown in Figure 2-6. Different models have different number of DC input strings.
Figure 2-5 Inverter’s exterior objects
10
Product Overview
Figure 2-6 Input / output interface
AC Connector
380/400Vac, 3Ph
Fan *5Manual
Switch
String1
String2
String3
Communication
-RS-485 *2
-EPO *1
-Dry Contact *2
-Digital Input*6
DC1 DC2
String8
String9
String10
-­String4 String5
-­String6 String7
RPI M50A
DC1 DC2
String1
String2
String3 String4
String5
String6
AC Connector
380/400Vac, 3Ph
Fan *3
Manual
Switch
Communication
-RS-485 *2
-EPO *1
-Dry Contact *2
-Digital Input*6
RPI M30A
11
Product Overview
CAUTION !
The unit should not be installed in direct sunlight.
WARNING !
Do not install the unit near or on flammable surfaces.
Please mount the unit tightly on a solid/smooth surface.
3.Installation
This unit is designed to be wall-mounted. Please ensure the installation is perpendicular to the floor and the AC plug at the bottom. Do not install the device on a slanting wall.
To mount the inverter on the wall, please follow the procedure below:
1.Screw the mounting bracket on the wall with 12 M6 Phillips head screws. Please refert to Figure 3-3.
2.Attach the inverter to the mounting bracket.
3.Fix the inverter with 2 M6 Phillips head screws. Please refer to Figure 3-4.
12
Installation
Figure 3-1 Mounting bracket dimension
Figure 3-2 Recommended installation
90
Not
Recommended
Not
Recommended
Keep >30 cm from floor and
water if installed this way
13
Installation
M6 Screw *6
Wall
M6 Screw *6
Figure 3-3 Screw the mounting bracket
Figure 3-4 Attach to the bracket and fasten with screws
14
Installation
CAUTION !
The bracket supplied with the unit is specially designed and should be the only mounting device used for the unit.
It is recommended to install the inverter in a suitable location which offers non-obscured and safe access, in turn ensuring easy access for service and maintenance.
Please leave an appropriate gap in between units when installing several solar inverter systems as shown in Figure 3-5.
Please install solar inverter at an eye level to allow easy observation for operation and parameter setting.
Ambient temperature -25
° C~60° C.(power de-rating above 40° C)
> 30 cm
> 20 cm
> 50 cm
> 30 cm
> 30 cm
Figure 3-5 Proper installation gap
15
Installation
4.1 Preparation Before Wiring (Models with Fuses)
4. Wiring
WARNINGSHOCK HAZARD
Whenever a PV array is exposed to sunlight, a shock hazard may exist due to output wires or exposed terminals. To reduce the risk of shock during installation, cover the array with an opaque (dark) material and ensure that the Disconnect Device in the inverter is set to OFF before commencing any wiring.
M50A has 15A DC fuse in each Plus and Minus DC connector, the maximum current of each string should not exceed 10A.
For models with fuses, PV arrays can connect to the inverter directly, but parallel connection at external DC distribution box is not recommended due to the limits of DC fuse. Please refer to Figure 4-1 for the detail wiring illustrations.
If you want inverter working at parallel input mode (only 1 MPPT), please install 2 bus bar kits in the inverter as shown in Figure 4-2. The outer wiring
at DC side is same as Firgure 4-1.
When grounding the solar array, an isolation transformer is required
because the RPI series does not have galvanic isolation between the DC-input and AC-output. In addition, Users must install a 1000V/1A midget size grounding fuse and 1 or 2 bus bar kits in the inverter. Wiring illustrations please refer to Figure 4-3, Figure 4-4.
When solar array is grounded,the PID function can not be enable,and the
insulation have to be setting “Plus Grounded” or “Minus Grounded”.
It must to keep DC and AC power off when disconnected the DC connector.
Different DC connections type need different settings of insulation detection.
Please refer to 5.2.7 Install Settings for further information.
16
Wiring
Figure 4-1 floating string with separate connection
1 2 3 4
L1 L2 L3
N
PE
Communication
Wiring
1
2
3
AC Wiring
DC Wiring
Must be Separate PV strings
*
* RPI M30A can support 3P3W system.
+-+
-
+
-
1 2 3 4
L1 L2 L3
N
PE
Communication
Wiring
1 2
3
AC Wiring DC Wiring
Must be Separate PV strings
*
* RPI M50A can support 3P3W system.
++++
- -- -
RPI M50A
RPI M30A
17
Wiring
bus bar kit *2
DC1+
DC2+
DC1-
DC2-
String 1~5 +
String 6~10 +
String 1~5 -
String 6~10 -
RPI M50A
Figure 4-2 Force M50A operate in parallel mode
18
Wiring
Communication
Wiring
1 2
3
AC Wiring DC Wiring
Separated connection only
- -- -
Isolated
transformer
Utility
To
Inverter
3Ph,
400Vac
3Ph,
400Vac
++++
DC1+
DC2+
DC1-
DC2-
String 1~5 +
String 6~10 +
String 1~5 -
String 6~10 -
1A Grounding fuse
bus bar kit
Figure 4-3 Minus grounding of M50A with fuse
19
Wiring
Communication
Wiring
1 2
3
AC Wiring DC Wiring
Separated connection only
- -- -
Isolated
transformer
Utility
To
Inverter
3Ph,
400Vac
3Ph,
400Vac
++++
1A Grounding fuse
bus bar kit *2
DC1+
DC2+
DC1-
DC2-
String 1~5 +
String 6~10 +
String 1~5 -
String 6~10 -
Figure 4-4 Plus grounding of M50A with fuse
20
Wiring
4.2 Preparation Before Wiring (Models without Fuse)
RPI M30A_121 does not have internal strings fuse. Each string can accept
maximum current 30A. It can use one pair of DC connector for each input (DC1 and DC2)
For floating PV array, inverter can accept DC input in parallel connection
or separate connection.
• When grounding the solar array, an isolation transformer at AC side is
required and DC inputs must be parallel connection due to the RPI-series not having galvanic isolation between the DC-input and AC-output.
When solar array is grounded,the PID function can not be enable,and the
insulation have to be setting “Plus Grounded” or “Minus Grounded”.
Different DC connection type needs different settings of insulation detection.
About setting, please refer to 5.2.7 Install Settings.
Figure 4-5 floating string of M30A_121
1 2 3 4
L1 L2 L3
N
PE
Communication
Wiring
1
2
3
PV Array
AC Wiring
DC Wiring
Parallel or
Separate
*
* RPI M30A can support 3P3W system.
DC Distribution box
DC1 DC2
21
Wiring
Figure 4-6 Plus or minus grounding wiring of M30A_121
Communication
Wiring
1
3
PV Array
AC Wiring
Must be Parallel
Connection
Do not enable the PID function and set the insulation with “Plus Grounded” or “Minus Grounded”.
DC Distribution box
(Plus-GND or Minus-GND)
Z
Z
or
Isolated
transformer
Utility
To
Inverter
3Ph,
400Vac
3Ph,
400Vac
Must install a
transformer
2
DC Wiring
22
Wiring
Connection with PV Combiner Box
M50A:
Note for Field Wiring
Due to the limitation of physical wire also the DC connector used in the inverter, the absolute maximum current of each DC connector should be always observed as following table to keep fire risk away. Note that, the following value is provided to identified and checked the justification for field wiring instead of the DC current rating of inverter.
-Normally, the output current of combiner box is larger than 16A. Thus it can’t be used as the following diagram (Shown as Figure 4-7).
M50A is not suitable to connected with PV combiner box.
RPI M30A_121 32A
RPI M50A_120 16A
RPI M50A_122 16A
Table 4-1 Maximun current rating of each DC connector
Figure 4-7
>16A >16A
>16A
>16A
23
Wiring
-Also, you can’t use two or more branch to share the current from combiner box to each dc connector of inverter (Shown as Figure 4-8). Because the current might not be symmetric among the branch,the current of one branch might larger than the limitation still.
Figure 4-8
>16A
>16A
>16A
>16A
Strictly forbiden
Risk of fire on internal entrance cabling
M50A:
24
Wiring
The following diagram shown risky connection with M30A and PV combiner box. As Figure 4-10 shown , the left pair of dc connector will suffer DC input current more than the limitation 32A.Thus it is not suitable for use.
Figure 4-10
M30A:
>32A
>32A
25
Wiring
As Figure 4-11 shown , the branch plug might suffer the DC current lager than its limitation. Thus it is not suitable for use.
*Note that the max current rating of MC4 brauch commercially available is 30A.
Figure 4-11
>30A
*Note
>30A
M30A:
26
Wiring
To Use RPI M50A with 12 PV string
To apply branch connector on specific indicated DC input connectors.
To replace relative string fuse for the branch from 15A to 25A by opening
the middle front cover.
The Specific DC input connectors
The inverter equips with 10 pair DC connector. When 12 string applied, branch plug are required. See following illustrate.
RPI M50A
String 1 String 2 String 3 String 5 String 4
String 6 String 7 String 8 String 9
String 10
String 1
String 2
String 3
String 5
String 6
String 8
String 9
String 11
String 12
String 10
String 7
String 4
Branch Plug
27
Wiring
For this application, the inverter provides specific 2 pairs of DC input connectors to connect with branch plugs. Both 2 pairs of DC input connectors indicated by symbols shown as following picture. Note that for Dc input connectors other than the specific two are forbidden with such application.
28
Wiring
The Relative String Fuse for the branch plug
The inverter provide string fuse with rating 15A in default. When 2 PV string are connected via branch plug to the specific DC connector, the current passed through specific connector will be higher than that with only one PV string. The rating of string fuse for the specific Dc connector should be enlarged, 25A is recommended. Please refer to Sec 6.2 to find where String Fuse are. 4 string fuse applied on the specific Dc connector are indicated as group “Max 25A”.
29
Wiring
Material List for application with 12 String
MC4 Branch Plug
25A String Fuse
-Male Cable Coupler (For polarity +) ,2 Pcs required per inverter
-Female Cable Coupler (For polarity –) ,2 Pcs required per inverter
Male Cable Coupler Female cable coupler
Vendor/Model No
Multi-Contact/PV-AZS4
Vendor/Model No
Multi-Contact/PV-AZB4
Little Fuse /0SPF025.T - 1000V/25A ,4 pcs required per inverter
Male cable coupler Female cable coupler
30
Wiring
Loading...
+ 198 hidden pages