Delta Electronics M-1K, M-3K, M-1.5K, M-2K User Manual

The power behind competitiveness
Delta UPS - Amplon Family
M Series, Single Phase 1/ 1.5/ 2/ 3 kVA
User Manual
www.deltapowersolutions.com
This manual contains important instructions and warnings that you should follow during the installation, operation, storage and maintenance of this product. Failure to heed these instructions and warnings will void the warranty.
Copyright © 2013 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc. (“Delta”). The Manual can only be applied to the operation or the use of this product. Any disposition, duplication, dissemination, reproduction, modification, translation, extraction, or usage of this Manual in whole or in part is prohibited without the prior written permission of Delta. Given that Delta will continuously improve and develop the product, changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes. Delta will make all possible efforts to secure the accuracy and the integrity of this Manual. Delta disclaims any kinds or forms of warranty, guarantee, or undertaking, either expressly or implicitly, including but not limited to the completeness, faultlessness, accuracy, non-infringement, merchantability or tness for a particular purpose of the Manual.
Amplon M Series
II
Table of Contents
Table of Contents
Chapter 1 : Important Safety Instructions --------------------------- 1
1.1 Safety Instructions ---------------------------------------------- 1
1.2 Glossary of Symbols -------------------------------------------- 5
1.3 Standard Compliance ------------------------------------------ 6
1.4 Storage ------------------------------------------------------------- 7
Chapter 2 : Introduction --------------------------------------------------- 8
2.1 General Overview ----------------------------------------------- 8
2.2 Package Inspection --------------------------------------------- 8
2.3 Features ----------------------------------------------------------11
2.4 Front Panel -------------------------------------------------------12
2.5 Rear Panel -------------------------------------------------------16
Chapter 3 : Installation ----------------------------------------------------19
3.1 Installation Data -------------------------------------------------19
3.2 Rack Mounting the UPS or the Delta External Battery Pack (Optional) -------------------------------------------------20
3.3 Tower Mounting the UPS or the Delta External Battery Pack (Optional) -------------------------------------------------22
Chapter 4 : Connections -------------------------------------------------25
4.1 Delta External Battery Pack Connection -----------------25
4.2 Connecting to Utility Power ----------------------------------27
4.3 Connecting the loads ------------------------------------------27
Chapter 5 : Operation -----------------------------------------------------28
5.1 Operation Modes -----------------------------------------------28
5.2 Other Operating Details ---------------------------------------28
III
5.3 Start-up Procedure ---------------------------------------------30
5.4 Shutdown Procedure ------------------------------------------30
5.5 UPS Self Test ---------------------------------------------------31
5.6 Alarm --------------------------------------------------------------31
Chapter 6 : Communication Interfaces ------------------------------32
Chapter 7 : Optional Accessories -------------------------------------34
Chapter 8 : Maintenance -------------------------------------------------35
8.1 UPS ----------------------------------------------------------------35
8.2 Batteries ----------------------------------------------------------35
Chapter 9 : Troubleshooting --------------------------------------------36
Appendix 1 : Specications ---------------------------------------------39
Appendix 2 : Warranty ----------------------------------------------------41
Amplon M Series
IV
Chapter 1 Important Safety Instructions
Chapter 1 : Important Safety Instructions
1.1 Safety Instructions
z
z
Intended Use
1. This unit serves as a line-interactive uninterruptible power supply (UPS) for connected loads.
2. Never connect a laser printer or scanner to the UPS. This may cause damage to the unit.
3. The UPS is available in 1kVA, 1.5kVA, 2kVA and 3kVA. Each model has internal batteries.
4. Only 3kVA model can be connected to a Delta external battery pack (optional).
5. The UPS can be used to power computers and associated peripheral devices, such as monitors, modems, cartridge tape drives, external hard drives, etc.
z
z
Handling
Transport the unit only in suitable packaging to protect it from jolts and shocks. The UPS must be kept upright at all times and handled with care.
z
z
Placement & Installation Warnings
1. Install the UPS in a well-ventilated area, away from extremes of temper­ature, excess moisture, heat, dust, ammable gas or explosives.
2. Leave adequate space at least 15cm in front and rear of the UPS for proper ventilation.
3. Electrical maintenance and service requires access to the front and back of the UPS. Leave necessary space to allow service personnel to access to the UPS.
4. The UPS can be installed vertically (tower-mounting) or horizontally (rack­mounting) depending on user ’s desired arrangement. Please obey the following:
1) Do not mount the UPS with its front or rear panel facing down at any
angle.
1
2) Keep the UPS upright at all times and handle it with care.
3) Do not stack units.
4) Do not place any objects on the UPS, the Delta external battery pack or
any other accessory associated with the UPS.
5) Install the UPS and the Delta external battery pack on a level and even
surface.
6) For tower-mounting installation, ensure that your chosen location’s oor
can bear the weight of the UPS, the Delta external battery pack and tower stands (optional).
7) For rack-mounting installation, make sure your chosen cabinet can
support the weight of the UPS, the Delta external battery pack and rails that may be mounted in an associated rack. You also need to take your chosen location’s oor weight loading into consideration.
8) For rack-mounting installation, do not allow your rack to become ‘top
heavy’. Install the heaviest equipment near the bottom of the rack.
9) Weights for the UPS and the Delta external battery pack are shown in
Appendix 1 : Specications.
10) Install the UPS in accordance with the conditions specified in 3.1
Installation Data.
5. The ideal operating temperature range is 0°C~40°C.
z
z
General Warnings
1. Electrical shock hazard: even when the UPS is disconnected from the mains, hazardous voltages may still exist at the output receptacles of the UPS. Before maintenance, cut off not only the AC source but also the battery source.
2. Even when all switches and/ or circuit breakers are open, dangerous voltages are present within this unit.
3. Forbid opening or removing the cover of the UPS to avoid high voltage electric shock. There are no user-serviceable parts inside.
4. Maintenance service must be performed by qualified service personnel. Only qualied service personnel can carry out any operation that requires protection panels to be opened and/or removed.
5. Any repairs or modications by the user may result in out-of-warranty repair charges or unsafe electrical conditions.
Amplon M Series
2
Chapter 1 Important Safety Instructions
6. Do not use extension cords to connect the UPS to an AC outlet.
7. Do not plug the UPS input cord into its own output receptacles.
z
z
Usage Warnings
1. Before usage, you must unpack the UPS and allow it to adjust to room te mperatu re ( 20°C~25 °C) for at l east two hour s to a voi d mois tur e condensing inside the UPS.
2. The external slits and openings in the UPS are provided for ventilation. To ensure reliable operation of the UPS and to protect the UPS from overheating, these slits and openings must not be blocked or covered. Do not insert any object into the slits and openings that may hinder ventilation.
3. Even though all buttons are in the OFF position, the UPS is not isolated from the mains. To completely isolate the UPS from the mains, please disconnect the input power cord.
4. This unit supplies power from two sources, the mains and the batteries. The output receptacles may have voltage present even when the unit is unplugged. Unplugging the UPS puts it into battery mode and the batteries supply power to the connected loads.
5. Route all cords well so that nobody can stand on them or trip over them.
6. When connecting the unit to the power supply, follow the instructions stated in Chapter 4 : Connections.
7. Ensure that no objects (e.g. rings, necklaces, paper clips, etc) get inside the unit.
8. In an emergency, switch off the unit, disconnect it from the mains and contact the responsible customer service representative.
9. Do not connect equipment that will overload the UPS and demand DC current.
10. Do not connect or disconnect data transmission lines during a thunderstorm.
11. The sum of current leakage from the UPS and its connected loads must not exceed 3.5 mA.
12. The UPS has a REPO (remote emergency power off) port locating on the rear. Please see 5.2 Other Operating Details for more information.
13. The UPS must be well grounded due to a possible risk of current leakage. The unit is equipped with a safety-inspected mains line and must be
3
connected to an earthing-contact wall socket. If the wall socket does not have an earthing connection, please ground the UPS via the ground terminal locating at the rear of the UPS (please see 2.5 Rear Panel).
14. Ensure that the sockets on the unit or the earthing-contact wall socket is freely accessible.
z
z
Battery Precautions
1. Do not open or mutilate the battery or batteries. The released electrolyte is harmful to the skin and eyes and may be toxic.
2. Do not dispose of the battery or batteries in a fire. The batteries may explode.
3. The risk of dangerous high voltage is possible when the batteries are still connected to the UPS even though the UPS is disconnected from the mains. Do not forget to pull out the battery cable to completely cut off the battery source.
4. Voltage is always present on the battery terminals.
5. Even when discharged, a battery has the capacity to supply a high short circuit current, which, in addition to causing damage to the battery itself and to associated cables, may expose the operator to the risk of burns.
6. Do not keep batteries in storage for periods exceeding 6 months at 25ºC without being recharged (having been charged to 100% at the beginning of any such period). If these conditions are not met, the battery performance can no longer be guaranteed. It is recommend that you recharge the internal batteries at least once every 3 months and each recharging time should not be less than 6 hours. If a Delta external battery pack is connected, the recharging time should not be less than 12 hours.
7. Since new batteries often do not provide full capacity after an initial charge, it may be necessary to carry out a number of discharge/recharge cycles before optimum performance is achieved.
8. Servicing of batteries and battery packs should be performed or supervised by qualied service personnel knowledgeable in batteries, battery packs and the required precautions.
9. Only use the same type of batteries from the same supplier. Never use old, new and different Ah batteries at the same time.
10. A battery can present a risk of electrical shock and high short-circuit current.
Amplon M Series
4
Chapter 1 Important Safety Instructions
OVERLOAD
FAULT
The following precautions should be observed before replacement of batteries:
1) Remove watches, rings, or other metal objects.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or disconnecting battery
terminals.
z
z
Disposal
1. To protect our environment, UPS & batteries must be disposed of in accord­ance with local laws and regulations.
2. For proper UPS & battery disposal, contact your local recycling/ reuse or hazardous waste center.
WARNING!
You must contact qualied service personnel if either of the following events occur:
1. Liquid is poured or splashed on the UPS or on the Delta external battery pack.
2. The UPS does not run normally after this User Manual is carefully observed.
1.2 Glossary of Symbols
No.
1 ON/ OFF Button
2
3
4
Symbol Description
MUT E
TES T
MUTE/ TEST Button
OVERLOAD LED
FAULT LED
5
No.
BOOST
BUCK
ONLINE
LOAD
BAT T.
S.W.F.
BATT.
ON BATT.
10 0%
Symbol Description
10
11
12
13
5
6
7
8
9
BOOST LED
BUCK LED
ONLINE LED
LOAD LED
BATT. LED
S.W.F. (Site Wiring Fault) LED
REPLACE
REPLACE BATT. LED
ON BATT. LED
Bar Graph LEDs
75 %
50 %
25 %
Amplon M Series
1.3 Standard Compliance
z
z
CE
z
z
CB Report (by TUV)
z
z
EN 62040-1
z
z
EMC EN62040-2 C1
6
Chapter 1 Important Safety Instructions
1.4 Storage
z
z
Prior to installation:
If the UPS needs to be stored prior to installation, it should be placed in a dry area. The allowable storage temperature and relative humidity (non-condensing) are -15°C ~ +45°C and 0 ~ 95% respectively.
z
z
After usage:
Press the ON/ OFF button (
), make sure the UPS is shutdown, disconnect the UPS from the utility power, remove all equipment from the UPS, and store the UPS in a dry and well-ventilated area at a temperature between -15°C and +45°C and at a relative humidity (non-condensing) between 0~95%. Idle batteries must be recharged fully approximately every three months if the UPS needs to be stored for an extended period of time. The charging time must not be less than 6 hours each time. If a Delta external battery pack is connected, the recharging time should not be less than 12 hours.
NOTE :
After storage and before start-up of the UPS, you must allow the UPS to adjust to room temperature (20°C~25°C) for at least two hours to avoid moisture condensing inside the UPS.
7
Chapter 2 : Introduction
2.1 General Overview
The M series UPS, available in 1kVA, 1.5kVA, 2kVA and 3kVA, is a line-interactive UPS providing sine-wave quality power to your electronic equipment. Each kVA model has internal batteries, and only 3kVA model can be connected to a Delta external battery pack. The unit’s output power factor is 0.9 and its efciency in online mode (full load) can reach at minimum 97% and 96% for 1/ 1.5kVA and 2/ 3kVA respectively. It produces greater electric power efciency at less cost and its com­pact design is perfect for IT applications.
2.2 Package Inspection
z
z
External
During UPS transportation, some unpredictable situations might occur. It is recommended that you inspect the UPS exterior packaging. If you notice any damage, please immediately contact the dealer from whom you purchased the unit.
z
z
Internal
1. Check the rating label stuck on the top of the UPS and make sure the device No. and capacity match what you ordered.
2. Examine if any parts are loose or damaged.
3. The UPS package contains the following items. Please check if any items are missing.
Amplon M Series
8
z
z
For 1kVA/ 1.5kVA model:
Chapter 2 Introduction
1
5
4
×
6
×
9
2
6 7
4
×
8
×
8
×
3
4
8
No. Item Quantity
1
UPS 1 PC
2
3
4
5
6
7
8
9
User’s Manual CD 1 PC
Software CD-UPSentry 2012 1 PC
Quick Guide 1 PC
Bracket Ear 1 Set
Output Cable 10A 1 PC
Input Cable 10A 1 PC
RS232 Cable 1 PC
Rail Kit 1 Set
9
z
z
For 2kVA/ 3kVA model:
1
5
4
×
6
×
9
2
6 7
4
×
8
×
8
×
3
10
4
8
No. Item Quantity
1
2
UPS 1 PC
User’s Manual CD 1 PC
Amplon M Series
3
4
5
6
7
8
9
10
Software CD-UPSentry 2012 1 PC
Quick Guide 1 PC
Bracket Ear 1 Set
Input Cable 16A 1 PC
Output Cable 16A 1 PC
Output Cable 10A 1 PC
Rail Kit 1 Set
RS232 Cable 1 PC
10
Chapter 2 Introduction
4. If there is any damage or anything missing, please immediately contact the dealer from whom you purchased the unit.
5. If the UPS needs to be returned, carefully repack the UPS and all of the accessories using the original packing material that came with the unit.
2.3 Features
z
z
User-friendly LED indicators
z
z
Output power factor =0.9
z
z
Cold start
z
z
REPO function
z
z
Input breaker protection
z
z
Generator compatible
z
z
Hot swappable internal batteries and Delta external battery pack
z
z
Battery deep discharging protection
z
z
Intelligent monitor software connectivity through RS232 port or USB port
z
z
Provides the following functions via configuration of UPSentry 2012 software (included in the provided CD), SNMP card (optional) or ModBus card (optional):
1. Regular self-test
2. History logs for records and analysis
3. Battery remaining time & lock time estimate
4. Real-time power condition monitoring
5. System shutdown control
6. UPS schedule ON/ OFF, 10 sec, and deep discharging test
11