Delta Electronics INX-1K, INX-2K, INX-3K User Manual

The power behind competitiveness
Delta UPS - Amplon Family
INX Series, Single Phase 1/ 2/ 3 kVA
User Manual
www.deltapowersolutions.com
This manual contains important instructions and warnings that you should follow during the installation, operation, storage and maintenance of this product. Failure to heed these instructions and warnings will void the warranty.
Copyright © 2018 by Delta Electronics Inc. All Rights Reserved. All rights of this User Manual (“Manual”), including but not limited to the contents, information, and figures are solely owned and reserved by Delta Electronics Inc. (“Delta”). The Manual can only be applied to the operation or the use of this product. Any disposition, duplication, dissemination, reproduction, modification, translation, extraction, or usage of this Manual in whole or in part is prohibited without the prior written permission of Delta. Given that Delta will continuously improve and develop the product, changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes. Delta will make all possible efforts to secure the accuracy and the integrity of this Manual. Delta disclaims any kinds or forms of warranty, guarantee, or undertaking, either expressly or implicitly, including but not limited to the completeness, faultlessness, accuracy,
non-infringement, merchantability or tness for a particular purpose of the Manual.
Amplon INX Series
II
Table of Contents
Table of Contents
Chapter 1 : Important Safety Warnings ------------------------------- 1
1.1 Transportation ---------------------------------------------------- 1
1.2 Preparation -------------------------------------------------------- 1
1.3 Installation --------------------------------------------------------- 1
1.4 Operation ---------------------------------------------------------- 2
1.5 Maintenance, Service and Faults --------------------------- 2
1.6 Packing List ------------------------------------------------------- 3
Chapter 2 : Installation and Setup ------------------------------------- 4
2.1 Rear Panel View ------------------------------------------------- 4
2.2 Operating principle ---------------------------------------------- 6
2.3 Setup the UPS --------------------------------------------------- 6
2.4 Battery Replacement ------------------------------------------- 9
Chapter 3 : Operation -----------------------------------------------------10
3.1 Button Operation -----------------------------------------------10
3.2 LCD Panel --------------------------------------------------------11
3.3 Audible Alarm ---------------------------------------------------- 13
3.4 LCD Display Wordings Index --------------------------------14
3.5 UPS Setting ------------------------------------------------------15
3.6 Operating Mode Description ---------------------------------19
3.7 Faults Reference Code ---------------------------------------21
3.8 Warning Indicator -----------------------------------------------22
Chapter 4 : Troubleshooting --------------------------------------------23
Chapter 5 : Storage and Maintenance -------------------------------25
Chapter 6 : Technical Specications ---------------------------------26
Chapter 7 : Warranty -------------------------------------------------------28
III
Chapter 1 : Important Safety Warnings
Please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructions carefully.

1.1 Transportation

z
z
Please transport the UPS system only in the original package to protect against shock and impact.

1.2 Preparation

z
z
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must be absolutely dry before being installed. Please allow at least two hours for the UPS system to acclimate the environ­ment.
z
z
Do not install the UPS system near water or in moist environments.
z
z
Do not install the UPS system where it would be exposed to direct sunlight or near heater.
z
z
Do not block ventilation holes in the UPS housing.

1.3 Installation

z
z
Do not connect appliances or devices which would overload the UPS system (e.g. laser printers) to the UPS output sockets.
z
z
Please do not attached half-sinewave load or motor load to the UPS.
z
z
Place cables in such a way that no one can step on or trip over them.
z
z
Do not connect domestic appliances such as hair dryers to the UPS output sockets.
z
z
The UPS can be operated by any individuals with no previous experience.
z
z
Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to the UPS system.
z
z
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system to the building wiring outlet (shock-
Amplon INX Series
1
Chapter 1 Important Safety Warnings
proof outlet).
z
z
Please use only VDE-tested, CE-marked power cables to connect the loads to the UPS system.
z
z
When installing the equipment, it should ensure that the sum of the leakage cur­rent of the UPS and the connected devices does not exceed 3.5mA.
1.4 Operation
z
z
Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
z
z
The UPS system features its own, internal current source (batteries). The UPS output sockets or output terminals block may be electrically live even if the UPS system is not connected to the building wiring outlet.
z
z
In order to fully disconnect the UPS system, rst press the OFF/ ENTER button
to disconnect the mains.
z
z
Prevent no uids or other foreign objects from inside of the UPS system.
1.5 Maintenance, Service and Faults
z
z
The UPS system operates with hazardous voltages. Repairs may be carried out
only by qualied maintenance personnel.
WARNING:
Risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the UPS system are still connected to the battery and electrically live and dangerous.
z
z
Before carrying out any kind of service and/ or maintenance, disconnect the bat­teries and verify that no current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
z
z
Only persons are adequately familiar with batteries and with the required pre­cautionary measures may replace batteries and supervise operations. Unauthor­ized persons must be kept well away from the batteries.
WARNING:
Risk of electric shock. The battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the battery terminals and the ground. Before touching, please verify that no voltage is present!
2
z
z
Batteries may cause electric shock and have a high short-circuit current. Please take the precautionary measures specied below and any other measures nec­essary when working with batteries:
- remove wristwatches, rings and other metal objects
- use only tools with insulated grips and handles.
z
z
When changing batteries, install the same number and same type of batteries.
z
z
Do not attempt to dispose of batteries by burning them. This could cause battery explosion.
z
z
Do not open or destroy batteries. Escaping electrolyte can cause injury to the
skin and eyes. It may be toxic.
z
z
Please replace the fuse only with the same type and amperage in order to avoid
re hazards.
z
z
Do not dismantle the UPS system.
1.6 Packing List
1
No. Item Q’ty
1
2
3
4
5
6
Amplon INX Series
2
3
4
5
6
UPS 1 PC
Input cable 1 PC
USB cable 1 PC
User manual 1 PC
Battery cable (for Extended Runtime Model only) 1 PC
Screws and nuts (for Extended Runtime Model only)
3
2 Sets
Chapter 2 Installation and Setup
1 kVA
2 kVA
3 kVA
Chapter 2 : Installation and Setup
NOTE :
Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use.

2.1 Rear Panel View

z
z
Standard Runtime Model
4
z
z
Extended Runtime Model
1 kVA 2 kVA 3 kVA
No. Item
1
2
3
4
5
6
7
8
AC input
Input circuit breaker
USB port
RS-232 port
Mini slot
Output socket
External battery connector
Output terminal
Amplon INX Series
5
Chapter 2 Installation and Setup
2.2 Operating principle
The operating principle of the UPS is shown as below
2.3 Setup the UPS
Step 1: Connect battery wires
If UPS is extended runtime model, please connect external batteries as below chart.
Please refer to below chart to secure battery cable to the terminal with supplied screws and nuts.
6
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords.
z
z
The power cord is attached to the UPS. For the type of power cord, please refer to the table below.
UPS Type of Power Cord
1kVA Plug 10A INDIA
Standard Runtime
Model
2kVA Plug 10A INDIA
3kVA Plug 16A INDIA
1kVA Plug 10A INDIA
Extended Runtime
Model
2kVA Plug 16A INDIA
3kVA Plug 16A INDIA
Step 3: UPS output connection
z
z
For socket-type outputs, simply connect devices to the outlets.
z
z
For terminal-type outputs, please follow below steps for the wiring conguration:
1. Remove the small cover of the terminal block
2. Suggest using AWG12 ~ 10 or 3.3mm Please also install a circuit breaker (40A) between the mains and AC input of the UPS in 3kVA for safety operation.
3. Upon completion of the wiring conguration, please check whether the wires are securely afxed.
4. Put the small cover back to the rear panel.
Amplon INX Series
2
~ 5.3mm2 power cords for 3kVA.